Professional Documents
Culture Documents
2 – ELECTRICAL WORKS
INTRODUCTION
The “Electrical Works” shall include (but not limited to) all underground
/ buried / cast-in works and system components, such as earth pits,
bore holes for earthing and lightning protection system, lightning pits,
lightning down conductors, cable ducts/draw pits, etc.
The Contractor shall note that the final installation and commissioning
activities for the Works shall be carried out within the existing IAC and
in close proximity to the area of the Works to the existing IAC. It shall
be the Contractor’s responsibility to ensure the safety of all personnel,
including but not limited to site staff, airlines, airfield personnel, at all
times.
MATERIALS
SUBMISSIONS
WORKMANSHIP
GENERAL
System Description
The Contractor shall design, supply, install, test and commission the
complete HV and LV electrical power supply and distribution system.
The Works shall be as shown on the Employer's Drawings and shall
include, but not limited to:
(b) The Contractor shall liaise with CLP and provide the services
and facilities to fulfil CLP’s requirements. All the associated
inspection shall be provided by the Contractor.
(c) The Contractor shall provide the services and facilities from the
points of power coupling on the low voltage side to complete
the low voltage distribution system. CLP will be responsible for
11 kV cabling and accessories from their 11 kV panels and their
transformer units to step down the distribution voltage from 11
kV to 380V, 50Hz at Site and for ultimate termination to the
main ACB incoming terminal of LV main switchboard adjacent
to the corresponding CLP Transformer Room.
The services and facilities shall include, but not limited to liaison with
the Utility Companies, submission, programming, application of tariff
metering and summation metering facilities, services co-ordination,
provisions of lead in ducts, and/or cable trenches, building services
installation in CLP transformer rooms, associated equipment provision,
Contract 3403 – Particular Specification 6 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
equipment settings, inspection, testing and commissioning activities to
enable the respective building power energisation date is achieved.
The Contractor shall arrange wall space and shall supply and install a
suitable wooden block for the installation of CLP meter and the
associated wiring, cable changing boxes, current transformers,
cable/conductor link boxes and all necessary accessories to fulfil the
requirements of the CLP metering installation.
The entire LV power distribution systems, including but not limited to,
LV main switchboards, sub-main distribution boards, earthing systems,
control systems, small power arrangements, power factor correction
equipment, other energy efficiency and/or power quality improvement
equipment installation, armoured and non-armoured power cables and
a complete low voltage distribution system are as shown on the
Employer’s Drawings.
The LV power distribution system works shall include, but not limited
to, the following:
(a) The Contractor shall supply and install the power system
including low voltage switchboards, sub-mains electrical
distribution equipment , cables, cable containment system,
small power arrangement, wiring and accessories, power
factor correction equipment, other energy efficiency and/or
power quality improvement equipment installation,
miscellaneous electrical equipment, lighting system, control
system, earthing system, lightning protection system, etc. and
the like as specified and/or shown on the Employer's Drawings.
(c) The electrical supply system from the CLP source will be at a
nominal voltage of 380 volts plus or minus 6% between phase
conductors and 220 volts plus or minus 6% between phase and
neutral conductors, using a 3-phase 4-wire system at a
frequency of 50 hertz plus or minus 2%.
(d) Real time stepped automatic power factor correction units shall
be provided to the landlord services sections of the
switchboards to improve the power factor to an adjustable
range from 0.9 to 0.95 lagging.
(f) The Contractor shall supply and install cable ladders, cable tray,
trunking and ducts for supporting and fixing the new cables in
accordance with the Employer's Drawings. Where cable routes
are not specifically shown on the Employer's Drawings or the
cable routes are obstructed by others, the Contractor shall take
the shortest possible route for the cable run. Details shall be
submitted to the Project Manager for review without objection
prior to installation.
(i) Central battery system with back-up time not less than 180
minutes shall be provided for all emergency lighting except the
CLP transformer room, Police Observation Room, Police
Equipment Room and CAD Equipment Room. Self-contained
type battery and charger with back-up time not less than 180
minutes shall be provided for emergency lighting in CLP
transformer rooms, Police Observation Room, Police
Equipment Room and CAD Equipment Room. Details are
shown on the Employer's Drawings.
(k) The Contractor shall supply and install power cables and all the
associated electrical accessories for the new road lights from
the power supply system at the existing pillar boxes which
obtain power from the substations serving to the new
connected roads.
(m) The Contractor shall prepare and submit the method statement
of the road lighting installation works for the new roads
including, but not limited to, the cable diversion services,
temporary power and lightings arrangement, etc. to the Project
Manager for review without objection.
(q) All busbars including both main bars, risers and tee-off bars
shall be of all insulated type.
(s) The Contractor shall provide normal power supply failure signal
from LV switchboard to lift control cabinet at upper most landing
of each machine room-less lift for lift homing purpose.
Small power provisions for internal and external areas complete with
all associated equipment and materials such as distribution boards,
harmonic filters, switches, switch plate socket outlets, cable, conduits
and cable containment and associated accessories as shown on the
Employer's Drawings. Installation of power points shall be at suitable
locations as close as possible to the equipment being served for
connection and operation of equipment.
The location and size of the power and communication junction box
shall be coordinated with Other Contractors and fixed to the
associated steelwork or cladding system where applicable. Fixing
details of the communication junction boxes shall be submitted to the
Project Manager for review without objection.
Dual redundant UPS units (each rated at 100% load) in parallel mode
configuration shall be provided inside 1/F UPS room for
equipment/server racks and all critical equipment like computer
workstations/equipment in the Primary IAC console desk, Airfield
SCADA control panels etc. Their inputs shall be supplied by dual 3-
phase essential power in-feeds with full back-up by emergency
generators. The output power factor of the UPS shall not be less than
0.9.
During normal operation, the demand load to each UPS unit shall not
exceed 50% of the rating of the UPS equipment. In case of one UPS
equipment is in failure, the other UPS unit shall take up the full
demand loading.
The battery bank of each UPS shall have sufficient capacity for
supporting normal equipment operation under full load for at least
one hour in case of mains failure. 30% aging factor shall be included
in UPS batteries sizing.
Each UPS for Comms Rooms and for Comms Cupboards shall be
equipped with an UPS normal power failure alarm at an integrated
alarm panel located at the Primary IAC Main Hall. The signalling
cable for this remote UPS alarm system shall be provided via VDC
cabling scope. The Contractor shall be responsible for the supply and
installation of this integrated alarm panel, the panel assembly and
layout arrangement and the internal wiring and accessories. The
indication of this UPS alarm shall not be affected by failure and /or
malfunction of the SCADA system.
The Contractor shall supply and install surge protection device (surge
arrester) as shown on the Employer’s Drawings and described in this
PTS.
The Contractor shall supply and install all necessary wiring, cable
containment, enclosure, fixing and mounting accessories for the
installation of surge protection device.
Type test certificate for the surge protection devices shall be submitted
for the Project Manager’s review without objection. The certificate shall,
unless otherwise specified, demonstrate that the equipment can fulfil
the requirements stipulated in the IEC 61643-1:2005 with the following
performance:
(b) The Electrical Distribution System design shall follow the latest
edition of Code of Practice for Energy Efficiency of Building
Services Installations. The Contractor shall report to the Project
Manager if it identifies any discrepancies.
(d) The cables and the protective devices for the LV power
distribution system shall be sized based on the assumed cable
routing and the indicative equipment location. The Contractor
shall verify and calculate the cable sizes and the rating of
Contract 3403 – Particular Specification 13 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
protective devices for all circuitries based on their offered
equipment and actual arrangements prior to ordering and
installation. Calculations shall be submitted to the Project
Manager for review without objection.
GENERAL
Description
The Contractor shall supply and install one (1) 2000kVA emergency
generators, complete with, but not limited to, essential power
distribution, fuel oil supply system, flue systems, acoustic treatments,
control and all other necessary accessories.
Emergency Generators
General Requirements
(c) The generator sets shall be of prime rating, with rated voltage
of 380V, 50Hz, and at a minimum power factor of 0.8. The
minimum prime rating of the generator sets is shown on the
Employer's Drawings and/or the Equipment Data Sheets. The
Contractor shall be responsible for confirming the final rating of
the emergency generators based on final plant selections.
(j) The generator sets shall comply with the EPD’s “Guidelines on
Application for Installation of Emergency Generator”.
Diesel Engine
(c) The engine shall be direct fuel injected in conjunction with turbo
charging.
(d) The engine shall be suitable for operation using fuel oil to BS
2869, DIN 51 601 or as specified. Fuel filters with renewable-
type elements shall be incorporated in the lift pump supply
system feeding the injector pumps.
(m) The type and capacity of the sump, together with consumption
rate of the lubricating oil shall be submitted to the Project
Manager for review without objection.
(r) The Contractor shall supply and install the whole section of
ductwork, complete with flexible connector between the
radiator and the metal louvres.
(w) An electrical battery starting system for each generator set with
a set of 24V battery charger, starting battery and all necessary
wiring and switchgear shall be provided. The starting system
shall have sufficient capacity to initiate four starting cycles.
(x) Starter batteries shall be of the nickel cadmium type with clear
plastic cases. The batteries shall be contained within a
purpose made corrosion-resistant frame with timber cover
located close to the engine. Leads between batteries and
engine shall be protected against physical damage.
AC Generators
(q) The steady state and transient behaviour shall comply with
performance G3 in ISO 8528-5:2005. The maximum
percentage of voltage dip shall not exceed 20% of the rated
value under all loading conditions including step load
application. In case that electronic equipment and computers
form a substantial amount of supply loads, the maximum
voltage dip shall not exceed 10%.
(b) The Contractor shall also provide a list of points from the
generator panel for combined Cat.1 and Cat.2 generator,
linking to FS control panel and submit to the Project Manager
for review without objection prior to manufacture. These shall
include, but not be limited, to the following:
(e) The Contractor shall provide all necessary interface works with
other equipment/systems such as LV switchboards, FS system,
airfield SCADA system, etc. complete with necessary
equipment, control devices, wiring, cable containment etc. for
the generator system to perform starting/control/shut-down
operations specified.
(h) The complete panel enclosures shall comply with IP51 (BS EN
60529) as a minimum standard unless a higher standard is
specified.
(j) Where the equipment standard finish differs from the above,
the Contractor shall record details of the paint finish and colour
and shall submit for review without objection by the Project
Manager.
(k) Cables or conduit entry shall be via removable plates at the top
and bottom of the panel.
(r) Power and control circuits shall be segregated from each other
within the panel.
(v) All wiring within the control panel shall be identified by means
of coded ferrules fitted to each end of the cable; the coding shall
be identified on the schematic wiring diagram.
(y) A main earth terminal bar shall be fixed within the control panel
and positioned to facilitate connection of external wiring.
(z) All indicating lamps shall be of the LED type and shall be
mounted on the front face of the panel.
(bb) Where timers are utilized in the protection and control circuits,
each timer shall have a readily adjustable setting range
incorporated in the timer module.
(cc) All control switches shall be mounted on the front face of the
panel and shall be of the rotary type.
(dd) All push buttons shall be mounted on the front face of the panel.
(ee) Audible alarms shall be located on the front face of the control
panel with a muting facility fitted in an adjacent position.
(gg) The front face of the control panel shall be illuminated with
easily replaceable lamps. The illumination shall be provided
glare free and shall not produce reflection from the glass
fronted instruments.
Exhaust System
(a) The exhaust system for each engine shall form a continuous
unique path from the engine to the termination position.
Inspection and cleaning doors shall be provided at changes of
direction and at the base of vertical stacks.
(c) Flexible, gas tight joints shall be provided between engines and
the exhaust system to permit thermal expansion and to prevent
vibration transmission.
(h) The enclosure shall have the fire rating protection to meet
FSD’s requirements and shall be demountable to allow major
maintenance and repair work to be carried out.
(j) For exhaust systems with over 600mm bore, dimensions shall
be calculated in accordance with BS EN 1993-3-2:2006, and
the installation shall be fabricated from steel plate to BS EN
ISO 18286:2010, BS EN 10029:2010, BS 7688:2004, BS EN
10025-1:2004, BS EN 10025-3:2004, BS EN 10025-4:2004,
BS EN 10210-1:2006, Grade 43EE.
(l) The pressure loss through the exhaust system shall not exceed
the value recommended by the manufacturer.
(n) Expansion devices shall have a low pressure rating suitable for
corrosive atmosphere and temperature up to 520°C with pipe
guides provided on either side of each expansion device.
Devices shall be corrugated bellows type with internal sleeves
of Incoloy 825 or similar, installed with maximum 'cold draw'.
(o) The base of any vertical section of the exhaust system shall
have a tee pocket and welded-in tunic of mild steel, tapped for
and provided with a 19mm carbon steel drain-pipe extended to
near floor level without causing obstruction to personnel or
operations.
(p) The low point of any horizontal section of the exhaust system
shall have a tee pocket, tundish and drain pipe splay cut at the
bottom or lower end.
(q) Before insulation all exhaust piping and brackets shall be wire-
brushed clean of rust, scale, etc., and cleaned of grease and
oil and painted with one full coat of silicone aluminium heat-
resisting paint.
(s) The outdoor part of the exhaust piping shall be stainless steel
grade 316 exhaust pipe complete with pipe supports for
100mm minimum thickness mineral wool rigid sections, applied
in two layers, secured with wire ties or metal bands. Aluminium
cladding shall be 1.2mm minimum thick of embossed style.
Silencers
(c) The airways shall be free from sharp edges, sharp screw ends
or other undue projections into the air stream.
(d) The total pressure losses from the intake and discharge
silencers shall not exceed a total of 100Pa. The Contractor
shall be responsible for ensuring that the generator cooling fan
provides sufficient capacity to overcome the resistance of the
acoustic treatment.
(c) Air intake and discharge points shall be protected from ingress
of moisture and dust by framed and shaped weather louvres.
(f) The louvre free area shall not be less than 50% of the total area
of the opening and the overall size shall match the airflow
requirements of the engine.
(h) Galvanized wire bird screens shall be fitted to the inner face of
all louvres with provision made for removal for cleaning.
Screens shall extend over the full face of the louvre and be of
10mm mesh size. All fixing clips, screws and washers shall be
hot dip spun galvanized.
(g) Where an exhaust system runs with less than two bends
between the flexible bellows connection at the manifold and the
point of exit from the plant room, a second bellows connection,
similar to the first, shall be located just before the point of exit.
(h) The parts of the exhaust system in the engine plant room shall
be suspended from spring hangers. The spring hangers shall
allow unstressed expansion of the exhaust system without
significant changes in hanger loads or excessive deflections of
the flexible connections.
(j) The isolators shall be suitable for the ambient temperature and
metal contact temperature specified.
(k) Supports for tail pipes passing through occupied spaces shall
include pads or bushed washers to prevent metal to metal
contact between the parts of the support fixed to the tail pipe
and the parts fixed to the structure.
(l) Supports for tail pipes passing through occupied spaces shall
include vibration isolators with efficiencies of not less than 90%
at the firing frequency of the manifold to which the tail pipe is
connected.
Contract 3403 – Particular Specification 31 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
(m) Intervals between spring hangers shall be chosen to give
adequate structural support without causing resonance of the
supported length at the manifold firing frequency or the engine
rotational frequency.
(q) During testing of the generators, the noise level generated from
the exhaust pipes and intake and discharge louvres shall
comply with the requirements of the relevant Technical
Memorandum under the Noise Control Ordinance, namely;
(r) This Contractor shall blank off all unused louvres after
complete installation of the generators and before handover.
The Contractor shall provide main underground storage fuel tanks, on-
ground storage fuel tanks, complete with, but not limited to, all
associated fuel mains, daily fuel tanks, fuel pump rooms and controls
as shown on the Employer’s Drawings.
The fuel oil control systems shall include, but not limited to, a low level
fuel monitoring system. The monitoring system shall provide both
audio and visual alarm warnings at the fuel pump room as well as
repeated audio and visual warnings at the fire services panels in the
FS control room and workstation in the Primary IAC Main Hall, Back
Up IAC, TDMO and FRTMO.
Fuel monitoring and alarm facilities shall be relayed back via AFA
system to the Primary IAC Main Hall, Back Up IAC, TDMO and
FRTMO.
Each fuel storage tank for the generator shall have the capacity for 6.5
hours continuous operation for Category 1 essential services plus 3
hours continuous operation for Category 2 services. The essential
power supply for Category 2 services shall be automatically cut off in
the following circumstances to maintain fuel storage for the generator
to back-up the Category 1 essential services for operation for 6 hours,
as follows:
(a) When CLP power supply fails and the fuel oil level drops to 6.5
hours of the fire services installations (FSI) full load
consumption; or
(b) When CLP power supply fails and common fire alarm signal is
received from the FS control panel; or
(c) When CLP power supply fails and open circuit or damage or
failure of any control circuits of the fuel monitoring and warning
system.
The low fuel oil alert signal system shall be of fail-safe design such that
any failure of the component would result in automatically cut off the
Category 2 essential loads to ensure the fuel oil supply to Category 1
essential loads.
All control cables used in fuel alarm and monitoring system and
Category 2 automatic cut off control system shall be fire resistant
cables complying with BS 6387 (1994: Category C,W,Z) to ensure fire
survival.
The single phase UPS system for fuel alarm and monitoring system
shall comply with the following technical requirements:
All fuel tanks shall be constructed from 6mm thick mild steel plate with
local reinforcement where supported and at connections.
Connections shall be provided for the vent pipe, fuel supply and return
pipes. The complete system shall be complete with all necessary
valves and drains. Fuel tanks and associated pipe work shall be tested
to 1.5 times the normal static pressure in accordance with the
requirements of BS 799: Part 5.
(h) Ultrasonic level sensor / Float switch of FSD approval type for
high level alarm, which would be monitored by the Airfield
SCADA system; and
(i) Ultrasonic level sensor / Float switch of FSD approval type for
low level alarm, which would be monitored by the Airfield
SCADA system.
The underground oil storage tanks having the specified capacity shall
be supplied and erected in the position shown on the Employer’s
Drawings.
The emergency pull handles outside the generator rooms and the fuel
pump room shall be provided to shut off the respective valves of the
fuel pipes and to shut down the emergency generators.
The fuel delivery pumps control panels in the fuel pump room
incorporating the starters, safety and protection devices, all necessary
wiring work, relays, fuel level control and alarm, push button and
indication lights shall be supplied and installed to provide the
performance as shown on the Employer’s Drawings and as specified
in the PTS. The panel shall be of wall-mounted type, flameproof
enclosure for operation in Zone 1 hazardous area as classified
Institute of Petroleum Code of Great British and IP 65 enclosure to
IEC 60529.
(a) EEx ib ; or
(b) EEx d ; or
The switch unit shall be mounted on the tank and with the level sensor
to form an integral unit. The unit shall be housed inside a casing made
of cast iron or aluminium alloy. It shall be capable of detecting the
signals from the sensor and transmitting the signals to control the
operation of the fuel delivery pumps systems and the fuel tank alarm
panels.
All the joints in the tank shells and dished ends shall comply with EB
1011-1 and EN 499.
An end plate is made up from two smaller plates the welded joint
between them shall be horizontal, and above, the centre of the tank
end.
The inside surfaces of the tank shall smooth and free from any
obstruction apart from essential pipe connections. No internal bracing
or gusset plates shall be permitted inside the tanks.
Tank-hole covers and all flanges and pads associated with each
manhole cover shall be provided and complete with bolts, washers,
and joint rings as shown on the Employer’s Drawings.
The underground storage fuel tank shall be double wall fuel tank. The
interstitial spaces for fuel storage tank shall be completed with
leakage detection.
SUBMISSIONS
The Contractor Drawings shall show all the installation details of the
intake / exhaust louvres and flue exhaust pipes to the generator systems.
The Contractor’s Drawings shall be submitted to the Project Manager for
review without objection prior to the installation.
The Contractor shall submit the details of radiant heat output from the
engines, exhaust systems and emergency generators.
The Contractor shall submit the calculations for the design of the intake
/ exhaust louvers and flue exhaust pipes to the generator systems. The
details of air resistance values and dimensions of all louvres (including
acoustic louvres) shall be submitted.
The Contractor shall submit the calculations for the selection of the
silencers.
The Contractor shall submit proposals to the Project Manager for review
without objection for treating the noise and vibration generated by
generators. The acceptable noise levels shall be as stated in “Noise and
Vibration” Section of this PTS.
The submissions from the Contractor shall include the details of all the
proposed noise and vibration control measures including, but not limited
to, noise test certificates, catalogues and calculation sheets. All test
certificates shall be prepared by an independent acoustic laboratory and
submitted to the Project Manager for review without objection.
The details and the official certificates issued by the BASEEFA of the
delivery pumps control panels shall be submitted.
The results of the calibrations of the underground fuel storage tanks shall
be tabulated and submitted for record purpose.
Contract 3403 – Particular Specification 38 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
WORKMANSHIP
The Contractor shall be responsible for carrying out all tests, including
the dummy load test as requested by the FSD during the FS inspection.
The Contractor shall supply and install the following items for the
generator rooms:
(a) Fuel oil pipe trench complete with mild steel (M.S.) checker
plate and sand filling inside the trench;
The Contractor shall for supply and install the underground fuel tanks
and the associated pipe work and valves for the fuel oil supply to the
generators as shown on the Employer’s Drawings.
Before fuel tanks are installed, all rust, mill scale, and grease shall be
removed from the external surface immediately before applying rust
inhibitor / protective finish, which shall consist of one coat of zinc rich
primer, one coat of epoxy based under coat and two finishing coats of
bituminous paint. When damage is sustained to the protective coating
due to handling etc., such coating shall be made good on site. After
hydraulic test, the internal surface of fuel tank shall be thoroughly
cleaned and dried out and a thick coat of linseed oil shall be applied to
the interior surface of fuel tanks to prevent rusting.
(a) Clean the outer surface of the pipe to remove all rust, mill scale,
grease and other foreign matter to achieve a rust free and dry
surface;
(c) Apply Denso Tape spirally on the pipe with minimum 55% overlap.
Care shall be taken to ensure the tape is in contact with the
underlying surface of the pipe and to smooth out any wrinkles or
air pockets; and
Contract 3403 – Particular Specification 39 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
(d) Apply Densopol 60 Tape on the pipe with minimum 55% overlap
as an outer wrap.
The Contractor shall paint the fuel pipe work with one coat of zinc rich
primer prior to installation. The Contractor shall then repaint the
installation after completion and testing with one coat of epoxy based
under-coat and two finishing coats. The paint specification and colour
shall be submitted to the Project Manager for review without objection
prior to procurement.
The Contractor shall thoroughly clean all the parts of the exterior
surfaces of the underground fuel storage tanks by mechanical means to
remove all rush, mill scale, grease and other foreign matters to achieve
bright, rust free and dry surfaces. The painting procedures shall comply
with ISO 12944.
The Contractor shall calibrate the underground fuel storage tanks after
the tanks have been installed in the tank chambers, by dipstick. The
measuring devices shall also be calibrated. After calibrating, the tank
shall be thoroughly dried out and applied with a thick coat of linseed oil
on the interior surfaces of the tanks to prevent rusting.
GENERAL
(a) Earthing and bonding systems for the Buildings, and all
exposed conductive parts and extraneous conductive parts in
all buildings;
(b) Earthing and bonding systems for the building services and
plant equipment, metal works with exposed conductive parts,
and extraneous conductive parts within the Works including
water pipes, fuel pipes, steel beams, railings, checker plates,
etc.;
(c) Earthing and bonding systems for the road lighting and pillar
boxes;
(d) Clean earth for the Airport Systems equipment and the
Communication Rooms / Communication Cupboards; and
As part of the detailed design, the Contractor shall carry out on site
earth resistivity measurements at the locations of the earthing points
and shall, where necessary provide ground treatment to ensure that
the earth fault will cause the protective device to operate effectively and
to comply EMSD Electrical COP. The detailed design and associated
earthing calculations shall be submitted to the Project Manager for
review without objection prior to installation.
Separate earthing systems shall be provided and installed for the main
earth system and clean earth system respectively.
GENERAL
(a) The Primary IAC Buildings, which are above ground, shall be
protected by a conventional air termination network formed by
copper tape complying with BSEN 62305 and mounted onto
the roof level of the building.
(c) All positioning and design of the air termination lightning rod
shall comply with the Airport Height Restrictions Plan.
Lightning earth pits shall connect with 80mm dia. uPVC cable ducts for
enclosure of lightning conductors connecting to lightning down conductor
from roof level. The locations of lightning earth pits indicated on the
Employer’s Drawings are for reference only. The Contractor shall verify,
coordinate and propose on the site the locations of lightning earth pits
as appropriate.
The system shall also be installed in the way that any surge current
induced by lightning strikes shall discharge directly to the earth, but not
to the structure, via the nearest lightning earth pits.
For New Antenna Tower, early streamer emission lightning air rod is
used. The early streamer emission lightning rod shall be connected to
lightning earth pits via two (2) 25mm x 3mm PVC sheathed down
conductors. This lightning protection system shall be a specialist design
system comprising one or more non-radioactive lightning control
terminal(s) connected to the lightning earth pits by PVC sheathed copper
tapes and cables.
(d) The terminal shall be mounted at least two meters above the
highest point of the structure. The supporting mast shall be
provided with suitable surface treatment against corrosion.
(e) The lightning control terminal shall fully comply with standard NF
C 17-102.
SUBMISSIONS
GENERAL
(c) The cable changing boxes should the cable for the lighting
circuit be too large to be terminated in the light fitting.
(e) Control for the complete lighting installation including the on/off
switches with integral time switches, photo-electric control
switches, etc. in accordance with the Employer's Drawings.
The lighting installations in all plant rooms shall be controlled
by lighting switches.
(h) Plug connection for power and control cables shall be provided
for each lighting fixture for ease of maintenance and
replacement of the lighting fixture.
(e) The Contractor shall supply and install the luminaires, lighting
system accessories for the architectural FOH lighting and
lighting control system installation. These shall include but not
limited to the following:
(f) The lighting control system shall be installed for the control of
the lighting system within the FOH public area. According to
the Schedule specified in the following Clauses, the lighting
control system shall be completed with contactors, relays,
control wirings, light sensors, switches converters, gateways,
controllers and all necessary accessories as required for the
complete installation and commissioning of the system;
(j) The Contractor shall verify all ceiling types and light fitting
quantities and locations and submit installation drawings for
review without objection by the Project Manager. The
Contractor shall also submit samples to the Project Manager
for review without objection. Unless integrated, the lamps
sources shall be supplied and installed for all light fittings.
(n) All fittings installed in the false ceiling of the Primary IAC Main
Hall shall be plug-in connection type. The plug-in connection
shall comply with BS 6972 and BS5733:2010 and shall be
plugged and unplugged under on-load condition. The socket
and plug shall be dedicated for light fitting connection and
non-compatible with other application. Socket outlets,
connection plug, ceiling rose and cover shall be low smoke
halogen free type fixing on standard BESA box. The flexible
cord connecting to luminaire shall comply with BS EN 50525-
3-11. The ceiling rose cover for emergency lights shall be in
red colour.
Unless otherwise specified, the design lux and maintenance of the lux
performance for different functional areas shall comply with the values
stated in the table below.
The lighting design shall be in accordance with the latest edition of the
Code of Practice of Energy Efficiency of Building Services Installation
issued by EMSD.
Contract 3403 – Particular Specification 51 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
An interleaving circuitry arrangement shall be applied in the lighting
layout as shown on the Employer's Drawings such that there is no total
blackout in the event of single power supply failure. The lighting circuits
shall be in a staggered arrangement.
Armoured cable with PVC ducting protection shall be adopted for cables
embedded in soil for lighting installation in external landscape areas.
The lighting and control system shall be designed with flexibility in the
circuit arrangement to allow for future optimization of operation schedule
to achieve energy saving.
INTERIOR
Recessed
AVSECO LED
downlight for 500 0.6 19 80 IP20
DSM Office 4000K
general lighting.
Barrisol Ceiling
and recessed
downlights for
Ground
general lighting.
Floor LED
Decorative linear 200 0.4 22 80 IP20
Entrance 4000k
luminaires at
Lobby
staircases and
window for accent
lighting.
Recessed
LED
Main Hall downlight for 500 0.6 19 80 IP20
4000K
general lighting.
Recessed linear
luminaire and
recessed downlight
LED
AEC for general lighting. 300 0.6 19 80 IP20
4000K
Linear luminaires
at wall for accent
lighting.
Recessed
downlight for
AEC LED
general lighting. 500 0.6 22 80 IP20
Reception 4000K
Cove luminaire for
accent lighting.
Recessed
downlight for
Toilets general lighting. LED IP5X /
200 0.4 25 80
(Floor/Sink) Linear luminaires 3000K 4X
at mirror for
accent lighting.
Recessed
downlight for
Toilet general lighting. LED IP5X /
200 0.4 25 80
Cubicle Decorative cove 3000K 4X
luminaire for
accent lighting.
Recessed
downlight for
general lighting.
Breast-
Decorative cove LED IP5X /
feeding 200 0.4 25 80
luminaire and 3000K 4X
Room
linear luminaire at
mirror for accent
lighting.
Recessed Linear
luminaire for
general lighting. LED
CMT Room 500 0.6 19 80 IP20
Decorative cove 4000K
luminaire for
accent lighting.
Recessed Linear
luminaire for
general lighting. LED
CCD Room 500 0.6 19 80 IP20
Decorative cove 4000K
luminaire for
accent lighting.
Recessed
LED
PA Room downlight for 500 0.6 19 80 IP20
4000K
general lighting.
Recessed
LED
POV Room downlight for 500 0.6 19 80 IP20
4000K
general lighting.
Recessed
downlight and LED
Corridor 100 0.4 28 80 IP20
linear luminaire for 4000K
general lighting.
Surface mounted
LED
Staircase luminaire for 100 0.4 25 80 IP20
4000K
general lighting.
Recessed linear
luminaire, pendant
light and recessed
Resting downlight for LED
300 0.4 22 80 IP20
Area general lighting. 3000K
Decorative linear
luminaire for
accent lighting.
Recessed
downlights for
First Floor general lighting.
LED
Entrance Decorative linear 200 0.4 22 80 IP20
4000K
Lobby luminaires at
staircases for
accent lighting.
Recessed Linear
ADM
luminaire and LED
Support 500 0.6 19 80 IP20
downlight for 4000K
Room
general lighting.
Recessed Linear
Briefing LED
luminaire for 500 0.6 19 80 IP20
Room 4000K
general lighting.
Recessed
downlight for
Viewing general lighting. LED
300 0.4 28 80 IP20
Gallery Decorative linear 4000K
luminaire for
accent lighting.
Recessed linear
luminaire, pendant
light and recessed
Staff
downlight for LED
Common 200 0.4 22 80 IP20
general lighting. 3000K
Room
Decorative linear
luminaire for
accent lighting.
Surface mounted
LED
Staircase luminaire for 100 0.4 25 80 IP20
4000K
general lighting.
EXTERIOR
Recessed linear
Canopy and recessed LED
35-50 0.4 50 80 IP54
Walkway luminaire for 4000K
general lighting.
The lighting design shall meet the Glare Limit requirements as specified
in BS EN 12464 Light and lighting - Lighting of work places - Part 1:
Indoor work places. In case of deviation from this the Contractor shall
submit calculations based on their selected light fittings and associated
photometric data to verify the compliance of the Glare Limit requirements.
Unless otherwise specified or reviewed without objection by the Project
Contract 3403 – Particular Specification 55 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
Manager, 30 degree is the maximum tilt angle that should be used.
Interior Lighting
Control Intent
SCENE 1 SCENE 2
Area Comments/Notes
Day Night
(dawn to dusk) (dusk to dawn)
Toilets
Occupancy Sensor.
Resting Area All Fittings Are All Fittings Are
Additional Manual Local
POV Room Switched ON When Switched ON When
Control (By-Pass) By
ADM Office Area Is In Use Area Is In Use
Occupants.
Main Hall
Occupancy Sensor.
Daylight Sensor.
Additional Manual Local
Staff Common Area
Control (By-Pass) By All Fittings Are All Fittings Are
AEC Hall
Occupants. Switched ON When Switched ON When
Viewing Gallery
Viewing Gallery To Have Area Is In Use Area Is In Use
An Additional Manual
Local Control For 3rd
Party Controller.
Exterior Lighting
Control Intent
SCENE 1 SCENE 2
Area Comments/Notes
Day Night
(dawn to dusk) (dusk to dawn)
All Fittings Are
Functional
Time Clock & Daylight Switched OFF All Fittings Are
Lighting Canopy Walkway
Sensor To Be Provided During Daylight Switched ON
General
Hours
Light sensors shall be supplied and installed for the Lighting Control
System according the Employer’s Drawings and the Specification. Light
sensor locations are indicated on lighting plans and shall be reviewed
during commissioning for actual site conditions.
Emergency lighting provisions shall integrate with and form part of the
Front of House architectural lighting. The provisions of emergency
lighting shall meet the local FSD requirements and be designed to
BS5266.
OVERVEIW
The lighting control system for the Primary IAC should allow for
grouping of physical circuits into logical areas/ rooms. Lighting control
groups typically divide into general and feature lighting which are likely
to operate together during everyday use.
Occupancy Sensors:
Contract 3403 – Particular Specification 57 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
(a) Certain areas are controlled by passive infra-red presence
sensors and the sensors control shall be integrated into the
lighting control system. The sensors should allow a dedicated
configuration to “stay-on” (when the fixtures remain turned on)
times as required by the operator.
All logical groups, lighting scenes, control panel functions, etc. should
be configurable through a laptop-based software package.
DETAILED DESCRIPTION
General
(a) The Networked Control System (NCS) shall be a state of the
art micro-processor addressable lighting management
solution, providing flexibility through independent, distributed
control of any circuit within the building. The NCS shall use
advanced windows based graphical programing to enable the
lighting operation to be centrally programmed and configured.
Location of the main control room may be off-site and in
adjacent building with a local sub-control room on site to
connect to the main control room.
1. Keypads
2. Sensors…..PIR, US, PE
3. Integration and networking gateways to other systems
such as BACnet interface via RS-485 or Ethernet
COMMPLIANCE
6.5.2.2.2 The NCS manufacturer shall also have in place and demonstrate
active waste minimization and CO2 footprint minimization work
practices.
SYSTEM ARCHITECTURE
6.5.2.3.3 The control system shall achieve the required functionality by using
a distributed intelligence network architecture. In the event of a
network cable being severed, the system will automatically continue
to operate as two independent lighting control networks. Systems
that require operator intervention or where one or both networks
cease to operate in the event of a network cable cut shall not be
accepted.
6.5.2.3.4 The control system shall use advanced Windows based graphical
programming to configure all network devices and define the
behaviour and relationship between network devices. The software
must be capable of configuring any device within the system from
any location on the network. The software shall not be dependent on
extra plugins or drivers to enable configuration of devices.
6.5.2.3.5 The control system shall use a PC running intuitive and user-friendly
software for the remote programming of all devices on the control
network. It shall be possible to connect the PC to any point on the
network, for access to the entire system. The performance of the
system shall not be affected when the PC is disconnected. The
ability to interrogate the system and save the uploaded configuration
information to disk shall be included. The ability to log all network
Contract 3403 – Particular Specification 59 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
messages to a file for later analysis while the PC is connected to the
network shall be included.
6.5.2.3.6 All load controllers and user interfaces shall be supplied with a basic
configuration that allows the control system to operate in a default
way immediately upon installation. This allows for user interfaces to
send on, off and preset selection commands onto the network. All
load controllers correctly connected to the network will respond to
these messages appropriately. Achievement of this functionality
shall not require any commissioning.
6.5.2.3.8 Within the system configuration software, the system shall be able to
be viewed in logical groups, so that preset scenes and states can be
easily configured for each logical area. This is required so that
during project commissioning the control system can be viewed from
the same perspective as the physical project layout. Systems that
can only be viewed or configured with reference to a physical
controller or channel will not be accepted.
6.5.2.4.2 All load controllers must internally support the required resources
such as mains power supply, micro-processor, memory, direct
communication port, and internal logic so that devices are
independently responsible for their functionality. This is required so
that there are no hidden extra accessories that are required for
network devices to operate. Control systems which are dependent
on external network accessories for devices to achieve their core
functionality will not be accepted.
NETWORK TOPOLOGY
PROTOCOL
6.5.2.6.3 All UIs that belong in an area will update and synchronize their
indicator status automatically from the same network message that
instigated the scene change. Control systems that require a
dedicated or separate network message to synchronize their
indicator status will not be accepted as this adds commissioning
complexities and introduces a high risk of system indicators
becoming unsynchronized.
6.5.2.6.4 All network devices are to support the same network structure,
development method, and firmware type. This is to ensure seamless
and fully supported functionality between all network devices.
6.5.2.6.6 The network protocol shall be an event based message packet type.
6.5.2.6.7 The output state of load controllers shall recall preset levels stored
within the controller’s memory for each relevant network message.
To ensure network traffic is minimized, the system shall be capable
of recalling a preset scene or state involving all controller channels
bound to the same logical area from a single network message
associated with that area. Control systems that require multiple
network messages, or a message for each control channel to recall
a preset scene or state, will not be accepted.
6.5.2.6.9 The network protocol shall also support variable length packets and
incorporate a file transfer control to allow over-the-network upgrades
of device firmware and other settings. The protocol shall also
support message source identification.
Network Gateway
Protocol TCP/IP
Supported
No. of Network At least 3 (one for system, one for IAC Thin Client
Interfaces Network (via Server Farm Switch)
• Ethernet 1Gbps on Single Mode fibre (for typical
Apron/Airfield/Airport Systems Server)
Connection Types
• Ethernet 40Gbps on Single Mode fibre (for CCTV
System Server)
• At least 1Gbps (for typical
Throughput Apron/Airfield/Airport Systems Server)
• At least 40Gbps (for CCTV System Server)
Routing Protocol Static Route / OSPF
IP Address Support IPv4 and IPv6 (for Future Use)
Resilience Support VRRP or HSRP
Required to perform Network Address Translation
NAT between system IP address with AA 168.106.0.0 IP
(if not using 168.106.0.0 IP)
Support Simple Network Management Protocol
Alarm Monitoring (SNMP) for Real-Time Alarm Monitoring and
Reporting
CONTROL FUNCTIONALITY
(b) Daylight Override: When motion is detected in an area with natural light
it shall be possible to configure the control system to only operate the
luminaries if the light level is below a certain threshold.
6.5.2.9.1 Switching:
6.5.2.9.2 Dimming:
(a) The system shall utilize closed loop light level management to
control extra lighting rows offset from the window rows, for at
least two extra rows. Zones adjacent to windows receive more
daylight than those closer to the core of the building including
corridors in open space offices. The system must be capable
of implementing:
1. Light level control of luminaires in the window areas and
the core areas to be defined by a ratio.
2. Window area luminaires to be dimmed to a lower level
than the luminaires in corridor or core areas.
3. The area in-between dimmed to a pre-defined percentage
in reference to both window and core area levels.
PERSONAL CONTROL
(a) The system shall have provision to enable manual user controls to be
implemented where appropriate. Manual controls shall also be able to
change the behaviour of automated functions such as daylight
harvesting, occupancy detection or illumination management.
(a) The system shall enable manual control to be implemented via the
provision of keypads or touchscreens typically installed at the point of
entry into areas or zones, where appropriate.
LOAD CONTROLLERS
6.5.2.11.1 General:
SWITCHING CONTROLLERS
6.5.2.12.2 Relay contact ratings shall be 2A, 5A, 10A, 16A or 20A
continuous AC3 ratings.
USER INTERFACES
6.5.2.14.3 Keypads must contain an internal macro control facility that will
allow them to perform conditional and sequential logic. Systems
that rely on an external logic processor or centralized logic
processor shall not be acceptable.
SENSORS
6.5.2.16.3 TIMECLOCKS:
MATERIAL
SUBMISSIONS
The Contractor shall submit isolux diagrams and false colour renderings
to demonstrate compliance of final lighting proposals of the equipment
selected with the design. Upon request the Contractor shall submit the
editable simulation model, in case detail settings cannot be documented
in the isolux diagrams and false colour renderings.
Final Commissioning will take place after lux measurements have been
taken to ensure that the required lux, uniformity and glare limits
requirements are met and this is the stage where minor adjustments of
the lighting system takes place. The Contractor shall be responsible to
fine tune the aiming angles and programme lighting levels as per
comments from the Project Manger before final commissioning is
deemed to be completed.
DALI Commissioning
Lighting fitting and control specification shall refer to the details as given
in:-
GENERAL
The Contractor shall supply and install cables as shown on the cable
schedules and Employer’s Drawings. Separate cable containment shall
be provided and installed for LV and ELV cables.
The cable containment system shall also include surface cable conduit
system works for power & lighting and provisions of cast-in & concealed
conduits within the buildings. Co-ordination with builder's works is
required among different discipline trades.
The Contractor shall be responsible for the sizing and coordination of the
cable containment works including, but not limited to, the underground
cable ducts, trenches, cable ladders, cable trays, trunkings and conduits,
etc., to suit the power distribution requirements. Detailed cable
containment sizing and calculations shall be submitted to the Project
Manager for review without objection.
The Contractor shall supply and install all necessary cable containment,
cable change boxes as well as all necessary accessories for the
completion of power distribution system.
GENERAL
The Contractor shall ensure that the power quality requirements of CLP
as stipulated in the CLP Supply Rules, shall be met.
The Contractor shall take note of salient items relating to power quality
such as voltage depression caused by frequent / infrequent machine
starting, power factor and harmonics requirement and incorporate
means to mitigate disruption to crucial operation equipment when
carrying out system design and equipment selection.
3. Chilled Water Pump Control Panel 1. Voltage dip ride through device equipped with capacitor will be provided for control
circuit to prevent interruption from voltage dip occurrence. (Remaining 40% rated
voltage within 170m sec)
4. Chilled Water Pumps 1. The system operation shall follow the chiller system starting procedure to resume
normal operation.
5. AHU/PAU Control Panel 1. Voltage dip ride through device equipped with capacitor will be provided for control
circuit to prevent interruption from voltage dip occurrence. (Remaining 40% rated
voltage within 170m sec)
2. Time delay circuits shall be added and the remote reset of the AHU/PAU control
panel via MBMS will be designed.
3. DDC will be provided with battery for 1 hour back-up to overcome the voltage dip.
6. AHU / PAU Units 1. The system operation shall resume normal automatically after voltage dip.
7. Potable Water Pump Control Panel 1. Voltage dip ride through device equipped with capacitor will be provided for control
circuit to prevent interruption from voltage dip occurrence. (Remaining 40% rated
voltage within 170m sec)
8. Potable Water Pump 1. The pump operation shall resume normal automatically after voltage dip.
9. Flushing Water Pump Control Panel 1. Voltage dip ride through device equipped with capacitor will be provided for control
circuit to prevent interruption from voltage dip occurrence. (Remaining 40% rated
voltage within 170m sec)
10. Flushing Water Pump 1. The pump operation shall resume normal automatically after voltage dip.
11. Cleansing Water Pump Control Panel 1. Voltage dip ride through device equipped with capacitor will be provided for control
circuit to prevent interruption from voltage dip occurrence. (Remaining 40% rated
voltage within 170m sec).
13. Drainage Sump Pump Control Panel 1. Voltage dip ride through device equipped with capacitor will be provided for control
circuit to prevent interruption from voltage dip occurrence. (Remaining 40% rated
voltage within 170m sec).
14. Drainage Sump Pumps 1. The pump operation shall resume normal automatically after voltage dip
15. Fire Control System The AFA panel shall be equipped with backup battery to overcome the voltage dip.
16. Fire Links, AFA, NOVEC Systems The AFA and NOVEC system shall be equipped with backup battery to overcome the
voltage dip.
17. Static Smoke Vent Control System The control panel shall be equipped with backup battery to overcome the voltage dip.
18. Lift Control Lift Control Equipment with ride-through capability, e.g., control power backup by kinetic
energy buffering and /or regenerate power drive. Enhanced type VSD shall be deployed
for lift control.
19. Lift Motor The lifts will land in the designated floor and lift doors open to discharge the
passengers. After power restoration, the lifts would resume to normal operation.
IEC61000-4-11 shall be referred.
20. Lighting Control Panel Voltage dip ride through device equipped with capacitor will be provided for control
circuit to prevent interruption from voltage dip occurrence. (Remaining 40% rated
voltage within 170m sec)
21. Front of House Area Lighting (Cat. 2) 1. Lighting control gear with wide input voltage window will be specified. (110V – 240V)
2. Power supply for lighting circuit in interleaving arrangement, with power supply
sourced from two different CLP supply sources to prevent total black-out from
voltage dip / failure of one supply source.
3. Voltage dip effect on LED lighting is minimal as compare with conventional HID
Lamp.
22. Essential Lighting (Cat. 1) Backup battery pack and emergency generator in the Cat 1 light fitting to overcome the
voltage dip condition.
AHF shall be compatible with any type of load, and shall guarantee
efficient compensation, even when changes are made to the
installation. The AHF shall also be capable of delivering its rated output
harmonic current to the point of connection irrespective of load
condition.
Start-up and shut down of AHF shall be initiated by control push buttons
or other means. After a main power break-down, start-up of AHF shall
be automatic.
The Contractor shall implement the operation setting at site and submit
final setting record to the Project Manager for review without objection.
The setting shall be able to distinguish voltage dip and true supply
interruption. Unwanted operation of generator set caused by short
voltage dip less than 1 second shall be avoided.
GENERAL
The water leakage detection system shall include electronic audio and
visual alarm module, location module, sensing cable, graphic display
map and all necessary auxiliary equipment. The system shall be able to
detect multiple leaks simultaneously upon presence of water at any point
along the cable length, provide immediate warning and indicate the
location on a digital LCD/LED graphic display map of leak location.
The alarm and locator module of the water leakage detection system
The sensing cable shall offer distributed sensing with the ability to detect
the location of water at any point along the cable’s length. The cable
shall be flexible, and carry less than 24 V DC under normal operating
conditions. The sensing cable shall be provided with factory installed
male/female connectors. The cable shall be fastened securely to the
floor surface with hold-down clips together with adhesive every 2.5
meters or as necessary. The cable shall be dried and reset at the control
unit within 15 seconds upon complete removal of leaked water. No air-
drying shall be required to dry the cable.
The alarm module shall include an event log with time and date stamp.
The event log shall be stored on a FIFO basis.
The Contractor shall provide the connection including cables and cable
containment for interfacing with the lift system at the terminal blocks near
lift control cabinet to receive a water leakage detection signal and flood
detection high water alarm from the lift pits.
(e) Drain Pan under Chilled Water Pipes in Main Hall raised floor
void and Drip Tray under fan coil unit at AEC Hall
GENERAL
(d) The power supply for the EV charging facilities system shall
integrate with the electrical LV distribution system at the Primary
IAC, including LV switchgears, control facilities, metering devices,
SCADA interfaces, distribution equipment and boards, etc. so as
to facilitate the complete power supply for EV charging facilities
system.
General Requirements
The system shall allow monitoring and control the entire system in real
time.
The system shall include the octopus card system and the interface
with the fee payment equipment system and car park management
system.
EV Charging Facilities
For mode 3 charging, a 32A single phase socket outlet complying with
international standard IEC 62196 EV type 2 shall be used.
The Contractor shall submit its proposed construction details for the
normal EV charging facility to the Project Manager for review without
objection.
For mode 3 charging, the charging cable shall be detachable from the
socket and will be kept by the Project Manager for maintenance
purposes.
(b) The display shall be back-lit monitor type for easy viewing,
display shall also be anti-glare and scratch resistant.
(c) The display shall be touch screen monitor type and constructed
by material compatible with the ambient temperature at Hong
Kong International Airport
(d) LED lamps shall be adopted for all push button and indicator
lamps.
The Contractor shall provide all necessary tools and equipment with
valid calibration certificates to demonstrate the chargers are in
compliance with the requirements of the Specification. In the event
that an EV of respective charging type cannot be provided, the
Contractor shall provide simulation tools to emulate the vehicle on
board communication module in order to carry out the tests as
required. The Contractor shall provide full FAT report and perform
SAT during the commissioning of charger on site to verify the
Contract 3403 – Particular Specification 94 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.2 – Electrical Works
following items as a minimum. The tests shall include, but not limited
to, the following:
(1) Single phase and DC circuits - phase and neutral or positive and
negative identification;
(4) Dummy load test (Factory test only) with measurements for the
following parameters:
• Full load current
• Overload setting and protection function
• Charging profile in coordination with the vehicle on board
controller
• Temperature rise and alarm (if applicable)
(7) All mechanical and electrical protection tests including, but not
limited to, door interlocks, plug interlocks and emergency stop.
SUBMISSIONS
The Contractor shall also provide all necessary control components &
accessories such as contactors, relays and wirings etc. where necessary
to complete the functional requirements of the whole lighting and small
power system even if these components are not shown on the MCB
board schedules as attached or the Employer’s Drawings. Details shall
be submitted to the Project Manager for review without objection.
(a) Appendix C1.1 – 14A – MCB Board Schedule at the Primary IAC
(b) Appendix C1.2 – 14B – MCB Board Schedule at the Backup IAC
GENERAL
The Contractor shall design, supply, install, test and commission the
building services electrical works as shown on the CLP transformer room
drawings.
General
The Contractor shall carry out detail site survey and measurement to
identify all necessary existing power information to facilities such as
existing IAC, fence lighting, external road lighting and etc.
The Contractor shall apply for the necessary Work Permit to carry out
the required site survey work and in no circumstance shall this survey
work interrupt airport operations.
(a) Details of their size and material, fixing method and their
mounting level shown on plans, sections and elevations;
The Contractor shall re-submit a revised survey report for the Project
Manager’s review without objection if the survey report is rejected by
the Project Manager.
Prior to and during the execution of works, the Contractor shall liaise
and coordinate with the Project Manager and the Authority’s
maintenance department (TSD), government user department and
other concerned parties to set up and hold briefing meetings to
discuss the planned stages, agreed duration of the planned diversion
works and all other related matters for any facilities that are likely to
be affected by the works for the agreed duration of the planned
diversion and demolition work.
System description
The console tables in AEC hall are added to and rearranged in the
existing IAC. The corresponding power points for console tables shall
be added and rearranged to suit the revised room layout.
The Contractor shall provide for all necessary information such as the
associated cables, cable draw-pits, cable ducts and any manholes
which are sufficient for the required diversion works and submit to the
Project Manager for review without objection.
The Contractor shall design, supply, install, test and commission the
power supply system for OSPS 2 including distribution board, MCB,
conduits, socket outlets, lighting fixtures, lighting switches, cables,
cable containment and associated accessories.
The Contractor shall carry out the termination of incoming cables and
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 1
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A7-P,EDB1
DB TYPE 12-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 1 (A7-P) 1.37 1.78 2.81 1.66
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in Corridor 3 8.50 0.04 Lighting Contactor Group No. B1 Occupancy Sensor
1 L2 10 2x2.5 1C LSOH Lighting in Corridor 4 17.00 0.08 Lighting Contactor Group No. B2 Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Pantry 52.40 0.24 Lighting Contactor Group No. C1 Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Corridor 5 8.50 0.04 Lighting Contactor Group No. B4 Occupancy Sensor
2 L2 10 2x2.5 1C LSOH Lighting in Corridor 6 25.50 0.12 Lighting Contactor Group No. B5 Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Corridor 7 8.50 0.04 Lighting Contactor Group No. B6 Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Male Toilet (A9-P) 34.00 0.15 Lighting Contactor Group No. B7 Local Push Button, Occupancy Sensor
3 L2 10 2x2.5 1C LSOH Lighting in Male Toilet (A9-P) 32.50 0.15 Lighting Contactor Group No. B7 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Female Toilet (A9-Q) 42.50 0.19 Lighting Contactor Group No. B8 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Female Toilet (A9-Q) 45.50 0.21 Lighting Contactor Group No. B8 Local Push Button, Occupancy Sensor
4 L2 10 2x2.5 1C LSOH Lighting in Breastfeeding Room 19.50 0.09 Lighting Contactor Group No. B9 Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Breastfeeding Room 4.00 0.02 Lighting Contactor Group No. B9 Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Corridor 3 78.60 0.36 Lighting Contactor Group No. B1 Occupancy Sensor
5 L2 10 2x2.5 1C LSOH Lighting in Corridor 4 235.80 1.07 Lighting Contactor Group No. B2 Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Corridor 5 157.20 0.71 Lighting Contactor Group No. B4 Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Main Hall 216.00 0.98 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
6 L2 10 2x2.5 1C LSOH Lighting in Main Hall 288.00 1.31 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
7 L2 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Covered Walkway 80.00 0.36 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
8 L2 10 2x2.5 1C LSOH Lighting in High Level Canopy 80.00 0.36 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Low Level Canopy 90.00 0.41 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Low Level Canopy 40.00 0.18 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
9 L2 10 2x2.5 1C LSOH Lighting in Carpark Shelter 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 Spare 0.00 0.00
10 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
11 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
12 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 2
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A7-P,EDB2
DB TYPE 14-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 1 (A7-P) 1.36 1.54 2.09 2.55
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in Corridor 4 8.50 0.04 Lighting Contactor Group No. B2 Occupancy Sensor
1 L2 10 2x2.5 1C LSOH Lighting in Pantry 8.50 0.04 Lighting Contactor Group No. C1 Time Schedule and Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Entrance Canopy 12.00 0.05 Lighting Contactor Group No. C2 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Entrance Canopy 12.00 0.05 Lighting Contactor Group No. C3 Daylight Sensor and Time Clock
2 L2 10 2x2.5 1C LSOH Lighting in Corridor 6 25.50 0.12 Lighting Contactor Group No. B5 Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Corridor 7 8.50 0.04 Lighting Contactor Group No. B6 Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Male Toilet (A9-P) 4.00 0.02 Lighting Contactor Group No. B7 Local Push Button, Occupancy Sensor
3 L2 10 2x2.5 1C LSOH Lighting in Male Toilet (A9-P) 32.50 0.15 Lighting Contactor Group No. B7 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Female Toilet (A9-Q) 42.50 0.19 Lighting Contactor Group No. B8 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Female Toilet (A9-Q) 78.00 0.35 Lighting Contactor Group No. B8 Local Push Button, Occupancy Sensor
4 L2 10 2x2.5 1C LSOH Lighting in Disabled Toilet (A9-Q) 19.50 0.09 Lighting Contactor Group No. C5 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Breastfeeding Room 132.00 0.60 Lighting Contactor Group No. B9 Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Corridor 3 78.60 0.36 Lighting Contactor Group No. B1 Occupancy Sensor
5 L2 10 2x2.5 1C LSOH Lighting in Corridor 4 157.20 0.71 Lighting Contactor Group No. B2 Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Corridor 5 78.60 0.36 Lighting Contactor Group No. B4 Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Corridor 6 157.20 0.71 Lighting Contactor Group No. B5 Occupancy Sensor
6 L2 10 2x2.5 1C LSOH Lighting in Main Hall 216.00 0.98 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Main Hall 288.00 1.31 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
7 L2 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
8 L2 10 2x2.5 1C LSOH Lighting in Covered Walkway 80.00 0.36 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in High Level Canopy 80.00 0.36 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Low Level Canopy 90.00 0.41 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
9 L2 10 2x2.5 1C LSOH Lighting in Low Level Canopy 40.00 0.18 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Carpark Shelter 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
10 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
11 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
12 L2 10 Spare 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
13 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
14 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 3
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A9-S,EDB1
DB TYPE 8-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 2 (A9-S) 0.92 1.06 1.40 1.71
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in Lobby (A9-S) 13.40 0.06 Lighting Contactor Group No. D1 Occupancy Sensor
1 L2 10 2x2.5 1C LSOH Lighting in Main Hall 17.00 0.08 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Disabled Toilet (A9-T) 56.00 0.25 Lighting Contactor Group No. D2 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Toilet (A9-T) 13.00 0.06 Lighting Contactor Group No. D3 Local Push Button, Occupancy Sensor
2 L2 10 2x2.5 1C LSOH Lighting in Resting Area 30.00 0.14 Lighting Contactor Group No. D4 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Resting Area 50.00 0.23 Lighting Contactor Group No. D4 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in POV Room 10.00 0.05 Controlled by DALI
3 L2 10 2x2.5 1C LSOH Lighting in CCD Room 230.00 1.05 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in CCD Room 230.00 1.05 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in AEC Hall Corridor 167.00 0.76 Lighting Contactor Group No. D5 Daylight Sensor
4 L2 10 2x2.5 1C LSOH Lighting in AEC Hall 10.00 0.05 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in AEC Hall 10.00 0.05 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in AEC Hall 20.00 0.09 Controlled by DALI
5 L2 10 2x2.5 1C LSOH Lighting in AEC Hall Corridor 0.00 0.00 Lighting Contactor Group No. D5 Daylight Sensor
L3 10 2x2.5 1C LSOH Lighting in CMT Room 20.00 0.09 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in CMT Room 10.00 0.05 Controlled by DALI
6 L2 10 2x2.5 1C LSOH Lighting in AEC Reception 20.00 0.09 Lighting Contactor Group No. D6 Local Push Button
L3 10 2x2.5 1C LSOH Lighting in Disabled Toilet (A4-S) 10.00 0.05 Lighting Contactor Group No. D7 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Main Lobby 30.00 0.14 Lighting Contactor Group No. D8 Daylight Sensor
7 L2 10 2x2.5 1C LSOH Lighting in Main Lobby 10.00 0.05 Lighting Contactor Group No. D8 Daylight Sensor
L3 10 Spare 0.00 0.00
L1 10 2x2.5 1C LSOH Lighting in Male Toilet (A3-T) 17.00 0.08 Lighting Contactor Group No. D9 Local Push Button, Occupancy Sensor
8 L2 10 2x2.5 1C LSOH Lighting in Female Toilet (A3-S) 17.00 0.08 Lighting Contactor Group No. D10 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Female Toilet (A3-S) 19.50 0.09 Lighting Contactor Group No. D10 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Main Hall 17.00 0.08 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
9 L2 10 2x2.5 1C LSOH Lighting in Entrance 18.80 0.09 Lighting Contactor Group No. D11 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
10 L2 10 2x2.5 1C LSOH Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 Spare 0.00 0.00
11 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
12 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
13 L2 10 Spare 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
14 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 4
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A9-S,EDB2
DB TYPE 14-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 2 (A9-S) 0.99 0.56 1.64 2.32
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in Main Hall 17.00 0.08 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
1 L2 10 2x2.5 1C LSOH Lighting in Disabled Toilet (A9-T) 20.00 0.09 Lighting Contactor Group No. D2 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Disabled Toilet (A9-T) 30.00 0.14 Lighting Contactor Group No. D2 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Resting Area 8.50 0.04 Lighting Contactor Group No. E1 Occupancy Sensor
2 L2 10 2x2.5 1C LSOH Lighting in Toilet (A9-T) 13.00 0.06 Lighting Contactor Group No. D3 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Resting Area 25.50 0.12 Lighting Contactor Group No. D4 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in POV Room 25.50 0.12 Controlled by DALI
3 L2 10 2x2.5 1C LSOH Lighting in CCD Room 93.60 0.43 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in CCD Room 42.50 0.19 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in AEC Hall Corridor 8.50 0.04 Lighting Contactor Group No. D5 Daylight Sensor
4 L2 10 2x2.5 1C LSOH Lighting in AEC Hall 210.00 0.95 Lighting Contactor Group No. D5 Daylight Sensor
L3 10 2x2.5 1C LSOH Lighting in AEC Hall 336.00 1.53 Lighting Contactor Group No. D5 Daylight Sensor
L1 10 2x2.5 1C LSOH Lighting in ADM Office 21.00 0.10 Lighting Contactor Group No. E2 Local Push Button, Occupancy Sensor
5 L2 10 2x2.5 1C LSOH Lighting in PA Room 7.50 0.03 Lighting Contactor Group No. E3 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in CMT Room 70.20 0.32 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in CMT Room 42.50 0.19 Controlled by DALI
6 L2 10 2x2.5 1C LSOH Lighting in AEC Reception 17.00 0.08 Lighting Contactor Group No. D6 Local Push Button
L3 10 2x2.5 1C LSOH Lighting in Disabled Toilet (A4-S) 6.50 0.03 Lighting Contactor Group No. D7 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Main Lobby 59.50 0.27 Lighting Contactor Group No. D8 Daylight Sensor
7 L2 10 2x2.5 1C LSOH Lighting in Main Lobby 120.00 0.55 Lighting Contactor Group No. D8 Daylight Sensor
L3 10 Spare 0.00 0.00
L1 10 2x2.5 1C LSOH Lighting in Male Toilet (A3-T) 17.00 0.08 Lighting Contactor Group No. D9 Local Push Button, Occupancy Sensor
8 L2 10 2x2.5 1C LSOH Lighting in Male Toilet (A3-T) 6.50 0.03 Lighting Contactor Group No. D9 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Female Toilet (A3-S) 17.00 0.08 Lighting Contactor Group No. D10 Local Push Button, Occupancy Sensor
L1 10 Spare 0.00 0.00
9 L2 10 2x2.5 1C LSOH Lighting in Main Hall 17.00 0.08 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Entrance 18.80 0.09 Lighting Contactor Group No. D11 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
10 L2 10 2x2.5 1C LSOH Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C LSOH Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C LSOH Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
11 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
12 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
13 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
14 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 5
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EL&P-02b/0,A2-Q,FDB1
DB TYPE 14-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION LV Switch Room 1.87 1.87 3.34 3.28
Cct. RCCB/ Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Fuel Filling Cabinet and Fuel Tank Room 56.80 0.26 Local Timer Switch
1 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Fuel Filling Cabinet and Fuel Tank Room 56.80 0.26 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Fuel Pump Room and Mobile Genset Socket Panel Room 61.90 0.28 Local Timer Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Fuel Pump Room and Mobile Genset Socket Panel Room 61.90 0.28 Local Timer Switch
2 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in FS Control Room, Genset Room and Lobby 134.00 0.61 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 1 100.50 0.46 Lighting Contactor Group No. A2 Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Pre-action Valve Chamber and Genset Room Lobby 67.00 0.30 Local Timer Switch
3 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Water Pump and Tank Room 91.50 0.42 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in FS Control Room and Chiller Plant Room 100.50 0.46 Local Switch (FS Control Room)
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in MCC Chiller Room and Gas Bottle Cabinet 100.50 0.46 Local Timer Switch
4 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in LV Switch Room and Pipe Duct (A2-P) 100.50 0.46 Local Timer Switch
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
5 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in CR 79 234.50 1.07 Lighting Contactor Group No. A3 Local Timer Switch and Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in CR 79 268.00 1.22 Lighting Contactor Group No. A3 Local Timer Switch and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Cable Lead-in Cabinet 2 33.50 0.15 Local Timer Switch
6 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Cable Lead-in Cabinet 2 33.50 0.15 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Locker Room 69.60 0.32 Lighting Contactor Group No. A6 Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Locker Room Changing Room 1 17.40 0.08 Lighting Contactor Group No. F1 Local Switch, Time Schedule and Occupancy Sensor
7 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Locker Room Changing Room 1 17.40 0.08 Lighting Contactor Group No. F1 Local Switch, Time Schedule and Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Locker Room Changing Room 2 17.00 0.08 Lighting Contactor Group No. F2 Local Switch, Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Locker Room Changing Room 2 17.00 0.08 Lighting Contactor Group No. F2 Local Switch, Time Schedule and Occupancy Sensor
8 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Locker Room 17.40 0.08 Lighting Contactor Group No. A5 Local Switch, Time Schedule and Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Locker Room Changing Room 1 17.40 0.08 Lighting Contactor Group No. F3 Local Switch, Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Locker Room Changing Room 1 34.80 0.16 Lighting Contactor Group No. F3 Local Switch, Time Schedule and Occupancy Sensor
9 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Locker Room Changing Room 2 30.00 0.14 Lighting Contactor Group No. F4 Local Switch, Time Schedule and Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Locker Room Changing Room 2 9.00 0.04 Lighting Contactor Group No. F4 Local Switch, Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 9.00 0.04 Always On
10 L2 10 2x2.5 1C FR/LSOH Emergency Lighting for Covered Walkway 40.00 0.18 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Covered Walkway 70.00 0.32 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 Spare 0.00 0.00
11 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
12 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 Space 0.00 0.00
13 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
14 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 6
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EL&P-02b/0,A7-P,FDB1
DB TYPE 18-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 1 (A7-P) 0.59 0.89 0.79 1.22
Cct. RCCB/ Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 3 17.00 0.08 Lighting Contactor Group No. B1 Occupancy Sensor
1 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Pantry 8.50 0.04 Lighting Contactor Group No. C1 Time Schedule and Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting for Hose Reel 7.00 0.03 Non-maintained
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 4 59.50 0.27 Lighting Contactor Group No. B2 Occupancy Sensor
2 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room 1 and TBE Room 67.00 0.30 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room 1 and TBE Room 67.00 0.30 Local Timer Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 5 17.00 0.08 Lighting Contactor Group No. B4 Occupancy Sensor
3 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Toilet (A9-P) 33.50 0.15 Lighting Contactor Group No. B7 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Toilet (A9-P) 20.00 0.09 Lighting Contactor Group No. B7 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in CC79A and Pipe Duct (A9-S) 80.00 0.36 Local Timer Switch
4 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in CC79A and Pipe Duct (A9-S) 30.50 0.14 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Toilet (A9-Q) 30.50 0.14 Lighting Contactor Group No. B8 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Toilet (A9-Q) 80.00 0.36 Lighting Contactor Group No. B8 Local Push Button, Occupancy Sensor
5 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Toilet Lobby (A9-P) 10.00 0.05 Lighting Contactor Group No. G1 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Toilet Lobby (A9-P) 10.00 0.05 Lighting Contactor Group No. G1 Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Hose Reel 10.00 0.05 Non-maintained
6 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Toilet Lobby (A9-Q) 20.00 0.09 Lighting Contactor Group No. G2 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Toilet Lobby (A9-Q) 20.00 0.09 Lighting Contactor Group No. G2 Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 6 15.00 0.07 Lighting Contactor Group No. B5 Occupancy Sensor
7 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 7 0.00 0.00 Lighting Contactor Group No. B6 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Disabled Toilet (A9-Q) 8.50 0.04 Lighting Contactor Group No. C5 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Disabled Toilet (A9-Q) 8.50 0.04 Lighting Contactor Group No. C5 Local Push Button, Occupancy Sensor
8 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Breastfeeding Room 17.00 0.08 Lighting Contactor Group No. B9 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Pipe Duct (A9-Q) 0.00 0.00 Local Timer Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Cable Lead-in Cabinet 1 and CC79B 67.00 0.30 Local Timer Switch
9 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Cable Lead-in Cabinet 1 and CC79B 67.00 0.30 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting for Hose Reel 7.00 0.03 Non-maintained
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in AVSECO DSM Office 21.00 0.10 Lighting Contactor Group No. G3 Timeclock, Local Push Button, Occupancy Sensor
10 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in AVSECO DSM Office 21.00 0.10 Lighting Contactor Group No. G3 Timeclock, Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Covered Walkway 0.00 0.00 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
11 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Covered Walkway 100.00 0.45 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C FR/LSOH Emergency Lighting for Hose Reel 14.00 0.06 Non-maintained
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in High Level Canopy 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
12 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Low Level Canopy 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Low Level Canopy 20.00 0.09 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Carpark Shelter 80.00 0.36 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
13 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Covered Walkway 90.00 0.41 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 6.00 0.03 Always On
L1 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs and Directional Signs 12.00 0.05 Always On
14 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
15 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
16 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 7
L1 10 Spare 0.00 0.00
17 L2 10 Spare 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
18 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 8
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EL&P-02b/0,A9-S,FDB1
DB TYPE 20-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 2 (A9-S) 0.84 1.73 0.92 1.16
Cct. RCCB/ Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A9-S) 80.40 0.37 Lighting Contactor Group No. D1 Occupancy Sensor
1 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room (A9-S) 13.40 0.06 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Main Hall 34.00 0.15 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Pipe Duct (A7-T and A5-T) 61.00 0.28 Local Timer Switch
2 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room 2 25.50 0.12 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room 2 51.00 0.23 Local Timer Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Disabled Toilet (A9-Q) 17.00 0.08 Lighting Contactor Group No. D2 Local Push Button, Occupancy Sensor
3 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Resting Area 17.00 0.08 Lighting Contactor Group No. E1 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Toilet (A9-T) 17.00 0.08 Lighting Contactor Group No. D3 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Toilet (A9-T) 17.00 0.08 Lighting Contactor Group No. D3 Local Push Button, Occupancy Sensor
4 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Resting Area 17.00 0.08 Lighting Contactor Group No. D4 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in POV Room 17.00 0.08 Controlled by DALI
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in CCD Room 46.80 0.21 Controlled by DALI
5 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in AEC Hall Corridor 25.50 0.12 Lighting Contactor Group No. D5 Daylight Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in AEC Hall 63.00 0.29 Controlled by DALI
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in AEC Hall 84.00 0.38 Controlled by DALI
6 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in AEC Hall 63.00 0.29 Controlled by DALI
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in ADM Office 42.00 0.19 Lighting Contactor Group No. E2 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Pipe Duct (A7-T and A5-T) 26.80 0.12 Local Timer Switch
7 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in AEC Hall Corridor 34.00 0.15 Lighting Contactor Group No. D5 Daylight Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in PA Room 15.00 0.07 Lighting Contactor Group No. E3 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in CMT Room 46.80 0.21 Controlled by DALI
8 L2 10 2x2.5 1C FR/LSOH Emergency Lighting for Hose Reel 7.00 0.03 Non-Maintained
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in AEC Reception 17.00 0.08 Lighting Contactor Group No. D6 Local Push Button
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Pipe Duct (A4-T) 61.00 0.28 Local Timer Switch
9 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Disabled Toilet (A4-S) 17.00 0.08 Lighting Contactor Group No. D7 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Main Lobby 42.50 0.19 Lighting Contactor Group No. D8 Daylight Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A3-T) 8.50 0.04 Lighting Contactor Group No. H1 Occupancy Sensor
10 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A3-T) 8.50 0.04 Lighting Contactor Group No. H1 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A3-S) 8.50 0.04 Lighting Contactor Group No. H2 Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A3-S) 8.50 0.04 Lighting Contactor Group No. H2 Occupancy Sensor
11 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Toilet (A3-T) 17.00 0.08 Lighting Contactor Group No. D9 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Toilet (A3-S) 25.50 0.12 Lighting Contactor Group No. D10 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Main Hall 34.00 0.15 Lighting Contactor Group No. B11 Daylight Sensor and Time Clock
12 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A3-S) 8.50 0.04 Lighting Contactor Group No. H3 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A3-S) 8.50 0.04 Lighting Contactor Group No. H3 Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Pipe Duct (A3-S) 30.50 0.14 Local Timer Switch
13 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Covered Walkway 60.00 0.27 Lighting Contactor Group No. A7 Daylight Sensor and Time Clock
14 L2 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs and Directional Signs 0.00 0.00 Always On
L3 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 15.00 0.07 Always On
L1 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 6.00 0.03 Always On
15 L2 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 6.00 0.03 Always On
L3 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 3.00 0.01 Always On
L1 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 3.00 0.01 Always On
16 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 9
L1 10 Spare 0.00 0.00
17 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
18 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
19 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
20 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 10
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A2-Q,EDB2
DB TYPE 12-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION LV Switch Room 24.82 59.82 25.18 27.82
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 4x4 1C LSOH 13A S/O in Corridor, and Male Locker Room 2500.00 11.36 Ring Circuit
1 L2 #32 4x4 1C LSOH 13A S/O in AVSECO DSM Room 1000.00 4.55 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Female Locker Room, and Cable Lead-in Room 2500.00 11.36 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in CR79 5000.00 22.73 Ring Circuit
2 L2 #32 4x4 1C LSOH 13A S/O for DALI Control in CR79 1500.00 6.82 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O for DALI Control in CR79 1500.00 6.82 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in LV Switch Room 500.00 2.27 Ring Circuit
3 L2 #32 4x4 1C LSOH 13A S/O in Chiller Plant Room, and Water Pump and Tank Room Ring Circuit
1500.00 6.82
L3 #32 4x4 1C LSOH 13A S/O in FS Control Room 1500.00 6.82 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in Chiller MCC Room, and Corridor 1500.00 6.82 Ring Circuit
4 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
13A S/O for Fuel Filling Cabinet, Fuel Tank Room, Fuel Pump
L1 #32 4x4 1C LSOH Ring Circuit
Room, and Mobile Genset Panel Room 2000.00 9.09
5 L2 #32 4x4 1C LSOH 13A S/O in Genset Room 1000.00 4.55 Ring Circuit
L3 #32 4x4 1C LSOH Spare 0.00 0.00
L1 20 2x4 1C LSOH 13A FSU for DIU 160.00 0.73
6 L2 20 2x4 1C LSOH 13A FSU for DIU 40.00 0.18
L3 20 2x4 1C LSOH 13A FSU for CCTV 120.00 0.55
L1 2.27
7 L2 32 4x6 1C LSOH 32A TPN Isolator for Roller Shutter 1500.00 2.27
L3 2.27
L1 #32 Spare 0.00 0.00
8 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 20 2x4 1C LSOH 13A FSU for Summation Metering Cubicle in LV Switch Room 1000.00 4.55
9 L2 20 Spare 0.00 0.00
L3 20 Spare 0.00 0.00
L1 Space 0.00 0.00
10 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
11 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
12 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 11
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A2-Q,EDB3
DB TYPE 12-way, TPN BUSBAR RATING: 160A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 160A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION LV Switch Room 65.40 114.5 92.7 90.0
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3000.00 13.64 Radial Circuit
1 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3000.00 13.64 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3000.00 13.64 Radial Circuit
2 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 1800.00 8.18 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 1800.00 8.18 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3000.00 13.64 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 1800.00 8.18 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3600.00 16.36 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
6 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3600.00 16.36 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
7 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 2400.00 10.91 Radial Circuit
8 L2 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 3000.00 13.64 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 1800.00 8.18 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 3000.00 13.64 Radial Circuit
9 L2 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 1800.00 8.18 Radial Circuit
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
10 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
11 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
12 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 12
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A7-P,EDB3
DB TYPE 12-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 1 (A7-P) 15.62 35.36 13.09 22.55
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 4x4 1C LSOH 13A S/O in Corridor, Breastfeeding Room, and Disable Toilet 2500.00 11.36 Ring Circuit
1 L2 #32 4x4 1C LSOH 13A S/O in LV Switch Room 500.00 2.27 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Male Toilet, and Female Toilet 2000.00 9.09 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in Corridor, EL Room, and TBE Room 2000.00 9.09 Ring Circuit
2 L2 #32 4x4 1C LSOH 13A S/O in Pantry 2000.00 9.09 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Pantry 1500.00 6.82
L1 20 2x4 1C LSOH 13A FSU for DIU 80.00 0.36
13A FSU for Auto-Flushing Sensor, and Water Tap in
3 L2 20 2x4 1C LSOH
Breastfeeding Room and Female Toilet 60.00 0.27
L3 20 2x4 1C LSOH 13A FSU for Water Tap in Female Toilet 1200.00 5.45
L1 20 2x4 1C LSOH 13A FSU for Hand Dryer in Female Toilet 1500.00 6.82
4 L2 20 2x4 1C LSOH 13A FSU for Auto-Flushing Sensor in Female Toilet 160.00 0.73
L3 20 2x4 1C LSOH 13A FSU for Auto-Flushing Sensor, and Water Tap in Male Toilet
160.00 0.73
L1 20 2x4 1C LSOH 13A FSU for Hand Dryer in Male Toilet 1500.00 6.82
5 L2 20 2x4 1C LSOH 13A FSU for Auto-Flushing Sensor, and Water Tap in Male Toilet
160.00 0.73
L3 20 2x4 1C LSOH 13A FSU for CCTV 100.00 0.45
L1 20 2x4 1C LSOH 13A FSU for Sliding Door in IAC Hall 200.00 0.91
6 L2 20 Spare 0.00 0.00
L3 20 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
7 L2 #32 Spare 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
8 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
9 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
10 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
11 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
12 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 13
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A7-P,EDB4
DB TYPE 12-way, TPN BUSBAR RATING: 160A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 160A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 1 (A7-P) 67.80 103.6 111.8 92.7
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
1 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3600.00 16.36 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 1800.00 8.18 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
2 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3600.00 16.36 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 1800.00 8.18 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3000.00 13.64 Radial Circuit
6 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3000.00 13.64 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 1800.00 8.18 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3000.00 13.64 Radial Circuit
7 L2 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 3000.00 13.64 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Main Hall Desk 2400.00 10.91 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 2400.00 10.91 Radial Circuit
8 L2 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 2400.00 10.91 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 3600.00 16.36 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 2400.00 10.91 Radial Circuit
9 L2 #32 2x6 1C LSOH 13A S/O for AEC Hall Desk 3600.00 16.36 Radial Circuit
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
10 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
11 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
12 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 14
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/0,A9-S,EDB3
DB TYPE 12-way, TPN BUSBAR RATING: 100A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 100A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 2 (A9-S) 40.20 71.36 61.18 50.18
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 4x4 1C LSOH 13A S/O in Lobby 1500.00 6.82 Ring Circuit
1 L2 #32 4x4 1C LSOH 13A S/O in Male Toilet, and Female Toilet 2000.00 9.09 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Disable Toilet 1000.00 4.55 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in Reception 2000.00 9.09 Ring Circuit
2 L2 #32 4x4 1C LSOH 13A S/O in Corridor, AEC Hall, and CMT Room 2500.00 11.36 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O for Smart Glass 1000.00 4.55 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in AEC Hall, and ADM 2000.00 9.09 Ring Circuit
3 L2 #32 4x4 1C LSOH 13A S/O in ADM Desk 2000.00 9.09 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in AEC Hall, Corridor, and CCD Room 2500.00 11.36 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in CCD Room Desk 4000.00 18.18 Ring Circuit
4 L2 #32 4x4 1C LSOH 13A S/O in POV Room, and Resting Corner 2000.00 9.09 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Toilet, and Disable Toilet 2000.00 9.09 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in EL Room, Cable Lead-in Cabinet, and CR79B 2000.00 9.09 Ring Circuit
5 L2 #32 4x4 1C LSOH 13A S/O in Resting Corner 1500.00 6.82 Ring Circuit
L3 #32 Spare 0.00 0.00
L1 20 2x4 1C LSOH 13A FSU for DIU 100.00 0.45
6 L2 20 2x4 1C LSOH 13A FSU for CCTV 80.00 0.36
L3 20 2x4 1C LSOH 13A FSU for Hand Dryer in Male Toilet 1500.00 6.82
L1 20 2x4 1C LSOH 13A FSU for Hand Dryer in Female Toilet 1500.00 6.82
13A FSU for Auto-Flushing Sensor, and Water Tap in Male Toilet
7 L2 20 2x4 1C LSOH
and Female Toilet 1800.00 8.18
L3 20 2x4 1C LSOH 13A FSU for Hand Dryer in Disable Toilet 1500.00 6.82
13A FSU for Auto-Flushing Sensor, and Water Tap in Disable
L1 20 2x4 1C LSOH
Toilet 400.00 1.82
8 L2 20 2x4 1C LSOH 13A FSU for DIU 80.00 0.36
L3 20 2x4 1C LSOH 13A FSU for CCTV 40.00 0.18
13A FSU for Auto-Flushing Sensor, and Water Tap in Resting
L1 20 2x4 1C LSOH
Corner, Toilet, and Disable Toilet 1400.00 6.36
9 L2 20 2x4 1C LSOH 13A FSU for Hand Dryer in Toilet 1500.00 6.82
L3 20 2x4 1C LSOH 13A FSU for Hand Dryer in Disable Toilet 1500.00 6.82
L1 20 2x4 1C LSOH 13A FSU for DALI Device 800.00 3.64
10 L2 20 Spare 0.00 0.00
L3 20 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
11 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
12 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 15
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EL&P-02a/0,A2-Q,FDB2
DB TYPE 8-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02a MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION LV SWITCH ROOM 14.50 29.55 27.27 9.09
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
13A FSU for Preaction Valve Control Panel and Air Compressor in
L1 20 2x4 1C FR/LSOH
Preaction Valve Cabinet 4500.00 20.45
13A FSU for Preaction Valve Control Panel and Air Compressor in
1 L2 20 2x4 1C FR/LSOH
Preaction Valve Cabinet 4500.00 20.45
L3 20 2x4 1C FR/LSOH 13A FSU for Instrinsically Safe Detector Panel in Genset Room
500.00 2.27
L1 #32 4x4 1C FR/LSOH 13A S/O for FS Workstation in FS Control Room 500.00 2.27 Ring Ciruut
2 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 20 2x4 1C FR/LSOH 13A FSU for AFA Panel in FS Control Room 500.00 2.27
3 L2 20 2x4 1C FR/LSOH 13A FSU for NOVEC1230 Panel for CR79 500.00 2.27
L3 20 2x4 1C FR/LSOH 13A FSU for Control Panel Heater 500.00 2.27
L1 20 2x4 1C FR/LSOH 13A FSU for Alternator Heater 500.00 2.27
4 L2 20 2x4 1C FR/LSOH 13A FSU for Engine Heater 500.00 2.27
L3 20 2x4 1C FR/LSOH 13A FSU for Battery Charger 500.00 2.27
L1 20 Spare 0.00
5 L2 20 Spare 0.00
L3 20 Spare 0.00
L1 2.27
6 L2 32 4x6 1C LSOH 32A TPN Isolator for Fire Roller Shutter 1500.00 2.27
L3 2.27
L1 2.27
7 L2 32 4x6 1C LSOH 32A TPN Isolator for Fire Roller Shutter 1500.00 2.27
L3 2.27
L1 Space 0.00
8 L2 Space 0.00
L3 Space 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 16
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE MS-02b/0,A2-Q,EDB1
DB TYPE 6-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION LV SWITCH ROOM 10.32 12.89 15.08 18.94
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 32 2x10 1C LOSH LCP(M)-006 for Pantry 370.00 1.68
1 L2 32 2x10 1C LOSH LCP(M)-009 for LV Switch Room 1100.00 5.00
L3 32 2x10 1C LOSH LCP(M)-010 for Water Tank and Pump Room 1650.00 7.50
L1 32 2x10 1C LOSH LCP(M)-011 for Genset Room 550.00 2.50
2 L2 32 Spare 0.00 0.00
L3 32 Spare 0.00 0.00
L1 0.00 6.67
3 L2 32 4x16 1C LOSH LCP(M)-008 for Chiller MCC Room 4400.00 6.67
L3 0.00 6.67
L1 20 2x4 1C LOSH 13A FSU for FCU 450.00 2.05
4 L2 20 2x4 1C LOSH 13A FSU for FCU 750.00 3.41
L3 20 2x4 1C LOSH 13A FSU for FCU 1050.00 4.77
L1 20 Spare 0.00 0.00
5 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
6 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 17
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE MS-02b/0,A7-P,EDB1
DB TYPE 6-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 1 (A7-P) 5.68 6.77 17.36 1.68
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 32 2x10 1C LOSH LCP(M)-002 for Nursing Room 370.00 1.68
1 L2 32 2x10 1C LOSH LCP(M)-003 for CC79A 370.00 1.68
L3 32 2x10 1C LOSH LCP(M)-004 for EL Room 1 370.00 1.68
L1 32 2x10 1C LOSH LCP(M)-005 for TBE Room 370.00 1.68
2 L2 32 2x10 1C LOSH LCP(M)-015 for Male Toilet 3000.00 13.64
L3 32 Spare 0.00 0.00
L1 32 Spare 0.00 0.00
3 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 20 2x4 1C LOSH 13A FSU for FCU 750.00 3.41
4 L2 20 2x4 1C LOSH 13A FSU for FCU 450.00 2.05
L3 20 Spare 0.00 0.00
L1 Space 0.00
5 L2 Space 0.00
L3 Space 0.00
L1 Space 0.00
6 L2 Space 0.00
L3 Space 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 18
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE MS-02b/0,A9-S,EDB1
DB TYPE 6-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 2 (A9-S) 5.00 9.82 6.09 6.82
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 32 2x10 1C LOSH LCP(M)-001 for CC79B 370.00 1.68
1 L2 32 2x10 1C LOSH LCP(M)-012 for Resting Area 370.00 1.68
L3 32 2x10 1C LOSH LCP(M)-013 for Male Toilet 1500.00 6.82
L1 32 2x10 1C LOSH LCP(M)-014 Accessible Toilet 740.00 3.36
2 L2 32 2x10 1C LOSH LCP(M)-016 EL Room 2 370.00 1.68
L3 32 Spare 0.00 0.00
L1 32 Spare 0.00 0.00
3 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 20 2x4 1C LOSH 13A FSU for FCU 1050.00 4.77
4 L2 20 2x4 1C LOSH 13A FSU for FCU 600.00 2.73
L3 20 Spare 0.00 0.00
L1 Space 0.00 0.00
5 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
6 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 19
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/0,A3-Q,UDB1
DB TYPE 16-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION CR79 66.10 100.45 100.00 100.00
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
1 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
2 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
3 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
4 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
5 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
6 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
7 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
8 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
9 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
10 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
11 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 Spare 0.00 0.00
12 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 20
L1 20 2x4 1C LSOH 13A FSU for AP in CR79 100.00 0.45
13 L2 20 Spare 0.00 0.00
L3 20 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
14 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
15 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
16 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 21
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/0,A3-Q,UDB2
DB TYPE 16-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION CR79 66.10 100.45 100.00 100.00
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
1 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
2 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
3 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
4 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
5 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
6 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
7 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
8 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
9 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
10 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
11 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CR79 2000.00 9.09
L1 #32 Spare 0.00 0.00
12 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 22
L1 20 2x4 1C LSOH 13A FSU for Airfield SCADA 100.00 0.45
13 L2 20 Spare 0.00 0.00
L3 20 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
14 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
15 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
16 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 23
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/0,A7-P,UDB1
DB TYPE 16-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 1 (A7-P) 77.27 122.43 113.80 114.98
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC79A 2000.00 9.09
1 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC79A 2000.00 9.09
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC79B 2000.00 9.09
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC79B 2000.00 9.09
2 L2 20 2x4 1C LSOH 20A FSU for AP in Corridor 100.00 0.45
L3 #32 4x4 1C LSOH 13A S/O for Printers 360.00 1.64
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
3 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
4 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
5 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
6 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
7 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
8 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
9 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
10 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
11 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
12 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 24
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
13 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48
L1 #32 Spare 0.00 0.00
14 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
15 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
16 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 25
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/0,A7-P,UDB2
DB TYPE 16-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 1 (A7-P) 76.91 122.43 113.80 113.34
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC79A 2000.00 9.09 Radial Circuit
1 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC79A 2000.00 9.09 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC79B 2000.00 9.09 Radial Circuit
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC79B 2000.00 9.09 Radial Circuit
2 L2 20 2x4 1C LSOH 20A FSU for Airfield SCADA 100.00 0.45
L3 #32 Spare 0.00 0.00
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
6 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
7 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
8 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
9 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
10 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 26
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
11 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
12 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
13 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 Spare 0.00 0.00
14 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
15 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
16 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 27
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/0,A9-S,UDB1
DB TYPE 10-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 2 (A9-S) 45.87 75.82 66.34 66.34
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
1 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
2 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
6 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 2x6 1C LSOH 13A S/O for Worksation in CCD 2085.00 9.48 Radial Circuit
7 L2 #32 2x6 1C LSOH 13A S/O for Worksation in CCD 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in CCD 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in CCD 2085.00 9.48 Radial Circuit
8 L2 #32 2x6 1C LSOH 13A S/O for Worksation in CCD 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in CCD 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Printers 360.00 1.64 Radial Circuit
9 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
10 L2 #32 Spare 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 28
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/0,A9-S,UDB2
DB TYPE 10-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 2 (A9-S) 39.62 66.34 56.86 56.86
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
1 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
2 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
6 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 4x4 1C LSOH 13A S/O in POV 2085.00 9.48 Ring Circuit
7 L2 #32 2x6 1C LSOH 32A S/O in POV 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O in POV 2085.00 9.48 Radial Circuit
L1 #32 Spare 0.00 0.00
8 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
9 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
10 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 29
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-02a/0,A3-Q,UDB1
DB TYPE 6-way, TPN BUSBAR RATING: 32A TPN A
FEEDER SUBSTATION 02a MAIN SWITCH RATING: 32A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION CR79 15.10 0.00 0.00 0.00
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
13A FSU for Low Level Fuel Alarm Panel in Genset
L1 20 2x4 1C FR/LSOH
Room 100.00
1 L2 20 Spare 0.00
L3 Space 0.00
L1 #32 2x6 1C FR/LSOH 32A S/O for Comms Rack in CR79 2000.00
2 L2 #32 2x6 1C FR/LSOH 32A S/O for Comms Rack in CR79 2000.00
L3 #32 2x6 1C FR/LSOH 32A S/O for Comms Rack in CR79 2000.00
L1 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
3 L2 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
L3 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
L1 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
4 L2 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
L3 #32 Spare 0.00
L1 #32 Spare 0.00
5 L2 Space 0.00
L3 Space 0.00
L1 Space 0.00
6 L2 Space 0.00
L3 Space 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 30
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-02a/0,A3-Q,UDB2
DB TYPE 6-way, TPN BUSBAR RATING: 32A TPN A
FEEDER SUBSTATION 02a MAIN SWITCH RATING: 32A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION CR79 16.80 0.00 0.00 0.00
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 Spare 0.00
1 L2 #32 Spare 0.00
L3 #32 Spare 0.00
L1 #32 2x6 1C FR/LSOH 32A S/O for Comms Rack in CR79 2000.00
2 L2 #32 2x6 1C FR/LSOH 32A S/O for Comms Rack in CR79 2000.00
L3 #32 2x6 1C FR/LSOH 32A S/O for Comms Rack in CR79 2000.00
L1 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
3 L2 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
L3 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
L1 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
4 L2 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
L3 #32 4x4 1C FR/LSOH 13A S/O for Worksation in Main Hall 1800.00
L1 Space 0.00
5 L2 Space 0.00
L3 Space 0.00
L1 Space 0.00
6 L2 Space 0.00
L3 Space 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 31
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/1,A3-R,EDB1
DB TYPE 8-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 3 (A3-R) 2.61 3.96 4.03 3.88
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in UPS Room 268.00 1.22 Local Timer Switch
1 L2 10 2x2.5 1C LSOH Lighting in UPS Room 435.50 1.98 Local Timer Switch
L3 10 2x2.5 1C LSOH Lighting in Staircase (A2-R) 53.60 0.24 Time Schedule
L1 10 2x2.5 1C LSOH Lighting in A/C Space 183.00 0.83 Local Timer Switch
2 L2 10 2x2.5 1C LSOH Lighitng in FS Pump & Tank Room 183.00 0.83 Local Timer Switch
L3 10 2x2.5 1C LSOH Lighting in AHU Room 569.50 2.59 Local Timer Switch
L1 10 2x2.5 1C LSOH Lighting in AHU Room 268.00 1.22 Local Timer Switch
3 L2 10 2x2.5 1C LSOH Lighting in Corridor 2 134.00 0.61 Lighting Contactor Group No. I1 Time Schedule and Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Corridor 1 167.50 0.76 Lighting Contactor Group No. I2 Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in SES Control Room and Gas Bottle Room 60.30 0.27 Local Timer Switch
4 L2 10 2x2.5 1C LSOH Lighting in CAD Equipment Room 33.50 0.15 Local Switch
L3 10 2x2.5 1C LSOH Lighting in CAD Equipment Room 33.50 0.15 Local Switch
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 32
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/1,A7-P,EDB1
DB TYPE 8-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 4 (A7-P) 2.27 4.01 4.14 2.18
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in Corridor 3 17.00 0.08 Lighting Contactor Group No. J1 Occupancy Sensor
1 L2 10 2x2.5 1C LSOH Lighting in Staircase (A8-P) 48.00 0.22 Time Schedule
L3 10 2x2.5 1C LSOH Lighting in MAF Room 67.00 0.30 Local Timer Switch
Occupancy Sensor, Local Push Button,
L1 10 2x2.5 1C LSOH Lighting in Staff Resting Area
17.00 0.08 Lighting Contactor Group No. J2 Daylight Sensor
Occupancy Sensor, Local Push Button,
2 L2 10 2x2.5 1C LSOH Lighting in Staff Resting Area
20.00 0.09 Lighting Contactor Group No. J2 Daylight Sensor
Occupancy Sensor, Local Push Button,
L3 10 2x2.5 1C LSOH Lighting in Staff Resting Area
40.00 0.18 Lighting Contactor Group No. J2 Daylight Sensor
Occupancy Sensor, Local Push Button,
L1 10 2x2.5 1C LSOH Lighting in Staff Resting Area
32.50 0.15 Lighting Contactor Group No. J2 Daylight Sensor
3 L2 10 2x2.5 1C LSOH Lighting in Corridor 3 157.20 0.71 Lighting Contactor Group No. J1 Occupancy Sensor
Occupancy Sensor, Local Push Button,
L3 10 2x2.5 1C LSOH Lighting in Staff Resting Area
157.20 0.71 Lighting Contactor Group No. J2 Daylight Sensor
L1 10 2x2.5 1C LSOH Lighting in Main Hall 600.60 2.73 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
4 L2 10 2x2.5 1C LSOH Lighting in Main Hall 686.40 3.12 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Main Hall 216.00 0.98 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Main Hall 216.00 0.98 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
5 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
6 L2 10 Spare 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
7 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
8 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 33
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/1,A7-P,EDB3
DB TYPE 8-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 4 (A7-P) 2.51 3.92 3.08 4.39
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in Corridor 3 8.50 0.04 Lighting Contactor Group No. J1 Occupancy Sensor
1 L2 10 2x2.5 1C LSOH Lighting in Staircase (A8-P) 48.00 0.22 Time Schedule
L3 10 2x2.5 1C LSOH Lighting in MAF Room 67.00 0.30 Local Timer Switch
Occupancy Sensor, Local Push Button,
L1 10 2x2.5 1C LSOH Lighting in Staff Resting Area
17.00 0.08 Lighting Contactor Group No. J2 Daylight Sensor
Occupancy Sensor, Local Push Button,
2 L2 10 2x2.5 1C LSOH Lighting in Staff Resting Area
20.00 0.09 Lighting Contactor Group No. J2 Daylight Sensor
Occupancy Sensor, Local Push Button,
L3 10 2x2.5 1C LSOH Lighting in Staff Resting Area
40.00 0.18 Lighting Contactor Group No. J2 Daylight Sensor
L1 10 2x2.5 1C LSOH Lighting in Corridor 3 235.80 1.07 Lighting Contactor Group No. J1 Occupancy Sensor
Occupancy Sensor, Local Push Button,
3 L2 10 2x2.5 1C LSOH Lighting in Staff Resting Area
393.00 1.79 Lighting Contactor Group No. J2 Daylight Sensor
L3 10 2x2.5 1C LSOH Lighting in Main Hall 643.50 2.93 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C LSOH Lighting in Main Hall 600.60 2.73 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
4 L2 10 2x2.5 1C LSOH Lighting in Main Hall 216.00 0.98 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
L3 10 2x2.5 1C LSOH Lighting in Main Hall 216.00 0.98 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
L1 10 Spare 0.00 0.00
5 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 Space 0.00 0.00
6 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
7 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
8 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 34
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/1,A9-S,EDB1
DB TYPE 10-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 5 (A9-S) 1.15 2.51 2.05 4.30
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in Corridor 4 8.50 0.04 Lighting Contactor Group No. K1 Occupancy Sensor
1 L2 10 2x2.5 1C LSOH Lighting in EL Room 5 13.40 0.06 Local Timer Switch
Local Switch, Time Schedule and Occupancy
L3 10 2x2.5 1C LSOH Lighting in Female Toilet (A9-T)
15.00 0.07 Lighting Contactor Group No. K2 Sensor
L1 10 2x2.5 1C LSOH Lighting in Female Toilet Corridor 26.40 0.12 Lighting Contactor Group No. K3 Time Schedule and Occupancy Sensor
2 L2 10 2x2.5 1C LSOH Lighting in Viewing Gallery 143.00 0.65 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in Viewing Gallery 182.00 0.83 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in Viewing Gallery 143.00 0.65 Controlled by DALI
3 L2 10 2x2.5 1C LSOH Lighting in Viewing Gallery 234.00 1.06 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in Viewing Gallery 80.00 0.36 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in Briefing Room 280.80 1.28 Controlled by DALI
4 L2 10 2x2.5 1C LSOH Lighting in Briefing Room 8.50 0.04 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in Briefing Room 17.00 0.08 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in Viewing Gallery Corridor 8.50 0.04 Lighting Contactor Group No. K6 Occupancy Sensor
5 L2 10 2x2.5 1C LSOH Lighting in Entrance Lobby 52.40 0.24 Lighting Contactor Group No. K4 Daylight Sensor
L3 10 2x2.5 1C LSOH Lighting in Entrance Lobby 51.00 0.23 Lighting Contactor Group No. K4 Daylight Sensor
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 35
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/1,A9-S,EDB2
DB TYPE 10-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 5 (A9-S) 2.73 2.35 5.26 4.81
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C LSOH Lighting in Corridor 4 8.50 0.04 Lighting Contactor Group No. K1 Occupancy Sensor
1 L2 10 2x2.5 1C LSOH Lighting in Staircase (A9-S) 26.80 0.12 Time Schedule
Local Switch, Time Schedule and Occupancy
L3 10 2x2.5 1C LSOH Lighting in Female Toilet (A9-T)
15.00 0.07 Lighting Contactor Group No. K2 Sensor
L1 10 2x2.5 1C LSOH Lighting in Female Toilet Corridor 13.10 0.06 Lighting Contactor Group No. K3 Time Schedule and Occupancy Sensor
2 L2 10 2x2.5 1C LSOH Lighting in Viewing Gallery 130.00 0.59 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in Viewing Gallery 182.00 0.83 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in Viewing Gallery 143.00 0.65 Controlled by DALI
3 L2 10 2x2.5 1C LSOH Lighting in Viewing Gallery 234.00 1.06 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in Viewing Gallery 80.00 0.36 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in Briefing Room 280.80 1.28 Controlled by DALI
4 L2 10 2x2.5 1C LSOH Lighting in Briefing Room 8.50 0.04 Controlled by DALI
L3 10 2x2.5 1C LSOH Lighting in Briefing Room 17.00 0.08 Controlled by DALI
L1 10 2x2.5 1C LSOH Lighting in Viewing Gallery Corridor 8.50 0.04 Lighting Contactor Group No. K6 Occupancy Sensor
5 L2 10 2x2.5 1C LSOH Lighting in Entrance Lobby 70.74 0.32 Lighting Contactor Group No. K4 Daylight Sensor
L3 10 2x2.5 1C LSOH Lighting in Entrance Lobby 34.00 0.15 Lighting Contactor Group No. K4 Daylight Sensor
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 36
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EL&P-02b/1,A3-R,FDB1
DB TYPE 16-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 3 (A3-R) 1.55 2.12 2.61 2.33
Cct. RCCB/ Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 Spare 0.00 0.00
1 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
2 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in UPS Room 134.00 0.61 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Staircase (A2-R) 26.80 0.12 Time Schedule
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Staircase (A2-R) 26.80 0.12 Time Schedule
3 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Check Meter Cabinet 67.00 0.30 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in FS Pump and Tank Room 67.00 0.30 Local Timer Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in AHU Room 67.00 0.30 Local Timer Switch
4 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Staircase (A3-S) 26.80 0.12 Time Schedule
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Staircase (A3-S) 26.80 0.12 Time Schedule
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 2 67.00 0.30 Occupancy Sensor
5 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 1 100.50 0.46 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Gas Bottle Room 67.00 0.30 Local Timer Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room (A3-R) 33.50 0.15 Local Timer Switch
6 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room (A3-R) 33.50 0.15 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in SES Control Room 26.80 0.12 Local Timer Switch
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 37
Local Switch, Time Schedule and Occupancy
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Male Shower
15.00 0.07 Lighting Contactor Group No. N2 Sensor
Local Switch, Time Schedule and Occupancy
12 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Male Shower
15.00 0.07 Lighting Contactor Group No. N2 Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Male Toilet Corridor 100.50 0.46 Lighting Contactor Group No. I4 Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting for Pipe Duct (A5-P) 13.40 0.06 Local Timer Switch
13 L2 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 9.00 0.04 Always On
L3 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs and Directional Signs 15.00 0.07 Always On
L1 10 Spare 0.00 0.00
14 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
15 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 Space 0.00 0.00
16 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
17 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
18 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 38
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EL&P-02b/1,A7-P,FDB1
DB TYPE 6-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 4 (A7-P) 0.99 1.96 0.87 1.69
Cct. RCCB/ Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 3 85.00 0.39 Lighting Contactor Group No. J1 Occupancy Sensor
1 L2 10 2x2.5 1C FR/LSOH Emergency Lighting for Hose Reel 7.00 0.03 Non-maintained
L3 10 2x2.5 1C FR/LSOH Emergency Lighting for Hose Reel 7.00 0.03 Non-maintained
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room 4 33.50 0.15 Local Timer Switch
2 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room 4 33.50 0.15 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Store 33.50 0.15 Lighting Contactor Group No. L1 Occupancy Sensor, Local Timer Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Store 33.50 0.15 Lighting Contactor Group No. L1 Occupancy Sensor, Local Timer Switch
3 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Staircase (A8-P) 24.00 0.11 Time Schedule and Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Staircase (A8-P) 24.00 0.11 Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in MAF Room 67.00 0.30 Local Timer Switch
Occupancy Sensor, Local Push Button,
4 L2 10 2x2.5 1C FR/LSOH
Emergency Lighting in Staff Resting Area 76.50 0.35 Lighting Contactor Group No. J2 Daylight Sensor
Occupancy Sensor, Local Push Button,
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Staff Resting Area
17.00 0.08 Lighting Contactor Group No. J2 Daylight Sensor
Occupancy Sensor, Local Push Button,
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Staff Resting Area
40.00 0.18 Lighting Contactor Group No. J2 Daylight Sensor
Occupancy Sensor, Local Push Button,
5 L2 10 2x2.5 1C FR/LSOH
Emergency Lighting in Staff Resting Area 17.00 0.08 Lighting Contactor Group No. J2 Daylight Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Main Hall 257.40 1.17 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Main Hall 171.60 0.78 Lighting Contactor Group No. B11 Local Push Button, Occupancy Sensor
6 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Maintenance Walkway 33.50 0.15 Local Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Maintenance Walkway 33.50 0.15 Local Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs and Directional Signs 9.00 0.04 Always On
7 L2 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs 6.00 0.03 Always On
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
8 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
9 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
10 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 39
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EL&P-02b/1,A9-S,FDB1
DB TYPE 18-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 5 (A9-S) 0.98 1.48 1.36 1.62
Cct. RCCB/ Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Corridor 4 8.50 0.04 Lighting Contactor Group No. K1 Occupancy Sensor
1 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in EL Room 5 26.80 0.12 Local Timer Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Staircase (A9-S) 26.80 0.12 Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Staircase (A9-S) 26.80 0.12 Time Schedule and Occupancy Sensor
2 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Pipe Duct (A9-T) 61.00 0.28 Local Timer Switch
Local Switch, Time Schedule and Occupancy
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Toilet (A9-T)
30.00 0.14 Lighting Contactor Group No. K2 Sensor
Local Switch, Time Schedule and Occupancy
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Disabled Toilet
15.00 0.07 Lighting Contactor Group No. M1 Sensor
Local Switch, Time Schedule and Occupancy
3 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Disabled Toilet
15.00 0.07 Lighting Contactor Group No. M1 Sensor
Local Switch, Time Schedule and Occupancy
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Shower
15.00 0.07 Lighting Contactor Group No. M2 Sensor
Local Switch, Time Schedule and Occupancy
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Shower
15.00 0.07 Lighting Contactor Group No. M2 Sensor
4 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Cleaner's Room 33.50 0.15 Local Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Cleaner's Room 33.50 0.15 Local Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Sleeping Quarters 52.20 0.24 Local Switch
5 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Sleeping Quarters 52.20 0.24 Local Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Sleeping Quarters 52.20 0.24 Lighting Contactor Group No. L2 Local Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Sleeping Quarters 52.20 0.24 Local Switch
6 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Sleeping Quarters 52.20 0.24 Local Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Sleeping Quarters 52.20 0.24 Local Switch
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Sleeping Quarters 52.20 0.24 Lighting Contactor Group No. L3 Local Switch
7 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Sleeping Quarters 52.20 0.24 Local Switch
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Female Toilet Corridor 42.00 0.19 Lighting Contactor Group No. M3 Time Schedule and Occupancy Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Viewing Gallery 104.00 0.47 Controlled by DALI
8 L2 10 2x2.5 1C FR/LSOH Emergency Lighting for Hose Reel 7.00 0.03 Non-maintained
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Viewing Gallery 104.00 0.47 Controlled by DALI
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Viewing Gallery 104.00 0.47 Controlled by DALI
9 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Briefing Room 93.60 0.43 Controlled by DALI
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Briefing Room 25.50 0.12 Controlled by DALI
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A4-S) 8.50 0.04 Lighting Contactor Group No. M4 Occupancy Sensor
10 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Lobby (A4-S) 8.50 0.04 Lighting Contactor Group No. M4 Occupancy Sensor
L3 10 2x2.5 1C FR/LSOH Emergency Lighting in Entrance Lobby 8.50 0.04 Lighting Contactor Group No. K4 Daylight Sensor
L1 10 2x2.5 1C FR/LSOH Emergency Lighting in Viewing Gallery Corridor 51.00 0.23 Lighting Contactor Group No. K6 Occupancy Sensor
11 L2 10 2x2.5 1C FR/LSOH Emergency Lighting in Entrance Lobby 68.00 0.31 Lighting Contactor Group No. K4 Daylight Sensor
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 40
L1 10 2x2.5 1C FR/LSOH Emergency Lighting for Exit Signs and Directional Signs 12.00 0.05 Always On
14 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
15 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
16 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
17 L2 10 Spare 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
18 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 41
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/1,A3-R,EDB2
DB TYPE 10-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 3 (A3-R) 33.18 63.91 45.55 41.36
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 4x4 1C LSOH 13A S/O in Sleeping Quarters 3000.00 13.64 Ring Circuit
1 L2 #32 4x4 1C LSOH 13A S/O in Sleeping Quarters 3000.00 13.64 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Sleeping Quarters 3000.00 13.64 RIng Circuit
L1 #32 4x4 1C LSOH 13A S/O in Sleeping Quarters 3000.00 13.64 Ring Circuit
2 L2 #32 4x4 1C LSOH 13A S/O in Male Toilet and Disable Toilet 2000.00 9.09 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in AHU Room 2000.00 9.09 RIng Circuit
L1 #32 4x4 1C LSOH 13A S/O in Corridor 1500.00 6.82 Ring Circuit
3 L2 #32 4x4 1C LSOH 13A S/O in Filing Room 1000.00 4.55 Ring Circuit
13A S/O in Gas Bottle Room (UPS), EL Room 3 and SES Control
L3 #32 4x4 1C LSOH
Room 1500.00 6.82 RIng Circuit
L1 #32 4x4 1C LSOH 13A S/O in UPS Room 1500.00 6.82 Ring Circuit
4 L2 #32 4x4 1C LSOH 13A S/O in FS Pump & Tank Room 1500.00 6.82 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Corridor 1000.00 4.55 RIng Circuit
L1 #32 4x4 1C LSOH 13A S/O in Corridor 1000.00 4.55 Ring Circuit
5 L2 #32 4x4 1C LSOH 13A S/O in CAD Equipment Room 1000.00 4.55 Ring Circuit
L3 #32 Spare 0.00 0.00
L1 20 2x4 1C LSOH 13A FSU for Hand Dryer in Disable Toilet 1500.00 6.82
6 L2 20 2x4 1C LSOH 13A FSU for Hand Dryer in Male Toilet 1500.00 6.82
13A FSU for Water Tap and Auto Flushing Sensor in Male Toilet
L3 20 2x4 1C LSOH
and Disable Toilet 1600.00 7.27
L1 20 2x4 1C LSOH 13A FSU for DIU 60.00 0.27
7 L2 20 2x4 1C LSOH 13A FSU for CCTV 20.00 0.09
L3 20 Spare 0.00 0.00
L1 63 2x35 1C LSOH 63A SPN Isolator in CAD Equipment Room for Battery Charger
2500.00 11.36
8 L2 63 Spare 0.00 0.00
L3 Space 0.00 0.00
L1 #32 Spare 0.00 0.00
9 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
10 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 42
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/1,A7-P,EDB2
DB TYPE 4-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 4 (A7-P) 17.06 20.73 36.36 20.45
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 4x4 1C LSOH 13A S/O in Common Area 2000.00 9.09 Ring Circuit
1 L2 #32 4x4 1C LSOH 13A S/O in Common Area 3000.00 13.64 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in MAF Room, Store and EL Room 4 2000.00 9.09 RIng Circuit
L1 #32 4x4 1C LSOH 13A S/O in Corridor 1000.00 4.55 Ring Circuit
2 L2 #32 4x4 1C LSOH 13A S/O in Maintenance Walkway 2500.00 11.36 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Maintenance Walkway 2500.00 11.36 RIng Circuit
L1 #32 4x4 1C LSOH 13A S/O in Common Area 1500.00 6.82 Ring Circuit
3 L2 #32 Spare 0.00 0.00
L3 63 2x35 1C LSOH 63A SPN Isolator in CAD Equipment Room for Battery Charger
2500.00 11.36
L1 20 2x4 1C LSOH 13A FSU for DIU 60.00 0.27
4 L2 20 Spare 0.00 0.00
L3 20 Spare 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 43
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE L&P-02b/1,A9-S,EDB3
DB TYPE 10-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 5 (A9-S) 34.04 60.09 50.09 44.55
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 4x4 1C LSOH 13A S/O in Sleeping Quarters 3000.00 13.64 Ring Circuit
1 L2 #32 4x4 1C LSOH 13A S/O in Sleeping Quarters 3000.00 13.64 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Sleeping Quarters 3000.00 13.64 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in Sleeping Quarters 3000.00 13.64 Ring Circuit
2 L2 #32 4x4 1C LSOH 13A S/O in Female Toilet and Disable Toilet 2000.00 9.09 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Viewing Gallery 2000.00 9.09 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in Briefing/Lecture Room 3000.00 13.64 Ring Circuit
3 L2 #32 4x4 1C LSOH 13A S/O in 1/F Lobby 1500.00 6.82 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in ADM Support Room 1000.00 4.55 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in ADM Support Room 2000.00 9.09 Ring Circuit
4 L2 #32 4x4 1C LSOH 13A S/O in ADM Support Room 2000.00 9.09 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Corridor and EL Room 5 1500.00 6.82 Ring Circuit
13A FSU for Water Tap and Auto Flushing Sensor in Female Toilet
L1 20 2x4 1C LSOH
and Disable Toilet 1200.00 5.45
5 L2 20 2x4 1C LSOH 13A FSU for Hand Dryer in Female Toilet 1500.00 6.82
L3 20 2x4 1C LSOH 13A FSU for Hand Dryer in Disable Toilet 1500.00 6.82
L1 20 2x4 1C LSOH 13A FSU for CCTV in Viewing Gallery 20.00 0.09
6 L2 20 2x4 1C LSOH 13A FSU for DIU 20.00 0.09
L3 20 2x4 1C LSOH 13A FSU for DALI Device 800.00 3.64
L1 #32 4x4 1C LSOH 13A S/O for Smart Glass 1000.00 4.55
7 L2 #32 4x4 1C LSOH 13A S/O for Smart Glass 1000.00 4.55
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
8 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
9 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
10 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 44
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EL&P-02a/1,A3-R,FDB2
DB TYPE 4-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02a MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 3 (A3-R) 1.00 2.27 2.27 0.00
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 20 2x4 1C FR/LSOH 13A FSU for NOVEC1230 Panel in Gas Bottle Room (UPS Room)
500.00 2.27
1 L2 20 2x4 1C FR/LSOH 13A FSU for NOVEC1230 Panel outside CAD Equipment Room 500.00 2.27
L3 20 Spare 0.00 0.00
L1 Space 0.00 0.00
2 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
3 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
4 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 45
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE MS-02b/1,A3-R,EDB1
DB TYPE 6-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 200A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 3 (A3-R) 11.26 14.18 21.77 15.23
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 32 2x10 1C LOSH LCP(M)-105 for Accessible Toilet 1100.00 5.00
1 L2 32 2x10 1C LOSH LCP(M)-107 for El Room 3 740.00 3.36
L3 32 2x10 1C LOSH LCP(M)-109 for FS Pump and Tank Room 2600.00 11.82
L1 } } } } 0.00 0.00
2 L2 32 4x10 1C LOSH LCP(M)-112 for AC Space 3000.00 13.64
L3 } } } } 0.00 0.00
L1 32 2x10 1C LOSH LCP(M)-113 for CAD Equipment Room 370.00 1.68
3 L2 32 Spare 0.00 0.00
L3 32 Spare 0.00 0.00
L1 20 2x4 1C LOSH 13A FSU for FCU 750.00 3.41
4 L2 20 2x4 1C LOSH 13A FSU for FCU 600.00 2.73
L3 20 2x4 1C LOSH 13A FSU for FCU 750.00 3.41
L1 20 2x4 1C LOSH 13A FSU for FCU 900.00 4.09
5 L2 20 2x4 1C LOSH 13A FSU for FCU in CAD Equipment Room 450.00 2.05
L3 20 Spare 0.00 0.00
L1 20 Spare 0.00 0.00
6 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 46
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE MS-02b/1,A7-P,EDB1
DB TYPE 4-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 4 (A7-P) 1.49 3.05 3.73 0.00
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 32 2x10 1C LOSH LCP(M)-102 for Staff Common Room 370.00 1.68
1 L2 32 2x10 1C LOSH LCP(M)-104 for EL Room 5 370.00 1.68
L3 32 Spare 0.00 0.00
L1 20 2x4 1C LOSH 13A FSU for FCU 300.00 1.36
2 L2 20 2x4 1C LOSH 13A FSU for FCU 450.00 2.05
L3 20 Spare 0.00 0.00
L1 Space 0.00 0.00
3 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
4 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 47
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE MS-02b/1,A9-S,EDB1
DB TYPE 4-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION ELECTRICAL ROOM 5 (A9-S) 4.64 8.50 9.18 3.41
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 32 2x10 1C LOSH LCP(M)-101 for Accessible Shower Room 370.00 1.68
1 L2 32 2x10 1C LOSH LCP(M)-108 for EL Room 4 370.00 1.68
L3 32 Spare 0.00 0.00
L1 20 2x4 1C LOSH 13A FSU for FCU 750.00 3.41
2 L2 20 2x4 1C LOSH 13A FSU for FCU 900.00 4.09
L3 20 2x4 1C LOSH 13A FSU for FCU 750.00 3.41
L1 20 2x4 1C LOSH 13A FSU for FCU 750.00 3.41
3 L2 20 2x4 1C LOSH 13A FSU for FCU 750.00 3.41
L3 20 Spare 0.00 0.00
L1 Space 0.00 0.00
4 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
5 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
6 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 48
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/1,A2-S,UDB1
DB TYPE 10-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION UPS Room 36.76 0.06 0.06 0.06
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
13A S/O for TV, Laptop and Phone Conference in CMT
L1 #32 4x4 1C LSOH
Room 2000.00 9.09 Ring Cirucuit
1 L2 #32 4x4 1C LSOH 13A S/O for Projector in CMT Room 2000.00 9.09 Radial Circuit
L3 #32 4x4 1C LSOH 13A S/O for Comms Equipment in PA Room 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for Comms Equipment in PA Room 2000.00 9.09 Ring Cirucuit
2 L2 #32 4x4 1C LSOH 13A S/O for Comms Equipment in ADM Room 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Comms Equipment in ADM Room 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AVSECO Room 2000.00 9.09 Ring Cirucuit
3 L2 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AVSECO Room 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AEC Support 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AEC Support 2000.00 9.09 Ring Cirucuit
4 L2 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AEC Support 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AEC Support 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AEC Support 2000.00 9.09 Ring Cirucuit
5 L2 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AEC Support 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AEC Support 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for Comms Equipment in AEC Support 2000.00 9.09 Ring Cirucuit
6 L2 #32 4x4 1C LSOH 13A S/O for Comms Equipment in Lecture/Briefing 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Comms Equipment in Lecture/Briefing 2000.00 9.09 Ring Cirucuit
L1 20 2x4 1C LSOH 13A FSU for AP 100.00 0.45
7 L2 20 2x4 1C LSOH 13A FSU for AP 100.00 0.45
L3 20 2x4 1C LSOH 13A FSU for AP 100.00 0.45
L1 20 2x4 1C LSOH 13A FSU for Airfield SCADA 100.00 0.45
8 L2 #32 4x4 1C LSOH 13A S/O for Printers 360.00 1.64
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00
9 L2 #32 Spare 0.00
L3 #32 Spare 0.00
L1 #32 Spare 0.00
10 L2 #32 Spare 0.00
L3 #32 Spare 0.00
L1 Space 0.00
11 L2 Space 0.00
L3 Space 0.00
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 49
L1 Space 0.00
12 L2 Space 0.00
L3 Space 0.00
# With 30mA RCD
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 50
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/1,A2-S,UDB2
DB TYPE 8-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION UPS Room 24.90 39.55 36.82 36.82
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
1 L2 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
2 L2 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
3 L2 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
4 L2 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
L3 #32 4x4 1C LSOH 13A S/O for Video Wall in Main Hall 2000.00 9.09 Ring Cirucuit
L1 #32 4x4 1C LSOH 13A S/O for AEC Reception 500.00 2.27 Ring Cirucuit
5 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
6 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 20 2x4 1C LSOH 13A FSU for AP 100.00 0.45
7 L2 20 2x4 1C LSOH 13A FSU for AP 100.00 0.45
L3 20 2x4 1C LSOH 13A FSU for AP 100.00 0.45
L1 20 2x4 1C LSOH 20A FSU for Airfield SCADA 100.00 0.45
8 L2 20 Spare 0.00 0.00
L3 20 Spare 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 51
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/1,A2-S,UDB3
DB TYPE 14-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION UPS Room 51.54 85.30 74.16 74.80
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
1 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
2 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
6 L2 #32 Spare 0.00
L3 #32 Spare 0.00
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
7 L2 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
8 L2 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
9 L2 #32 2x6 1C LSOH 13A S/O for Video Wall in AEC Hall 1620.00 7.36 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Video Wall and Central Table in AEC Hall
1620.00 7.36 Radial Circuit
L1 20 Spare 0.00 0.00
10 L2 20 2x4 1C LSOH 13A FSU for AP in AEC Hall 100.00 0.45
L3 20 4x4 1C LSOH 13A S/O for Printers 240.00 1.09 Ring Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall Work Bench 500.00 2.27 Radial Circuit
11 L2 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 840.00 3.82 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 840.00 3.82 Radial Circuit
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 52
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 840.00 3.82 Radial Circuit
12 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
13 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
14 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 53
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/1,A2-S,UDB4
DB TYPE 14-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION UPS Room 51.30 85.75 73.70 73.70
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
1 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
2 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
6 L2 #32 Spare 0.00
L3 #32 Spare 0.00
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
7 L2 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
8 L2 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 2085.00 9.48 Radial Circuit
9 L2 #32 2x6 1C LSOH 13A S/O for Video Wall in AEC Hall 1620.00 7.36 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Video Wall and Central Table in AEC Hall
1620.00 7.36 Radial Circuit
L1 20 2x6 1C LSOH 13A FSU for AP in AEC Hall 100.00 0.45
10 L2 20 Spare 0.00 0.00
L3 20 Spare 0.00 0.00
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall Work Bench 500.00 2.27 Radial Circuit
11 L2 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 840.00 3.82 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 840.00 3.82 Radial Circuit
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 54
L1 #32 2x6 1C LSOH 13A S/O for Worksation in AEC Hall 840.00 3.82 Radial Circuit
12 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
13 L2 #32 Spare 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
14 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 55
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/1,A2-S,UDB5
DB TYPE 14-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION UPS Room 60.47 94.77 94.77 85.30
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
1 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
2 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 Spare 0.00 0.00 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
6 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
7 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
8 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
9 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
10 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 4x4 1C LSOH 13A S/O for Printers 0.00 0.00 Ring Circuit
11 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
12 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
13 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
14 L2 Space 0.00 0.00
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 56
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 57
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE COMMS-04/1,A2-S,UDB6
DB TYPE 14-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 04 MAIN SWITCH RATING: 200A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION UPS Room 60.47 94.77 94.77 85.30
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
1 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
2 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
3 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
4 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
5 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
6 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
7 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
8 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
9 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L1 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
10 L2 #32 2x6 1C LSOH 13A S/O for Worksation in Main Hall 2085.00 9.48 Radial Circuit
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
11 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
12 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
13 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 58
14 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 59
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE HKPF-02b/1,A1-T,NDB1
DB TYPE 8-way, TPN BUSBAR RATING: 100A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 100A TP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION Police Equipment Room 16.43 31.76 19.06 27.58
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
Lighting Contactor
L1 10 2x2.5 1C LSOH Lighting in Police Equipment Room
134.00 0.61 Group No. C16 Local Switch and Photocell Sensor
1 L2 10 2x2.5 1C LSOH Lighting in Police Equipment Room 160.00 0.73 Local Switch
L3 10 2x2.5 1C LSOH Lighting in Police Equipment Room 68.00 0.31 Local Switch and Photocell Sensor
L1 10 2x2.5 1C LSOH Lighting in Police Observation Room 33.50 0.15 Local Switch
2 L2 10 2x2.5 1C LSOH Lighting in Police Observation Room 33.50 0.15 Local Switch
L3 10 Spare 0.00 0.00
L1 10 Spare 0.00 0.00
3 L2 10 Spare 0.00 0.00
L3 10 Spare 0.00 0.00
L1 #32 4x4 1C LSOH 13A S/O in Police Equipment Room and Police Observation Room
4000.00 18.18 Ring Circuit
4 L2 #32 4x4 1C LSOH 13A S/O in Police Equipment Room and Police Observation Room
4000.00 18.18 Ring Circuit
L3 #32 4x4 1C LSOH 13A S/O in Police Equipment Room for Comms Equipment 6000.00 27.27 Ring Circuit
L1 #32 4x4 1C LSOH 13A S/O in Police Observation Room for Comms Equipment 2000.00 9.09 Ring Circuit
5 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 16 2x4 1C LSOH LCP(M)-106 for Police Equipment Room 370.00 1.68
6 L2 16 Spare 0.00 0.00
L3 16 Spare 0.00 0.00
L1 20 2x4 1C LOSH 13A FSU for FCU 450.00 2.05
7 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
8 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 60
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE CLP-A1/0,A1-P,NDB1
DB TYPE 4-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION Transformer A1 MAIN SWITCH 60A 4P SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION Transformer Room A 0.00 0.00 0.00 0.00
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 61
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE CLP-B1/0,A2-P,NDB1
DB TYPE 4-way, TPN BUSBAR RATING: 63A TPN A
FEEDER SUBSTATION Transformer B1 MAIN SWITCH 60A 4P SW 20-Mar-2019
LEVEL G/F LOAD (kVA) L1 L2 L3
LOCATION Transformer Room B 0.00 0.00 0.00 0.00
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 62
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE CAD-02b/1,A3-R,EDB1
DB TYPE 6-way, SPN BUSBAR RATING: 100A SPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A DP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA)
LOCATION CAD Equipment Room 8.00 36.36
Cct. Min. Cable Cable Connected Load Phase Control
Ref. MCB (A) (mm2) Type Description Load (VA) Remarks Code
1 #32 2x6 1C LSOH 32A S/O for Battery Charger at Equipment Rack 2000.00 9.09 Radial Circuit
2 #32 2x6 1C LSOH 32A S/O for Battery Charger at Equipment Rack 2000.00 9.09 Radial Circuit
3 #32 2x6 1C LSOH 32A S/O for Battery Charger at Equipment Rack 2000.00 9.09 Radial Circuit
4 #32 2x6 1C LSOH 32A S/O for Battery Charger at Equipment Rack 2000.00 9.09 Radial Circuit
5 #32 Spare
6
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 63
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE CAD-02b/1,A3-R,EDB2
DB TYPE 6-way, SPN BUSBAR RATING: 100A SPN A
FEEDER SUBSTATION 02b MAIN SWITCH 63A DP AI SW 20-Mar-2019
LEVEL 1/F LOAD (kVA)
LOCATION CAD Equipment Room 8.00 36.36
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) Remarks Code
1 #32 2x6 1C LSOH 32A S/O for Battery Charger at Equipment Rack 2000.00 9.09 Radial Circuit
2 #32 2x6 1C LSOH 32A S/O for Battery Charger at Equipment Rack 2000.00 9.09 Radial Circuit
3 #32 2x6 1C LSOH 32A S/O for Battery Charger at Equipment Rack 2000.00 9.09 Radial Circuit
4 #32 2x6 1C LSOH 32A S/O for Battery Charger at Equipment Rack 2000.00 9.09 Radial Circuit
5 #32 Spare
6
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 64
3133 - Primary IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE EV-02b/0,A9-S,EDB1
DB TYPE 4-way, TPN BUSBAR RATING: 200A TPN A
FEEDER SUBSTATION 02b MAIN SWITCH 200A TP AI SW 20-Mar-2019
LEVEL G/F LOAD (kVA)
LOCATION ELECTRICAL ROOM 2 (A9-S) 56.00 95.45 95.45 63.64
Cct. Min. Cable Cable Connected Load Phase Control
Ref. MCB (A) (mm2) Type Description Load (VA) Remarks Code
L1 #32 1x10 2C XLPE/SWA/LSOH 32A 5 Pin S/O for EV Charger 7000.00 31.82
1 L2 #32 1x10 2C XLPE/SWA/LSOH 32A 5 Pin S/O for EV Charger 7000.00 31.82
L3 #32 1x10 2C XLPE/SWA/LSOH 32A 5 Pin S/O for EV Charger 7000.00 31.82
L1 #32 1x10 2C XLPE/SWA/LSOH 32A 5 Pin S/O for EV Charger 7000.00 31.82
2 L2 #32 1x10 2C XLPE/SWA/LSOH 32A 5 Pin S/O for EV Charger 7000.00 31.82
L3 #32 1x10 2C XLPE/SWA/LSOH 32A 5 Pin S/O for EV Charger 7000.00 31.82
L1 #32 1x10 2C XLPE/SWA/LSOH 32A 5 Pin S/O for EV Charger 7000.00 31.82
3 L2 #32 1x10 2C XLPE/SWA/LSOH 32A 5 Pin S/O for EV Charger 7000.00 31.82
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
4 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 65
APPENDIX C1.2 – 14B - PART A – MCB BOARDS AT EXISTING BACK UP
IAC
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 1
3133 - Backup IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE UPSPC4
DB TYPE 12WAY, TPN BUSBAR RATING: 100A TPN A
FEEDER SUBSTATION LV Switchboard at LV Switchroom MAIN SWITCH RATING: 100A TPN AI SW 12-Mar-2019
LEVEL 1/F LOAD (kVA) L1 L2 L3
LOCATION CR78A 43.00 65.91 64.09 65.45
Cct. Min. Cable Cable Connected Load Phase Control
Ref. Phases MCB (A) (mm2) Type Description Load (VA) L1 L2 L3 Remarks Code
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
1 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
2 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
3 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
4 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
5 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
6 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L1 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
7 L2 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L3 #32 2x6 1C LSOH 32A S/O for Comms Rack in CC78A 2000.00 9.09 Radial Circuit
L1 20 2x4 1C LSOH 13A FSU for DIU 500.00 2.27
8 L2 20 2x4 1C LSOH 13A FSU for AP in SOCC 100.00 0.45
L3 20 2x4 1C LSOH 13A FSU for MBMS in A/C Plant 400.00 1.82
L1 #32 Spare 0.00 0.00
9 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 #32 Spare 0.00 0.00
10 L2 #32 Spare 0.00 0.00
L3 #32 Spare 0.00 0.00
L1 Space 0.00 0.00
11 L2 Space 0.00 0.00
L3 Space 0.00 0.00
L1 Space 0.00 0.00
12 L2 Space 0.00 0.00
L3 Spare 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 2
3133 - Backup IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE UPSPMW5
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 3
3133 - Backup IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE UPSPMW6
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 4
3133 - Backup IAC
DISTRIBUTION PANELBOARD ASSEMBLY SCHEDULE-SUBSTATION REF.
DB REFERENCE PG2
DB TYPE 14WAY, TPN BUSBAR RATING: 100A TPN A
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 5
14 L2 Space 0.00 0.00
L3 Space 0.00 0.00
# With 30mA RCBO
Note 1: Separate circuit protective conductor in accordance with the EMSD's COP for the Electricity (Wiring) Regulations shall be provided. The material of the protective conductor shall be as that of the phase conductor.
C3403
MCB BOARD/ PANELBOARD SCHEDULE PAGE 6
APPENDIX C1.3 – LUMINAIRE & LIGHTING CONTROL DATASHEETS
General Description
Recessed mounted downlight. Luminaire complete with C.O.B. technology. Fixture with 30° beam angle and the LED unit in neutral
white colour 4000K. Fxture to be tilted, related to the horizontal plane, at 0°. Including remote electronic ballast. Ballast to be
located at maintenance catwalks at dry, ventilated and accessible location.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Luminaire to be mounted in customade cases and must be maintainable from behind the ceiling.
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
• Customised cable length to be ~5-6 meter to reach remote located drivers.
General Description
Recessed mounted downlight. Luminaire complete with C.O.B. technology. Fixture with 30° beam angle and the LED unit in neutral
white colour 4000K. Fxture to be tilted, related to the horizontal plane, at -15°/ 15°. Including remote electronic ballast. Ballast to
be located at maintenance catwalks at dry, ventilated and accessible location.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Luminaire to be mounted in customade cases and must be maintainable from behind the ceiling.
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
• Customised cable length to be ~5-6 meter to reach remote located drivers.
General Description
Recessed mounted downlight. Luminaire complete with Non Glare Refelctor technology. Fixture with 40o and the LED unit in
neutral white colour 4000K.
Illustration Control
• Dali Dimmable 1-100%
POV Room
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
General Description
Recessed mounted downlight. Luminaire complete with Non Glare Refelctor technology. Fixture with 40o and the LED unit in warm
white colour 3000K. Including remote electronic ballast.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
General Description
Recessed mounted downlight. Luminaire complete with Non Glare Refelctor technology. Fixture with 20o and the LED unit in warm
white colour 3000K.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
DESCRIPTIO
Lamp Specification Architectural Series of suspe
• Lamp Type LED • Dimensions/Cutout ø80mm x (H) 330 mm output LEDs, R
• Lamp Wattage 10 W • Materials aluminum available in dif
• Beam Angle 20° • Colour Finish to match with ceiling black/blue.Stee
• Base/Socket - • Weight 1.1 kg high-output sp
• Luminaire/System Lumen 1027 lm (lamp) • Mounting Suspended 270 LED uses a
• Colour Temperature/CRI 3000K / >90 • IP Rating IP20 to create defin
• Lifetime - • Adjustable/Fixed Fixed come with a PM
• Colour Consistency - sources.Monoc
• UGR - electronic pow
Accessories Electrical lighting availab
• Brackets/Mounting Structure IP20 cables • Voltage/V
Steel suspension Dimmerable: 220V-240V and 970 fluore
• Glare Protection n/a • System Load/W 14 W
• Lenses n/a • Power Supply/Driver Integrated
• Dimming on/off
• LOR -
Control
TECHNICAL DRAWINGS FEATURES
• Ballast Lost/W 4W
• ON/OFF PRODUCT DATA SHEET Article Code:
PRODUCT CODE:
Colour:
Illustration Tagora Suspension 80 - Led 36° 3000K - Grey/White - Dimmable Dali
Installation:
DESIGN BY
S./R. Cornelissen
DIMENSION
DESCRIPTION
Height:
Series of suspended luminaires available in 4 diameters (80 mm, 270 mm, 570 mm, 970 mm), usi
Weight:
output LEDs, Retrofit LEDs, 12V halogen lamps, metal halide and fluorescent sources.Aluminium
available in different two-coloured versions: beige/white, grey/white, black/orange, black/vert and
Base Diamete
black/blue.Steel suspension cables allowing quick adjustment, 2 metre length.Tagora 80 and 270
high-output spot light with aluminium optics. 2 beam angles for LED versions and 3 for HIT versio
Max Height fr
270 LED uses a proprietary system based on a hybrid combined lens and reflector optic. This syst
to create defined narrow beams using high-powered LED modules of large dimensions.Tagora 57
come with a PMMA diffuser, offering a comfortable diffused light. LED versions use high-output
INCLUDED
sources.Monochromatic LED option with warm white (3000 K) and neutral white (4000 K) tones.In
electronic power supply, dimmable or non-dimmable options, depending on the version. Emerge
lighting available on Tagora 570 fluorescent option.Option of double light emission available on T
IP20 Dimmerable: Category:
and 970 fluorescent modules.Compliant with standard EN60598-1 and other specific standards.
DIMENSIONS LUMINAIRE
Height: cm 33 Glow Wire Test: 960
Weight: kg 1.1
Contract 3403_Particular Specification 6
pageDiameter:
Base cm 10 AAPower
25
08 // 02 19Supply
03 // 19
Appendix F - Particular Technical Specification
Part F3.2 - Electrical Works
Max Height from ceiling: cm 200 Trasformer av
INCLUDED SOURCES Watt:
Category: LED Voltage:
Color temperature (K): 3000K
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
LI-007
Area Staff common room
General Description
Suspended luminaire in different two-colored. Steel suspension cables allowing quick adjustment, 2 metre length. Fixture with 40o
and the LED unit in warm white colour 3000K.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
General Description
Recessed mounted downlight. Luminaire complete with C.O.B, technology. Fixture with 42° beam angle and super comfort reflec-
tor. LED unit in neutral white colour 4000K. Including remote electronic ballast. Ballast to be located at maintenance catwalks at
dry, ventilated and accessible location.
Illustration Control
• Dali Dimmable 1-100%
AEC
Briefing Room
• On/Off ADM
AVSECO DSM OFFICE
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
General Description
Recessed mounted downlight. Customised to mounting box. Recessed in customized mounting box (byArchitects) Luminaire
complete with C.O.B, technology. Fixture with 42° beam angle and super comfort reflector. LED unit in neutral white colour 4000K.
20 deg tilt
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
General Description
Recessed mounted downlight. Luminaire complete with Non Glare Refelctor technology. Fixture with 20o and the LED unit in
neutral white colour 4000K.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
General Description
Recessed mounted adjustable downlight. Fixture to be tilted, relative to the horizontal plane at -30°/ 30°. Luminaire complete with
Non Glare Reflector technology. Fixture with 30° beam angle and the LED unit in neutral white colour 4000K.
Illustration
11311
DRAWING DATA
l luminaire, O3 series.
SMPS
DATA
mm Contract
Ø96 X H86 3403_Particular Specification page 11 AA 25
08 // 02
03 // 19
19
Kg 0.3Appendix F - Particular Technical Specification
Part F3.2 - Electrical Works
V AC 100~240V
NOTES
W 16 (with power supply unit)
W 13 Attention Read carefully before installing.
The safety of this fixture is guaranteed only if you comply with these instructions. Save these instructions for future use.
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
LI-011
Area Staircases
General Description
Surface mounted luminaire with 1 miniaturised adjustable spotlights. Fixture to be tilted and rotated by 90°and 360°. Luminaire
complete with Non Glare Reflector technology. Fixture with 42o and the LED unit in warm white colour 3000K.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
General Description
Recessed mounted downlight. Luminaire complete with Non Glare Refelctor technology. Fixture with 25° beam angle and the
LED unit in warm white colour 3000K.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture backed up by CBS where applicable.
General Description
Recessed mounted downlight. Luminaire complete with Non Glare Refelctor technology. Fixture with 55° beam angle and the
LED unit in neutral white colour 4000K.
H11150
• UGR 16.4
Accessories Electrical
• Brackets/Mounting Structure torison spring • Voltage/V AC 100-240V
• Glare Protection Non Glare Reflector • System Load/W 10 W
• Lenses n/a • Power Supply/Driver Remote
• Dimming DALI (1-100% Dimming); on/off
• LOR 70%
• Ballast Lost/W 1.5 W
Control
H11150
Illustration
• Dali Dimmable 1-100%
CMT Room
CCD Room
Briefing Room
General Description
Surface mounted LED Linear fixture, iIncluding integrated electronic ballast. Luminaire complete with LED unit neutral white colour
4000K.
Control
45° [65.9]
Wire Box
• Ballast Lost/W 0.1 W
1.99 2.14
1.64 [50.5] [54.5]
onduit Connection, Wire Box, TROV, Interior Only, L50 ...........CC-L-WIREBOX [41.7] Wire box can be used instead of a leader cable to start a run. 1/2” conduit
fitting can attach directly toOPTIONAL the box onACCESSORIES
one end and the fixture to the other.
• ON/OFF Masking Plates 1.64
[41.6]
1.64
Masking Plate, 3 inch high, 12 inch, [41.6]
L50 & L35 ....................... MP-L50-3H-12 2.21
Masking
[56.1]
Plates needed = One 12” lens is needed per 12” fix
M EN S I O N S + M O U NTI N G [ASYMMETRIC]
Masking Plate, 3 inch high, 48 inch, L50 & L35 .................... MP-L50-3H-48 is needed per 48” fixture.
Illustration 12
[304.8]
47.3
[1201]
2
[50.2]
Landscape Stake
90°
Landscape Stake, 6 inch, TROV, Set of 2 ..................................
180°
LS-L-STK-06
180°
Landscape Stakes needed = 12” and 48” fixtures both need
2.25
[57.1]
Landscape Stake, 12 inch, TROV, Set of 2 .................................. LS-L-STK-12
I O N S • O R D ER I N G I NTER I O R + E X TER I O R | L 50 G RLandscape
A ZE 2 ................................. LS-L-STK-18
Stake, 18 inch, TROV, Set of 2.59
45° [65.9] 1.38 1.53
1.99 2.14 [34.9] [38.9]
1.64 6.00 [50.5] [54.5]
Ø 5.5
[10.2]
0.40
22
1.64
0.87
[151.7]
0. 2]
[
22
2.64 2.90
PHASE [67.0] [73.7] 2.90 1.64
1.64
[73.7] [41.6] [41.6] 2.21
12.00 47.3 [56.1
[22.1]
1.64
0.87
[ASYMMETRIC] [ASYMMETRIC]
[41.7] [304.7] [1201]
2 180°
[50.2] * 4FT FIXTURE 90°
2.25
S 2.01 1.00 1.00 2.01 0.27 0.13 [57.1]
[51.1] [25.4] [25.4] [51.1] [6.89 3.30]
TERIOR OPTIONS
1.38
[34.9]
41.3 6.00
Ø 5.5
[10.2]
0.40
[1049] [151.7]
0. 2]
[
2.64 2.90
6.00 29.3 6.00 [67.0] [73.7]
R [151.7] [744.6] [151.7]
12.00 47.3
[22.1]
1.64
0.87
[
[41.7] [304.7] [1201]
12" 02 WHITE MONO 80 MULT GRAZING WASHING 2.01 1.00 1.00 2.01
48" AdditionalCCT
04 Notes:Fine
COLOR Adjustable
90* Bracket: (120-277V)
9x9
9 x 17
25 x 25
25 x 33
[51.1] [25.4] [25.4] [51.1]
AA 3/
25
083// 02
03 // 19
6W 9˚x 29˚ [70.7] 482 Im/LF ( 1614 lm/m
Contract 3403_Particular Specification
VISIT ECOSENSELIGHTING.COM FOR THE MOST CURRENT SPECIFICATIONS.
[67.5]
page 15 19
FOR A LIST OF PATENTS VISIT ECOSENSELIGHTING.COM/IP-PORTFOLIO/
[62.8] 837 NORTH SPRING STREET F • 310 . 496
8W 9˚x 29˚ 675 Im/LF ( 2224 lm/m ) 84 .Im/W
6256 2.30
©2018 ECOSENSE LIGHTING INC. ALL RIGHTS RESERVED. ECOSENSE, THE
ECOSENSELIGHTING .COM
10W Appendix 9˚x
F -29˚Particular
0.61
Technical Specification
SUITE785103 Im/LF ( 2644 lm/m ) T • 855 . 632
79 .Im/W
6736 [58.5]
ECOSENSE LOGO, TRoV, TROV AND ECOSPEC ARE REGISTERED TRADEMARKS
OF ECOSENSE LIGHTING INC.
1
Part F3.2 9˚x
- Electrical Works LOS ANGELES,
923 Im/LF CA 90012 855 . 677. ECOSEN RISE™, SLIM COVE™, FREEDOM TO CREATE™, MACRO™, FLIP-TO-FLAT™ ARE
12W 29˚ 15° ( 3109 lm/m
15° ) Im/W 15° 15°
[15.5] TRADEMARKS OF ECOSENSE LIGHTING INC.
15° 45° 75°
2.78 2.66
UMEN DATA IS FROM 4000K 80CRI FIXTURES. PLEASE SEE PHOTOMETRY SPEC SHEET FOR ADDITIONAL LUMEN DATA. 2.47 [70.7] [67.5] 20180817
[62.8]
2.50 3.22 2.30
R RENDERING INDEX 1.68 80+, 90+ 2.84
[63.4] [81.9] [58.5]
[42.8] [72.2]
R CONSISTENCY 2-STEP MACADAM ELLIPSE 0.61
15° 15° 15°
[15.5]
N DEPRECIATION / RATED LIFE
1.93 WATTS L70 @ 25C L70 @ 50C L90 @ 25C L90 @ 50C *CALCULATIONS FOR LED FIXTURES ARE BASED
[48.9] ON MEASUREMENTS THAT COMPLY WITH IES LM-80
2W-12W >150,000 >70,000 >50,000 >25,000 TESTING PROCEDURES AND IES TM-21 CALCULATOR 2.50 3.22
1.68
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
LI-101
Area Staff common room
General Description
Surface mounted LED Linear fixture, iIncluding integrated electronic ballast. Luminaire complete with LED unit warm white colour
3000K.
• UGR
V ERV I E W • S P EC I FI C ATI O N S • O R D ER I N G
Landscape Stake
- I NTERI O R + E X TERI O R | L 50 G R A ZE
Control
45° [65.9]
Wire Box
• Ballast Lost/W 0.1 W
1.99 2.14
1.64 [50.5] [54.5]
onduit Connection, Wire Box, TROV, Interior Only, L50 ...........CC-L-WIREBOX [41.7] Wire box can be used instead of a leader cable to start a run. 1/2” conduit
fitting can attach directly toOPTIONAL
the box onACCESSORIES
one end and the fixture to the other.
• ON/OFF Masking Plates 1.64
[41.6]
1.64
Masking Plate, 3 inch high, 12 inch, [41.6]
L50 & L35 ....................... MP-L50-3H-12 2.21
Masking
[56.1]
Plates needed = One 12” lens is needed per 12” fix
M EN S I O N S + M O U NTI N G [ASYMMETRIC]
Masking Plate, 3 inch high, 48 inch, L50 & L35 .................... MP-L50-3H-48 is needed per 48” fixture.
Illustration 12
[304.8]
47.3
[1201]
2
[50.2]
Landscape Stake
90°
Landscape Stake, 6 inch, TROV, Set of 2 ..................................
180°
LS-L-STK-06
180°
Landscape Stakes needed = 12” and 48” fixtures both need
2.25
[57.1]
Landscape Stake, 12 inch, TROV, Set of 2 .................................. LS-L-STK-12
I O N S • O R D ER I N G I NTER I O R + E X TER I O R | L 50 G RLandscape
A ZE 2 ................................. LS-L-STK-18
Stake, 18 inch, TROV, Set of 2.59
45° [65.9] 1.38 1.53
1.99 2.14 [34.9] [38.9]
1.64 6.00 [50.5] [54.5]
Ø 5.5
[10.2]
0.40
22
1.64
0.87
[151.7]
0. 2]
[
22
2.64 2.90
PHASE [67.0] [73.7] 2.90 1.64
1.64
[73.7] [41.6] [41.6] 2.21
12.00 47.3 [56.1
[22.1]
1.64
0.87
[ASYMMETRIC] [ASYMMETRIC]
[41.7] [304.7] [1201]
2 180°
[50.2] * 4FT FIXTURE 90°
2.25
S 2.01 1.00 1.00 2.01 0.27 0.13 [57.1]
[51.1] [25.4] [25.4] [51.1] [6.89 3.30]
TERIOR OPTIONS
1.38
[34.9]
41.3 6.00
Ø 5.5
[10.2]
0.40
[1049] [151.7]
0. 2]
[
2.64 2.90
6.00 29.3 6.00 [67.0] [73.7]
R [151.7] [744.6] [151.7]
12.00 47.3
[22.1]
1.64
0.87
[
[41.7] [304.7] [1201]
12" 02 WHITE MONO 80 MULT GRAZING WASHING 2.01 1.00 1.00 2.01
48" AdditionalCCT
04 Notes:Fine
COLOR Adjustable
90* Bracket: (120-277V)
9x9
9 x 17
25 x 25
25 x 33
[51.1] [25.4] [25.4] [51.1]
AA 3/
25
083// 02
03 // 19
6W 9˚x 29˚ [70.7] 482 Im/LF ( 1614 lm/m VISIT ECOSENSELIGHTING.COM FOR THE MOST CURRENT SPECIFICATIONS.
8W Contract 3403_Particular
[62.8]
9˚x 29˚ Specification 837 NORTH SPRING
675 Im/LF STREET
( 2224 lm/m )
[67.5]
F • 310 . 496
84 .Im/W
6256 2.30
©2018 ECOSENSE page 16
FOR A LIST OF PATENTS VISIT ECOSENSELIGHTING.COM/IP-PORTFOLIO/
LIGHTING INC. ALL RIGHTS RESERVED. ECOSENSE, THE
ECOSENSELIGHTING .COM 19
10W Appendix 9˚x
F -29˚Particular
0.61
Technical Specification
SUITE785103 Im/LF ( 2644 lm/m ) T • 855 . 632
79 .Im/W
6736 [58.5]
ECOSENSE LOGO, TRoV, TROV AND ECOSPEC ARE REGISTERED TRADEMARKS
OF ECOSENSE LIGHTING INC.
1
LOS ANGELES,
923 Im/LF CA 90012 855 . 677. ECOSEN
Part F3.2 9˚x
- Electrical Works
RISE™, SLIM COVE™, FREEDOM TO CREATE™, MACRO™, FLIP-TO-FLAT™ ARE
12W 29˚ 15° ( 3109 lm/m
15° ) Im/W 15° 15°
[15.5] TRADEMARKS OF ECOSENSE LIGHTING INC.
15°
45° 75°
2.78 2.66
UMEN DATA IS FROM 4000K 80CRI FIXTURES. PLEASE SEE PHOTOMETRY SPEC SHEET FOR ADDITIONAL LUMEN DATA. 2.47 [70.7] [67.5] 20180817
[62.8]
2.50 3.22 2.30
R RENDERING INDEX 1.68 80+, 90+ 2.84
[63.4] [81.9] [58.5]
[42.8] [72.2]
R CONSISTENCY 2-STEP MACADAM ELLIPSE 0.61
15° 15° 15°
[15.5]
N DEPRECIATION / RATED LIFE
1.93 WATTS L70 @ 25C L70 @ 50C L90 @ 25C L90 @ 50C *CALCULATIONS FOR LED FIXTURES ARE BASED
[48.9] ON MEASUREMENTS THAT COMPLY WITH IES LM-80
2W-12W >150,000 >70,000 >50,000 >25,000 TESTING PROCEDURES AND IES TM-21 CALCULATOR 2.50 3.22
1.68
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
LI-102
Area pantry, portal
General Description
Surface mounted rigid linear LED fixture. Remote electronic ballast; ballast to be lcoated at a dry, ventilated and accessible
location. Luminaire complete with LED unit in cool white colour 4,000K. Length to be coordinated by contractor as required to
match lighting layout.
2018.05.09
5-1 4 5-2
(80) 1008 ±2 (80)
9.2
9.2
12.0
2 3 ■ Side View
9.3
14
8.4
16
-Multiclip K Mounted
12 (Upward lighting)
14
19 24.2
2
7
1
2 14
2
7 10
17.5
19
14
16
12 4.8
16
14
4.8 2
2
3
3.5
34 10
2
6 15.4 10
9
25.8
A) Multiclip K Mounted B) Multiclip K Mounted (screwed C) Outerclip Mounted D) Magnet Mounted 6.8
34
17.5
Option parts :
Power supply cable 3000mm for SL connector (CAD-3000-MCRN-I)
3000 +40
0
5
Additional Notes: Option parts :
Liftclip for silux (LSX-PTL) (2pcs / 1bag)
• Length to be coordinated by contractor as required to match lighting layout and site conditions
5-2 9 Check the label on the DC + side
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
Option parts :
for polarity.
44 4.8
14
±15
15.8
13
10.3
16
13
• Contractor shall include cables, connection and accessories as site situation requires.
2
39.8 12 12
1.5
• Fixture backed up by CBS where applicable. 5-2 9 5-1 51.2
62.6
Installation Dimensions
(Side View)
General Description
Surface mounted flexible LED tube. Remote electronic ballast; ballast to be lcoated at a dry, ventilated and accessible
location. Luminaire complete with LED unit in neutral white colour 3,000K. Length to be coordinated by contractor as required to
match lighting layout.
Illustration
Additional Notes:
• Length to be coordinated by contractor as required to match lighting layout and site conditions.
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture backed up by CBS where applicable.
General Description
Linear LED fixture with aluminum channel and continuous opal PC optic. Fitted with a DALI controllable ballast. Luminaire com-
plete with LED unit in cool white colour 4,000K. Length to be coordinated by contractor as required to match lighting layout.
ZS_SLI_F_slim_Einzelleuchte.jpg ZS_SLI_M_slim_Gerade_alle.wmf
ZS_SLI_F_slim_Einzelleuchte.jpg ZS_SLI_M_slim_Gerade_alle.wmf
Light Distribution
Light Distribution STD - standard
STD - standard
h: 100% • Light Source: LED
Additional150° Notes: 180° 180°
h: 100% • Light
• Luminaire•luminous
Source: LED
150°
150°
150° Luminaireflux*: 1630 flux*:
luminous lm 1630 lm
• Luminaire•efficacy*: 70 lm/W 70 lm/W
• Length to be coordinated by contractor as required to• Colour match lighting
Luminaire
Rendering layout
efficacy*:
Index min.: and
80 site conditions.
• Colour Rendering Index min.: 80
• 120°Fixture to be connected with plug connector between•• Correlated
120°
fixture
Chromaticity
colour temperature*:
•and driver
Correlated for
colour
tolerance (initial
quick4000 Kelvin4000 Kelvin
maintenance
temperature*:
MacAdam)*: 3
120° 120° • Chromaticity tolerance (initial MacAdam)*: 3
• Contractor shall provide installation detail and to coordinate • Rated median
with useful
• Rated life*:useful
interior
median designer
life*: and lighting consultant
50000h L8550000h
at 25°CL85 at 25°C
• Contractor shall include cables, connection and accessories • Ballast: as site situation
1x• LED_Con
Ballast: 1xTridonic
LED_Con requires.
DRV TR LCA
Tridonic DRV 50W
TR1.05A
LCA 50W 1.05A
50V D #O4A 50V lp DPRE
#O4A (28000656)
lp PRE (28000656)
90°• Fixture
300 200require fire100
certification to comply with
90° FSD PPA/104. Fixture backed Wup by CBS where applicable.
100 90° • Luminaire•input power*: 23.4 Lambda = 0.98
90° 300 200 Luminaire input power*: 23.4 W Lambda = 0.98
• Standby Power*:
• Standby 0.15 W
Power*: 0.15 W
• Dimming: •LDE dimmable
Dimming: LDEto 1%
dimmable to 1%
over DALI, over
DSI and DALI,switchDIM
DSI and switchDIM
DC level is DC
adjustable
level is adjustable
60° 60° • Maintenance category: Dcategory:
- Enclosed
60° 60° • Maintenance D -IP2X
Enclosed IP2X
Contract 3403_Particular Specification page 19 AA 25
08 // 02
03 // 19
19
Appendix F - Particular
30° Technical Specification
30°
Part F3.2 - Electrical Works30°0° 30°
C180 | C0
C180 | C0
0° C270 | C90
cd/klm C270 | C90
cd/klm
D36769AA_SLOIN_slim_SL_LED1800-840_L1004_PC.ldt
D36769AA_SLOIN_slim_SL_LED1800-840_L1004_PC.ldt
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
LI-105
Area Main Hall
General Description
Side bendable dotless LED strip fitted with LED unit in cool colour 4,000K. Length to be coordinated by contractor as required to
match lighting layout.
RoHS Ra IP
-25°c
· Length: 3m/roll
· Life time: >30,000hrs
RoHS F LVD EMC
-25°c
to
IP · Operation temperatures:
+50°c 67
-25°C to +50°C
• ContractorPLA5-A60CWA1-H3
shall include cables,
2400K connection1675lmand accessories
460lux as site situation requires.
PLA5-A60CWA2-H3 2700K 1775m 460lux
• Fixture require fire certification
PLA5-A60CWW-H3 3000K to comply
60W/5m with FSD
1775m 500luxPPA/104. Fixture backed up by CBS where applicable.
PLA5-A60CWN-H3 4000K 1830m 500lux
General Description
Wall mounted luminaire with aluminium boday with linear profile with PC diffuser. Fixture IP68
Illustration
Additional Notes:
• Customised curved aluminmum channel with flexible LED where applicable.
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Length to be coordinated by contractor as required to match lighting layout and site conditions.
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable.
• Maximum distance between driver and luminaire is 4 meter
General Description
Surface mounted LED Linear fixture with integrated electronic ballast. Luminaire complete with LED unit neutral white colour
4000K.
Illustration
Additional Notes:
• Length to be coordinated by contractor as required to match lighting layout and site conditions.
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture backed up by CBS where applicable.
General Description
Flexible LED strip. IP67. Length to be coordinated by contractor as required to match lighting layout.
Illustration
Additional Notes:
• Length to be coordinated by contractor as required to match lighting layout and site conditions.
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture backed up by CBS where applicable.
General Description
Linear LED fixture with rigid aluminum channel and continuous opal PC optic diffuser. Fitted with a DALI controllable ballast. Lumi-
naire complete with LED unit in cool white colour 4,000K. Length to be coordinated by contractor as required to match lighting
layout.
• LOR 100%
Control • Ballast Lost/W -
High recessed linear
Dimension (mm)
Technical description 2000x24.4x22
Rigid aluminium profile with contact tab edge for re
monochrome Ledstrips with front emission LEDs,
Colour
Finishes available: anodised grey - white.
White The pro
(01) | Aluminium
translucid. The raised section of the profile, couple
Weight (Kg)
0.55
Installation
recessed in prepared milled parts; with blind milled
Mounting
to facilitate drilling. If through milled parts are pres
wall recessed|ceiling re
pcs); fix the springs on the module (centre distanc
Additional Notes:
leaflet), insert in the milled part prepared. Accesso
• Length to be coordinated by contractor as required to match lighting layout and site conditions. Wiring
Carefully read the Leds
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
Dimension (mm)
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant 2000x24.4x22 Notes
Carefully read the Leds
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture require fire certification to comply with FSD PPA/104. Fixture backed up by CBS where applicable. Colour
White (01) | Aluminium (12)
Weight (Kg)
0.55
Contract 3403_Particular Specification page 24 AA 25
08 // 02
03 // 19
19
Appendix F - Particular Technical Specification
Part F3.2 - Electrical Works Mounting
wall recessed|ceiling recessed|ceiling surface
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
LX-001
Area entrance canopy
General Description
Wall mounted luminaire. Fixture with 34° beam angle and the LED unit in neutral white colour 4000K. IP66.
Illustration
Additional Notes:
• Fixture to be connected with plug connector between fixture and driver for quick maintenance
• Contractor shall provide installation detail and to coordinate with interior designer and lighting consultant
• Contractor shall include cables, connection and accessories as site situation requires.
• Fixture backed up by CBS where applicable.
General Description
Recessed mounted downlight. Luminaire complete with C.O.B. technology. Fixture with 38° beam angle and the LED unit in neutral
white colour 4000K. Including integrated electronic ballast. IP66
Installation
Weight (Kg)
Recessed in false ceilings 5 - 50mm thick. Hole for preparation of false ce
Contract 3403_Particular Specification page 26 to be ordered separately.
outer casing, AA 25
0.95 08 // 02
03 // 19
19
Appendix F - Particular Technical Specification
Part F3.2 - Electrical Works
General Description
Linear LED fixture with aluminum channel fior gerneral lighting. Luminaire complete with LED unit in cool white colour 4,000K.
Length to be coordinated by contractor as required to match lighting layout.
Dimensions & available lengths Fixture build to length (not field cuttable):
Additional Notes: Lmin : 84 mm; Lmax : 4,021 mm (HD25: 3,021 mm); in 62.5 mm increments
42 mm / 1.65" Lmin : 3.31"; Lmax : 13.19' (HD25: 9.91'); in 2.46" increments
• Length to be coordinated by contractor as required to match lighting layout and site conditions.
• Fixture to be 33 connected with plug connector between fixture and driver for quick maintenance
mm / Electrical & output data
• Contractor shall 1.3"
provide installation detail and to
Viewcoordinate
rotated by 90°with interior designer and lighting consultant
Tc Voltage 24 Volt (23 Vmin , 25 Vmax)
• Contractor shall include cables, connection and accessories
Trimless as site situation requires. Opal encapsulation Recessed
TemperatureB Tcmin = -25°C / -13°F, Tcmax (Table below)
• Fixture require
(H x L) fire certification to comply with FSD PPA/104. Fixture backed up by
Storage temperature
CBS where
Length applicable.
(L) mm / ft Ts = -30°C / -22°F, Ts = 70°C / 158°F 7 mm /
min max
65 mm x 100 mm 0.28"
2.65" x 3.94" Ambient temperature Tamin = -25°C / -13°F, Tamax = 40°C / 104°F
CRI / R9 up to 95 / up to 65
62 mm /
2.44" +
Contract 3403_Particular Specification XOOLIGHT™ HYDRA
page 27 HD6 HD10 AA 25
08 // 02 // 19
03HD1519
Appendix F - Particular Technical Specification Power (W/m / W/ft)
A
6 / 1.8 10 / 3.1 15 / –4.6
Part F3.2 - Electrical Works Efficacy (lm/W)A @ W850 83 83 89
max. length (m / ft) 4 / 13.1 4 / 13.1 4 / 13.1
65 mm / 2.65" Temperature Tc-point (Tcmax)B 55°C / 131°F 55°C / 131°F 55°C / 131°F 60
Recessed Trimless Finish: Anodized Al-Silver/White powder coated Tc-point (Case temp.) on the rear side of the module
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
LC-000
Function: Lighting Control Software
General Description
Windows based, multi-user software tool for centralized lighting management. Graphic based system for remote control, monito-
ring and programming of all devices on the control network. To be located in workstation LC-001.
Illustration
Note:
anager
em control, monitoring and management
Contract 3403_Particular Specification page 28 AA 25
08 // 02
03 // 19
19
Appendix
s Dynalite SystemF Manager
- ParticularisTechnical Specification
a multi-user control system
Part F3.2 - Electrical Works
gement and monitoring software tool. It provides users with full
ty of the lighting and energy management system status and
mance, while enabling simple local or global system adjustments.
Project Name Terminal 2 Expansion
LC-001
Function: Headend Workstation
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
Control Equipment Name: Lenovo™ ThinkCentre® M900 / M800 Tower & Small Form Factor LC-001
Function: Headend Workstation
General Description
Control
Windows Equipment
based work station to Name: Lenovo™
interface lighting control ThinkCentre®
software. To be locatedM900 / M800
in Operating Tower & Small Form Factor
Room
General Description
Windows based work station to interface lighting control software. To be located in CR79
PERFORMANCE Connectivity
Processor I/O (Input/Output) Ports Front, 2 x USB 3.0, 2 x
· 6th Generation
PERFORMANCE Intel® Core™ Celeron® Processor up USB 2.04, Card Reader4, 2 x Audio
Connectivity
to i7Processor
Processor I/O (Input/Output) Ports Front, 2 x USB 3.0, 2 x USB 2.04, Card
· 6th Generation Intel® Core™ Celeron® Processor up to i7 Rear: Reader4, 2 x Audio
Operating System
Processor M900:Rear: 6 x USB 3.0
· Windows 10 Pro
Operating System M800:M900: 4 x USB 6 x3.0
USB + 23.0x USB 2.0
· Windows 10 Home
· Windows 10 Pro DisplayPort™ 1.2 + DisplayPort™ 1.2 2.0 DisplayPort™ 1.2 +
M800: 4 x USB 3.0 + 2 x USB
· Windows 7 Professional
· Windows 10 Home SP1 (pre-installed through VGA
DisplayPort™ 1.2
· Windows
downgrade 7 Professional
rights SP1 (pre-installed
in Windows 10 Pro) through down-1 x Serial VGA
grade rights in Windows 10 Pro)
1 x Lenovo ThinkCentre® M900 / M800 Tower & Small Form Factor
™
· DOS · DOS LAN1 x Serial
GraphicsGraphics
3 x Audio 1 x LAN
· Intel®· Integrated Graphics
Intel® Integrated Graphics PS/24 3 x Audio
· NVIDIA®
· NVIDIA® GeForce®
GeForce® GT720GT720 2 GBVGA
2 GB VGA + + HDMI™
HDMI™· NVIDIA® Parallel4 PS/24
GeForce® GT720 1 GB 64-bit DP + DP · NVIDIA® Quadro® K420 2Enterprise-level
Parallel4 performance
· NVIDIA® GeForce® GT720 1 GB 64-bit DP + DP
GB DVI + DP Memory WLAN:
· NVIDIA® Quadro®
· M900 / M800:K420 2 GBupDVI
4 x DDR4 + GB
to 64 DPStorage Tower Desktop performance and productivity that’s ready for business
1 x 1 802.11 a/c WLAN + Bluetooth® 4.0
WLAN:
Memory · 2 x 3.5“ Bay for HD / SSD / SSHD The all new ThinkCentre M-series M900 and M800 Tower & Small Form Factor come in a sleek new ID
2 x offering
2 802.11 a/clevel
WLAN + Bluetooth®
®
4.0 Intel Core i processor and optional PCIe S
1 xenterprise
1 802.11 a/c WLAN
performance + up
with Bluetooth®
to 6 Generation4.0 th ® ™
· M900· SFF
/ M800: 4 x DDR4 up to 64 GB 2 x The
2 802.11
desktopsa/c WLAN
also feature + Bluetooth®
the ThinkCentre
2 x 2 802.11 a/c WLAN + Bluetooth® 4.0an+unique
Dust Shield, vPro™1
4.0 Lenovo solution, that reduces dust int
® ®
· 1 x 3.5“ / 2.5“ HD up to 57%2 reducing maintenance and extending the life of the machine.
Storage Tower 2 xis217%
The SFF 802.11
smallera/c WLAN
than its + Bluetooth®
predecessor 4.0an+integrated
whilst the tower has vPro™1handle and front accessibl
Power Supply Tower removable HDD delivering robust protection for your critical data.
· 2 x 3.5“ Bay400W
· 92% for HD / SSD / SSHD
Adapter For enhanced features the M900 and M800 offer PCI slot for expansion and Intel® Stable Image Platform P
Illustration
M900Illustration
also offers Intel® vPro™ for enterprise management.
· SFF · 85% 250W Adapter
· 85%
· 1 x 3.5“ 180W
/ 2.5“ HDAdapter6
SFF
Power Supply Tower
· 92% 210W Adapter
· 92% 400W
· 85% 210WAdapter
Adapter
· 85% 250W Adapter
· 85% 180W Adapter6
SFF
· 92% 210W Adapter
· 85% 210W Adapter
WHY YOU SHOULD BUY THE LENOVO™ THINKCENTRE® TOWER & SMALL FORM FACTOR
- Lenovo™ isor
17%equivalent.
will free-up valuable desk space and solution, is an easily removable and washable
ThinkCentre® M900
Supplier product info / M800 Tower & Small Form Factor smaller than its predecessor. filter that fits discreetly on the front chassis of the
system and reduces dust intake by up to 57%2.
- The contractor
Note: shall provide installation detail and coordinate with interior designer and lighting consultant.
SSD storage for a turbo boost. Optional PCI slot
is available for expansion.
with Intel vPro™1 for enterprise manageability.
- Contractor
- The shall provide
contractor theprovide
shall cable, connection
installationand accessories
detail to match
and coordinate the
with site situation.
interior designer and lighting consultant.
- Back-up PC Required
- Contractor shall provide the cable, connection and accessories to match
THE LENOVO ™
the site® situation.
THINKCENTRE TOWER & SMALL FORM FACTOR IS BEST SUITED FOR
LUMINAIRE- &
Back-up
LIGHTINGPC Required
1 2 3
Business looking for powerful Businesses looking for Businesses that need a
CONTROL DATASHEETS page 63 of 71 enterprise-level performance, AA 13 / 04 / 18
reliable machines in space-saving desktop form
with available enterprise dusty environments. factor to free up valuable
management and support desk space.
for legacy systems.
TENDER DESIGN
Contract 3403_Particular Specification page 29 AA 25
08 // 02
03 // 19
19
Appendix F - Particular Technical Specification 1
M900 only.
Part F3.2 - Electrical Works Testing simulated 3 year usage in an end-user environment using 400g of free-settling dust.
2
The test compared the amount of dust accumulated inside a ThinkCentre® tower with a dust filter
and a ThinkCentre® M900 Tower without.
Project Name TRC - HKIA Third Runway Concourse - IAC Contract 3133
LC-002
Function: DALI Controller
General Description
The DDBC320-DALI features three DALI outputs, allowing control of up to 192 DALI devices. It also features 3 x 20 A feed-through
switched cicuits for DALI driver mains supply.
Illustration
Note:
- The contractor shall provide installation detail and coordinate with interior designer and lighting consultant.
- Contractor shall provide the cable, connection and accessories to match the site situation.
General Description
DDRC1220FR-GL provides control of mulitple types of switched loads. 12 channel controller supports switched loads of up to 20A
per channel, up to a maximum device load of 180A. Controller to have integrated processor.
Electrical Physical
Output Channel Current: 20 A (max) Dimensions (H x W x D) : 93 x 215 x 64 mm
Outputs: 12 x SPST feed-through relay with manual override Packed Weight: 1.1 kg
Maximum Device Load: 180 A Construction: Polycarbonate DIN rail enclosure (12 unit)
DyNet DC Output Voltage: 12 VDC Serial Ports: 2 x RJ12
DyNet DC Output Current: 200 mA (supply for approximately 1 x 6-way screw terminal SHLD, GND, D+, D-, +12V, AUX
10 user interfaces) Serial Port Conductor Size: 2.5 mm2 (#12 AWG) (max)
Supply Terminal Conductor Size: 5 mm2 (#10 AWG) (max)
Control Load Terminals: 12 x 2-way screw terminal Line IN, Line OUT
Serial Ports: 1 x RS-485 Load Terminal Conductor Size: 5 mm2 (#10 AWG) (max)
Supported Protocols: DyNet, DMX Rx Operating Temperature: 0° to 50°C ambient (32° to 122°F)
Dry Contact Inputs: 1 (AUX) Storage/Transport Temperature: 25° to 70°C ambient (-13° to
Diagnostic Functions: Device online/offline status 158°F)
Humidity: 0 to 90% non-condensing
User Controls: 1 x service switch Manual override switch for
each channel
Indicators: 1 x diagnostic LED
Certification
CE, RCM, UL/cUL, FCC, ICES-003, RoHS
Illustration
Note:
- The contractor shall provide installation detail and coordinate with interior designer and lighting consultant.
- Contractor shall provide the cable, connection and accessories to match the site situation.
General Description
The DUS360CR-DALI is a recess mountable 360° multifunction sensor that combines motion detection (PIR), Infrared remote
control reception (IR) and ambient light level detection (PE) into one device. The DUS360CR-DALI is powered and communicates
with the network control system via a DALI bus.
Hardware Network
PE Cell: Range <5 lux to >5000 lux Configuration: All functions remotely
Automatic ‘Daylight Harvesting’ mode programmable
Controls: Service switch Red LED indicator Physical
Terminals: 2 way terminal strip, loop in, loop out Dimensions: 72 mm dia. x 41 mm (2.8 in dia. x 1.6
1 x 5 mm² max conductor size in)
Control Bus: DALI bus with a Philips Dynalite Multi- Packed Weight: 105 g (0.23 lb)
Master controller Construction: Polycarbonate plastic enclosure
DALI Power Consumption: 9 mA (total 10 user Color: off-white
interfaces Operating Conditions:
on one DALI universe) Temperature: 0 to 45° C (32 to 104° F) ambient
Humidity: 0 to 90% non-condensing
Storage & Transport:
Temperature: -25 to 70° C (-13 to 158° F) ambient
Humidity: 0 to 90% non-condensing
Mounting Substrate Thickness 3 - 25 mm (0.12 - 1
in)
Certification
cULus, CE, RCM, FCC, RoHS, ices-003
Illustration
Note:
- The contractor shall provide installation detail and coordinate with interior designer and lighting consultant.
- Contractor shall provide the cable, connection and accessories to match the site situation.
General Description
Control panel with flexible configuration possibilities, with sensors to provide light-wash effect when being approached and used
and built-in temperature sensor.
Hardware Network
PE Cell: - Configuration: -
Terminals: - Physical
Control Bus: - Dimensions: (L)88 mm × (W)88 mm × (D)35mm
Packed Weight: 0.2 kg
Construction: -
Color: white/magnesium/chrome/silver, TBC
Operating Conditions:
Temperature: -5 to 50°C ambient
Humidity: 0 to 90% RH non-condensin
Storage & Transport:
Temperature: -25 to 60°C ambient
Humidity: 0 to 90% RH non-condensing
Certification
CE, C-Tick, FCC, ICES
Illustration
Note:
- The contractor shall provide installation detail and coordinate with interior designer and lighting consultant.
- Contractor shall provide the cable, connection and accessories to match the site situation.
General Description
Flush surface bell switch with dimension 87×87×31mm.
Hardware Network
PE Cell: - Configuration: -
Controls: - Physical
Terminals: pillar terminals Dimensions: (L)87 mm × (W)87 mm × (D)31mm
Control Bus: - Packed Weight: -
Construction: -
Color: silver bronze
Operating Conditions:
Temperature: -5 to 35°C ambient
Humidity: 0 to 95%
Storage & Transport:
Temperature: -
Humidity: -
Certification
BS EN 60669-1
GB 16915.1
IEC 60669-1
MS 60669-1
SS 227-1
Illustration
Note:
- The contractor shall provide installation detail and coordinate with interior designer and lighting consultant.
- Contractor shall provide the cable, connection and accessories to match the site situation.
General Description
The built-in daylight sensor can measure ambient natural light. It will switch off the fixture in 5minutes automatically, whenever
artificial light is not required (natural light lux level exceeds daylight threshold).
Double L N terminal makes it easy for wire loop-in and loop-out, saves the cost of terminal block and assembly time.
Hardware Network
PE Cell: - Configuration: -
Controls: - Physical
Terminals: - Dimensions: (L)67 mm × (W)37 mm × (D)26mm
Control Bus: - Packed Weight: -
Construction: -
Color: -
Operating Conditions:
Temperature: -20 to 60°C ambient
Humidity: -
Storage & Transport:
Temperature: -
Humidity: -
Certification
-
Illustration
Note:
- The contractor shall provide installation detail and coordinate with interior designer and lighting consultant.
- Contractor shall provide the cable, connection and accessories to match the site situation.
General Description
The sensor is a motion switch, which turns on the light on detection of people movement, and turns off after a pre-selected hold-
time when there is unoccupied.time; built-in daylight sensor can read ambient natural light and switch off the fixture automati-
cally whenever artificial light is not required; Semi-auto Funct; Manual Override
Hardware Network
PE Cell: - Configuration: -
Controls: - Physical
Terminals: - Dimensions: (dia)85 mm × (D)56 mm
Control Bus: - Packed Weight: -
Construction: -
Color: -
Operating Conditions:
Temperature: -20 to 60°C ambient
Humidity: -
Storage & Transport:
Temperature: -
Humidity: -
Certification
-
Illustration
Note:
- The contractor shall provide installation detail and coordinate with interior designer and lighting consultant.
- Contractor shall provide the cable, connection and accessories to match the site situation.
General Description
Provides a tamper resistant solution for time-based event control on a DyNet network. Remote programming, Advanced clock
controls, Performs as an energy management controller, Flexible mounting sol
Hardware Network
PE Cell: - Configuration: -
Controls: - Physical
Terminals: - Dimensions: (L)86 mm × (H)35 mm × (D)58 mm
Control Bus: - Packed Weight: 0.1 kg
Construction: ABS DIN-rail enclosure (2 unit)
Color: -
Operating Conditions:
Temperature: 0 to 40°C ambient
Humidity: -
Storage & Transport:
Temperature: -25 to 70°C ambient
Humidity: -
Certification
CE, RCM, RoHS
Illustration
Note:
- The contractor shall provide installation detail and coordinate with interior designer and lighting consultant.
- Contractor shall provide the cable, connection and accessories to match the site situation.
SCENE 1 SCENE 1
AREA GROUP TYPE INPUT WATTS QUANTITY TOTAL WATTS CONTROL TYPE CONTROL TYPE Day Night
(dawn to dusk) (dusk to dawn)
Interior G/F
ON ON
00.001 LI-002 Fixed ceiling recessed downlight 10 W 20 200 W ON/OFF
ON ON
entrance lobby
00.003 LI-105 Horizontal Bendable Flex linear light 12 W/m 30.0 m 360 W ON/OFF Daylight Sensor ON ON
00.004 LI-102 Linear LED profile for portal decorative lighting 13 W/m 9.8 m 129 W ON/OFF ON ON
00.060 LI-013 Fixed ceiling recessed downlight 10 W 10 100 W DALI Keypad Control ON ON
CMT room Occupancy Sensor
00.061 LI-104 Recessed framless linear profile 23 W/m 8.0 m 187 W DALI Time Schedule ON ON
Occupancy Sensor
PA room 00.070 LI-009 Fixed ceiling recessed downlight 9W 4 34 W ON/OFF Local Switch ON ON
Time Schedule
00.081 LI-008 Fixed ceiling recessed downlight 24 W 26 621 W DALI ON ON
Keypad Control
00.082 LI-008 Fixed ceiling recessed downlight 24 W 7 167 W DALI Daylight Sensor ON ON
AEC
00.083 LI-008 Fixed ceiling recessed downlight 24 W 16 382 W DALI Occupancy Sensor ON ON
00.084 LI-008a Fixed ceiling recessed downlight 24 W 22 526 W DALI ON ON
SCENE 1 SCENE 1
AREA GROUP TYPE INPUT WATTS QUANTITY TOTAL WATTS CONTROL TYPE CONTROL TYPE Day Night
(dawn to dusk) (dusk to dawn)
Occupancy Sensor
ADM office 00.120 LI-008 Fixed ceiling recessed downlight 24 W 4 96 W ON/OFF ON ON
Local Switch
00.131 LI-103 Linear LED profile for cove light 7 W/m 2.8 m 18 W ON/OFF ON ON
00.170 LI-103 Linear LED profile for cove light 7 W/m 7.5 m 49 W ON/OFF ON ON
00.175 LI-103 Linear LED profile for cove light 7 W/m 10.6 m 69 W ON/OFF ON ON
00.180 LI-103 Linear LED profile for cove light 7 W/m 7.6 m 49 W ON/OFF ON ON
LI-012 Fixed ceiling recessed downlight 4W 5 18 W ON/OFF ON ON
00.181
LI-003 Fixed ceiling recessed downlight 10 W 6 60 W ON/OFF ON ON
male toilet
00.183 LI-013 Fixed ceiling recessed downlight 10 W 2 20 W ON/OFF ON ON
SCENE 1 SCENE 1
AREA GROUP TYPE INPUT WATTS QUANTITY TOTAL WATTS CONTROL TYPE CONTROL TYPE Day Night
(dawn to dusk) (dusk to dawn)
00.200 LI-002 Fixed ceiling recessed downlight 10 W 5 50 W ON/OFF ON ON
00.206 LI-100 Wall grazing linear LED 13 W/m 12.9 m 171 W ON/OFF ON ON
00.045 LI-105 Horizontal Bendable Flex linear light 12 W/m 71.8 m 862 W ON/OFF ON ON
00.046 LI-105 Horizontal Bendable Flex linear light 12 W/m 77.6 m 931 W ON/OFF ON ON
Occupancy Sensor
main hall 00.047 LI-013 Fixed ceiling recessed downlight 10 W 8 80 W ON/OFF ON ON
Local Switch
00.048 LI-013 Fixed ceiling recessed downlight 10 W 8 80 W ON/OFF ON ON
SCENE 1 SCENE 1
AREA GROUP TYPE INPUT WATTS QUANTITY TOTAL WATTS CONTROL TYPE CONTROL TYPE Day Night
(dawn to dusk) (dusk to dawn)
Interior 1/F
Occupancy Sensor
ADM support room 01.010 LI-008 Fixed ceiling recessed downlight 24 W 15 359 W ON/OFF Local Switch ON ON
Time Schedule
SCENE 1 SCENE 1
AREA GROUP TYPE INPUT WATTS QUANTITY TOTAL WATTS CONTROL TYPE CONTROL TYPE Day Night
(dawn to dusk) (dusk to dawn)
01.050 LI-003 Fixed ceiling recessed downlight 10 W 14 140 W ON/OFF ON ON
01.056 LI-101 Wall grazing linear LED 13 W/m 20.0 m 264 W ON/OFF ON ON
01.058 LI-103 Linear LED profile for cove light 7 W/m 2.9 m 19 W ON/OFF ON ON
05.000 LX-100 Strip light with recessed linear profile 10 W/m 264.0 m 2640 W ON/OFF OFF ON
05.009 LX-001 Fixed surface mounted downlight 6W 8 51 W ON/OFF ON/OFF OFF ON
canopy Time Clock Depending
05.010 LX-002 Recessed downlight 12 W 2 24 W ON/OFF Daylight Sensor OFF ON
00.253 LI-107 Surface mounted indirect luminaire 7W 2 14 W ON/OFF ON ON
1.1 INTRODUCTION
This Particular Technical Specification (PTS) covers the requirements for the
Mechanical Works to be carried out under the Contract. The general
requirements of works shall be read in conjunction with the Section of Electrical
and Mechanical Works General in the Specification.
The Mechanical Works shall cover all Mechanical Services without limitation
to the design, manufacture, supply, transportation, delivery, installation,
relocation, modification, diversion, dismantling, reinstatement, site survey,
coordination with Other Contractors, design data submission, statutory and
utilities submissions, testing, setting to work, commissioning and rectification
of defects for the areas associated with the Primary Integrated Airport Centre
(IAC) and the Backup Integrated Airport Centre (IAC).
The Mechanical Works shall be a complete, safe, operable, reliable and readily
maintainable mechanical system with the following items forming the principal
components:
The Addition and Alteration (A&A) Works for the Mechanical Services shall
include but not limited to the following:
(c) Properly demolish, terminate and make good for existing services as
per Employer’s Drawing and the Specification to suit new Mechanical
Services designs and new architectural designs. The Contractor shall
return the dismantled equipment and materials to store of the Authority
in good condition if requested by the Project Manager.
The Contractor shall supply, install and modify the MBMS control and
monitoring system for chiller plant in the Primary IAC for changeover of
seawater supply system from the existing seawater pump house to the re-
provisioned seawater pump house.
The Contractor shall coordinate with Other Contractors to carry out the testing
and commissioning for the seawater distribution system in the Primary IAC for
changeover of seawater supply system at the existing seawater pump house
to the re-provisioned seawater pump house.
For the Primary IAC, the Contractor shall supply and install appropriate IAQ
equipment in the air conditioning and ductwork system to achieve the Excellent
Class Indoor Air Quality (IAQ) requirements as defined by A Guide on Indoor
Air Quality Certification Scheme for Offices and Public Places published by
Environmental Protection Department for the areas which shall be normally
occupied by people such as but not limited to the IAC Hall, AEC Hall, offices,
meeting rooms, restroom and resting areas. The Contractor shall submit the
calculations of the air filtration system to achieve the Excellent Class IAQ to
1.2.1 The relevant Definitions and Abbreviations shall be in accordance with the
Employer’s Drawings and/or the Specification thereof. The Definitions and
1.3.1 The Mechanical Works shall comply, without limitation, with all relevant
regulations, ordinances and requirements as stated in the Section of Electrical
and Mechanical Works General in the Specification.
1.4.1 The Contractor’s responsibility shall include but not limited to the requirements
as stated in the Section of Electrical and Mechanical Works General in this
Specification.
1.5.1 The Contractor shall produce and submit a full set of drawings and the
associated calculations for the entire Works to the Project Manager for review
without objection.
1.6.1 The Contractor shall produce As-Constructed Drawings in accordance with the
requirements as stated in the Section of Electrical and Mechanical Works
General in the Specification.
1.7.1 The facility identification shall comply with all relevant requirements as stated in
the Section of Electrical and Mechanical Works General in the Specification.
1.8.1 The requirements of installation cleaning shall comply with all relevant
requirements as stated in the Section of Electrical and Mechanical Works
General in the Specification.
1.9.1 The requirements of painting and finishes shall be in accordance with the
Electrical and Mechanical Works General in the Specification.
1.10 WATERPROOFING
Contract 3403 – Particular Specification 4 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
1.10.1 Where any work pierces the waterproofing, including the waterproof structure,
the method of installation shall be submitted to the Project Manager for review
without objection prior to manufacture.
1.11.1 The relevant Codes and Standards shall be in accordance with the Electrical
and Mechanical Works General in the Specification.
1.12 MATERIALS
1.13 SUBMISSIONS
1.14 WORKMANSHIP
1.15.1 The requirements for the inspection, testing and commissioning shall be in
accordance with the Specification.
2.1 GENERAL
2.1.1 Design and performance criteria associated with the Mechanical Works shall
be in accordance with this PTS and the GMWS or amendments thereof.
2.1.2 The control and monitoring system for Mechanical Installations shall follow
the point schedule as stated in MBMS typical I/O point schedule in Sections
of Airport Systems in this Specification.
2.1.3 Extreme care shall be taken by the Contractor to protect existing services
during re-installation or new services, it is the Contractor’s responsibility to
report and carry out remedial works to any damaged installations right after
an incident has occurred. Should the Contractor fail to carry out the required
rectification work within one hour after the incident is reported, the Project
Manager is entitled to employ a third party to execute the remedial works.
(b) All overnight works to carry out modification, diversion, demolition and
installation etc. works are the Contractor’s responsibility.
(c) All affected areas shall be carefully identified and the necessary
temporary provision made for the affected areas during modification,
diversion, demolition and installation etc. works.
(d) The Contractor shall return the dismantled equipment and materials to
store of the Authority in good condition if requested by the Project
Manager.
2.1.5 Where a particular item is not addressed within the above-specified criteria,
the Contractor shall design based on recognized international standards
including the CIBSE and/or ASHRAE.
2.2.1 Unless otherwise stated, the Contractor shall base the design of the
Mechanical Works on the following external conditions.
(ii) The noise level in external areas shall meet the statutory
requirements. Under no circumstances, the noise levels shall
exceed 85 dB (A) at 1m from the source. Compliance with the
Technical Memorandum for the Assessment of Noise from
Places other than Domestic Premises, Public Places or
Construction Sites, issued by the Environmental Protection
Department will be considered.
2.3.1 Unless otherwise stated, the Contractor shall base on the design of the air
conditioning installations on the following internal conditions:
2.3.3 Unless otherwise stated, the Contractor shall design, select, supply and
install the equipment for the air-conditioning systems and mechanical
ventilation systems by means of adding silencers, acoustic duct lining,
acoustic panels, acoustic lagging, acoustic enclosures or other methods
without affecting the system performance to satisfy EPD’s statutory
requirements and achieve the following noise levels stipulated on below
Acoustic Specification for Electrical and Mechanical Systems Installations.
Overall Internal
Area Mechanical Services NC Level
Noise Level
NC 35
POV Room (1 m away from the inlet/ return duct NC 25
of FCU)
NC 35
PA Room (1 m away from the inlet/ return duct NC 25
of FCU)
AEC Hall Refer to Overall Internal Noise Level NC 35(1)
IAC Hall Refer to Overall Internal Noise Level NC 35
AVSECO Refer to Overall Internal Noise Level NC 35
Contract 3403 – Particular Specification 11 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
Overall Internal
Area Mechanical Services NC Level
Noise Level
DSM Office
ADM Support
Refer to Overall Internal Noise Level NC 40
Team Room
CMT Room Refer to Overall Internal Noise Level NC 35
CCD Room Refer to Overall Internal Noise Level NC 35
ADM Refer to Overall Internal Noise Level NC 35
Nursing
Refer to Overall Internal Noise Level NC 35
Room
IAC Lobby NC 45 --
Pantry NC 45 --
Reception Refer to Overall Internal Noise Level NC 40
Briefing/
Refer to Overall Internal Noise Level NC 40
Lecture
Exhibition
Area /
Refer to Overall Internal Noise Level NC 40
Viewing
Gallery
Resting Area NC 45 --
CAD
Equipment NC 50 --
Room
Police
Observation NC 40 --
Room
Filing Room NC 50 --
HKPF
Equipment NC 50 --
Room
Common
Refer to Overall Internal Noise Level NC 40
Area
Sound Lobby
NC 40 --
(buffer zone)
Toilets NC 45 --
Locker NC 45 --
2.4.1 Fresh air quality criteria shall be in accordance with the latest EPD Annual
Air Quality Statistics, 95 Percentile measured in Tung Chung.
2.4.2 The Contractor shall design, install, test and commission IAQ equipment,
including but not limited to, particle filters, chemical filters, UV sterilizers and
high efficiency filters, to achieve the following indoor air quality criteria:
Remark: Fresh air rate per person for the Backup IAC of 8.5 L/s per
person is the benchmark for the existing IAC fresh air provisions.
a) Main Ducts (concrete duct and vent shaft / metal duct for
smoke extraction) – 10 m/s
(i) Intake air / makeup air / transfer air inlet weather-proof louvre:
2 m/s
(i) Pipes under 50mm dia. - 1.2 m/s (normal design max);
(ii) Pipes 50mm dia. and over - 400 Pa/m and 3 m/s (normal
design max.); and
a) Primary IAC
- Supply 6 oC
- Return 12 oC
b) Backup/Existing IAC
- Supply 7 oC
- Return 12 oC
a) Supply 29 oC
Contract 3403 – Particular Specification 17 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
b) Return 34 oC
2.6.1 The Contractor shall design, install, test and commission the smoke
extraction system in accordance with the minimum requirements of the FSD.
2.6.2 Equipment and ductwork required to handle and contain hot smoke shall be
suitable for continuous operation at 250oC for not less than 1 hour. This
includes fans, motors, drives, damper operators and ductwork etc.
2.6.3 All equipment, ductwork, grilles, louvres, power cables and control cables
shall comply with FSD requirements.
3.1 GENERAL
3.1.1 The Chilled Water Installations works shall be as shown on the Employer’s
Drawings and shall include, but not limited to:
(b) Supply and installation of the feed and expansion system for chilled
water system including feed and expansion tanks, pumps, pneumatic
vessels, power and control systems and associated works;
(c) Supply and installation of the thermal insulation for pipework and
equipment;
(f) Supply and installation of the electrical and controls works, including
but not limited to the associated MCC, LCP, control valves, power and
controls cablings, field devices (e.g. sensors, relay etc.), etc.;
3.2.1 A chiller plant shall be supplied and installed in the allocated area at the
Chiller Plant Room to serve the Primary IAC. The plant shall comprise of
three (3) Low Voltage (LV) titanium seawater cooled chillers (2 duty and 1
standby), three (3) chilled water pumps (2 duty and 1 standby) with variable
speed drives and feed and expansion system etc.
3.3.1 The Contractor shall submit method statement and associated drawings
detailing how the chiller plant and other equipment such as pumps, AHUs,
PAUs and fans etc. will be delivered to the Site and installed at the various
locations. This method statement shall include the means to facilitate the
future replacement of the equipment.
3.4.1 The chilled water pumps shall be located adjacent to the chillers. Three (3)
chilled water pumps (2 duty and 1 standby) shall be provided to circulate the
chilled water to the associated air handling equipment. The standby pump
shall be operated when there is any electrical or mechanical failure. The
chilled water circuit shall be designed to operate with variable flow control
for maintaining the minimum system pressure. In addition, the chilled water
main circuit will operate in a ring circuit arrangement on each floor to
enhance the reliability of chilled water supply. The speed of the chilled water
pumps shall be adjusted to deliver the required water flow in response to the
actual system demand by means of the differential pressure sensors
installed at critical locations.
3.4.2 Pressure Independent Control Valve (PICV) shall be installed for AHUs,
PAUs, CRAC Units and main chilled water pipes branch (Zone control) or
where indicated on Employer’s Drawings.
3.4.3 Isolation valves shall be provided along the chilled water ring mains to
ensure individual sections of chilled water circuit can be isolated in the event
of pipe leakage, whilst the remaining chilled water circuit sections can be
kept in operation.
3.4.4 Chilled water shall be supplied to all PAUs, AHUs, CRACs and FCUs.
3.4.5 Water treatment system shall be provided to maintain the quality of water to
an acceptable condition to comply with the Specification. The water
treatment system shall be timer controlled and locally controlled by the
conductivity sensor installed at the pipework.
3.4.7 Package type feed and expansion system shall be provided to cater for
expansion and make up of chilled water system. The pressurization unit shall
comprise of duty and standby booster pumps, duty and standby pneumatic
pressure vessels, control panel etc. Water supply for the feed and expansion
system shall be fed from 250L fibre glass break tank locating inside Chiller
Plant Room. The feed and expansion pumps shall be locally controlled by
the pressure switch with MBMS control under remote mode operation.
3.4.8 A 250L fibre glass break tank located inside AHU Room at 1/F shall be
provided to supply AC potable water to humidifier of CRAC units at Comms
Room CR79 at G/F.
3.4.9 The Contractor shall provide a full design, supply and installation of floor
mounted and ceiling-mounted I-beam/hollow section support systems for all
chilled water pipes, condensing seawater pipes and air ducts in the Chiller
Plant Room to meet the actual construction spatial arrangements. No
Mechanical Services that may cause vibration shall be mounted on the
ceiling inside the Chiller Plant Room. The Contractor shall also design,
supply and install the hoisting equipment such as I-beam and eye-bolt etc.
for maintenance of chillers and seawater strainers. In carrying out the
supporting structural works for the chiller plant before obtaining Occupation
Permit from BD, the Contractor shall appoint an Independent Checking
Engineer (ICE), who shall be a “Registered Professional Engineer (RPE) of
Structural Engineering Discipline” and “Registered Structural Engineer
(RSE)” to the Hong Kong Building Ordinance. The structural design
calculations and construction drawings checked and endorsed by the ICE
shall be submitted to the Project Manager for review without objection before
commencement of works.
3.5.1 Seawater shall be adopted for heat rejection of the chiller plant at the Primary
IAC.
3.5.2 Two (2) 250mm dia. seawater cooling supply pipes (seawater supplied from
existing seawater pump house) each with 100% heat rejection capacity shall
be provided to serve the chiller plant of the Primary IAC, with the interface
located at underground valve pit (West of Chiller Plant Room). A seawater
cooling outfall of dia. 250mm shall be discharged to the storm water drainage
system which as shown on the Employer’s Drawings. Changeover of
seawater supply from existing seawater pump house to re-provision of
seawater water pump house shall be required once the re--provided
seawater supply system is available to be operated.
3.5.4 Pressure sensors and flow meter shall be installed at the seawater cooling
supply and discharge mains to sense the seawater supply/ discharge
pressure and the flow status of the sea water supply.
3.5.5 Twin seawater by-pass lines completed with pressure differential sensors,
motorized modulating valve and flow meter shall be installed across the
seawater cooling supply and discharge mains as a safety device for
preventing pipe bursting owing to seawater supply system overpressure.
3.6.1 The Contractor shall provide condensate drain collection system including
pipework, insulation and cladding, for handling the condensate water
collected between various mechanical equipment and the drain points. The
condensate pipe shall be provided with sufficient cleaning plugs to ensure
that each portion of the pipework can be effectively cleaned in case of
blockage. If the fall of the condensate drain pipe is not sufficient due to site
constraints, condensate drain pump with appropriate power supply and
control with alarm to MBMS system shall be provided by the Contractor.
3.6.2 The condensate drain water from mechanical equipment shall be collected
and then discharged to the drainage system as shown on the Employer’s
Drawings and shall fully comply with statutory requirements.
3.7.1 The seawater cooled chillers shall include, but not limited to, the following:
(a) Low voltage (LV) hermetic drive direct seawater cooled chillers,
complete with:
(i) compressors;
(d) low voltage motor control centres for control systems, oil heaters, oil
pumps, refrigerant transfer compressors and associated plant; and
3.7.2 General
The Contractor shall allow for the interchange-ability of spare parts and
accessories in the selection of each chiller; and
(a) Motor shall be rated for re-start. Minimum with one immediate re-start
and another re-start within ten (10) minutes;
(i) Materials shall comply with the relevant British Standards and
International Standards, including but not limited to those listed in the
GMWS or amendments thereof; and
(j) All factory applied acoustical and thermal insulation, including facing and
adhesives shall be fire-resistant and shall conform to the requirements of
National Fire Protection Association (NFPA) and the FSD.
Each chiller shall be factory tested to verify the refrigerant capacity in tons and
the kW/ton at full load. Prior to delivery, a factory certified test report shall be
submitted to the Project Manager for review without objection in order to
confirm that each chiller performs as specified in this PTS. The FAT shall be
Contract 3403 – Particular Specification 25 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
conducted in conformance with AHRI Standard 550/590-2015 at the chiller
manufacturer’s plant;
The FAT shall be run with clean tubes in accordance with AHRI Standard
550/590-2015 or AHRI Standard 551/591-2015 including but not limited to the
following requirements:
The FAT shall be run at the design leaving evaporator water temperature and
a range of entering condenser water (i.e. seawater) temperatures including but
not limited to the design entering condenser water temperature;
The chiller manufacturer shall conduct FAT in accordance with AHRI Standard
550/590-2015 or AHRI Standard 551/591-2015 tolerance, except as modified
below, to verify design capacity and part load capacity points. A maximum of
two (2) points with tolerance allowed for kW or Tonnage for all tested points.
kW input in no case shall exceed that indicated on the Equipment and
Materials Schedule for the full load condition. Therefore, the chiller must
demonstrate the ability to meet the specified full-load capacity without
exceeding the kW input listed;
During the test, all machinery performance data including but not limited to oil
pressures, gas pressures, and component temperatures shall be recorded at
fifteen (15) minute intervals and compared to standard conditions supplied by
the chiller manufacturer. If at any time during the test, the recorded machinery
performance data is in excess of the standard conditions, the test will be
All proposals for chiller performance must include an AHRI approved selection
method for the specified refrigerants. Verification of data and version of
computer program selection or catalogue shall be available through the
Engineering Division of AHRI;
At least eight (8) weeks before the FAT, the Contractor shall notify the Project
Manager to arrange the relevant parties for the witness of FAT in the dedicated
factory. The Contractor shall make allowances for three (3) staff representing
the Project Manager, each time to witness the testing at the manufacturer’s
premises or at a mutually agreed site suitable for carrying out the test. The
staff shall be provided with full access to the manufacturing sites where
inspection, testing and commissioning for the various items of equipment
supplied by the Contractor are carried out. The FAT arrangements shall be
submitted to the Project Manager for review without objection eight (8) weeks
prior to conducting the FAT.
Before dispatch of each chiller unit, after having been completely factory
assembled, the manufacturer shall provide Factory Performance for AHRI
Points Test and Cold Condenser Water Test witnessed by both the Project
Manager and Contractor to ensure satisfactory operation of the chiller
including but not limited to the following:
(c) The 100% full-load condition, 75%, 50% and 25% part-load conditions
at the entering condenser water temperatures. The test results of
coefficient of performance (COP) shall be expressed in the format as
shown below:
(b) 25% load operation and 12.78 °C ECWT and design flow rates.
The refrigerant circuit shall be fully leak tested at the factory, evacuated and
pumped up with a holding charge of refrigerant for delivery under positive
pressure. If the holding charge is lost on arrival, the system will not be
accepted;
A certified and original test report of all data shall be submitted to the Project
Manager prior to delivery. The factory certified test report shall be signed off
by an representative of the chiller manufacturer's company while pre-printed
certification will not be accepted;
After all the tests and prior to delivery, the chiller manufacturer shall perform
the despatch including but not limited to the following:
(c) Drain water from boxes and heat exchangers and dry thoroughly; and
(d) Remove refrigerant and pressurize refrigerant side to five (5) psig with
dry nitrogen unless delivery with refrigerant in unit.
The Contractor shall be responsible for ensuring that all FATs are carried out
in safe manner with properly organised testing facility meeting all relevant
statutory safety requirements; and
3.7.5 Manufacture
(a) The seawater cooled chillers and drives shall be supplied by a single
manufacturer experienced in the design and construction of similar
equipment and who have made chillers for similar duties for at least
five years prior to the date of this tender. All guarantees, test
certificates, etc., shall be deemed to apply to the entire assembly;
(b) All water chillers and drives shall be the product of the manufacturers
listed in the relevant schedule of Third Runway Concourse for the
provisional suppliers for major materials and equipment, or an
equivalent reviewed without objection by the Project Manager.
3.7.6 Submissions
Submittal Drawings
(a) Within one month after the award of the Contract and prior to ordering
the equipment, the Contractor shall furnish the following information
for each unit, for review without objection by the Project Manager:
(g) Electrical data: Motor full load current, Job full load
current, inrush current, max fuse size
or breaker size;
materials specification
Characteristic curves;
(a) The product performance data sheet shall be submitted to the Project
Manager for review without objection prior to commencement of the
Works. The product performance data sheet shall include, but not
limited to the following:
Contract 3403 – Particular Specification 30 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
(i) Electric Chiller: - Refrigerant Type – HFO
(Material Safety Data
Sheet (MSDS) shall be
submitted for any
refrigerants used that is
NOT classified as ‘A1’ for
flammability and toxicity
by ASHRAE 34);
- Capacity (kW);
- Chilled-Water
Temperatures;
- Condenser Water
Temperatures;
(iv) Additional power or water sources for auxiliaries (water for oil
coolers, etc.) and the effect of compressor motor heat losses
to the refrigerant stream in all rating calculations shall be
included;
(c) Mounting and fixing details shall include details and dimensions of
chiller bases, fixing bolts, supporting steelwork, flexible connections,
vibration isolators and any special builder's work requirement.
(g) Within two months of the Date of the Practical Completion, the
Contractor shall provide complete commissioning and testing reports
for each unit in accordance with the recommendations of an approved
(h) In carrying out the supporting structural works for the chiller plant
before obtaining Occupation Permit from BD, the Contractor shall
appoint an Independent Checking Engineer (ICE), who holds
”Registered Professional Engineer (RPE) of Structural Discipline”, to
check and endorse the structural design calculations and construction
drawings and submit to the Project Manager for review without
objection before commencement of work. For the above submission
of structural design calculations and construction drawings which, in
the opinion of the Project Manager, are required for statutory
approval, those submitted structural design calculations and
construction drawings shall be checked and endorsed by an ICE to
the HK Building Ordinance, before submission to the Project
Manager.
3.7.8 Selection
(a) The Contractor shall select all chillers suitable for the equipment
schedule.
(c) Seawater cooled chillers shall be of the packaged type and suitable
for continuous operation inside plant room of 40°C DB and 98% RH.
(d) All seawater cooled chillers shall be of minimum vibration and noise
level during operation; should these be excessive and not within the
standards as stated in the GMWS, the Contractor shall be responsible
for provision of adequate vibration isolation and sound attenuation as
recommended and required by the Project Manager.
(e) The sound pressure levels for the chillers shall not exceed the criteria
stated in this PTS when tested in accordance with AHRI Standard
575.
(f) All chillers must be suitable for operation in parallel to give the
required duties.
(h) The water system shall be designed to tolerate a flow change of 50%
in one minute as well as being able to operate with minimum chilled
water flow down to 30% - 40% of the design full load chilled water
flow.
3.8.1 Each chiller unit shall include compressor, motor (in case of hermetic design),
evaporator, seawater cooled condenser, lubrication system, integral sub-
cooler or flash economizer, capacity controller, control panel, motor starter,
and all necessary accessories to enable the chilled water system to operate
as specified in the PTS;
3.8.2 Each chiller unit shall require only water connections, one electrical power
connection to the starter panel, one essential power connection for control
and oil heater;
3.8.3 The entire chiller unit shall be specifically designed for the type of refrigerant
to be used, which shall be HFO of Class A1 (Material Safety Data Sheet
(MSDS) shall be submitted for any refrigerants used that is NOT classified
as ‘A1’ for flammability and toxicity by ASHRAE 34), which fully comply with
the capacity requirements specified in this PTS and the Equipment and
Materials Schedule. All chillers shall be provided with a full charge of oil and
refrigerant. All the component parts, including but not limited to compressor,
motor (in case of hermetic design) bearings and seals, control device
lubricating oil, etc. shall be fully field proven to be suitable for the specific
type of refrigerant used;
3.8.4 The materials and items of equipment used in the refrigerant and water
circuits shall not corrode or set up corrosion when in contact with the liquids
conveyed and/ or other metals. Where corrosion occurs, appropriate
corrosion resistant materials and assembly methods must be used including
isolation of dissimilar metals against galvanic interaction;
3.8.5 Each chiller unit shall be completely factory assembled, piped, wired,
charged with refrigerant, tested and delivered complete with all starting gear,
3.8.6 Each chiller unit shall be dynamically and statically balanced after assembly;
3.8.8 The Contractor shall provide proper facilities for lifting for all removable parts,
including motor, compressor casing, gear box casing, water boxes covers,
etc. The hoisting facilities shall be in the form of lugs, rings, etc. of suitable
design;
3.8.9 The Sound Pressure Level (SPL) generated by each chiller under all
operating conditions shall not exceed the following values, when measured
1.0 m from any point on the chiller in accordance with latest edition of AHRI
Standard 575:
3.8.10 If chiller noise generation exceeds this level, the chiller manufacturer shall
provide acoustical devices with the chiller to reduce the noise generation to
the level specified. In addition, If all chillers operate at full load and the overall
acoustic requirements exceed the plant room noise level specified in other
cause of PTS, the Contractor shall propose and provide relevant acoustic
measurements to comply with relevant causes specified in PTS without other
implications;
3.8.11 Each chiller unit shall be field insulated in the evaporator, end sheets, suction
line, liquid line and other cold surfaces with not less than 40 mm closed-cell
neoprene foam insulation, adhered with vapor-proof cement. The water
3.8.12 All factory applied acoustical and thermal insulation, including facings and
adhesives shall be fire-resistant and shall conform to the requirements of
NFPA and the Fire Services Department.
The chiller shall operate at a power factor of better than 0.85 throughout the
operating range. If the design power factor of the motor should drop below
0.85 during low load conditions, an automatic fuse protected power factor
correction capacitor shall be provided as an integral part of the starter panel;
Each chiller shall have control panel, interface port, and interface cable. The
control panel shall contain USB port(s) for downloading the unit’s history,
major parameter trends, alarms, fault history, and unit operating manual that
is stored in the microprocessor. The fault history shall be displayed with date
and time stamped. The alarm and fault history shall be downloadable from
the chiller’s USB port(s);
The control panel shall connect to the MBMS. The chiller manufacturer shall
provide all required hand-held tools with licensed software for the interfacing
to chiller and chiller control system. Access code at client level shall be
provided for the proprietary monitoring software. Bearing oil temperatures
and motor windings for both compressors shall be monitored by chiller
manufacturer’s controller and sensor shall be provided to the bearings;
ii. High and low refrigerant pressure safety cut-outs with adjustable
differential pressure set point. Protection settings shall be pre-set in
accordance with manufacturer’s recommendations;
In case open type motors are adopted, the open type compressor motors
shall be horizontal foot mounted, open drip-proof, squirrel cage induction
design in accordance with BS EN 60034 and BS 5000. The motors shall be
statically and dynamically balanced to minimize vibration at all range of the
design duty, including the starting up period. Motor and compressor shall
be coupled and mounted rigidly on a common and substantial framework to
avoid misalignment due to vibration when chiller operates;
The low voltage open motor shall be Totally Enclosed Closed Air Circuit
Water Cooled (CACWC) type to protection code of IP 54 BS EN 60034 or
as specified in the Equipment and Materials Schedule. Motor coolers shall
be designed to IC W37 A81 of BS EN 60034. The shaft mounted fans shall
be provided for self-circulation of air;
The cooling medium for the open type motor shall be fresh water and the
heat shall be dissipated to the chilled water circuit through a plate type heat
exchanger. The cooling coils shall allow a maximum pressure drop of not
exceeding 45 kPa. The maximum winding temperature shall not be
exceeded when the cooling water temperature is at 13°C. The modulating
motorised valve shall be provided for each motor cooler to maintain winding
temperature;
The motor water coolers shall be fitted with drip trays and spray baffles to
prevent water, in the event of leakage, falling on live components. Leakage
detectors shall also be fitted to raise signal in the chiller control panel. Power
supply to chiller motor shall be cut off when one of over-temperature or
water leakage signals is activated;
The rotor and stator windings shall be high grade copper bars with low
resistance and good electrical and mechanical properties. The rotor copper
bars shall be brazed to the end ring. The stator and rotor bars shall be tightly
fitted together to avoid vibration. The stator and rotor insulation shall be
specially designed to ensure that there is no undue deformation due to
physical movement of the conductors arising out of differential thermal
expansion;
The stator frame shall be fabricated from steel to produce a light and rigid
structure with the stator core supported by terminal and intermediate
supports. The entire assembly shall be secured rigidly to avoid vibration
under all operating conditions, including overloading conditions during fault
conditions before clearance by the protection devices;
The motor insulation shall be Class F to B.S. 2757 and rated for Class B
maximum temperature rise limit in accordance with BS EN 60034. The main
insulation shall be synthetic resin bonded mica tape or approved equivalent
and finished stator winding shall be baked or vacuum pressure
impregnated;
Contract 3403 – Particular Specification 39 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
The motor shall be provided with a NEMA D-flange configuration. Bolted
cast iron adapter shall be provided to allow the motor to be rigidly coupled
to the compressor, providing factory alignment of motor and compressor
shafts, and to allow access to the motor for repair without removing
refrigerant charge from the chiller;
Each chiller unit shall be provided with an automatic oil re-claim basin. Shaft
seal shall be double face bellows type or floating carbon ring oil film type.
Maximum oil leakage rate of the shaft seals shall be less than 25 fluid
ounces of oil per 1000 hours of chiller operation.
The entire rotor and stator assembly shall be designed for efficient
ventilation and to avoid any hot spot within the entire winding assembly;
The entire electrical circuits, including the motor and the starter, shall be
capable of withstanding transient or fault conditions, including any possible
fault conditions due to the supply network;
The cable termination boxes for the LV motors shall be suitable for the
application of XLPE insulated cables and the terminations shall be suitable
for the local unconditioned climatic conditions and shall not require any
jointing compound. The termination shall also be of adequate strength to
withstand the stress due to fault conditions as stated in the other parts of
this PTS;
The cable joint boxes shall be phase segregated pressure relief type and
shall be designed to withstand the electrical, mechanical and thermal
stresses produced by fault conditions at the motor equivalent to a short
circuit current of not less than 50 kA symmetrical. A water tight air insulated
disconnected chamber shall be provided for the testing of the cable
termination. Terminal blocks for circuits of different voltages shall be
segregated into groups by permanent rigid barriers and distinctively
labelled. Each terminal shall be provided with white ferrules for
identification of internal and external wiring according to the wiring diagram;
The motor circuit shall be designed for minimum lagging power factor of
0.85 and efficiency better than 95%. If necessary, power factor correction
capacitor shall be provided. The wiring of the capacitor shall be on the
outgoing connection of the starter connected in such a manner that the
over-current drawn by the motor and not that of the motor and capacitor
combined. The short circuit protection of the starter, however, shall include
the capacitor in its circuit;
The shaft shall be designed such that first critical speed is well above
operating speed;
The bearing shall be cartridge sleeve type supporting rotating assembly and
shall be readily accessible for servicing with a rated life of minimum 200,000
hours;
The hermetic motor shall be designed for minimum lagging power factor 0.9
and efficiency better than 95%. If necessary, power factor correction
capacitor shall be provided. The wiring of the capacitor shall be on the
outgoing connection of the starter connected in such a manner that the over-
current drawn by the motor and not that of the motor and capacitor
combined. The short circuit protection of the starter shall include the
capacitor in its circuit;
The Contractor shall provide factory applied 20mm thick, anti-sweat, closed-
cell, plastic type insulation to motor housing; and
3.8.17 Evaporators
Variable primary flow control shall be employed in the chilled water circuit,
and the flow characteristics of the evaporator shall meet the following
criteria:
(1) The minimum allowable chilled water flow shall be 30% - 40% of design
evaporator full flow;
(2) The evaporator shall tolerate a minimum 50% flow rate change per
minute; and
(3) The maximum water velocity shall not exceed 2.3 m/s.
The refrigerant side shall be hydro tested in accordance with the ASME
Code. Water side shall be designed for working pressure as specified in the
PTS and Equipment Schedule on Employer’s Drawing;
The shell shall be fabricated such that each tube can be cleaned or replaced
individually without dismantling any pipework. Steel water boxes shall be
provided;
The tubes shall be minimum 0.71 mm thick, seamless copper and with
integral fin, and shall be mechanical roller expanded into steel tube sheets
providing a leak-proof seal at two ends and at mid-tube supports of material
same as evaporator shell. Each tube shall be individually cleanable and
Contract 3403 – Particular Specification 44 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
replaceable. Fin tube root thickness not less than 0.64 mm for working
pressure 16 bar and below and 0.71mm for working pressure not exceeding
25 bar;
The tube sheet shall be 25 mm thick carbon steel welded to the evaporator
shell;
Mid-tube supports shall be spaced at internals not greater than 1.4m and not
less than two supports must be used;
The water boxes shall be marine type and be provided with drain and vent
connections extended beyond the insulations, vapour seal and finish and
terminated with a vent/drain valve. Lifting eye bolt and/ or hinge shall be
provided so that maintenance can be carried out without removing
connection pipes;
The end-cover of the marine water box and evaporator shell shall be hinged
or provided with lifting eye bolt. The hinged water boxes shall be capable of
carrying the full weight of the end plate without additional supports or lifting
devices;
The pressure relief valves with rupture disk piped to the perimeter of the
building shall be provided in accordance with ASHRAE 15. The pressure
relief valves shall be factory installed in accordance with ANSI B9.1 safety
code. Independent alarms shall be provided for each rupture disk and
The seawater cooled condenser shall be of a single horizontal shell and tube
type design matching the compressor’s requirements and performance.
Construction and materials shall conform to ANSI B9.1 Safety code and
ASME Code;
The maximum water velocity in the water cooled condensers shall not
exceed 2.3 m/s;
The refrigerant side shall be pressure tested to 1.5 times the operating
pressure following the proper BS EN 378-2 or ASME Code for Unfired
Pressure Vessel;
The shell construction shall be horizontal and fabricated such that the tube
may be replaced and/or cleaned without dismantling any pipework. Steel
water boxes shall be provided and be suitable for flange connection to BS
EN 1092;
Tubes shall comply with all mandatory requirements of ASTM B891, and to
any additional requirements of this standard;
The basic tube shall not contain any surface defects, which would be
detrimental to the finning operations;
Tubes shall be provided in the "as-finned" temper. The plain ends and skip
sections shall be provided in the original "as-annealed" temper and shall be
suitable for subsequent expanding/rolling-in manufacturing operations or
any other normal tube fastening operation such as welding; and
(b) Mill test reports to SB-338, for each heat of basic tubing comprising
the shipment shall include the chemical composition, tensile test
results, flattening test results, reverse flattening test results and flaring
test results;
(f) Dimensional results of finned tube wall measurements, i.e. plain end
wall thickness and minimum wall thickness under fins.
The tube sheets shall be titanium cladded 9.5 mm thick for protection against
attack of sea-water, and shall be mechanical roller expanded into tube
sheets at two ends and free suspended at mid-tube supports (minimum
20mm thick and maximum spacing 1.4m) of material same as condenser
shell. Each tube shall be individually cleanable and replaceable;
Discharge gas baffle and headers shall be provided to avoid direct high
velocity impingement on condenser tubes;
The water boxes shall be marine type so that the condenser tubes can be
serviced without dismantling any piping. For chillers with dual condensers
design, provisions must be allowed at site and the Contractor shall
demonstrate that condenser water piping does not need to be dismantled
upon replacement of tubes;
The end-cover of the marine water box and condenser shell shall be hinged
or provided with lifting eye bolt. The hinged water boxes shall be capable of
carrying the full weight of the end plate without additional supports or lifting
devices.
The water chiller shall be a factory assembled as one piece packaged unit.
All factory wiring and piping shall be contained within the unit enclosure.
Panels shall be bonderized to remove grease and dirt after fabrication and
all external parts shall be coated with zinc phosphate and finished with baked
enamel.
Panels shall be of interlocking design with the base raised to prevent water
from entering the unit. Screws shall be cadmium plated.
Sufficient lubrication to all required locations shall continue at all times whilst
the compressor is rotating under all operating, shutdown and fault conditions
including but not limited to total power failure, fault trip on start-up, contactor
welding, oil pump failure, etc. Standby oil pumps with automatic start-up shall
be provided;
The lubrication system shall be factory package, assembled and piped and
be complete with the following:
(a) Main rotor shaft driven oil-pump for force feed lubrication to all
bearings, gears, and rotating surfaces by an external variable speed
oil pump for prestart, continuously during operation, and during shut
down;
In case of separate lubrication systems for the compressor, gear box and
motor are provided, each system shall separately comply with the specified
requirements including standby facilities with automatic start-up and manual
changeover without chiller shutdown;
Oil shall be filtered by a replaceable cartridge oil filter equipped with service
valves. Filter shall be serviceable without machine disassembly or pump-
down; and
The refrigerant cooled oil coolers shall be completely factory mounted and
piped, including service valves for the oil circuit.
The refrigerant circuit shall be constructed of copper tubing with brazed joints
and shall include isolating valves, charging connection, sight glass,
expansion valve or other throttling devices, solenoid valve, pressure relief
valves and filter-drier, etc. The entire suction line shall be insulated with 50
mm thick preformed closed-cell plastic-type pipe insulation or approved
equal; and
The chiller unit shall be fully tested with the specified refrigerant and the test
results shall be fully certified.
The entire chiller plant shall be supplied and installed with a refrigerant
leakage detector for each chiller. The detector shall be located at the bottom
of each chiller and fully comply with ASHRAE Standard 15-2016;
The relevant control & monitoring panel, dry-contact for interfacing with
mechanical ventilation system alarm & monitoring signal (including but not
limited to “Normal”, “Risk” & “ Power Healthy”), alarm system, control &
power cabling and any other accessories for the refrigerant leakage
detection shall be provided.
A refrigerant relief pipe connected from the safety relief valve and discharge
to outdoor shall be provided in compliance with ASHRAE Standard 15-2016;
Relief devices shall be provided for the refrigerant side, in accordance with
ANSI B9.1 safety code ASME B31.5 and ASHRAE Standard 15-1994.
Multiple relief devices shall be brought to a common vent connection. The
Contractor shall also provide the discharge piping.
Hot gas bypass valve and piping, designed to artificially load the evaporator,
shall be factory furnished to permit chiller stable operation without cooling
load demand.
The Contractor shall provide evaporator and condenser marine water box
type connections include but not limited to the following:
(c) Austenitic stainless steel drain plugs shall be provided at the lowest
point of the marine box;
(d) Water connection shall be extended flange end and blanked off with
mild steel plate; and
(e) Cover of water box shall be provided with lifting eye bolt.
Strainers shall be filled in all chiller water line inlets to the chillers; and
The body of the strainers shall be of cast iron and suitable for the system
pressure. The filtering medium of the strainer shall be stainless steel with
total available filtering area of at least five times the sectional area of the
pipe inlet to the strainer.
The Contractor shall ensure that the various components of the plants are
accurately levelled and aligned in relation to the base and other components
to ensure that the complete assembly operates in a proper manner without
creating undue stresses, out of balance forces, unnecessary noise or
vibration. Each chiller shall be supported on minimum 50mm static deflection
restrained type spring isolators.
A type of combination spring and rubber mounts giving not less than 95%
vibration isolation shall be supplied, subject to review without objection by
the Project Manager. The Contractor shall ensure that spring isolators are
supplied by the chiller manufacturer or from a source recommended by the
chiller manufacturer.
The details indicated on the Employer’s Drawings are for guidance only, and
it shall be the Contractor's responsibility to ensure that the mounting details
and vibration isolation equipment effectively eliminate the transmission of
vibration into the structure.
All service connections (including water pipes, cables and trunking) to the
chillers, if not inherently flexible in nature, shall be fitted with flexible sections
for review without objection by the Project Manager and sufficient to prevent
the transmission of noise and vibration away from the chiller.
The panel shall be factory installed and tested on each chiller unit;
The panel shall include a display screen with integral keypad for operator
interface showing all system parameters in the English language with
numeric data in English (or metric) units;
The panel shall provide control of chiller operation and monitoring of chiller
sensors, actuators, relays, switches and remote equipment.
The display screen shall provide details all operations and parameters, using
a graphical representation of the chiller and its components. Graphics
screens shall be provided for, including, but not limited to the following:
(b) Evaporator;
(c) Condenser;
(d) Compressor(s);
Contract 3403 – Particular Specification 54 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
(e) Economizer Compressor (if any);
(k) Trending.
(e) Percent motor current (%), ampere drawing (A) and power (kW);
The chiller control panel shall feature automatic safety shutdown and manual
reset. All cycling and safety shutdowns shall be enunciated through the
alphanumeric display and consist of day, time, cause of shutdown, and type
of restart required. Safety shutdowns shall include, but not limited to the
following:
The chiller unit control module shall utilize adaptive control or other means
of control which automatically takes action to avoid shutdown due to
abnormal operating conditions and details shall be submitted for review
without objection by the Project Manager. Only when the abnormal operating
condition continues until a protective limit is violated shall the chiller unit be
shut down; and
All compressors shall have a time delay relay system (adjustable) to prevent
the compressor from starting more than five times per hour;
(1) Interlock via the DDC controller with chiller water pumps and
condensing water pumps for both auto sequence start-stop and
manual start-stop controls;
(2) Interlock with lubricating oil pump and all other auxiliary components
of the chiller for sequence starting; and
The safety devices shall include, but not limited to the following:
The indicating devices in the chiller shall include, but not limited to the
following:
(j) Green indicating lights for compressor running and lubricating oil
pump running; and
The Contractor shall charge the chillers with all necessary refrigerant and oil
for carrying out tests and shall ensure that the chillers are correctly
maintained with refrigerant and oil until the expiry of the Defects Liability
Period (DLP); and
Before the expiry of the DLP, the Contractor shall furnish a complete
refrigerant charge and oil charge for each type of chiller.
The chiller unit shall be effectively earthed. The metal parts not forming part
of the electrical circuit shall be earthed separately from the electrical system,
with particular attention given to earthing of the condensing water system
and the cathodic protection system to minimize electrical stray current thus
increasing galvanic corrosion effects;
"DANGER"
Any damage to finishes which may have occurred during transit, storage,
installation or otherwise shall be made good in the manner recommended
Contract 3403 – Particular Specification 60 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
by the chiller manufacturer and submitted to the Project Manager for review
without objection;
All chillers shall be provided with an identification plate showing the code
number for each chiller as indicated on the system schematics. This plate
shall be securely fixed to the chiller in a prominent position;
Each chiller shall have a specification plate which shall show full details of
chilled water flow rates and design temperatures, condensing and
evaporating temperatures and pressures, refrigerants and lubricants,
compressor type and duty, electrical connections, motor speeds and any
other pertinent information as may be required by the Project Manager. This
plate shall also be securely fixed to the chiller; and
All chillers shall bear the chiller manufacturer's nameplate giving the chiller
manufacturer's name, serial and model number, and date of manufacture.
The Contractor shall ensure the chiller manufacturer shall have an adequate
local service organization where the staff shall have been factory trained,
certified and are capable of responding to service calls;
The Contractor shall ensure there is a stock of the refrigerant at the chiller
manufacturer for the life of the chiller, or not less than twenty-five (25) years
from the date of issuance of Completion Certificate of the Works, whichever
is greater in capacities sufficient to replace the full chiller refrigerant charge,
to be supplied to the Authority by the chiller manufacturer if a leak occurs
after the warranty period and also during the warranty period;
The Contractor shall submit Shop Drawings that relate to or impact the plant
supplied by the chiller manufacturer, marked to indicate the review and
approval by the chiller manufacturer, to the Project Manager for review
without objection;
(f) high voltage, low voltage and control cabling including selection,
installation and termination; and
The Contractor shall arrange staff from the chiller manufacturer to review
works associated with the chiller plant include, but not limited to the
following:
3.8.34 Controls
All necessary safety and operating controls shall be furnished and factory
wired in accordance with the National Electrical Code and all wiring shall be
terminated in the electric control centre.
Power and starting controls shall include circuit breakers for compressors,
companion trip with 3-phase overload protection, starting contactors for
compressors and condenser fans, and any supplementary overload
protection as may be required.
Compressors for the chillers shall use variable speed drive to ensure the
starting current of each motor does not exceed its full load current.
Relay contacts shall be provided for all units as required for interlocking with
chilled water pumps and other plant as may be indicated on the Employer’s
Drawings.
The Contractor shall provide the compatible high-level interlace from chiller
system to MBMS system.
(ii) Safety controls shall be interlocked with manual reset, master and
auxiliary timers to sequence starting and auxiliary oil pump;
All MCCs and motor control panels in the Chiller MCC Room serving the
chiller plant shall fulfil the voltage dip ride through requirement of 40% rated
voltage for 170 milliseconds. Volt dip ride through time delay circuits shall be
3.9.1 General
(a) The Contractor shall develop a detailed and complete chiller plant
control system for chillers, pumps and associated equipment based
on the requirements of this PTS and submit for review without
objection by the Project Manager. The control system shall be
based on the use of Direct Digital Control (DDC) / Programmable
Logic Controller (PLC) supplemented with electric and electronic
controls.
(c) The chiller plant control program shall be fully editable and set-up via
point and click on a standard windows screen. It shall not require
special software tools or a MBMS technician to operate and modify
chiller sequencing control. The chiller controls shall have high level
interface with the MBMS as stated in the PTS for MBMS. The
operation of the central chiller plant shall be in sequence and
controlled by the chiller plant optimization system.
(d) The following data shall be provided for chiller plant control and
optimization:
(iv) COP;
(ii) A chiller binary output shall control the operation of the chiller
evaporator isolation valve and/or call for pumps operation;
(vii) When called to stop, the chilled water pump shall be allowed
to run for a pre-determined period through a time delay
(adjustable) before closing down, unless the chiller pump is
stopped by an emergency stop. When chilled water flow is
stopped, the motorized valve shall be closed accordingly. The
condensing water flow shall be maintained for a preset time
period (adjustable) before closing the motorized valves at the
seawater cooling supply and discharge pipes.
(viii) In case the chiller fails to start, the failed unit shall be skipped
and disabled and the next lag chiller shall be enabled and
switched on. Audio and visual alarm signal for the failed unit
shall be actuated in the MBMS;
(x) The system shall incorporate a failsafe recycler which runs all
stops switches to the “OFF” position on failure of power. On
resumption of power, the controller shall commence loading
the chillers in normal control steps by means of manual starting
via the chiller controller panel or the MBMS control console as
selectable. Once started, the complete system shall operate
automatically, unless manual operation mode is selected, as
mentioned above. In order to limit the burden on the power
sources, chiller plant control shall incorporate individual timers
with adjustable time delays from 5 minutes to 30 minutes, so
arranged that when the mains power is resumed, the chiller
plant shall only be started by manual means before elapse of
the time delays as measured from the instant when the
corresponding source is available;
(xv) The system control shall maintain the flow fluctuations within
the chiller manufacturer's recommendation;
(xvi) A chiller binary output shall control the operation of the chiller
condenser isolation valve and/or call for pump operation;
(xvii) During cold start-up the condensing water flow through the
chiller shall be modulated as per the manufacturer's
recommendations to maintain no less than the minimum
condenser/evaporator refrigerant pressure differential;
(xviii) The chilled water system set points shall be editable by the
operator; and
(a) The chiller sequencing software will start the chiller system based
upon a graphical calendar time of day scheduling application.
(b) The chiller plant shall start in response to the optimum start, night
setback or timed override operation of any system air handler.
(a) Chiller sequencing for variable primary flow chilled water system
(iii) The lead chiller then starts with the pre-rotation vanes;
(v) For the chiller staging, the first lag chiller will be called for
whenever the system load exceeds the maximum capacity of
the operating chiller for 5 minutes (adjustable) as determined
by flow meters and the chiller water supply & return
temperature of the lead chiller is 95% loaded;
(vi) The second lag chiller will start under the same conditions and
sequences. Whenever a lag chiller starts, all running chillers
load and unload as necessary within 5% of the same percent
load (based on rated current);
(vii) In case the chiller fails to start, the failed unit shall be skipped
and disabled and the remaining unit in the plant which has not
be started will be enabled and switched on. Audio and visual
alarm signal for the failed unit shall be actuated in the MBMS;
(ix) All chillers and pumps will turn OFF when all cooling coil valves
are less than 15% open for 10 minutes or all air handling
equipment is OFF;
(ii) The Contractor shall provide control for the following sequence
to occur automatically when a call is made for the lag chiller to
start:
(1) A current limit set point of 40% shall be sent to all of the
operating chiller control panels. This shall raise the
Leaving Chilled Water Temperature of the operating
chillers away from the low water cutout threshold,
reducing the risk of a nuisance trip due to flow variations
when the lag chiller’s chilled waterside isolation valve is
opened;
(3) The lag chiller shall be started only when its chilled
water side isolation valve is completely open and the
chilled water flow is proven; and
(4) A current limit set point of 100% shall then be sent to all
of the operating chillers.
(iii) On a call for the lag chiller to stop, the following sequence shall
occur:
(ii) When the lag chiller is proven off, the lag chiller's chilled
water isolation valve shall be closed.
(i) The chilled water pump volume control loop shall be enabled
when at least one (1) of the chilled water pump is proven on;
(ii) The chilled water pump volume control loop shall be disabled
when all of the chilled water pumps are proven off;
(iv) The set point for the volume control shall include a 10% safety
factor and shall be calculated as the sum of the design
waterside pressure drop through the coil, plus the design of the
valve pressure drop when the valve is fully open.
(i) The minimum flow control loop shall be enabled when at least
one (1) chilled water pump and one (1) chiller are proven on;
(ii) The minimum flow control loop shall be disabled when all of
the chilled water pumps and all of the chillers are proven off;
(v) The bypass valve shall modulate to the fully open position
whenever the system is shutdown to ensure minimum flow and
prevent the possibility of water hammer wherever a pump is
started; and
(ii) As the flow increases in the bypass line, the chiller plant control
system shall raise the chilled water supply temperature by
0.5ºC (adjustable) for each 15-minute period (adjustable),
provided that the bypass flow control valve is opened for more
than 2% (adjustable) and the total system flow has not
exceeded 125% (adjustable) of the design chiller minimum
flow. These conditions must be continuous for the entire 15-
minute period. If the system flow exceeds 150% of the design
chiller minimum flow for 15 minutes, the chiller plant control
system shall decrease the chilled water supply temperature by
1.0 ºC.
(iii) This calculated chilled water supply temperature reset set point
shall be limited to a minimum value equal to the design set
point of the chilled water supply temperature and a maximum
value of 8 ºC.
(a) Chiller minimum flow bypass line and valve shall be sized to allow for
the manufacturer's recommended minimum flow, with all load control
valves closed, for a chiller in the system.
(b) The "Chiller Minimum Flow Bypass Valve" shall be of the type as
specified in this PTS above.
(c) Following the confirmed start of the lead chiller and whenever the
system is enabled, the chiller sequencing system shall modulate the
"Chiller Minimum Flow Bypass Valve" such that the chilled water flow
through any operating chiller(s) shall not drop below the
manufacturer’s recommended minimum flow.
4.1 GENERAL
4.1.1 This part of the specification covers the provision, testing, installation and
commissioning of the low voltage (LV) primary compressor starter for each
water cooled chiller unit;
4.1.2 The starter shall be a low voltage variable speed drive (VSD) inverter with a
low voltage transformer in mounted in a NEMA-1 enclosure;
(1) All control circuit voltages are physically and electrically isolated from
power circuit voltage;
(2) The instantaneous torque for improved surge control shall be 150%;
4.1.4 The starter shall be equipped with including but not limited to the following
components:
4.1.5 Installation, testing and commissioning procedure shall be laid down by the
equipment manufacturer, and shall be closely adhered to;
4.1.6 The Contractor shall note the following declared requirements for the LV
supply to the starter:
Contract 3403 – Particular Specification 74 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
(a) System nominal voltage: 380 V (r.m.s.) +10%, -2.5%
IEC 60060, IEC 60094–4 Surge diverter for alternating current system
BS 2914
IEC 282, BSEN 60282 Specification for high voltage fuse links for
motor circuit applications
4.3.1 Construction
(a) Automatic shutters which cover the exposed fixed contacts as soon
as the breaker truck is withdrawn shall be provided. The operation of
the shutters for the upper and lower fixed contacts shall be
independent of each other so that each individual set can be manually
opened; and
(b) The busbar shutter shall be painted “Signal Red” and labelled with
“BUSBARS” in large white letters. Circuit shutter shall be painted
“RED” colour.
4.3.3 Earthing
(a) Each starter shall be provided with its own earthing terminal. Earthing
leads shall be provided, one set for each cubicle.
4.3.4 Busbar
(b) The low voltage busbars shall be of minimum rating 630A. The
busbars shall be constructed to withstand any electro-mechanical
stress under normal condition or under fault condition of up to a
maximum fault current to meet CLP’s requirements. All busbars that
Contract 3403 – Particular Specification 77 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
penetrate into the wall partition of adjacent panel shall be insulated
by cast resin wall bushing insulators mounted on the opening of the
partition walls; and
(a) ACB shall comply with B.S. 5227 and 5311 and fitted with current
transformer (CT) and voltage transformer (VT);
(b) ACBs shall be of trip-free, triple pole, totally enclosed, metal clad,
withdrawable, trunk mounting type;
(c) Provision shall be made for disconnection of the ACB from the
busbars by vertical isolation, and removal from the cubicle by
horizontal withdrawal;
(d) The Contractor shall provide three possible positions for the circuit-
breaker trunk:
'Service' Position:
'Test' Position:
'Disconnected' Position:
(a) Each phase end of the secondary winding shall be brought out to
fuses, and the neutral end shall be brought out to insulated links. Each
4.4.1 Variable speed drive (VSD) shall be provided for a voltage input of
380V/3phase/50Hz;
4.4.2 The VSD shall be completely factory-built, assembled, wired, and tested.
When it is necessary to disassemble the units for ease of transportation,
adequate materials and instructions shall be provided by the Contractor for
easy field assembling;
4.4.3 The VSD assembly shall be designed and constructed to allow listing by
Underwriters Laboratory (UL);
4.4.4 The VSD shall vary the compressor motor speed by controlling frequency
and voltage of the electrical power to the compressor motor. The adaptive
capacity control shall automatically adjust motor speed and compressor pre-
rotation vane position independently for maximum part-load efficiency by
analyzing information fed to it by sensors located throughout the chiller;
4.4.6 The VSD shall be unit mounted in a NEMA-1 enclosure with integral fan to
provide cooling for the drive. The fan motors shall be protected by an input
circuit breaker;
4.4.7 The VSD shall also be equipped with, but not limited to the following features:
4.4.8 The VSD shall include all necessary components to protect the VSD and
motor against motor overload, internal faults in either the motor of VSD and
disturbances in the incoming AC line;
4.4.9 The VSD shall comply with the guidelines of IEEE Standard 519-1992 for
total harmonic current and voltage distortion. Total current harmonic
distortion shall not exceed 4% while in operation;
4.4.10 The harmonic filter shall be unit mounted with the same NEMA-1 enclosure
and shall be UL listed. The digital readouts shall be provided as part of filter
package including, but not limited to the following:
4.4.11 The following conditions shall cause the VSD to be shut down with the output
voltage reduced to zero, and the failure shall be annunciated on the
Mechanical Building Management System (MBMS):
4.4.12 The VSD shall be specifically designed to interface with the water chiller
controls and allow for the operating ranges and specific characteristics of the
chiller. The VSD control logic shall optimize chiller efficiency by coordinating
compressor motor speed and compressor inlet guide vane position to
maintain the chilled water set-point while avoiding surge. If a surge is
detected, VSD surge avoidance logic will make adjustments to move away
from and avoid surge at similar conditions in the future; and
Contract 3403 – Particular Specification 81 AA 08/03/19
Appendix F - Particular Technical Specification
Part F3.3 – Mechanical Works
4.4.13 Each VSD shall each be furnished in a NEMA 1 metal enclosure having as
minimum a short circuit withstanding rating of 50,000 amps per UL 508. Each
VSD shall include three phase input lugs plus a grounding lug for electrical
connections, output motor connection via factory installed bus bars and all
components properly segregated and completely enclosed in a single metal
enclosure. The enclosure shall include a pad lockable, door-mounted circuit
breaker with shunt trip and AIC rating of 50,000 amps.
(c) The input current Total Harmonic Distortion (THD) typically less than
3% shall be used;
(d) The transformer and rectifier shall be an integral part of the VSD
assembly along with primary disconnects switch, input vacuum
contactor and secondary fusing eliminating the need for separate
components field installation wiring;
(f) The VSD shall comply with the requirements of IEEE 519 -1992 for
total harmonic input current and voltage distortion measurement and
calculation. Voltage distortion shall not exceed 3% and current
distortion shall not exceed 5% at the input lugs of the VSD over an
operating power range of 30% to 100% of rated power with phase
voltage imbalance per the 3% specification;
(g) The VSD shall be capable of providing rated output for continuous
voltage deviations of +10%;
(i) The VSD shall be able to ride through voltage dips down to 10% of
minimum, such as those experienced during motor starting; and
(j) The VSD 40-second overload current rating shall be set at 105% of
rated compressor current.
(a) All operator VSD displays shall be through the chiller control panel;
(b) The following items will be monitored and displayed in chiller control
panel:
4.6.1 The VSD and the motor shall be protected from the following faults:
(e) Over-voltage;
4.6.2 In case the input reference is lost, automatic operation at minimum speed
shall be applied;
4.6.3 The following VSD status indicators shall be available to facilitate start-up
and maintenance:
5.1 GENERAL
5.1.1 Description
(a) The Central Air Handling Systems Works shall be as shown on the
Employer’s Drawings and shall include, but not limited to:
(ii) Supply and installation of all air registers/air terminals and air
distribution system accessories including manual and
motorized volume control dampers associated with the air
conditioning systems;
(ix) All AHU/PAU local control panels shall fulfill the voltage dip
ride through requirement of 40% rated voltage for 170
milliseconds. Volt dip ride through time delay circuits shall be
included in the local control panels and remote reset shall be
via the MBMS interface as stated in Electrical System of the
Specification.
Primary IAC
(i) Except toilets with single fitment, chilled water FCU(s) with
duct type temperature sensor shall be provided to communal
area, basin area and grouped controlled through MBMS to
maintain the space temperature set point.
(ii) Pre-treated fresh air shall be served by PAU to the fan coil units;
and
(d) LV Switch Room / MCC Room / SES Control Room / UPS Room /TBE
Room
(i) Chilled water FCU(s) or constant air volume AHU with room
thermostat shall be provided for plantrooms and group
controlled through MBMS to maintain the space temperature
set point at 24ºC (Adjustable);
(ii) Pre-treated fresh air shall be provided via PAU serving the fan
coil units;
(vi) All supply air grilles, condensate drain pipes and chilled water
pipes shall not be located directly above electrical equipment
to avoid the risk of condensate dripping; and
(i) Duty and standby chilled water FCU(s) shall be provided and
group controlled through MBMS to maintain the space
temperature set point at 24ºC (adjustable);
(iii) Pre-treated fresh air shall be provided via PAU serving the
BOH Area to the AHU;
(vi) All supply air grilles, condensate drain pipes and chilled water
pipes shall not be located directly above electrical/ electronic
equipment to avoid the risk of condensate dripping; and
(i) Chilled water fan coil unit with wall mounted thermostat shall
be provided to serve and shall be controlled through MBMS to
maintain the space temperature set point at 24ºC;
(ii) Pre-treated fresh air shall be provided via PAU serving the
BOH Area to the fan coil;
(i) Duty chilled water fan coil units with wall mounted thermostat
(with 3-speed and ON/OFF controller) and standby VRF units
shall be provided for the CAD Equipment Room;
(ii) In case of chilled water fan coil units failure, the MBMS shall
switch off the fan coil systems and switch on the standby VRF
(iv) Pre-treated fresh air shall be provided via PAU serving the
room;
(v) Insulated secondary drain pan and drip tray shall be provided
to prevent water damage to electrical equipment;
(vi) Condensate drain pipes and chilled water pipes shall not be
located directly above electrical/ electronic equipment to avoid
the risk of condensate dripping; and
(iv) Condensate drain pipes and chilled water pipes shall not be
located directly above electrical/ electronic equipment to avoid
the risk of condensate dripping; and
(iii) Pre-treated fresh air shall be provided via PAU serving the
room;
(v) All supply air grilles, refrigerant pipes, condensate drain pipes
and chilled water pipes shall not be located directly above
electrical/ electronic equipment to avoid the risk of condensate
dripping;
Backup IAC
(a) AEC Support / PA Room / CCD Room / ADM Room / SOCC/ CMT
Room
(i) Chilled water FCU(s) with wall mounted type thermostat shall
be provided and group controlled through MBMS to maintain
the space temperature set point at 24ºC (Adjustable); and
(ii) Pre-treated fresh air shall be provided via PAU serving the
BOH Area to the fan coil and AHU.
(i) Duty Chilled water compact air handling units & standby VRF
units shall be provided and group controlled through MBMS for
CC78A;
(ii) In case of chilled water compact air handling units failure, all
standby VRF units shall be operated;
(iii) Pre-treated fresh air shall be provided via PAU serving the
room;
(v) Condensate drain pipes and chilled water pipes shall not be
located directly above electrical/ electronic equipment to avoid
the risk of condensate dripping.
6.1 GENERAL
6.1.1 Description
(i) No smoke management system shall be provided for the Backup IAC.
(ii) Smoke management system shall be provided for the Primary IAC.
The Smoke Management System Works is shown on the Employer’s
Drawings and shall include, but not limited to:
(a) The general design and performance requirements for the smoke
control systems shall follow prescriptive code as per FSD CoP.
(b) Dynamic Smoke Control shall be provided for the following areas:
Primary IAC
(c) Make-up air supply for dynamic smoke extraction system shall be
provided by mechanical means to provide not less than 80% of the
smoke extraction rate.
(d) All the smoke extraction fans / makeup air fans and motorized fire and
smoke damper shall be powered by Category 1 essential power. The
smoke control system configuration shall be operated based on the
mode table as shown on the Employer’s Drawings.
(e) Supply air ducts and return air ducts serving for air-conditioning shall
be dual-purpose to provide for both smoke extraction / makeup air.
(f) Smoke extraction discharge locations shall comply with all FSD
requirements for such as separation distance of 5m from other
openings etc.
(h) Upon receiving fire alarm zone signal from a smoke detector or the
actuation of sprinkler flow switch, AFA panel will transmit fire alarm
signal to the smoke extraction system control panel. The smoke
extraction system control panel with control logic function shall
compute and initiate the required mode in accordance with the smoke
control mode table for the smoke control system. Smoke control
modes are to be initiated from the smoke control panel then
transmitted via AFA panel to the smoke control panels in SES Control
Room. The smoke extraction system control panel shall be able to
carry out the manual override function of the smoke control system
by authorized staff / FSD personnel.
(i) The smoke control system shall remain in operation until manually
reset.
(k) The smoke extraction control panel shall be of the same specification
as the fire alarm control and indication panel. The requirements for
the materials associated with the smoke extraction manual override
control panel shall be in accordance with the Specification.
(b) VAC shutdown Method ‘C’ was adopted in the existing/Backup IAC.
The Contractor shall co-ordinate and modify the location of duct
smoke detectors / sprinkler subsidiary valves to trip the relevant
existing and new fans and/or air handling equipment. The Contractor
shall modify the existing VAC manual override control panel and AFA
control system to fulfil the requirements as stated in the FSD COP. In
the event of fire occurring at a specific fire compartment, relevant fans
and air handling equipment serving the respective affected
compartment shall be shut down accordingly.
(a) The Contractor shall be responsible for carrying out hot smoke tests
of the installations in accordance with the FSD requirements. The hot
smoke test shall be carried out in accordance with FSD circular letter
No.2 of 2002 and Australian Standard AS4391-1999. Method
statement and test report shall be prepared and endorsed by a fire
specialist employed by the Contractor and shall be submitted to the
Project Manager for review without objection and FSD for approval.
The size of test fire shall be at least 1MW or of such size as agreed
by FSD.
(b) Test fire locations shall be agreed with FSD prior to commencement
of the hot smoke test shall include, but not limited to the following
locations:
(c) The equipment for hot smoke test shall include, but not limited to, the
following:
(ix) Fuel;
(x) Water;
(d) Prior to instigation of a hot smoke test, preliminary mock-up test shall
be carried out to ensure adequate operation of all installed systems.
(e) The Contractor shall protect (against heat, radiation, tracer smoke
damage) to floor and other building finishes that may be affected by
the hot smoke tests.
(f) A 'thermocouple tree' shall be provided at the test site including data
logger and associated computer to record multiple temperature
readings for the duration of the hot smoke tests.
7.1 GENERAL
7.1.1 Description
(a) Supply and installation of the mechanical ventilation systems for the
Primary IAC and the Backup IAC, including but not limited to exhaust
fans, outside air fans, toilet exhaust fans, ductwork, thermal insulation,
fire rated enclosures, air filtration and treatment systems and
associated works;
(b) Supply and installation of all air registers/air terminals and air
distribution system accessories including manual and motorized
volume control dampers associated with the ventilation system;
(c) Supply and installation of all dampers such as fire dampers, smoke
dampers, motorized smoke and fire dampers and control dampers
associated with the ventilation system;
(d) The Contractor shall provide vent ducts with fire rated enclosures for
lifts and staircases as shown on the Employer’s Drawings to achieve
the required fire rating and to prevent the spread of fire to adjacent
rooms through the vent ducts. The vent ducts shall achieve minimum
120 minutes fire rating requirements for both integrity and insulation.
The Contractor shall check the Architectural Works drawings for fire
compartmentation requirements and provide the necessary fire
proofing installations (e.g. fire rated gaskets, fire rated sealants, fire
rated enclosures etc.) for vent ducts;
(f) Supply and installation of the electrical works and control systems
works (MCC, LCP, power distribution cabling, field equipment wiring,
etc.);
(i) Materials associated with openings through fire barriers and vertical
shaft shall be in accordance with FSD Code of Practice, associated
FSD Circular Letters and Code of Practice for Fire Safety in Buildings
issued by the Buildings Department.
Primary IAC
(i) An exhaust air fan shall be provided for general periodic ventilation
of 5 ACH at normal operation under predetermined time schedule
(Adjustable).
(iii) The mechanical ventilation system shall be shut down in the event
of fire at the room. Any air ducts that pass through the wall of the
rooms serving the rooms shall be provided with motorized smoke
and fire dampers where the dampers shall be closed in the event
of fire.
1) Primary air;
(v) In the event of fire at specific VAC zone, the relevant ventilation
equipment shall be tripped.
(e) Water Pump & Tank Room / FS Tank & Pump Room
(i) Natural ventilation by means of wall louvres (H/L and L/L) plus
fire dampers completed with electro-thermal link shall be
provided for these rooms located aboveground.
(ii) Provisions to the fuel tank room shall follow the requirements
as stipulated by the FSD.
Pre-treated air fed from AHU / PAU with air supply flow rate based on
0.3 L/s.m2 shall be provided for general ventilation.
(ii) The ventilation system shall be shut down in the event of fire
at the room.
Backup IAC
(a) CC78A
(i) An exhaust air fan shall be provided for periodic ventilation of 5 ACH
at normal operation under predetermined time schedule (Adjustable).
(ii) The ventilation system shall be shut down in the event of fire at the
room. Any air ducts that pass through the wall of the rooms serving
the rooms shall be provided with motorized smoke and fire dampers
where the dampers shall be closed in the event of fire.
(iv) The mechanical ventilation system shall be shut down in the event
of fire at the room. Any air ducts that pass through the wall of the
rooms serving the rooms shall be provided with motorized smoke
and fire dampers where the dampers shall be closed in the event of
fire.