The design of the earthing grid is based on IEEE 80-2000, with the tolerable touch and step
voltages as prescribed. The design current for the earthing grid, in respect of touch and step
voltages, is 50 kA for the 150 kV KDL Substation.
Critical points in the substation area are identified by graphical analysis, with colour coding
according to safety thresholds.
The calculated ground resistance is 0.238 Ω and the ground potential rise is 8599.16V
The potential plots from this calculation shows that the station is designed to be safe using selected
earthing grid, see plots in clause 9.
Table of Content
Project
2. Objective
The objectives of grounding system in KDL Substation project is
To provide low impedance to ground fault current return path i.e., less than one ohm and
in-turn activate the ground fault protection relay as soon as possible.
To limit potential rise of grounding system as such GPR does not exceed a value which
could damage electrical equipment or affect continuity of service
To provide a safe environment for operating personnel, i.e, to assure that a person in the
vicinity is not exposed to the danger of electric shock by limiting touch voltage & step voltage
to safer limit in particular areas
3. Soil resistivity
The resistivity of the soil is based on the soil resistivity report measured with Wenner method.
A Single-layer soil model has been used for the calculations, see Figure 1 for resistivity layer values.
4. Fault current
Maximum ground fault current considered for earthing system is 50kA for earthing design of
150kV KDL Substation.
Project
6. Input to CYMGRD
conductor sizing
2. Fault current diversion factor Sf = 0.7
3. Duration of shock for determining allowable body ts = 0.5 s
current
4. Surface Gravel layer resistivity s = 3000 m
8. Body Weight = 50 Kg
Project
As per "Design of steel Earthing Grids in India" IEEE transaction on power Apparatus and System,
Vol. PAS 98 No. 6 Nov./Dec 1979. pp 2126-2134, Corrosion allowance is recommended as per
following rule
1 mil = 0.0254mm
22.5 mil = 0.571mm
Project
9. Result
The program CYMGRD calculates the actual step and touch voltages for each part of the grid. The
result is presented with equipotential graphs of surface and touch potentials with simultaneous
dynamic display of actual station coordinates for detailed safety analyses. The plot shows that the
station is safe with regards to step and touch voltage. This is guaranteed when maximum allowable
step and touch voltage are higher than actual voltage in the plots below. Upto fence area the touch
and step voltages are under the permissible limit. The result and the plots below shows that the step
and touch voltages are guaranteed.
Project
Potential
profile 1
Project
Project
Calculated maximum
Potential Rise - 8411.79 V
Project
Calculated maximum
Potential Rise - 8414.44 V
Project
The potential plots from this calculation shows that the station is designed to be safe using selected
earthing grid, see plots in clause 9.
11 References
[1] IEEE Guide for safety in AC substation earthing, Std 80-2000
[2] Earthing Layout, 210014-P7001-E06-0104.
[3] Report on soil resistivity for KDL Substations
Project
Parameters
Title KDL
Output Results
42.919
42.419
41.919
41.419
Resistivity (ohm-meters)
40.919
40.419
39.919
39.419
38.919
38.419
37.919
37.419
36.919
36.419
35.919
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 105
Length (meters)
Calculated Points
Grid analysis report Monday, October 29, 2012, 16:28:41
Parameters
Output Results
Parameters
Bus ID 150kV SS
LG Fault Current 50000 amps
Remote Contribution 100 %
Return Electrode Current 0 amps
Parallel Z 1 ohms
Upper Layer Thickness 100 meters
Upper Layer Resistivity 39.91 ohm-m
Lower Layer Resistivity 39.91 ohm-m
Equal Potentials (Distinct) Yes
X1 0 meters
Y1 0 meters
X2 89.5 meters
Y2 53 meters
X Intervals 10
Y Intervals 10
Potential Thresholds
Maximum
X (meters) Y (meters)
0 37.1
5500
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 105
Length (meters)
Surface Potentials Step Potentials
Touch Potentials Ground Potential Rise = 8599.16 volts
Maximum Permissible Step = 2581.78 volts Maximum Permissible Touch = 768.48 volts
Potential profile report Monday, October 29, 2012, 16:48:01
Parameters
Bus ID 150kV SS
LG Fault Current 50000 amps
Remote Contribution 100 %
Return Electrode Current 0 amps
Parallel Z 1 ohms
Upper Layer Thickness 100 meters
Upper Layer Resistivity 39.91 ohm-m
Lower Layer Resistivity 39.91 ohm-m
Equal Potentials (Distinct) Yes
X1 88 meters
Y1 0 meters
X2 0 meters
Y2 51.5 meters
Potential Thresholds
Maximum
5500
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 105
Length (meters)
Surface Potentials Step Potentials
Touch Potentials Ground Potential Rise = 8599.16 volts
Maximum Permissible Step = 2581.78 volts Maximum Permissible Touch = 768.48 volts
Potential profile report Monday, October 29, 2012, 16:49:13
Parameters
Bus ID 150kV SS
LG Fault Current 50000 amps
Remote Contribution 100 %
Return Electrode Current 0 amps
Parallel Z 1 ohms
Upper Layer Thickness 100 meters
Upper Layer Resistivity 39.91 ohm-m
Lower Layer Resistivity 39.91 ohm-m
Equal Potentials (Distinct) Yes
X1 0 meters
Y1 51.5 meters
X2 88 meters
Y2 0 meters
Potential Thresholds
Maximum