Do not turn off the system or any valve to make repair Calculation example
or test the system, without placing a roving Fire Patrol Tank type : Fixed roof storage tank
in the area covered by the system. The Patrol should Tank diameter : 40 meters.
continue until the system is put back in service. Also Foam concentrate to be used : AFFF 3%
inform the local security guard and control alarm Pressure at inlet of Foam Chamber : 3.5 kg/sq.cm.
station, so as to avoid false alarm. Flash point of liquid stored in tank : - 27°C.
Surface area = d 2 ÷ 4 = ( 3.14 X 40 2 .) ÷ 4
Each system is to be flushed properly. The vapour seal
must be replaced if the system has been operated. = 1257 Sq. mts.
Normal testing of the chamber can be carried out by a) Foam solution application rate
removing the cover plate from the top of the chamber. = *4.1 LPM /Sq. mts. X Surface area
This allows the system to draw a sample of the = 4.1 X 1257
expanded foam without removing the vapour seal or = 5154 LPM
disconnecting the Foam Chamber from the tank. *4.1 LPM is as per NFPA-11 ( 5 LPM as per OISD
recommendations ) or it should be as per prevailing
The air screen is to be inspected periodically for the rules of local authority having jurisdiction.
obstruction of air inlet holes. If any obstruction is
noticed, remove the same and flush if necessary. b) Number of Foam Chamber required for 40 metres
diameter tank = 3 nos. minimum (Reference
It is recommended to have regular maintenance NFPA-11)
programme to inspect the Vapour Seal Chamber
discharge area and deflector for possible deposit or Capacity of Foam Chamber required
obstruction. = 5154 ÷ 3
= 1718 LPM
NOTE
A PROVISION IS TO BE MADE FOR PRESSURE The K-Factor for flow of 1718 LPM at 3.5 kg./sq.cm.
GAUGE MOUNTING AT INLET OF FOAM CHAMBER, K =Q ÷ P = 1718 ÷ 3.5
WHICH CAN BE PLUGGED AFTER SUCCESSFUL
= 918.30
Note
THE ABOVE ARE THEORETICAL CALCULATIONS. IT IS,
THEREFORE, RECOMENDED THAT SYSTEM DESIGNER
CONSIDERS AN APPROPRIATE FACTOR OF SAFETY
3
= 5154 X X 55
100
= 8505 litres.
Add 5% = 8930 litres.
Note
1. It is recommended to select next higher size of
Foam Chamber when the K-Factor is very much
close to upper limit of the model.
2. For the best performance the inlet pressure at
the Foam Chamber should be 2.8 kg/sq.cm. or
higher.
FIREGUARD SAFETY EQUIPMENT CO. LTD.
www.fireguard-uk.com
Foam Chamber
C
9
8
7
13
14
5
‘A’ F2
A
16
B
4 DETAIL ‘A’
11
15
10
3
12
2
F1
1
- Dimension of inlet / outlet flanges ( F1 / F2 ) are as 10 VAPOUR SEAL RING & SEAT STEEL
per ANSI B16.5 11 VAPOUR SEAL GLASS
12 WING NUT & STUD S.S. 304
- Pipes used are ERW (Seamless Pipes are optional on
request) 13 DISCHARGE PIPE STEEL PIPE
14 OUTLET FLANGE STEEL
15 AIR STRAINER S.S. 304
16 CHAMBER PLATE STEEL
400 2600
2200
300
2000
1800
200 1600
1400
1200
100
1000
800
2 3 4 5 6 7 8 2 3 4 5 6 7 8
INLET PRESSURE (KG./SQ.CM.) INLET PRESSURE (KG./SQ.CM.)
4000
FOAM SOLUTION FLOW (LPM )
3700
800
3400
FOAM SOLUTION FLOW (LPM )
3100
600
2800
2500
400
2200
200 1900
1600
2 3 4 5 6 7 8 2 3 4 5 6 7 8
INLET PRESSURE (KG/CM ) INLET PRESSURE (KG./SQ.CM)
1400
1200
FOAM SOLUTION FLOW (LPM)
1000
800
600
400
2 3 4 5 6 7 8
INLET PRESSURE (KG./SQ.CM)
SIZE 80NB
FIREGUARD SAFETY EQUIPMENT CO. LTD.
www.fireguard-uk.com
200
200
FOAM
DEFLECTOR
MODEL FD
FOAM FOAM
CHAMBER CHAMBER FOAM
DEFLECTOR
MODEL FD 53
STORAGE STORAGE
TANK TANK
ORIFICE ORIFICE
PLATE PLATE