TABLE OF CONTENTS
1.0 SCOPE 2
2.0 STANDARDS 2
3.0 PERFORMANCE REQUIREMENT 2
4.0 DRAWINGS 3
5.0 DESIGN AND CONSTRUCTION 3
5.1 CLEARANCES 3
5.2 CORONA 4
5.3 TEMPERATURE RISE 4
5.4 SHORT CIRCUIT WITHSTAND 4
5.5 CONSTRUCTION DETAILS - DISCONNECTOR 4
5.5.1 VOLTAGE TYPES 4
5.5.2 INSULATORS 5
5.5.3 CURRENT CARRYING CAPACITY 5
5.5.4 DISCONNECTOR BLADES 6
5.5.5 PRIMARY CURRENT CARRYING CONTACTS 6
5.5.6 TERMINAL PADS 6
5.5.7 BEARINGS 7
5.6 CONSTRUCTION DETAILS – EARTHING SWITCHES 7
5.7 OPERATING MECHANISM 7
5.7.1 MANUAL OPERATIONS 7
5.7.2 MOTORISED OPERATIONS 7
5.7.3 AUXILIARY SWITCHES 8
5.7.4 INTERLOCKS 9
6.0 TECHNICAL DATA 9
6.1 EQUIPMENT DATA SHEET OF 500kV OUTDOOR DISCONNECTOR
AND EARTHING SWITCHES 9
6.2 EQUIPMENT DATA SHEET OF 275kV OUTDOOR DISCONNECTOR
AND EARTHING SWITCHES 10
6.3 EQUIPMENT DATA SHEET OF 132kV OUTDOOR DISCONNECTOR
AND EARTHING SWITCHES 11
7.0 TESTS 12
The technical specification covers the design and construction for the outdoor
open terminal disconnectors and earthing switches of 3-phase 50 Hz system of
nominal voltage 500kV, 275kV and 132kV.
2.0 STANDARDS
No Standard Description
1 IEC 62271 – 1 High-voltage switchgear and controlgear - Part 1: Common
specifications
(To replace IEC 60694)
2 IEC 62271 – 102 High-voltage switchgear and controlgear - Part 102:
Alternating current switches for rated voltages of 52kV and
above
3 IEC 62271 – 104 High-voltage switchgear and controlgear - Part 104: High
voltage alternating current disconnectors and earthing
switches
4 IEC 60168 Tests on indoor and outdoor post insulators of ceramic
material or glass for systems with nominal voltages greater
than 1 000 V
5 IEC 60865-1 Short-circuit currents - Calculation of effects - Part 1:
Definitions and calculation methods
The disconnector and/or earthing switches shall be designed for operation at the
following primary system voltages, system fault level and insulation level as per
Table 1 below:
4.0 DRAWINGS
Before the work is put in hand, dimensioned drawings and diagrams, as listed
below, showing all details of the plant and materials to be used shall be submitted
to the Engineer for approval.
i. Title Page
ii. Content List
iii. Legend
iv. Component List
v. General Arrangement
vi. Name Plate
vii. External Detail Part of Disconnector
viii. Porcelain Details
ix. Operating Mechanism Cubicle – Internal Arrangement
x. Operating Mechanism Cubicle – External Arrangement
xi. Control Circuit
xii. Terminal Block Arrangement
5.1 Clearances
Electrical Clearance between live metal work and earth shall not be less than
those in the appropriate sections of the latest revision of BS 7354, IEC 60071,
and the clearances given in this Specification. The height from ground to the
Nearest Point Not at Earth potential of all post type or bushing insulators shall
not be less than 2440mm. For equipment when installed, the minimum ground,
safety and other clearances shall be as per Schedule B. The distance from
ground or a working platform such as the climbing bolt of the gantry structure
to the Nearest Live Unscreened Conductor, or to a disconnector arm tip in the
open position, shall satisfy the Minimum Safety Clearance.
5.2 Corona
Each part of the switchgear shall also withstand, without mechanical or thermal
damage, the instantaneous peak currents and rated short time current
pertaining to the rated breaking capacity of the circuit breaker.
Switch operators for the 500kV disconnect switches shall be provided for each
phase mounted on the corresponding structure and shall be electrically group
operated. Switch operators for the 132 & 275kV disconnect switches shall be
grouping operated utilizing a single motor operator with mechanical linkage
connecting all three phases.
132kV disconnector shall be of Range I type as defined in IEC 62271-1 Table 1a.
500kV and 275kV disconnector shall be of Range II type as defined in IEC 62271-1
Table 2a.
Test voltages with respect to isolating distance between the terminals shall be as
specified in this standard.
The insulators shall be wet-process porcelain of the highest grade, dense and
homogeneous. The glaze shall be smooth, hard, dense and uniform and shall
not be affected by weather or sudden change in temperature and salt laden
atmosphere in an area subject to intense lightning storms. The entire porcelain
surface of the insulator that will be exposed after assembly shall be glazed and
shall be relatively free from imperfections. Colour of porcelain surface shall be
dark brown for 275kV and 132kV and grey colour for 500kV.
Porcelain shall be free from defects and thoroughly vitrified and the glaze shall
not be depended upon for insulation. Creepage distances shall be to guidelines
stated in Schedule B, The creepage distance measured from the insulator metal
cap to the base over the insulation cells shall not be less than 20mm per kV of
rated voltage between phases or as specified in Specification, whichever is
higher.
Porcelain shall not engage directly with hard metal and where necessary
approved water and oil resistant yielding material shall be interposed between
the porcelain or glass fittings. All porcelain clamping surfaces shall be of
approved quality applied in an approved manner and shall not be chemically
active with the metal parts or cause fracture by expansion in service. Where
cement is used as a fixing medium, the cement thickness shall be as small and
as even as possible and care shall be taken to correctly centre and locate the
individual parts during cementing.
All fittings and clamps shall be hot-dip galvanized, malleable iron or bronze. The
minimum of zinc coating shall comply to the requirements of ASTM A153 or
approved equivalent. Bolts and nuts shall be galvanized after being threaded.
Excessive zinc shall be removed and the nuts shall run freely (by hand) over the
entire length of the thread. Aluminum fittings and clamps shall not be used.
All insulators and hardware shall operate corona free at rated line-to-line voltages.
It is the intent of this specification that all equipment, materials and fabrication
shall conform to the latest revision of applicable codes and standards. Equivalent
codes, specifications and standards established and approved in the country of
equipment or material manufacture may be subject to TNB approval.
Disconnector shall be designed for live operations and required to switch charging
current of open busbars and bus-transfer load currents shunted by parallel busbar
through bus-coupler circuit breaker.
All disconnector shall be furnished with copper or aluminum alloy live parts.
Copper switch blades shall be hard drawn. Aluminum switch blades shall be
aluminum alloy (E91e BS2895 or equivalent).
All other switch components fabricated of copper and in contact with aluminum
shall be provided with electrical joint compound between the contact surfaces.
Silver shall not be applied directly to aluminum. The silver shall be applied to a
base of copper and then tin plated to prevent the wash of copper salts over
aluminum. Each tenderer shall state the method of silver application they propose
to use in the space provided in the proposal data pages.
The use of welded parts is not allowed on any of the disconnector parts.
For single terminal type, the quantity and arrangement of bolt holes in pad shall be
coordinated with the switch continuous current rating and shall be in accordance
with the following table:
For the cylindrical terminal type, it shall conform to the current ratings of the
disconnector.
The Contractor shall furnish all miscellaneous brackets and bearing supports not
already indicated on the steel structure drawings, and bolting materials needed to
install them on the steel structures. Disconnector bearings other than the thrust
type bearings shall be of the sealed, permanent lubrication type.
The operation of disconnector shall not cause significant movement of the jumper
conductor connected to the terminal pad.
All feeder disconnector shall be fitted with approved three phase line earthing
devices, mechanically coupled or interlocked with the main disconnector so that
the earthing device and disconnector cannot be closed at the same time. The
feeder disconnector and line earthing switches shall be provided with facility to
connect auxiliary contacts for under voltage relays to prevent closing of the
earthing switch even if the line disconnector is open as the line may be
energized from the remote end. The under voltage relays are to be included in
the control panel and to be supplied by the contractor. The earthing contact
shall not be part of the feeder disconnector’s current conducting arm.
All levers, interphase shafts, and operating rods shall be cut to length and
threaded at the factory. All group operator components fabricated of ferrous
materials, excluding operator components mounted in motor operator
enclosures, shall be hot-dip galvanised after fabrication or shall be stainless
steel. All switch interphase-operating pipes shall be of push & pull type at each
phase.
The earthing switches shall be mechanically group operated, except for the 550
kV which shall be individually operated. Manual operating mechanism shall be
located 1 metre above the steel structure base-plate and shall be of the swing
handle or heavy-duty geared crank type with gearbox. Manual operating
mechanism shall not require an operating force greater than 220 Newtons.
Earthing switches shall be manually operated at the local position and any
remote operation of the earthing switch is NOT permitted.
Each operating motor shall be located such that the hub of the manual
operating handle is located 1metre above the steel structure base-plate.
Each operating mechanism shall have provisions for manual operation without
removal or disassembly of the motor operator. Insertion of the manual crank
shall electrically disconnect the motor control circuit and release any limit
stops.
Operating motor shall have sealed bearings with permanent lubrication. The
operating mechanism shall be equipped with external adjustable mechanical
stops.
The component of the control panel shall be fully accessible and preferably
using the swing out type. The door handle(s) must be operable with one hand,
and have provisions for padlocking.
The door shall be of swing out type for access to all components inside the
mechanism. Sliding type cover shall not be accepted.
This manual operation shall not require an operating force greater than 220
Newton.
Each motor operated switch shall be provided with a set of reliable wiping
contact type of auxiliary switch assembly mounted to the operating rod. Cam
actuated type must be adjusted and locked at the factory by suitable means. The
use of plastic cam is not permitted. This auxiliary switch shall be mounted in a
weatherproof housing with a cable gland plate for installing cable to the
auxiliary switch contacts.
The auxiliary switch shall function with the operating mechanism at all times,
either in the motor or manual (crank) mode of operation.
The number of auxiliary switch contacts (normally open and normally close)
shall be in accordance to TNB approved scheme.
Over-current protection shall be provided for both motor control and heater
circuits utilizing molded case circuit breakers on each circuit. The motor
contactors shall be mechanically or electrically interlocked to prevent
simultaneous energisation of both contactors.
5.7.4 Interlocks
All disconnector and earthing switches shall be provided with continuously rated
solenoid bolt-type electrical interlock system rated at 125 V d.c. All these
interlocks shall be of fail safe type. Suitable individual interlocking arrangements
shall be provided. The mechanical interlocking system shall be between line
disconnector and earth switches.
6.1 Equipment Data Sheet of 500kV Outdoor Disconnector and Earthing Switches
Rated Voltage :
Nominal : Un kVrms 500
Maximum : Um kVrms 550
6.2 Equipment Data Sheet of 275kV Outdoor Disconnector and Earthing Switches
Rated Voltage :
Nominal : Un kVrms 275
Maximum : Um kVrms 300
6.3 Equipment Data Sheet of 132kV Outdoor Disconnector and Earthing Switches
Rated Voltage :
Nominal : Un kVrms 132
Maximum : Um kVrms 145
o
Temperature Rise C IEC 62271-1 Clause 4.4.2 & Table 3
7.0 TESTS
Type Tests, Routine Tests, Additional Test and Site Acceptance Tests shall be
referred to Product Testing and Inspection document (TTS – SS – TEST).