Fault Level Calculation

Fault Level Calculation of consumer end point from kallaynpur 33/11 KV S/S to resedinetial
Building of STDL Tipti,Plot #80,Road#06, Monsurabad R/A, Adabor,Dhaka-1207

33 KV N/C

20/28MVA 20/28 MVA


13.67% Imp. 13.67% Imp.

U/G Cable 11KV O/H Line


11 KV N/C 185 mm2 XLPE(A) Conductor DOG

50mm2 Xlpe(Cu)

Load point

Assuming 33 KV BUS FAULT LEVEL = 1000 MVA


Using % REACTANCE METHOD

% of Source impedance at 10 MVA Base Substation =

Transformer % impedance at 10 MVA Base =

Percentage (%) Impedance of U/G Cable =

Percentage (%) Impedance of DOC Conductor =

Total Circuit % REACTANCES AT PCC IS =


FAULT LEVEL AT THE POINT OF COMMON COUPLING =

FAULT LEVEL KILO-AMPS =

Recommended Minimum size of HT Cable =

Calculation for PFI Plant

kVA kVA kVAR


Φ1 Φ2
kW kW

A) Consider Power factor (cos Φ1) = 0.70


Φ1 = cos⁻¹(0.70)
tan Φ1 = tan (cos⁻¹0.70)
= 1.0202

B) Required Power factor (cos Φ2) = 0.95


Φ2 = cos⁻¹(0.95)
tan Φ2 = tan (cos⁻¹0.95)
= 0.328

Capacitor Bank (Capacity of PFI Plant) required to enhance PF from 0.70 to 0.95
kVAR = kW (tan Φ1- tan Φ2)
= 120 (1.202-0.328)
= 120 X 0.6922
= 83.064
90 KVAR
The 90 kVAR PFI plant (Auto) is capable for maintaining power fator from 0.70 to 0.95 lagging.