You are on page 1of 3

Analysis for Transfer Function

Considering a grid connected system with grid as current harmonic


source

Fig. 1: Grid connected System


Considering LCL equivalent as ZLCL;

Fig. 2: Equivalent Circuit


Where,

Z L : Resistive Load

Zg
: Grid Impedance
sC  s 3 L2C  sL
Z LCL : LCL Equivalent = s 2 LC  1

I Ih : I g  I L  I LCL
Where:

I L : Load Current

Ig
: Grid Impedance Current

I LCL : LCL filter Current

Now applying KCL we get,

Vo Vo Vo  1 1 1 
Ih :    Vl    
Z g Z l Z LCL  Z g Z l Z LCL
 
Rearranging;

I h Z l  Z g  Z LCL

Vo Z g Z l Z LCL
Now the transfer function V0/Ih (Output / Input);

Vo Z g Z l Z LCL

I h Z l  Z g  Z LCL

Considering without Grid Impedance the transfer function will be:

Vo ZZ
 l LCL
I h Z l  Z LCL