0% found this document useful (0 votes)
215 views7 pages

iCOM Control Board Sensor Settings

The document lists settings for various analog sensors in an iCOM control board, including zero and full scale readings, offsets, and actual current values. It includes sensors for cooling airflow, process airflow, low pressure, high pressure, clogged filter status, water flow, conductivity, humidity, overpressure, waste water level, and compressed air pressure. The settings allow calibrating the sensors and monitoring their real-time readings.

Uploaded by

juan guerrero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
215 views7 pages

iCOM Control Board Sensor Settings

The document lists settings for various analog sensors in an iCOM control board, including zero and full scale readings, offsets, and actual current values. It includes sensors for cooling airflow, process airflow, low pressure, high pressure, clogged filter status, water flow, conductivity, humidity, overpressure, waste water level, and compressed air pressure. The settings allow calibrating the sensors and monitoring their real-time readings.

Uploaded by

juan guerrero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

11/6/2020 iCOM Control Board

Analog Inputs

Devices settings

Cooling Airflow 4-20ma 0-10V 0-5V


Sensor Type

Cooling Airflow Sensor Zero Scale 0 Pa

Cooling Airflow Sensor Full Scale 4000 Pa

Constant/Offset 290 K 0 Pa

Actual Values 0 Pa 0 m³/h

Process Airflow 4-20ma 0-10V 0-5V


Sensor Type

Process Airflow Sensor Zero Scale 0 Pa

Process Airflow Sensor Full Scale 4000 Pa

Constant/Offset 290 K 0 Pa

Actual Values 0 Pa 0 m³/h

Low Pressure 1 4-20ma 0-10V 0-5V


Sensor Type

10.120.22.68/factory/factory-aninput.html 1/7
11/6/2020 iCOM Control Board

Low Pressure Sensor 1 Zero Scale 0.0 bar

Low Pressure Sensor 1 Full Scale 13.4 bar

Offset 0.0 bar

Actual Value 15.3 bar

Low Pressure 2 4-20ma 0-10V 0-5V


Sensor Type

Low Pressure Sensor 2 Zero Scale 0.0 bar

Low Pressure Sensor 2 Full Scale 17.3 bar

Offset 0.0 bar

Actual Value 15.1 bar

HP Sensor 1 Type 4-20ma 0-10V 0-5V

HP Sensor 1 Zero Scale 0.0 bar

HP Sensor 1 Full Scale 45.0 bar

Offset 0.0 bar

Actual Value 15.2 bar

10.120.22.68/factory/factory-aninput.html 2/7
11/6/2020 iCOM Control Board

HP Sensor 2 Type 4-20ma 0-10V 0-5V

HP Sensor 2 Zero Scale 0.0 bar

HP Sensor 2 Full Scale 45.0 bar

Offset 0.0 bar

Actual Value 16.4 bar

Clogged Filter 4-20ma 0-10V 0-5V


Sensor Type

Clogged Filter Sensor Zero Scale 0 Pa

Clogged Filter Sensor Full Scale 250 Pa

Offset 0 Pa

Actual Value 0 Pa

Water Meter Sensor 4-20ma 0-10V 0-5V


Type

Water Meter Sensor Zero Scale 160 l/h

Water Meter Sensor Full Scale 4000 l/h

Offset 0 l/h

Actual Value 0 l/h

10.120.22.68/factory/factory-aninput.html 3/7
11/6/2020 iCOM Control Board

Conductivity Sensor 4-20ma 0-10V 0-5V


Type

Conductivity Sensor Zero Scale 100 uS

Conductivity Sensor Full Scale 2500 uS

Offset 0 uS

Actual Value 2 uS

Humidity Sensor 1 4-20ma 0-10V 0-5V


Type

Humidity Sensor 1 Zero Scale 0 %

Humidity Sensor 1 Full Scale 100 %

Offset 0 %

Actual Value 55 %

Humidity Sensor 2 4-20ma 0-10V 0-5V


Type

Humidity Sensor 2 Zero Scale 100 %

Humidity Sensor 2 Full Scale 20 %

Offset 0 %

Actual Value 0 %

10.120.22.68/factory/factory-aninput.html 4/7
11/6/2020 iCOM Control Board

Humidity Sensor 3 4-20ma 0-10V 0-5V


Type

Humidity Sensor 3 Zero Scale 40 %

Humidity Sensor 3 Full Scale 40 %

Offset 0 %

Actual Value 33 %

Humidity Sensor 4 4-20ma 0-10V 0-5V


Type

Humidity Sensor 4 Zero Scale 0 %

Humidity Sensor 4 Full Scale 0 %

Offset 0 %

Actual Value 32 %

Overpressure 4-20ma 0-10V 0-5V


Sensor 1 Type

10.120.22.68/factory/factory-aninput.html 5/7
11/6/2020 iCOM Control Board

Overpressure Sensor 1 Zero Scale 0 Pa

Overpressure Sensor 1 Full Scale 3000 Pa

Offset 0 Pa

Actual Value 0 Pa

Overpressure 4-20ma 0-10V 0-5V


Sensor 2 Type

Overpressure Sensor 2 Zero Scale 0 Pa

Overpressure Sensor 2 Full Scale 3000 Pa

Offset 0 Pa

Actual Value 0 Pa

Waste Water Sensor 4-20ma 0-10V 0-5V


Type

Waste Water Sensor Zero Scale 100 l/h

Waste Water Sensor Full Scale 2500 l/h

Offset 0 l/h

Actual Value 0 l/h

10.120.22.68/factory/factory-aninput.html 6/7
11/6/2020 iCOM Control Board

CAP Press. Zero Scale 0 Pa

CAP Press. Full Scale 50 Pa

Probe 1 Probe 2

Offset 0 Pa 0 Pa

Actual Value 0 Pa 0 Pa

Save Cancel

© Vertiv 03:06 PM V 2.5.1R

10.120.22.68/factory/factory-aninput.html 7/7