ETHIOPIAN ELECTRIC POWER (EEP)

TRANSMISSION & SUBSTATION ENGINEERING OFFICE,


EEP

CONTRACTAKAKBL-LOT1:
DESIGN,MANUFACTURE,SUPPLY & CONSTRUCTION 400& 230kV
SUBSTATIONS BOLE LEMI & KLINTO INDUSTRIAL ZONE POWE
TRANSMISSION PROJECT

CONTRACT NO. CO/33.20/124/08

230/33kV BOLE LEMI SUBSTATION


CALCULATION NOTE
- PROTECTION RELAY SETTING
- 33KV FEEDER

FOR REVIEW
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET REV A05

Table of Contents
Table of Contents........................................................................................2

1 Technical Data..........................................................................................1

1.1. Parameters of 33kV Line...............................................................................................1


1.2. Parameters of 33kV Bus Section...................................................................................1
1.3. Parameters of 33kV Aux. Transformer..........................................................................1
1.4. Parameters of 33kV Capacitor......................................................................................1

2 Calculating Protection Settings.............................................................2

2.1 Overcurrent Protection of 33kV Line......................................................................2


2.2 Zero Sequence Overcurrent Protection of 33kV Line..............................................3
2.3 Overcurrent Protection of 33kV Bus Section...........................................................4
2.4 Zero Sequence Overcurrent Protection of 33kV Bus Section...................................5
2.5 Overcurrent Protection of 33kV Aux. Transformer..................................................6
2.6 Zero Sequence Overcurrent Protection of 33kV Aux. Transformer..........................7
2.7 Protection of 33kV Shunt Capacitor........................................................................7

3 Protection Settings Lists......................................................................10

3.1 Settings List of 33kV Line......................................................................................10


3.2 Settings List of 33kV Bus Section..........................................................................17
3.3 Settings List of 33kV Aux. Transformer.................................................................24
3.4 Settings List of 33kV Capacitor.............................................................................32
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET REV A05
1 Technical Data
1.1. Parameters of 33kV Line

Rated voltage 33kV Rated current 250A


CT ratio 400/1

1.2. Parameters of 33kV Bus Section

Rated voltage 33kV Rated current 2500A


CT ratio 2500/1

1.3. Parameters of 33kV Aux. Transformer

Rated voltage 33kV Rated capacity 315 KVA


CT ratio 75/1

1.4. Parameters of 33kV Capacitor

Fundamental wave Maximum harmonic current


15Mvar 208.33A
capacity (A)

Rated voltage 33kV Connect type Star

Series segment number in


Shunt group number in a single-
a single-phase capacitor 2 6
phase capacitor (M)
(N)

Series number of Shunt number of capacitor unit


5 10
capacitor unit(n) (m)

CT Parameter
CT Position CT Ratio Type Connection
Branch CT 100/1 — Y
VT Parameter

1
VT Position VT Ratio Type
33 0.1
Reactor HV side / kV —
√3 √3
2 Calculating Protection Settings
2.1 Overcurrent Protection of 33kV Line

2.1.1 Basic Parameters

CT ratio: 400/1

VT ratio:33kV/100V

2.1.2 The Stage 1 Overcurrent Protection

The current setting set as 0.5*minimumtwo phase bus fault current.

0.5*10530
I op .stage 1= =13.163 A
400 /1
 Time setting

t1  0 s It is used to trip circuit breakers of 33kV line.

2.1.3 The Stage 2 Overcurrent Protection

The current setting set as 500% of rated current.

250  5
I op.stage 2   3.125A
400 /1

 Time setting

t2  0.3s It is used to trip circuit breakers of 33kV line.

2.1.4 The Stage 4 Overcurrent Protection

 Current setting

The current setting set as 1.2* Line capability (1.2*250) with TMS 0.2.

1.2∗250
I op .stage 4= =1.25 A
400/1
 Time setting

Using Standard Inverse characteristic. The time delay set to achieve an operating stage2

timeof 0.5 seconds under maximum let through conditions.

2
0.14
t= 0.02
∗TMS=0.5 , I f =13140 / K ct =32.85 A
If
( )
IS
−1

Hence, TMS=0.2, take TMS=0.2

It is used to trip circuit breakers of 33kV line.

2.2 Zero Sequence Overcurrent Protection of 33kV Line

2.2.1 Parameters

CT ratio : 400/1

2.2.2 The Stage 1 Zero Sequence Overcurrent Protection

 Current setting

The current setting set as 90A with a time setting of 0.3 second.

90
I op .stage 1= =0.225 A
400/1
 Time setting
t 1=0.3 s It is used to trip circuit breakers of 33kV line.

2.2.3The Stage 4 Zero Sequence Overcurrent Protection

 Current setting

The current setting set as 20% of rated current.

0.2  250
I op.stage 4   0.125A
400
 Time setting

With TMS is set to 0.1and I f =200 A (measured current by the relay), then the tripping time will be:

0.14 0.14
t= 0.02
∗TMS= 0.02
× 0.1=0.5 sec
If 200
( )
IS
−1 ( 0.125∗400 ) −1

It is used to trip circuit breakers.

3
2.3 Overcurrent Protection of 33kV Bus Section

2.3.1 Parameters

CT ratio: 2500/1

2.3.2 The Stage 1 Overcurrent Protection

 Current setting

The current setting set as maximum fault current at the busbar.

I op.stage1  13140/2500=5.26A

 Time setting

t1  0 s It is used to trip circuit breakers of 33kV Bus Section.

2.3.3The Stage 2 Overcurrent Protection

 Current setting

The current setting set as 2 times rated current.

I op.stage 2  2*2500/2500=2A

 Time setting

t2  0.3s It is used to trip circuit breakers of 33kV Bus Section.

2.3.4The Stage 4 Overcurrent Protection

 Current setting

The current setting set as 2 timesof rated current.

2500  2
I op.stage 2   2A
2500 /1

 Time setting

Using Standard Inverse characteristic. The time delay set to achieve an operating stage2

time of 0.3 seconds under minimum bus bar fault.

4
0.14
t= 0.02
∗TMS=0.3 , I f =13140 / K ct =5.26 A
If
( )
IS
−1

Hence, TMS=0.06 .

2.4 Zero Sequence Overcurrent Protection of 33kV Bus Section

2.4.1 Parameters

CT ratio: 2500/1

2.4.2 The Stage1 Zero Sequence Overcurrent Protection

The current setting set as 20% of rated current.

I op.stage1  0.2A

 Time setting

t1  0 s It is used to trip circuit breakers of 33kV Bus Section.

It is used to trip circuit breakers.

2.4.3 The Stage 4 Zero Sequence Overcurrent Protection

 Current setting

The current setting set as 10% of rated current.

2500  0.1
I op.stage 4   0.1A
2500 /1

 Time setting

Using Standard Inverse characteristic. The time delay set to achieve an operating time of 0. 1

seconds under minimum bus bar fault.

0.14
t= 0.02
∗TMS=0.1, I f =10671 / K ct =4.27 A
If
( )
IS
−1

Hence, TMS=0.06

5
2.5 Overcurrent Protection of 33kV Aux. Transformer

2.5.1 Basic Parameters

CT ratio : 75/1

VT ratio:33kV/100V

2.5.2 The Stage 4 Overcurrent Protection

 Current setting

Auxiliary Transformer natural power = 315kVA

Then Imax =5.5A

The current setting should be greater than the rated current of the Aux. transformer.

K rel I 1.2 5.5


I op.stage 4   rated    0.1A
K dropoff KCT 0.95 75 /1

Where:

K rel
is the reliability coefficient, and it is taken as 1.2.

K dropoff is the drop-off coefficient, and it is taken as 0.95.

I rated
is the rated current of 33kV Aux. transformer.

KCT is the CT ratio.

 Time setting

With TMS=0.15, I f =200A,then:

0.14
t= 0.02
∗TMS=0.31 s
If
( )
IS
−1

6
2.6 Zero Sequence Overcurrent Protection of 33kV Aux.

Transformer

2.6.1 Parameters

CT ratio : 75/1

2.6.2 The Stage 4 Zero Sequence Overcurrent Protection

CT ratio factor ki : 75
Earth fault current factor R : 0.1
Line nominal current In : 5.5 A
In  R 5.5 A  0.1
 =0.05
Setting IN> = Ki 75

 Time setting

 With TMS is set to 0.1 and I f =100 A (measured current by the relay), then the tripping time will be:

0.14 0.14
t= 0.02
∗TMS= ×0.1=0.2 sec
If 100 0.02
( )
IS
−1 ( 0.05∗75 ) −1

It is used to trip circuit breakers.

2.7 Protection of 33kV Shunt Capacitor

 CT ratio: 100/1, unbalance protection CT ratio: 5/1

2.7.1 The Overcurrent Protection

 Setting of stage1 overcurrent

The setting of the stage 1 overcurrent protection:

Qc 1 15 ×1 06 1
3× × =3 × 3
× =7.873 A
√ 3× U n K ct √ 3 × 33× 1 0 1 00

Where:
Qc is capacity of the capacitor

7
Un is rated voltage
Kct is CT ratio

Time setting

The time setting is taken as 0.00s

 Setting of stage2 overcurrent

The setting of the stage 2 overcurrent protection:

Qc 1 15 ×1 06 1
1.5 × × =1.5 × 3
× =3.936 A
√3 × U n K ct √ 3 ×33 × 10 100

Time setting

The time setting is taken as 1.5s

2.7.2 Unbalance Current Protection

 Setting of Instantaneous Unbalance Current (60)

Allowed removal component number of in the same string segment within the capacitor

3 MNmn (K V −1)
K=
K V (3 MNn−3 MN +6 N −5)

Here, “Kv” is taken as 1.7225, so K is 5

Where:

M is parallel group numbers in a single-phase capacitor, M=6

N is series group numbers in a single-phase capacitor, N=2

m is parallel elements numbers in a group capacitor, m=10

n is series elements numbers in a group capacitor, n=5

Kv is factor permissive of over voltage, Kv=1.7225 recommend by manufacturer for tripping

K is Allowed removal component number

The unbalance current setting of the unbalance current protection

Qc
1.5 K
√ 3× U n 1
I o= =0.406 A
3 MNmn−K (3 MNn−3 MN +6 N −5) K ct
Considering sensitivity recommended by manufacturer,
hence, set Iun=0.406/1.1=0.364A

8
Time setting

The time setting is taken as 0.03s

 Setting of Unbalance Current (60)

Allowed removal component number of in the same string segment within the capacitor

3 MNmn( K V −1)
K=
K V (3 MNn−3 MN +6 N −8)

Here, “Kv” is taken as 1.505 recommended by manufacturer, so K is4

The unbalance current setting of the unbalance current protection

Qc
1.5 K
√ 3× U n 1
I o= =0. 2801 A
K
3 MNmn−K (3 MNn−3 MN +6 N −5) ct
Considering sensitivity recommended by manufacturer,,
hence, set Iun=0.2801/1.1=0.255A
Time setting

The time setting is taken as 0.2s

 Setting of Unbalance Currentalarm (60)

Allowed removal component number of in the same string segment within the capacitor

3 MNmn( K V −1)
K=
K V (3 MNn−3 MN +6 N −8)

Here, “Kv” is taken as 1.0916 recommended by manufacturer, so K is1,thelossofthefirstelement

The unbalance current setting of the unbalance current protection

Qc
1.5 K
√ 3× U n 1
I o= =0. 05078 A
K
3 MNmn−K (3 MNn−3 MN +6 N −5) ct
Considering sensitivity recommended by manufacturer,,
hence, set Iun=0.05078/1.1=0.046A for alarm
Time setting

The time setting is taken as 10s

Note: The unbalance current setting should be revised during commissioning considering the
natural unbalance of the capacitor banks.

9
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 10 REV A05

3 Protection Settings Lists


3.1 Settings List of33kV Line

3.1.1 Device model: PCS-9611

System Settings
No. Item Value Unit Remark
1 Active_Grp 1   The active setting group number
2 Opt_SysFreq 0   Select the rated system frequency: “0”, 50Hz; “1”, 60Hz
3 PrimaryEquip_Name /   The name of the protected primary equipment
4 Prot.I1n 400 A Rated primary value of protection phase CT
5 Prot.I2n 1 A Rated secondary value of protection phase CT
6 Measmt.I1n 400 A Rated primary value of metering phase CT
7 Measmt.I2n 1 A Rated secondary value of metering phase CT
8 Neu1.I1n 400 A Rated primary value of the No.1 zero sequence CT
9 Neu1.I2n 1 A Rated secondary value of the No.1 zero sequence CT
10 Neu2.I1n / A Rated primary value of the No.2 zero sequence CT
11 Neu2.I2n 1 A Rated secondary value of the No.2 zero sequence CT
12 SEF.I1n / A Rated primary value of sensitive zero sequence CT
13 SEF.I2n 1 A Rated secondary value of sensitive zero sequence CT
14 Prot.U1n 33 kV Rated primary value of protection VT

10
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 11 REV A05

15 Prot.U2n 100 V Rated secondary value of protection VT


16 Syn.U1n / kV Rated primary value of synchro-check VT
17 Syn.U2n / V Rated secondary value of synchro-check VT
18 Delt.U1n / kV Rated primary value of zero sequence VT
19 Delt.U2n / V Rated secondary value of zero sequence VT
Zero sequence current is self calculated
20 Opt_3I0 1  
0:from neutral CT; 1:self calculated
Zero sequence voltage is self calculated
21 Opt_3U0 1  
0:from neutral VT; 1:self calculated
22 Opt_PwrDir /   Power Measurement Mode
Overcurrent Protection Settings (OC Settings)
No. Item Value Unit Remark

1 50/51P.U2_VCE 4.62 V The voltage setting of the negative sequence voltage blocking element (phase voltage)

2 50/51P.Upp_VCE 70 V The voltage setting of the low voltage blocking element (phase-tophase voltage)

50/51P.En_VCE_Cro
3 0   The logic setting of the external voltage control function
ssCtrl
4 50/51P.RCA / ° The relay characteristic angle for the directional overcurrent protection
The logic setting of the function which can block the OC protection related voltage measurement when the
5 50/51P.En_VTS_Blk 0  
voltage transformer is failed

6 50/51P.K_Hm2 0   The percent setting of the harmonic blocking element for OC protection

7 50/51P.I_Rls_HmBlk / A The current setting for releasing the harmonic blocking element of OC protection

The setting is used to select the harmonic blocking mode of OC protection.


8 50/51P.Opt_Hm_Blk /  
1: Phase blocking; 2: Cross blocking; 3: Maximum blocking

11
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 12 REV A05

9 50/51P1.I_Set 13.163 A The current setting of the stage 1 overcurrent protection


10 50/51P1.t_Op 0 s The time setting of the stage 1 overcurrent protection

11 50/51P1.En_VCE 0   The logic setting of the voltage control element for the stage 1 overcurrent protection

The setting is used to select the directional mode for the stage 1 overcurrent protection.
12 50/51P1.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

13 50/51P1.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 1 overcurrent protection

14 50/51P1.En 1   The logic setting of the stage 1 overcurrent protection


15 50/51P1.OutMap 0005   The output matrix setting of the stage 1 overcurrent protection
16 50/51P2.I_Set 3.125 A The current setting of the stage 2 overcurrent protection
17 50/51P2.t_Op 0.3 s The time setting of the stage 2 overcurrent protection

18 50/51P2.En_VCE 0   The logic setting of the voltage control element for the stage 2 overcurrent protection

The setting is used to select the directional mode for the stage 2 overcurrent protection.
19 50/51P2.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

20 50/51P2.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 2 overcurrent protection

21 50/51P2.En 1   The logic setting of the stage 2 overcurrent protection


22 50/51P2.OutMap 0005   The output matrix setting of the stage 2 overcurrent protection
23 50/51P3.I_Set 30 A The current setting of the stage 3 overcurrent protection
24 50/51P3.t_Op 10 s The time setting of the stage 3 overcurrent protection

25 50/51P3.En_VCE 0   The logic setting of the voltage control element for the stage 3 overcurrent protection

The setting is used to select the directional mode for the stage 3 overcurrent protection.
26 50/51P3.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

27 50/51P3.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 3 overcurrent protection

12
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 13 REV A05

28 50/51P3.En 0   The logic setting of the stage 3 overcurrent protection


29 50/51P3.OutMap 0   The output matrix setting of the stage 3 overcurrent protection

30 50/51P3.Opt_Curve 0   The setting is for selecting the inverse time characteristic curve for OC3 protection

31 50/51P3.TMS 1   The time multiplier setting of the stage 3 IDMT overcurrent protection

32 50/51P3.tmin 10 s The minimum operation time setting of the stage 3 IDMT overcurrent protection

33 50/51P3.K 0.14   Constant “k” for the stage 3 IDMT overcurrent protection
34 50/51P3.C 0   Constant “C” for the stage 3 IDMT overcurrent protection
35 50/51P3.Alpha 0.02   Constant “α” for the stage 3 IDMT overcurrent protection
36 50/51P4.I_Set 1.25 A The current setting of the stage 4 overcurrent protection
37 50/51P4.t_Op 0.5 s The time setting of the stage 4 overcurrent protection

38 50/51P4.En_VCE 0   The logic setting of the voltage control element for the stage 4 overcurrent protection

The setting is used to select the directional mode for the stage 4 overcurrent protection.
39 50/51P4.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

40 50/51P4.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 4 overcurrent protection

41 50/51P4.En 1   The logic setting of the stage 4 overcurrent protection


42 50/51P4.OutMap 0005   The output matrix setting of the stage 4 overcurrent protection

43 50/51P4.Opt_Curve 1   The setting is for selecting the inverse time characteristic curve for OC4 protection

44 50/51P4.TMS 0.2   The time multiplier setting of the stage 4 IDMT overcurrent protection

45 50/51P4.tmin 0.02 s The minimum operation time setting of the stage 4 IDMT overcurrent protection

46 50/51P4.K 0.14   Constant “k” for the stage 4 IDMT overcurrent protection
47 50/51P4.C 0   Constant “C” for the stage 4 IDMT overcurrent protection
48 50/51P4.Alpha 0.02   Constant “α” for the stage 4 IDMT overcurrent protection

13
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 14 REV A05

49 50/51P5.I_Set / A The current setting of the stage 5 overcurrent protection


50 50/51P5.t_Op / s The time setting of the stage 5 overcurrent protection
51 50/51P5.En 0   The logic setting of the stage 5 overcurrent protection
52 50/51P6.I_Set / A The current setting of the stage 6 overcurrent protection
53 50/51P6.t_Op / s The time setting of the stage 6 overcurrent protection
54 50/51P6.En 0   The logic setting of the stage 6 overcurrent protection

55 50/51P.I_CCE / A The current setting of the heavy current blocking element for the overcurrent protection

56 50/51P.En_CCE 0   The logic setting of the heavy current blocking element for the overcurrent protection

No.1 Zero Sequence Overcurrent Protection Settings(EF1 Settings)


No. Item Value Unit Remark

1 50/51G.RCA / ° The relay characteristic angle for the No.1 directional zero sequence overcurrent protection

The logic setting of the function which blocks the No.1 ROC protection related voltage measurement when the
2 50/51G.En_VTS_Blk 0  
voltage transformer is failed

3 50/51G.K_Hm2 0   The percent setting of the harmonic blocking element for the No.1 ROC protection

50/51G.3I0_Rls_Hm
4 / A The current setting for releasing the harmonic blocking element of the No.1 ROC protection
Blk
5 50/51G1.3I0_Set 0.225 A The current setting of the No.1 stage 1 zero sequence overcurrent protection

6 50/51G1.t_Op 0.3 s The time setting of the No.1 stage 1 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC1 protection.
7 50/51G1.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

8 50/51G1.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC1 protection

14
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 15 REV A05

9 50/51G1.En 1   The logic setting of the No.1 stage 1 zero sequence overcurrent protection

10 50/51G1.OutMap 0005   The output matrix setting of the No.1 stage 1 zero sequence overcurrent protection

11 50/51G2.3I0_Set 30 A The current setting of the No.1 stage 2 zero sequence overcurrent protection

12 50/51G2.t_Op 10 s The time setting of the No.1 stage 2 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC2 protection.
13 50/51G2.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

14 50/51G2.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC2 protection

15 50/51G2.En 0   The logic setting of the No.1 stage 2 zero sequence overcurrent protection

16 50/51G2.OutMap 0   The output matrix setting of the No.1 stage 2 zero sequence overcurrent protection

17 50/51G3.3I0_Set 30 A The current setting of the No.1 stage 3 zero sequence overcurrent protection

18 50/51G3.t_Op 10 s The time setting of the No.1 stage 3 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC3 protection.
19 50/51G3.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

20 50/51G3.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC3 protection

21 50/51G3.En 0   The logic setting of the No.1 stage 3 zero sequence overcurrent protection

22 50/51G3.OutMap 0   The output matrix setting of the No.1 stage 3 zero sequence overcurrent protection

23 50/51G3.Opt_Curve 0   The setting is for selecting the inverse time characteristic curve for the No.1 ROC3 protection

24 50/51G3.TMS 1   The time multiplier setting of the No.1 stage 3 zero sequence IDMT overcurrent protection

15
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 16 REV A05

25 50/51G3.tmin 10 s The minimum operation time setting of the No.1 stage 3 zero sequence IDMT overcurrent protection

26 50/51G3.K 0.14   Constant “k” for the No.1 stage 3 zero sequence IDMT overcurrent protection

27 50/51G3.C 0   Constant “C” for the No.1 stage 3 zero sequence IDMT overcurrent protection

28 50/51G3.Alpha 1   Constant “α” for the No.1 stage 3 zero sequence IDMT overcurrent protection

29 50/51G4.3I0_Set 0.125 A The current setting of the No.1 stage 4 zero sequence overcurrent protection

30 50/51G4.t_Op 0.3 s The time setting of the No.1 stage 4 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC4 protection.
31 50/51G4.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

32 50/51G4.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC4 protection

33 50/51G4.En 1   The logic setting of the No.1 stage 4 zero sequence overcurrent protection

34 50/51G4.OutMap 0005   The output matrix setting of the No.1 stage 4 zero sequence overcurrent protection

35 50/51G4.Opt_Curve 1   The setting is for selecting the inverse time characteristic curve for the No.1 ROC4 protection

36 50/51G4.TMS 0.1   The time multiplier setting of the No.1 stage 4 zero sequence IDMT overcurrent protection

37 50/51G4.tmin 0.02 s The minimum operation time setting of the No.1 stage 4 zero sequence IDMT overcurrent protection

38 50/51G4.K 0.14   Constant “k” for the No.1 stage 4 zero sequence IDMT overcurrent protection

39 50/51G4.C 0   Constant “C” for the No.1 stage 4 zero sequence IDMT overcurrent protection

40 50/51G4.Alpha 0.02   Constant “α” for the No.1 stage 4 zero sequence IDMT overcurrent protection

41 50/51G5.3I0_Set / A The current setting of the No.1 stage 5 zero sequence overcurrent protection

16
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 17 REV A05

42 50/51G5.t_Op / s The time setting of the No.1 stage 5 zero sequence overcurrent protection

43 50/51G5.En 0   The logic setting of the No.1 stage 5 zero sequence overcurrent protection

44 50/51G6.3I0_Set / A The current setting of the No.1 stage 6 zero sequence overcurrent protection

45 50/51G6.t_Op / s The time setting of the No.1 stage 6 zero sequence overcurrent protection

46 50/51G6.En 0   The logic setting of the No.1 stage 6 zero sequence overcurrent protection

Supervision Element Settings (Superv Settings)


No. Item Value Unit Remark
1 CTS.3I0_Set 0.1 A The threshold current setting of the CTS element
2 CTS.3U0_Set 5 V The threshold voltage setting of the CTS element
3 CTS.En 1   The logic setting of the CTS element
4 VTS.I_Set 1 A The phase current setting of the protection VTS element
5 VTS.I2_Set 0.1 A The negative sequence current setting of the protection VTS element
6 VTS.En 0   The logic setting of the protection VTS element
7 VTS.En_SynVT 0   The logic setting of the synchro-check VTS element

3.2 Settings List of 33kV Bus Section

3.2.1 Device model: PCS-9611

System Settings
No. Item Value Unit Remark

17
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 18 REV A05

1 Active_Grp 1   The active setting group number


2 Opt_SysFreq 0   Select the rated system frequency: “0”, 50Hz; “1”, 60Hz
3 PrimaryEquip_Name /   The name of the protected primary equipment
4 Prot.I1n 2500 A Rated primary value of protection phase CT
5 Prot.I2n 1 A Rated secondary value of protection phase CT
6 Measmt.I1n 2500 A Rated primary value of metering phase CT
7 Measmt.I2n 1 A Rated secondary value of metering phase CT
8 Neu1.I1n 2500 A Rated primary value of the No.1 zero sequence CT
9 Neu1.I2n 1 A Rated secondary value of the No.1 zero sequence CT
10 Neu2.I1n / A Rated primary value of the No.2 zero sequence CT
11 Neu2.I2n 1 A Rated secondary value of the No.2 zero sequence CT
12 SEF.I1n / A Rated primary value of sensitive zero sequence CT
13 SEF.I2n 1 A Rated secondary value of sensitive zero sequence CT
14 Prot.U1n 33 kV Rated primary value of protection VT
15 Prot.U2n 100 V Rated secondary value of protection VT
16 Syn.U1n / kV Rated primary value of synchro-check VT
17 Syn.U2n / V Rated secondary value of synchro-check VT
18 Delt.U1n / kV Rated primary value of zero sequence VT
19 Delt.U2n / V Rated secondary value of zero sequence VT
Zero sequence current is self calculated
20 Opt_3I0 1  
0:from neutral CT; 1:self calculated
Zero sequence voltage is self calculated
21 Opt_3U0 1  
0:from neutral VT; 1:self calculated
22 Opt_PwrDir /   Power Measurement Mode
Overcurrent Protection Settings (OC Settings)

18
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 19 REV A05

No. Item Value Unit Remark

1 50/51P.U2_VCE 4.62 V The voltage setting of the negative sequence voltage blocking element (phase voltage)

2 50/51P.Upp_VCE 70 V The voltage setting of the low voltage blocking element (phase-tophase voltage)

50/51P.En_VCE_CrossCtr
3 0   The logic setting of the external voltage control function
l
4 50/51P.RCA / ° The relay characteristic angle for the directional overcurrent protection
The logic setting of the function which can block the OC protection related voltage measurement when the
5 50/51P.En_VTS_Blk 0  
voltage transformer is failed

6 50/51P.K_Hm2 0   The percent setting of the harmonic blocking element for OC protection

7 50/51P.I_Rls_HmBlk / A The current setting for releasing the harmonic blocking element of OC protection

The setting is used to select the harmonic blocking mode of OC protection.


8 50/51P.Opt_Hm_Blk /  
1: Phase blocking; 2: Cross blocking; 3: Maximum blocking
9 50/51P1.I_Set 5.26 A The current setting of the stage 1 overcurrent protection
10 50/51P1.t_Op 0 s The time setting of the stage 1 overcurrent protection

11 50/51P1.En_VCE 0   The logic setting of the voltage control element for the stage 1 overcurrent protection

The setting is used to select the directional mode for the stage 1 overcurrent protection.
12 50/51P1.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

13 50/51P1.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 1 overcurrent protection

14 50/51P1.En 1   The logic setting of the stage 1 overcurrent protection


15 50/51P1.OutMap 0005   The output matrix setting of the stage 1 overcurrent protection
16 50/51P2.I_Set 2 A The current setting of the stage 2 overcurrent protection
17 50/51P2.t_Op 0.3 s The time setting of the stage 2 overcurrent protection

19
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 20 REV A05

18 50/51P2.En_VCE 0   The logic setting of the voltage control element for the stage 2 overcurrent protection

The setting is used to select the directional mode for the stage 2 overcurrent protection.
19 50/51P2.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

20 50/51P2.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 2 overcurrent protection

21 50/51P2.En 1   The logic setting of the stage 2 overcurrent protection


22 50/51P2.OutMap 0005   The output matrix setting of the stage 2 overcurrent protection
23 50/51P3.I_Set 30 A The current setting of the stage 3 overcurrent protection
24 50/51P3.t_Op 10 s The time setting of the stage 3 overcurrent protection

25 50/51P3.En_VCE 0   The logic setting of the voltage control element for the stage 3 overcurrent protection

The setting is used to select the directional mode for the stage 3 overcurrent protection.
26 50/51P3.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

27 50/51P3.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 3 overcurrent protection

28 50/51P3.En 0   The logic setting of the stage 3 overcurrent protection


29 50/51P3.OutMap 0   The output matrix setting of the stage 3 overcurrent protection

30 50/51P3.Opt_Curve 0   The setting is for selecting the inverse time characteristic curve for OC3 protection

31 50/51P3.TMS 1   The time multiplier setting of the stage 3 IDMT overcurrent protection

32 50/51P3.tmin 10 s The minimum operation time setting of the stage 3 IDMT overcurrent protection

33 50/51P3.K 0.14   Constant “k” for the stage 3 IDMT overcurrent protection
34 50/51P3.C 0   Constant “C” for the stage 3 IDMT overcurrent protection
35 50/51P3.Alpha 0.02   Constant “α” for the stage 3 IDMT overcurrent protection
36 50/51P4.I_Set 2 A The current setting of the stage 4 overcurrent protection
37 50/51P4.t_Op 0.3 s The time setting of the stage 4 overcurrent protection

20
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 21 REV A05

38 50/51P4.En_VCE 0   The logic setting of the voltage control element for the stage 4 overcurrent protection

The setting is used to select the directional mode for the stage 4 overcurrent protection.
39 50/51P4.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

40 50/51P4.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 4 overcurrent protection

41 50/51P4.En 1   The logic setting of the stage 4 overcurrent protection


42 50/51P4.OutMap 0005   The output matrix setting of the stage 4 overcurrent protection

43 50/51P4.Opt_Curve 1   The setting is for selecting the inverse time characteristic curve for OC4 protection

44 50/51P4.TMS 0.06   The time multiplier setting of the stage 4 IDMT overcurrent protection

45 50/51P4.tmin 0.02 s The minimum operation time setting of the stage 4 IDMT overcurrent protection

46 50/51P4.K 0.14   Constant “k” for the stage 4 IDMT overcurrent protection
47 50/51P4.C 0   Constant “C” for the stage 4 IDMT overcurrent protection
48 50/51P4.Alpha 0.02   Constant “α” for the stage 4 IDMT overcurrent protection
49 50/51P5.I_Set / A The current setting of the stage 5 overcurrent protection
50 50/51P5.t_Op / s The time setting of the stage 5 overcurrent protection
51 50/51P5.En 0   The logic setting of the stage 5 overcurrent protection
52 50/51P6.I_Set / A The current setting of the stage 6 overcurrent protection
53 50/51P6.t_Op / s The time setting of the stage 6 overcurrent protection
54 50/51P6.En 0   The logic setting of the stage 6 overcurrent protection

55 50/51P.I_CCE / A The current setting of the heavy current blocking element for the overcurrent protection

56 50/51P.En_CCE 0   The logic setting of the heavy current blocking element for the overcurrent protection

No.1 Zero Sequence Overcurrent Protection Settings(EF1 Settings)


No. Item Value Unit Remark

21
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 22 REV A05

1 50/51G.RCA / ° The relay characteristic angle for the No.1 directional zero sequence overcurrent protection

The logic setting of the function which blocks the No.1 ROC protection related voltage measurement when
2 50/51G.En_VTS_Blk 0  
the voltage transformer is failed

3 50/51G.K_Hm2 0   The percent setting of the harmonic blocking element for the No.1 ROC protection

4 50/51G.3I0_Rls_HmBlk / A The current setting for releasing the harmonic blocking element of the No.1 ROC protection

5 50/51G1.3I0_Set 0.2 A The current setting of the No.1 stage 1 zero sequence overcurrent protection

6 50/51G1.t_Op 0 s The time setting of the No.1 stage 1 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC1 protection.
7 50/51G1.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

8 50/51G1.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC1 protection

9 50/51G1.En 1   The logic setting of the No.1 stage 1 zero sequence overcurrent protection

10 50/51G1.OutMap 0005   The output matrix setting of the No.1 stage 1 zero sequence overcurrent protection

11 50/51G2.3I0_Set 30 A The current setting of the No.1 stage 2 zero sequence overcurrent protection

12 50/51G2.t_Op 10 s The time setting of the No.1 stage 2 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC2 protection.
13 50/51G2.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

14 50/51G2.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC2 protection

15 50/51G2.En 0   The logic setting of the No.1 stage 2 zero sequence overcurrent protection

16 50/51G2.OutMap 0   The output matrix setting of the No.1 stage 2 zero sequence overcurrent protection

22
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 23 REV A05

17 50/51G3.3I0_Set 30 A The current setting of the No.1 stage 3 zero sequence overcurrent protection

18 50/51G3.t_Op 10 s The time setting of the No.1 stage 3 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC3 protection.
19 50/51G3.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

20 50/51G3.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC3 protection

21 50/51G3.En 0   The logic setting of the No.1 stage 3 zero sequence overcurrent protection

22 50/51G3.OutMap 0   The output matrix setting of the No.1 stage 3 zero sequence overcurrent protection

23 50/51G3.Opt_Curve 0   The setting is for selecting the inverse time characteristic curve for the No.1 ROC3 protection

24 50/51G3.TMS 1   The time multiplier setting of the No.1 stage 3 zero sequence IDMT overcurrent protection

25 50/51G3.tmin 10 s The minimum operation time setting of the No.1 stage 3 zero sequence IDMT overcurrent protection

26 50/51G3.K 0.14   Constant “k” for the No.1 stage 3 zero sequence IDMT overcurrent protection

27 50/51G3.C 0   Constant “C” for the No.1 stage 3 zero sequence IDMT overcurrent protection

28 50/51G3.Alpha 1   Constant “α” for the No.1 stage 3 zero sequence IDMT overcurrent protection

29 50/51G4.3I0_Set 0.1 A The current setting of the No.1 stage 4 zero sequence overcurrent protection

30 50/51G4.t_Op 0.1 s The time setting of the No.1 stage 4 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC4 protection.
31 50/51G4.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

32 50/51G4.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC4 protection

23
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 24 REV A05

33 50/51G4.En 1   The logic setting of the No.1 stage 4 zero sequence overcurrent protection

34 50/51G4.OutMap 0005   The output matrix setting of the No.1 stage 4 zero sequence overcurrent protection

35 50/51G4.Opt_Curve 1   The setting is for selecting the inverse time characteristic curve for the No.1 ROC4 protection

36 50/51G4.TMS 0.06   The time multiplier setting of the No.1 stage 4 zero sequence IDMT overcurrent protection

37 50/51G4.tmin 0.02 s The minimum operation time setting of the No.1 stage 4 zero sequence IDMT overcurrent protection

38 50/51G4.K 0.14   Constant “k” for the No.1 stage 4 zero sequence IDMT overcurrent protection

39 50/51G4.C 0   Constant “C” for the No.1 stage 4 zero sequence IDMT overcurrent protection

40 50/51G4.Alpha 0.02   Constant “α” for the No.1 stage 4 zero sequence IDMT overcurrent protection

41 50/51G5.3I0_Set / A The current setting of the No.1 stage 5 zero sequence overcurrent protection

42 50/51G5.t_Op / s The time setting of the No.1 stage 5 zero sequence overcurrent protection

43 50/51G5.En 0   The logic setting of the No.1 stage 5 zero sequence overcurrent protection

44 50/51G6.3I0_Set / A The current setting of the No.1 stage 6 zero sequence overcurrent protection

45 50/51G6.t_Op / s The time setting of the No.1 stage 6 zero sequence overcurrent protection

46 50/51G6.En 0   The logic setting of the No.1 stage 6 zero sequence overcurrent protection

Supervision Element Settings (Superv Settings)


No. Item Value Unit Remark
1 CTS.3I0_Set 0.1 A The threshold current setting of the CTS element
2 CTS.3U0_Set 5 V The threshold voltage setting of the CTS element
3 CTS.En 1   The logic setting of the CTS element

24
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 25 REV A05

4 VTS.I_Set 1 A The phase current setting of the protection VTS element


5 VTS.I2_Set 0.1 A The negative sequence current setting of the protection VTS element
6 VTS.En 0   The logic setting of the protection VTS element
7 VTS.En_SynVT 0   The logic setting of the synchro-check VTS element

3.3 Settings List of 33kV Aux. Transformer

3.3.1 Device model: PCS-9611

System Settings
No. Item Value Unit Remark
1 Active_Grp 1   The active setting group number
2 Opt_SysFreq 0   Select the rated system frequency: “0”, 50Hz; “1”, 60Hz
3 PrimaryEquip_Name /   The name of the protected primary equipment
4 Prot.I1n 75 A Rated primary value of protection phase CT
5 Prot.I2n 1 A Rated secondary value of protection phase CT
6 Measmt.I1n 75 A Rated primary value of metering phase CT
7 Measmt.I2n 1 A Rated secondary value of metering phase CT
8 Neu1.I1n 75 A Rated primary value of the No.1 zero sequence CT
9 Neu1.I2n 1 A Rated secondary value of the No.1 zero sequence CT
10 Neu2.I1n / A Rated primary value of the No.2 zero sequence CT
11 Neu2.I2n 1 A Rated secondary value of the No.2 zero sequence CT
12 SEF.I1n / A Rated primary value of sensitive zero sequence CT

25
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 26 REV A05

13 SEF.I2n 1 A Rated secondary value of sensitive zero sequence CT


14 Prot.U1n 33 kV Rated primary value of protection VT
15 Prot.U2n 100 V Rated secondary value of protection VT
16 Syn.U1n / kV Rated primary value of synchro-check VT
17 Syn.U2n / V Rated secondary value of synchro-check VT
18 Delt.U1n / kV Rated primary value of zero sequence VT
19 Delt.U2n / V Rated secondary value of zero sequence VT
Zero sequence current is self calculated
20 Opt_3I0 1  
0:from neutral CT; 1:self calculated
Zero sequence voltage is self calculated
21 Opt_3U0 1  
0:from neutral VT; 1:self calculated
22 Opt_PwrDir /   Power Measurement Mode
Overcurrent Protection Settings (OC Settings)
No. Item Value Unit Remark

1 50/51P.U2_VCE 4.62 V The voltage setting of the negative sequence voltage blocking element (phase voltage)

2 50/51P.Upp_VCE 70 V The voltage setting of the low voltage blocking element (phase-tophase voltage)

3 50/51P.En_VCE_CrossCtrl 0   The logic setting of the external voltage control function

4 50/51P.RCA / ° The relay characteristic angle for the directional overcurrent protection
The logic setting of the function which can block the OC protection related voltage
5 50/51P.En_VTS_Blk 0  
measurement when the voltage transformer is failed

6 50/51P.K_Hm2 0   The percent setting of the harmonic blocking element for OC protection

7 50/51P.I_Rls_HmBlk / A The current setting for releasing the harmonic blocking element of OC protection

26
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 27 REV A05

The setting is used to select the harmonic blocking mode of OC protection.


8 50/51P.Opt_Hm_Blk /  
1: Phase blocking; 2: Cross blocking; 3: Maximum blocking
9 50/51P1.I_Set 30 A The current setting of the stage 1 overcurrent protection
10 50/51P1.t_Op 10 s The time setting of the stage 1 overcurrent protection

11 50/51P1.En_VCE 0   The logic setting of the voltage control element for the stage 1 overcurrent protection

The setting is used to select the directional mode for the stage 1 overcurrent protection.
12 50/51P1.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

13 50/51P1.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 1 overcurrent protection

14 50/51P1.En 0   The logic setting of the stage 1 overcurrent protection


15 50/51P1.OutMap 0   The output matrix setting of the stage 1 overcurrent protection
16 50/51P2.I_Set 30 A The current setting of the stage 2 overcurrent protection
17 50/51P2.t_Op 10 s The time setting of the stage 2 overcurrent protection

18 50/51P2.En_VCE 0   The logic setting of the voltage control element for the stage 2 overcurrent protection

The setting is used to select the directional mode for the stage 2 overcurrent protection.
19 50/51P2.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

20 50/51P2.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 2 overcurrent protection

21 50/51P2.En 0   The logic setting of the stage 2 overcurrent protection


22 50/51P2.OutMap 0   The output matrix setting of the stage 2 overcurrent protection
23 50/51P3.I_Set 30 A The current setting of the stage 3 overcurrent protection
24 50/51P3.t_Op 10 s The time setting of the stage 3 overcurrent protection

25 50/51P3.En_VCE 0   The logic setting of the voltage control element for the stage 3 overcurrent protection

27
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 28 REV A05

The setting is used to select the directional mode for the stage 3 overcurrent protection.
26 50/51P3.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

27 50/51P3.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 3 overcurrent protection

28 50/51P3.En 0   The logic setting of the stage 3 overcurrent protection


29 50/51P3.OutMap 0   The output matrix setting of the stage 3 overcurrent protection

30 50/51P3.Opt_Curve 0   The setting is for selecting the inverse time characteristic curve for OC3 protection

31 50/51P3.TMS 1   The time multiplier setting of the stage 3 IDMT overcurrent protection

32 50/51P3.tmin 10 s The minimum operation time setting of the stage 3 IDMT overcurrent protection

33 50/51P3.K 0.14   Constant “k” for the stage 3 IDMT overcurrent protection
34 50/51P3.C 0   Constant “C” for the stage 3 IDMT overcurrent protection
35 50/51P3.Alpha 0.02   Constant “α” for the stage 3 IDMT overcurrent protection
36 50/51P4.I_Set 0.1 A The current setting of the stage 4 overcurrent protection
37 50/51P4.t_Op 0.3 s The time setting of the stage 4 overcurrent protection

38 50/51P4.En_VCE 0   The logic setting of the voltage control element for the stage 4 overcurrent protection

The setting is used to select the directional mode for the stage 4 overcurrent protection.
39 50/51P4.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

40 50/51P4.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the stage 4 overcurrent protection

41 50/51P4.En 1   The logic setting of the stage 4 overcurrent protection


42 50/51P4.OutMap 0005   The output matrix setting of the stage 4 overcurrent protection

43 50/51P4.Opt_Curve 1   The setting is for selecting the inverse time characteristic curve for OC4 protection

44 50/51P4.TMS 0.15   The time multiplier setting of the stage 4 IDMT overcurrent protection

45 50/51P4.tmin 0.02 s The minimum operation time setting of the stage 4 IDMT overcurrent protection

28
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 29 REV A05

46 50/51P4.K 0.14   Constant “k” for the stage 4 IDMT overcurrent protection
47 50/51P4.C 0   Constant “C” for the stage 4 IDMT overcurrent protection
48 50/51P4.Alpha 0.02   Constant “α” for the stage 4 IDMT overcurrent protection
49 50/51P5.I_Set / A The current setting of the stage 5 overcurrent protection
50 50/51P5.t_Op / s The time setting of the stage 5 overcurrent protection
51 50/51P5.En 0   The logic setting of the stage 5 overcurrent protection
52 50/51P6.I_Set / A The current setting of the stage 6 overcurrent protection
53 50/51P6.t_Op / s The time setting of the stage 6 overcurrent protection
54 50/51P6.En 0   The logic setting of the stage 6 overcurrent protection

55 50/51P.I_CCE / A The current setting of the heavy current blocking element for the overcurrent protection

56 50/51P.En_CCE 0   The logic setting of the heavy current blocking element for the overcurrent protection

No.1 Zero Sequence Overcurrent Protection Settings(EF1 Settings)


No. Item Value Unit Remark

1 50/51G.RCA / ° The relay characteristic angle for the No.1 directional zero sequence overcurrent protection

The logic setting of the function which blocks the No.1 ROC protection related voltage
2 50/51G.En_VTS_Blk 0  
measurement when the voltage transformer is failed

3 50/51G.K_Hm2 0   The percent setting of the harmonic blocking element for the No.1 ROC protection

4 50/51G.3I0_Rls_HmBlk / A The current setting for releasing the harmonic blocking element of the No.1 ROC protection

5 50/51G1.3I0_Set 30 A The current setting of the No.1 stage 1 zero sequence overcurrent protection

6 50/51G1.t_Op 10 s The time setting of the No.1 stage 1 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC1 protection.
7 50/51G1.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

29
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 30 REV A05

8 50/51G1.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC1 protection

9 50/51G1.En 0   The logic setting of the No.1 stage 1 zero sequence overcurrent protection

10 50/51G1.OutMap 0   The output matrix setting of the No.1 stage 1 zero sequence overcurrent protection

11 50/51G2.3I0_Set 30 A The current setting of the No.1 stage 2 zero sequence overcurrent protection

12 50/51G2.t_Op 10 s The time setting of the No.1 stage 2 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC2 protection.
13 50/51G2.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

14 50/51G2.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC2 protection

15 50/51G2.En 0   The logic setting of the No.1 stage 2 zero sequence overcurrent protection

16 50/51G2.OutMap 0   The output matrix setting of the No.1 stage 2 zero sequence overcurrent protection

17 50/51G3.3I0_Set 30 A The current setting of the No.1 stage 3 zero sequence overcurrent protection

18 50/51G3.t_Op 10 s The time setting of the No.1 stage 3 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC3 protection.
19 50/51G3.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

20 50/51G3.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC3 protection

21 50/51G3.En 0   The logic setting of the No.1 stage 3 zero sequence overcurrent protection

22 50/51G3.OutMap 0   The output matrix setting of the No.1 stage 3 zero sequence overcurrent protection

The setting is for selecting the inverse time characteristic curve for the No.1 ROC3
23 50/51G3.Opt_Curve 0  
protection

30
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 31 REV A05

24 50/51G3.TMS 1   The time multiplier setting of the No.1 stage 3 zero sequence IDMT overcurrent protection

The minimum operation time setting of the No.1 stage 3 zero sequence IDMT overcurrent
25 50/51G3.tmin 10 s
protection

26 50/51G3.K 0.14   Constant “k” for the No.1 stage 3 zero sequence IDMT overcurrent protection

27 50/51G3.C 0   Constant “C” for the No.1 stage 3 zero sequence IDMT overcurrent protection

28 50/51G3.Alpha 1   Constant “α” for the No.1 stage 3 zero sequence IDMT overcurrent protection

29 50/51G4.3I0_Set 0.05 A The current setting of the No.1 stage 4 zero sequence overcurrent protection

30 50/51G4.t_Op 0.2 s The time setting of the No.1 stage 4 zero sequence overcurrent protection

The setting is used to select the directional mode for the No.1 ROC4 protection.
31 50/51G4.Opt_Dir 0  
0: Non-directional; 1: Forward directional; 2: Reverse directional

32 50/51G4.En_Hm_Blk 0   The logic setting of the harmonic blocking element for the No.1 ROC4 protection

33 50/51G4.En 1   The logic setting of the No.1 stage 4 zero sequence overcurrent protection

34 50/51G4.OutMap 0005   The output matrix setting of the No.1 stage 4 zero sequence overcurrent protection

The setting is for selecting the inverse time characteristic curve for the No.1 ROC4
35 50/51G4.Opt_Curve 1  
protection

36 50/51G4.TMS 0.1   The time multiplier setting of the No.1 stage 4 zero sequence IDMT overcurrent protection

The minimum operation time setting of the No.1 stage 4 zero sequence IDMT overcurrent
37 50/51G4.tmin 0.02 s
protection

38 50/51G4.K 0.14   Constant “k” for the No.1 stage 4 zero sequence IDMT overcurrent protection

39 50/51G4.C 0   Constant “C” for the No.1 stage 4 zero sequence IDMT overcurrent protection

31
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 32 REV A05

40 50/51G4.Alpha 0.02   Constant “α” for the No.1 stage 4 zero sequence IDMT overcurrent protection

41 50/51G5.3I0_Set / A The current setting of the No.1 stage 5 zero sequence overcurrent protection

42 50/51G5.t_Op / s The time setting of the No.1 stage 5 zero sequence overcurrent protection

43 50/51G5.En 0   The logic setting of the No.1 stage 5 zero sequence overcurrent protection

44 50/51G6.3I0_Set / A The current setting of the No.1 stage 6 zero sequence overcurrent protection

45 50/51G6.t_Op / s The time setting of the No.1 stage 6 zero sequence overcurrent protection

46 50/51G6.En 0   The logic setting of the No.1 stage 6 zero sequence overcurrent protection

Supervision Element Settings (Superv Settings)


No. Item Value Unit Remark
1 CTS.3I0_Set 0.1 A The threshold current setting of the CTS element
2 CTS.3U0_Set 5 V The threshold voltage setting of the CTS element
3 CTS.En 1   The logic setting of the CTS element
4 VTS.I_Set 1 A The phase current setting of the protection VTS element
5 VTS.I2_Set 0.1 A The negative sequence current setting of the protection VTS element
6 VTS.En 0   The logic setting of the protection VTS element
7 VTS.En_SynVT 0   The logic setting of the synchro-check VTS element

32
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 33 REV A05

3.4 Settings List of 33kV Capacitor

3.4.1 Device model: PCS-9631

System Settings
No. Item Value Unit Remark
1 Active_Grp     The active setting group number
2 Opt_SysFreq 1   Select the rated system frequency: “0”, 50Hz; “1”, 60Hz
3 PrimaryEquip_Name     The name of the protected primary equipment
4 Prot.I1n 100 A Rated primary value of protection phase CT
5 Prot.I2n 1 A Rated secondary value of protection phase CT
6 Neu1.I1n 0 A Rated primary value of the No.1 zero sequence CT
7 Neu1.I2n 1 A Rated secondary value of the No.1 zero sequence CT
8 Prot.U1n 33 kV Rated primary value of protection VT
9 Prot.U2n 100 V Rated secondary value of protection VT
10 U1n_Tap 0 kV Rated primary value of tapped-point VT
11 U2n_Tap 0 V Rated secondary value of tapped-point VT
12 60P1.I1n 5 A Rated primary value of the No.1 unbalance CT
13 60P1.I2n 1 A Rated secondary value of the No.1 unbalance CT
14 60P2.I1n 5 A Rated primary value of the No.2 unbalance CT
15 60P2.I2n 1 A Rated secondary value of the No.2 unbalance CT
16 60P3.I1n 5 A Rated primary value of the No.3 unbalance CT
17 60P3.I2n 1 A Rated secondary value of the No.3 unbalance CT
18 Opt_3I0 1   Zero sequence current is self calculated

33
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 34 REV A05

0:from neutral CT; 1:self calculated


Overcurrent Protection Settings (OC Settings)
No. Item Value Unit Remark
1 50/51P1.I_Set 7.873 A The current setting of the stage 1 overcurrent protection
2 50/51P1.t_Op 0.00 s The time setting of the stage 1 overcurrent protection
3 50/51P1.En 1   The logic setting of the stage 1 overcurrent protection
4 50/51P1.OutMap 000D   The output matrix setting of the stage 1 overcurrent protection
5 50/51P2.I_Set 3.936 A The current setting of the stage 2 overcurrent protection
6 50/51P2.t_Op 1.5 s The time setting of the stage 2 overcurrent protection
7 50/51P2.En 1   The logic setting of the stage 2 overcurrent protection
8 50/51P2.OutMap 000D   The output matrix setting of the stage 2 overcurrent protection
9 50/51P3.I_Set 20 A The current setting of the stage 3 overcurrent protection
10 50/51P3.t_Op 10 s The time setting of the stage 3 overcurrent protection
11 50/51P3.En 0   The logic setting of the stage 3 overcurrent protection
12 50/51P3.OutMap 0   The output matrix setting of the stage 3 overcurrent protection
13 50/51P4.I_Set 20 A The current setting of the stage 4 overcurrent protection
14 50/51P4.t_Op 10 s The time setting of the stage 4 overcurrent protection
15 50/51P4.En 0   The logic setting of the stage 4 overcurrent protection
16 50/51P4.OutMap 0   The output matrix setting of the stage 4 overcurrent protection

17 50/51P4.Opt_Curve 0   The setting is for selecting the inverse time characteristic curve for OC4 protection

18 50/51P4.TMS 100   The time multiplier setting of the stage 4 IDMT overcurrent protection

19 50/51P4.tmin 100 s The minimum operation time setting of the stage 4 IDMT overcurrent protection

20 50/51P4.K 120   Constant “k” for the stage 4 IDMT overcurrent protection
21 50/51P4.C 1   Constant “C” for the stage 4 IDMT overcurrent protection

34
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 35 REV A05

22 50/51P4.Alpha 3   Constant “α” for the stage 4 IDMT overcurrent protection


23 50/51R1.I_Set 20 A The current setting of the stage 1 RMS overcurrent protection
24 50/51R1.t_Op 10 s The time setting of the stage 1 RMS overcurrent protection
25 50/51R1.En 0   The logic setting of the stage 1 RMS overcurrent protection
26 50/51R1.OutMap 0   The output matrix setting of the stage 1 RMS overcurrent protection
27 50/51R2.I_Set 20 A The current setting of the stage 2 RMS overcurrent protection
28 50/51R2.t_Op 10 s The time setting of the stage 2 RMS overcurrent protection
29 50/51R2.En 0   The logic setting of the stage 2 RMS overcurrent protection
30 50/51R2.OutMap 0   The output matrix setting of the stage 2 RMS overcurrent protection
Unbalance Currrent Protection Settings (UnbalProt Settings)
No. Item Value Unit Remark
1 60P1.I_Set 0.364 A The current setting of the No.1 unbalance current protection
2 60P1.t_Op 0.03 s The time setting of the No.1 unbalance current protection
3 60P1.En 1   The logic setting of the No.1 unbalance current protection
4 60P1.OutMap 000D   The output matrix setting of the No.1 unbalance current protection

5 Alm_DOC1_1.I_Set 0.046 A The current setting of the stage 1 alarm function of the No.1 unbalance current protection

6 Alm_DOC1_1.I_Op 10 s The time setting of the stage 1 alarm function of the No.1 unbalance current protection

7 Alm_DOC1_1.En 1   The logic setting of the stage 1 alarm function of the No.1 unbalance current protection

8 Alm_DOC1_2.I_Set 30 A The current setting of the stage 2 alarm function of the No.1 unbalance current protection

9 Alm_DOC1_2.I_Op 100 s The time setting of the stage 2 alarm function of the No.1 unbalance current protection

10 Alm_DOC1_2.En 0   The logic setting of the stage 2 alarm function of the No.1 unbalance current protection

11 60P2.I_Set 0.255 A The current setting of the No.2 unbalance current protection

35
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 36 REV A05

12 60P2.t_Op 0.2 s The time setting of the No.2 unbalance current protection
13 60P2.En 1   The logic setting of the No.2 unbalance current protection
14 60P2.OutMap 000D   The output matrix setting of the No.2 unbalance current protection

15 Alm_DOC2_1.I_Set 0.046 A The current setting of the stage 1 alarm function of the No.2 unbalance current protection

16 Alm_DOC2_1.I_Op 10 s The time setting of the stage 1 alarm function of the No.2 unbalance current protection

17 Alm_DOC2_1.En 1   The logic setting of the stage 1 alarm function of the No.2 unbalance current protection

18 Alm_DOC2_2.I_Set 30 A The current setting of the stage 2 alarm function of the No.2 unbalance current protection

19 Alm_DOC2_2.I_Op 100 s The time setting of the stage 2 alarm function of the No.2 unbalance current protection

20 Alm_DOC2_2.En 0   The logic setting of the stage 2 alarm function of the No.2 unbalance current protection

21 60P3.I_Set 0.17 A The current setting of the No.3 unbalance current protection
22 60P3.t_Op 10 s The time setting of the No.3 unbalance current protection
23 60P3.En 1   The logic setting of the No.3 unbalance current protection
24 60P3.OutMap 0000   The output matrix setting of the No.3 unbalance current protection

25 Alm_DOC3_1.I_Set 0.046 A The current setting of the stage 1 alarm function of the No.3 unbalance current protection

26 Alm_DOC3_1.I_Op 10 s The time setting of the stage 1 alarm function of the No.3 unbalance current protection

27 Alm_DOC3_1.En 1   The logic setting of the stage 1 alarm function of the No.3 unbalance current protection

28 Alm_DOC3_2.I_Set 30 A The current setting of the stage 2 alarm function of the No.3 unbalance current protection

29 Alm_DOC3_2.I_Op 100 s The time setting of the stage 2 alarm function of the No.3 unbalance current protection

30 Alm_DOC3_2.En 0   The logic setting of the stage 2 alarm function of the No.3 unbalance current protection

Thermal Overload Protection Settings (ThOvLd Settings)

36
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 37 REV A05

No. Item Value Unit Remark


1 49.Ib_Set 2.887 A The reference current setting of the thermal overload protection
2 49.Tau 10 s The time constant setting of the IDMT overload protection

3 49.C_Disspt 1   The thermal dissipation constant setting of the thermal overload protection

4 49.K_Trp 1.03   The factor setting of the thermal overload protection which is associated to the thermal state formula

5 49.K_Alm 1.0   The factor setting of the thermal overload alarm element which is associated to the thermal state formula

6 49.En_Trp 0   The logic setting of the thermal overload protection for tripping
7 49.En_Alm 1   The logic setting of the thermal overload protection for alarming
8 49.OutMap 000D   The output matrix setting of the thermal overload protection
VoltProt_Settings Editor
Uni
No. Item Value Description
t
The setting for selecting the undervoltage protection calculation method
1 27P.Opt_1P/3P 0   0: all of the three voltage must be less than the setting;
1: anyone of the three voltage must be less than the setting.

The setting for selecting the voltage input mode for the undervoltage protection
2 27P.Opt_Up/Upp 0  
0: phase voltage; 1: phase-to-phase voltage

3 27P1.U_Set 23.11 V The voltage setting of the stage 1 undervoltage protection


4 27P1.t_Op 0.5 s The time setting of the stage 1 undervoltage protection
5 27P1.K_DropOut 1.03   The dropout coefficient setting of the stage 1 undervoltage protection
6 27P1.En 1   The logic setting of the stage 1 undervoltage protection
7 27P1.OutMap 000D   The output matrix setting of the stage 1 undervoltage protection
8 27P2.U_Set 2.2 V The voltage setting of the stage 2 undervoltage protection

37
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 38 REV A05

9 27P2.t_Op 1 s The time setting of the stage 2 undervoltage protection


10 27P2.K_DropOut 1.03   The dropout coefficient setting of the stage 2 undervoltage protection
11 27P2.En 0   The logic setting of the stage 2 undervoltage protection
12 27P2.OutMap 0   The output matrix setting of the stage 2 undervoltage protection
The setting for selecting the overvoltage protection calculation method
13 59P.Opt_1P/3P 1   0: all of the three voltage must be less than the setting;
1: anyone of the three voltage must be less than the setting.

The setting for selecting the voltage input mode for the overvoltage protection
14 59P.Opt_Up/Upp 0  
0: phase voltage; 1: phase-to-phase voltage

15 59P1.U_Set 69.23 V The voltage setting of the stage 1 overvoltage protection


16 59P1.t_Op 3 s The time setting of the stage 1 overvoltage protection
17 59P1.K_DropOut 0.97   The dropout coefficient setting of the stage 1 overvoltage protection
18 59P1.En 1   The logic setting of the stage 1 overvoltage protection
19 59P1.OutMap 000D   The output matrix setting of the stage 1 overvoltage protection
20 59P2.U_Set 66.4 V The voltage setting of the stage 2 overvoltage protection
21 59P2.t_Op 10 s The time setting of the stage 2 overvoltage protection
22 59P2.K_DropOut 0.97   The dropout coefficient setting of the stage 2 overvoltage protection
23 59P2.En 1   The logic setting of the stage 2 overvoltage protection
24 59P2.OutMap 0   The output matrix setting of the stage 2 overvoltage protection
Supervision Element Settings (Superv Settings)
No. Item Value Unit Remark
1 CTS.3I0_Set 0.1 A The threshold current setting of the CTS element
2 CTS.3U0_Set 5 V The threshold voltage setting of the CTS element
3 CTS.En 1   The logic setting of the CTS element

38
CLIENT & PROJECT ETHIOPIAN ELECTRIC POWER (EEP)& CONTRACT AKAKBL-LOT1
CONSULTANT TRANSMISSION & SUBSTATIONENGINEERING OFFICE, EEP
CONTRACTOR TBEA Co.,Ltd.
CONTRACT NO. CO/33.20/124/08 DOCUMENT NO. BOLE-DD-EL-CC-317A SHEET 39 REV A05

4 VTS.En 1 The logic setting of the protection VTS element


5 En_Alm_TCCS 0  