A water-to-water cooling system (Figure 4-3) has a water-
cooled condenser and cooling tower on the heat rejection side. Chilled water coil(s) in the air handling unit(s) (AHU) or fan-coil unit(s) (FCU) are on the heat pickup side.
Figure 4-3. Water-to-Water AC System
60 HVAC Fundamentals
AC COOLING SYSTEM #2
Heat Rejection Side Heat Pickup Side
Air to Water
An air-to-water cooling system (Figure 4-4) has an air-cooled
condenser on the heat rejection side. Notice that while the con- denser is rated for 3.75 tons or 45,000 Btuh (3.75 ton × 12,000 Btuh/ton) the evaporator is rated for 3 tons or 36,000 Btuh. Why is the condenser rated for more Btuh than the evaporator? Be- cause of the additional heat from the compressor, 25% more Btuh from “heat of compression.” If a condenser rated at 36,000 Btuh was installed the system would not work. Chilled water coil(s) in the air handling units (AHU) or fan-coil units (FCU) are on the heat pickup side.
AC COOLING SYSTEM #3
Heat Rejection Side Heat Pickup Side
Air to Air
An air-to-air cooling system (Figure 4-5) has an air-cooled
condenser on the heat rejection side. On the heat pickup side there is an evaporator (refrigerant DX) coil in the air handling units (AHU) or fan-coil units (FCU). In this system the condenser is rated for 3 tons for a 3 ton evaporator. This is because the con- denser is rated at 15,000 Btuh per ton (12,000 × 1.25HRF). When we say a 3 ton or X ton system, we are talking about the evapo- rator or heat pickup side of the system. The heat rejection side will always be more tonnage.
The Complete HVAC BIBLE for Beginners: The Most Practical & Updated Guide to Heating, Ventilation, and Air Conditioning Systems | Installation, Troubleshooting and Repair | Residential & Commercial