Professional Documents
Culture Documents
ETAP Cable library is built with typical Positive Sequence Reactance (X) and Positive
Sequence Resistance (R) values from either AS3008.1.1:2017 or the Olex Catalogue.
Zero Sequence Reactance and Zero Sequence Resistance values were calculated following
ETAP’s guidelines presented in Appendix A.
The current carrying capacity is taken from AS3008.1.1:2017 considering a single circuit only
with 40˚C ambient temperature and 25˚C ambient soil temperature with no additional
derating factor.
When cable installation information is unavailable, worse case installation has been
considered.
Switchboards:
In the calculation of maximum and minimum fault current, the impedance of the buses and
terminals is neglected.
Protective devices:
For LV switchgear where peak short circuit capacity is not available, it is assumed as per
AS/NZS 61439 Table 7.
The type of the short-circuit involved will remain the same for the duration of the short-
circuit. That is, a three-phase short circuit will remain as a three-phase fault or a line-to-
earth short circuit will remain a line-to-earth fault;
Network conditions will remain unchanged for the duration of the short-circuit;
While these simplifications are not strictly correct for power systems, the calculations will provide
results of acceptable accuracy.
Minimum voltage factor Cmin is used for calculating the short-circuit currents;
When the external networks are represented by equivalent impedances ZQ, the maximum
equivalent short-circuit impedance is applied which would result in the minimum short-
circuit current from the network feeders;
The resistances RL for the cables and the overhead lines are increased to 1.5 times their
resistance at 20˚C;