Professional Documents
Culture Documents
Abstract— This work studies the changes that occur in failure of the step-up transformers that connect the wind
transformer insulation properties when voltages with steep fronts turbine generators to the distribution networks has occurred as
and high-frequency contents are applied. With a significant early as two years after their installation; or in other cases the
growth in the number of wind-farms and solar-plants that use dissolved gas contents in oil have reached significantly high
power-electronic-based converters, the problems associated with levels.
such voltages on insulation has led to increasing concerns.
Distorted voltages accelerate the transformer insulation Distorted voltages with high-frequency contents might
degradation. Two identical transformers are studied by affect the transformers in three ways: internal resonances
energizing independently under power frequency sinusoidal and between conductive parts [3], travelling of voltage surge along
width-modulated pulse trains. The dielectric characteristics of the windings [4] and the steeply-raised voltages affecting
the test objects, like partial discharge activities, insulation dielectric parts intensively [5]. Although, these phenomena are
resistance, are periodically measured during the ageing process. discussed in earlier studies about the motors and cables; no
After a period of 500 hours of testing the dissolved gases are also studies have evaluated the effect of distorted voltages on
analyzed. The results for both transformers are compared and transformer insulation materials, as per the authors’ knowledge.
discussed. For transformers, generally, studies on the influences of voltage
and current distortion are limited to low-order harmonics which
Keywords- transformer; insulation; dielectric properties;
are generated by distorted loads or by the mal functioning of
renewable energies; high-frequency voltage; ageing
generators.
I. INTRODUCTION This paper examines the influence of distorted voltage
waveforms due to voltage converter operations on the dielectric
Transformers are one of the most complicated apparatuses properties of transformer insulation. To evaluate the effect of
in the power grid. Their insulation system is a composition of such high-frequency voltages on the transformer, two identical
both liquid and solid materials which embrace the energized transformers were subjected to stresses from two different
windings and grounded core. This convoluted geometry of types of voltages. Both transformers were connected to the
different dielectric and conductive parts results in a large same type of loads; while one was fed with a sinusoidal voltage
network of partial capacitances, inductances and resistances. waveform and the other with distorted voltages generated by a
In addition to the conventional stresses on transformer voltage-sourced converter. A variety of different parameters
insulation systems caused by transient voltages, repetitive such as the insulation resistance, polarization index, dissolved
voltage pulses are a concern for transformers connected to the gas analysis (DGA), dissipation factor, winding temperature
renewable energy plants. The inverters in renewable energy and partial discharge (PD) can be considered as indicators of
plants generate width-modulated pulse trains with very high transformer insulation conditions. Of these factors, PD
slew rates (up to 50 kV/µs) and frequency (10-50 kHz) [1]. measurement and DGA are frequently used in the assessment
Although these pulses are being created during generation of transformer wellness [6]. In this research, these two
(renewable energy plants) and consumption (power-electronics parameters along with the insulation resistance have been
loads), the step-up transformers that are installed in wind-farms measured periodically during the ageing process. The results
and solar-plants with voltage-sourced converters are the are compared to observe which properties are more affected by
components that are more severely exposed to high-frequency high-frequency voltages and how much the ageing process is
noises and impulse trains. accelerated under distorted voltage waveforms.
The adverse effects on the performance of power system
components such as transformers, cables and accessories in the II. TEST TRANSFORMERS AND EXPERIMENTAL
presence of fast transients and high frequency components PROCEDURES
have been reported recently [2]. Further, transformer failures Two identical oil-filled transformers were designed and
have been documented by wind-farm developers. In specific, constructed for ageing studies, following the standard
ageing. 0
the two test specimens, using two separate sources. Source-1 is -200
236
Dissolved gas analysis has been accepted as the industry
standard for the determination of incipient faults in
transformers. Table II shows a comparison of different gas
quantities in oil, generated by different types of faults. It is
important to document the trend of the variation of different
gases during the ageing. For instance, if at a certain time two
transformers have the same quantities of hydrogen, but in one
transformer, the gas content level has increased gradually, and
in the other, in a short period of time; then the latter
transformer would be in a worse condition than the former one.
B. Insulation Resistance
Insulation resistances of both transformers were measured
at three stages of the ageing and using two different winding
IV. RESULTS AND DISCUSSION connection arrangements. The arrangements and their
corresponding values ( at 24° C) are shown in Table IV.
Results of the ageing process tests are presented here in
four sections: partial discharge activities, insulation resistance,
dissolved gas analysis, and oil temperature. TABLE IV. MEASURED INSULATION RESISTANCES
C. Oil Temperature
TABLE III. PD TEST RESULTS
While the ambient temperature of the test setup was
PD values of Inverter- PD values of Power- maintained steady at 24° C, oil temperature was measured
Ageing Time
fed transformer grid-fed transformer during the ageing. The average oil temperature reading after
(hours)
@10 kV @10 kV
0 (initial) every 100-hour period is presented in Table V.
12 pC 8 pC
100 76 pC 11 pC
200 350 pC 13 pC
500 7.5 nC 21 pC
237
TABLE V. MEASURED OIL TEMPERATURES V. CONCLUSION
Oil temperature Oil temperature This ageing experiment on two identical oil-filled
Ageing Period (Inverter-fed (Power-grid-fed
transformer) transformer)
transformers energized with different voltages for 500 hours
has led to the following conclusions:
0-100 31°C 29°C
The exposure of the transformer to a high-frequency
100-200 34°C 30°C distorted voltage has a strong influence on transformer
200-300 37°C 33°C insulation properties.
300-400 37°C 34°C Of the measured parameters, PD activities showed the
highest changes during the ageing under distorted
voltages.
D. Dissolved gas analysis
Variations in the measured values confirm that a severe
Fig. 5 and Fig. 6 respectively show the results of DGA for degradation in the insulation system of the inverter-fed
both the power-grid-fed and inverter-fed transformers. The transformer has occurred.
gases were extracted from the oil and analyzed using the flame
ionization detection technique as per ASTM D3612 standard The relatively high content of acetylene in the oil from
test method. The result for the transformer energized by pure inverter-fed transformer could be caused by internal
AC voltage shows only air gases. The inverter-fed transformer low-power arcing.
oil has higher H2, CO, CH4, CO2, C2H4 and C2H2. Thus, there
are more fault gases present indicating that this transformer is The transformer which was energized with power
closer to failure than the other. The gas of real concern is C2H2, frequency AC voltage showed nearly no changes in its
because its level is above the threshold warning level. The dielectric properties.
other gas contents are still below the warning levels.
ACKNOWLEDGMENT
The financial support from the Natural Sciences and
Engineering Research Council is acknowledged. The help from
Moloney Electric Inc. in supplying the sample transformers and
from Kinectrics Inc. in oil sample analysis is appreciated.
REFERENCES
[1] Nagel, M.; Leibfried, T., "Investigation on the high frequency, high
voltage insulation properties of mineral transformer-oil," Electrical
Insulation and Dielectric Phenomena, 2006 IEEE Conference on , vol.,
no., pp.226,228, 15-18 Oct. 2006.
[2] Y. Weijun, "Failure mechanism of winding insulations in inverter-fed
motors", IEEE Electr. Insul. Mag., Vol. 13, n. 6, pp. 18-23, 1997. K.
Elissa, “Title of paper if known,” unpublished.
[3] D. Fabiani, G. C. Montanari, and A. Contin, "Aging acceleration of
insulating materials for electrical machine windings supplied by PWM
Figure 5. DGA result of power-grid-fed transformer in the presence and in the absence of partial discharges", IEEE 7th
Intern. Conf. Solid Dielectrics, (ICSD),Cat. No.01CH37117, Eindhoven,
Netherlands, pp. 283-286, 2001.
[4] J.P. Bellomo, P. Castelan, and T. Lebey, “The effect of pulsed voltages
on dielectric material properties,” IEEE Trans on Diel. and El. Ins., vol.
6, no. 1, Feb. 1999, pp. 20-26.
[5] Moradi, M.; Gholami, A., "Transformer condition assessment via oil
quality parameters and DGA," Condition Monitoring and Diagnosis,
2008. CMD 2008. International Conference on , vol., no., pp.993,999,
21-24 April 2008.
[6] K. D. Wolter, J. F. Johnson, and J. Tanaka, "Polymer Degradation and
Its Measurement", in Engineering Dielectrics, Vol. II B, R. Bartnikas,
Ed., pp. 408-9, 1987.
238