APPLICATION 03
Design principles of escape route travels auditoriums are given in Figure 1 and maximum
permitted number of seats is given in Table 1.
20
IKU FACULTY of ARCHITECTURE PHYSICAL ENVIRONMENTAL CONTROL 2
Fire detection
The operational radius of the detectors located inside the 5% of the floor height are given on
the Table 6. The horizontal distance depicted on the Table between the areas protected and
the detectors should not be exceeded.
Detectors (except optical and beam types smoke detectors) should not be located closer
than 0.5m to partitions and walls. In case of air-conditioning through suspended ceilings each
detector should have an unpunctured ceiling section around it.
Table 2. Operational radius and floor height limits for detectors (Yangın Söndürme Sistemleri
Uygulama El Kitabı, 2009)
The aim of the automatic sprinkler system is providing early response to a fire initiated,
discharging determined amount of water onto design area to suppress and extinguish
purposes.
An automatic sprinkler heads should be mounted as to cover maximum 21 m 2 area for low-
risk and medium risk-1 areas.
In case of using standard upright and pendent type automatic sprinkler heads in low-risk and
medium-risk groups the maximum distance amongst them should be 4.6 m and the distance
between a wall and a sprinkler head should be 2.3 m. The symbols to use for sprinkler heads
and detectors for drawing on plan can be seen on Table 3.
Desciption Symbol
Sprinkler head S
21
IKU FACULTY of ARCHITECTURE PHYSICAL ENVIRONMENTAL CONTROL 2
For a given space with many occupants, appropriate HVAC systems are determined by
comparing heating and ventilating systems. HVAC system elements belonging to this system
should be shown on 1/50 scale ceiling plan and section. The explanations related with the
subject are given in Figure 2.
22