Professional Documents
Culture Documents
detected before fault occurring, the serious faults can be Fig. 2 Schematic figure of holes in the different surfaces of switchgear
avoided, which will be useful for safe running of power cabinet
grids. Generally speaking, weak-amplitude abnormal
discharges, namely, Partial Discharges (PDs) often Fig. 3 shows two kinds of PD models.
locally occur before the formation of insulation and
current-carrying faults. And at this stage, the abnormal
signals should be captured using different monitoring
tools. At present, there are several kinds of methods used
in PDs detection for medium-voltage switchgear, i.e.
Radio Frequency (RF) method [2], Pulse Current (PC)
method [3, 4], Ultra High Frequency (UHF) method [5,
6], Acoustic Emission (AE) method [7], and transient
earth voltage (TEV) method [9].
(a) (b)
II. EXPERIMENTAL SETUP
Fig. 3 Two kinds of PD models in the experiments
Fig. 1 shows the experimental set-up. It consists of (a) needle-plane model; (b) suspended-metal model
1000 1.5
Amplitude of AE signal / mV
Discharge capacity / pC
1.0
900
0.5
800 (a)
0.0
700
-0.5
11.5 12.0 12.5 13.0 13.5 14.0 14.5 15.0 2.66kV 2.86kV 3.80kV
Voltage / kV
11
2.68kV 3.80kV 4.56kV
Amplitude of UHF signal / mV
10
394
0.06 TEV 1 0.06 1.00 1.00
TEV 2
TEV 1 TEV 2
0.04
0.04
Magnitude (a.u.)
Amplitude / V
-0.04 -0.06 0.00 0.00
0 1 2 3 4 5 0 1 2 3 4 5
0.010 0 40 80 120 160 200 0 40 80 120 160 200
0.02
0.000 0.50 0.50
-0.02
-0.005
0.25 0.25
0.00 0.00
-0.04
-0.010
0 1 2 3 4 5
0 1 2 3 4 5 0 40 80 120 160 200 300 600 900 1200 1500
t / s Frequency / MHz
(a) (b)
Fig. 6 PRPD graphs of needle-plane model under different distances C. Suspended-metal Model
and voltage (a) 5mm; (b) 7.5mm; (c) 15mm; (d) 30mm
The distances between the power electrode (connected
There is also one phenomenon worth noticing that with high-voltage source) and the suspended metal
when hen the distance is 5mm and voltage is 2.17kV, PD needle under three cases are 0.5mm, 1mm and 1.5mm,
signal is firstly detected by PC method. Meanwhile, AE respectively. From Fig.9, it can be seen that the
sensor can successfully detect PD signals, but TEV or significant stratification phenomena appear in the
UHF cannot. When the voltage reaches to 6.06kV, the suspended-metal PD. When the voltage reaches to about
discharge capacity increased to 300pC. At this stage, 10kV, the discharge phenomena appear at both positive
TEV and UHF sensors could successfully get the PD and negative half waves. The shape is similar to a line
signal. When the distance is bigger than 15mm, and the segment. As the voltage increases, the amplitude of
discharge capacity stays still below 200pC, TEV and PRPD graph keeps steady, but the graph begins to
UHF sensors cannot get PD signals all the way. It can be separate into two parts at negative half wave. The
inferred that TEV and UHF methods can only get the PD discharge phase positions always keep at 30°~120°and
signals when discharge capacity is higher than 200pC. 240°~290°. Compared Fig. 9, (a) with Fig. 9, (c), it can
Fig. 7 shows AE signals and FFT graph of be seen that discharge phase changes little as the distance
needle-plane model. The main frequency of AE sensor is increases, but the band width of discharge phase under
40 kHz. In the FFT graph, it can be seen that the highest longer-distance condition becomes shorter. For 1.5mm
spectral line is around 40 kHz. gap distance model, when the voltage reaches to 14kV,
0.15 the PRPD graphs of positive and negative half wave
0.10
begin to become not symmetric. The discharge capacity
Amplitude / V
0.05
0.00
-0.05
under longer-distance condition is smaller than that
-0.10 under shorter-distance condition.
-0.15
-2 -1 0 1 2
t / ms
10.70kV 12.15kV
1.00
Magnitude (a.u.)
0.75
0.50
0.25
0.00
395
11.75kV
IV. CONCLUSIONS
12.69kV
0.75
[2] M. Tozzi, “Partial Discharges in Power Distribution Electrical
0.50
Systems: Pulse Propagation Models and Detection
0.25 Optimization”, University of Bologna, 1979.
0.00 [3] S. Birlasekaran, W. H. Leong, “Comparison of Known PD
0 40 80 120 160 200
Signals with the Developed and Commercial HFCT Sensors”,
IEEE Trans. Power Delivery., 2007, 22(3): 1581-1590.
Frequency / kHz
[4] M.D. Noskov, M. Sack, A.S. Malinovski, A.J. Schwab,
Fig.10 AE signals and FFT graph (d = 0.5mm) “Measurement and Simulation of Electrical Tree Growth and
Partial Discharge Activity in Epoxy Resin”, J. Phys. D: Appl.
Phys., 2001, 34(9): 1389-1398.
Fig. 11 shows TEV/UHF signals and FFT graph of
[5] S. Tenbohlen, D. Denissov, S. Hoek, et al, “Partial discharge
suspended-metal model. Compared with Fig.10, it can be Measurements in the Ultra High Frequency (UHF) range”,
seen that the signal amplitude of the suspended-metal IEEE Transactions on Dielectric and Electrical Insulation,
model is higher than that of needle-plane model. In the 2008, 15(6):1544-1552.
FFT graph (Fig11, (b)), it can be seen that TEV signal [6] E. Jennings, A. Collinson, “A Partial Discharge Monitor for
the Measurement of Partial Discharges in a High Voltage
contains rich signals with different frequencies. The Plant by the Transient Earth Voltage Technique”, IEEE
frequency of peak value is about 10 MHz and its International Conference on Partial Discharge, Canterbury,
frequency multiplication. The frequency band of UHF New Zealand: IEEE, 1993: 90-91.
signal is mainly concentrated on from 750MHz to [7] Y. Li, F. Lu, H. Xie, et al, “Study on Ultrasonic Generation
Mechanism of Partial Discharge”, IEEE International
1000MHz. Symposium on Electrical Insulating Materials, Kitakyushu,
TEV 1 TEV 2
Japan, 2005: 467-471.
1.00 1.00
0.75 0.75
0.2 0.2
0.0 0.0
0.50 0.50
Earth Voltage Measurement in PD Detection of Artificial
Defect Models in SF6”, IEEE Transactions on Plasma Science,
0.25 0.25
-0.2 -0.2
Magnitude (a.u.)
Amplitude / V
0.00 0.00
-0.4 -0.4
0.4
-1.0 -0.5 0.0 0.5 1.0 -1.0
0.25
0.20
-0.5 0.0 0.5 1.0
1.00
0 40 80 120 160 200 0 40 80 120 160 200
2001, 40(8): 2002-2008.
TEV 3 UHF 1.00 UHF
t / s Frequency / MHz
2002,149(2):73-78.
(a) (b)
[10] S. A. Boggs and G. C. Stone, “Fundamental Limitations In
The Measurement Of Corona And Partial Discharge”, IEEE
Fig.11 TEV / UHF signals and FFT graphs (d = 0.5mm) Transactions on Electrical Insulation,1982,17(2).
(a) TEV and UHF signals (b) FFT graphs
Email: lijunwang@mail.xjtu.edu.cn
396