Introduction REV A
Applications:
This document is for the following models:
GR-12/15/20
GRC-12
Observe and Obey: QS-12/15/20
This procedure shall be completed by a person GS-30/32/46
trained and qualified on the repair of this
machine. GS-46AV
REV A
Procedure
Software Version 2 Press the ground control scroll down button.
Note: Before proceeding verify the version of Result: The GCON LCD will indicate the
software installed on your machine. The software revision and hour meter information.
software revision is displayed at the GCON After 5 seconds, the ground controls LCD will
LCD. return to machine model and hour meter
information.
1 Pull out the red Emergency Stop buttons at
both the GCON and the PCON. At the GCON
turn the key switch to ground controls. SOFTWARE REV
Result: The display at the platform controls will 00000.0 Hours
show "CH".
=+ -
=+ -
PROCEDURE REV A
a GCON LCD
b escape button
c enter button
REV A PROCEDURE
4 Locate the diagnostic port on the side of the 7 Launch a web browser such as Internet
GCON. Remove one of the fasteners securing Explorer ® or Firefox ® on your PC or laptop.
the cover and set aside. Loosen the other Type in the IP address from step 6 into the web
fastener. Do not remove it. browser address bar and press enter.
Result: The following screen will be displayed.
a diagnostic port
8 Select the Choose File tab and navigate to the
5 Connect one end of a CAT5 Ethernet cable into
downloaded Genie Flash File (.gff).
the diagnostic port. Connect the other end into
a PC or laptop. Note: Verify it is the correct flash file.
Result: The GCON LCD will display the 9 Select the Load Flash File button to verify the
following screen. file is a .gff file.
Result: The following screen will be displayed.
OPEN WEB BROWSER
<IP ADDRESS>
PROCEDURE REV A
10 Select the Reprogram Device (s) button to If you have any further questions regarding these
start the ECM software update. instructions or need assistance, please contact the
Genie Service Department at one of the following
Result: The following screen will be displayed
telephone numbers:
after the software update is complete.
United States: 800-536-1800
Note: Do not turn off power while the ECM is
being reprogrammed. Canada: 425-881-1800
12 Push in the red Emergency Stop button and All other locations 001-425-881-1800
disconnect the CAT5 cable from the GCON.
13 Secure the diagnostic port cover using the
retaining fasteners removed in step 4. Do not
over tighten.
14 Perform function test. Refer to the Operator's
Manual on your machine.
15 Return the machine to service.
REV A PROCEDURE
Machine Application Mode 4 Connect one end of a CAT5 Ethernet cable into
the diagnostic port. Connect the other end into
1 Open the GCON compartment. a PC or laptop.
Note: Some models will require opening the Result: The GCON LCD will display the
ground control box to access the GCON. following screen.
2 Turn the key switch to the GCON or PCON
position. Pull out the red Emergency Stop
buttons to the on position at the GCON and
OPEN WEB BROWSER
PCON. <IP ADDRESS>
Result: The display at the platform controls will
show "CH".
5 Read and record the IP address.
= + -
= + -
Note: The display will only show the IP address for
3 seconds. Press the scroll up button to
display the IP address again for another 3
seconds.
6 Launch a web browser such as Internet
3 Locate the diagnostic port on the side of the
Explorer ® or Firefox ® on your PC or laptop.
GCON. Remove one of the fasteners securing
Type in the IP address from step 5 into the web
the cover and set aside. Loosen the other
browser address bar and press enter.
fastener. Do not remove it.
Result: The following screen will be displayed.
a diagnostic port
PROCEDURE REV A
7 Enter the following username and password 9 Select the Update Machine Software button.
then select OK.
Result: The following screen will be displayed.
Note: The username and password are case
sensitive.
Username: smart.link
Password: SL1000
Result: The following screen will be displayed.
REV A PROCEDURE
12 Select the Reprogram Device (s) button to If you have any further questions regarding these
start the ECM software update. instructions or need assistance, please contact the
Genie Service Department at one of the following
Result: The following screen will be displayed
telephone numbers:
after the software update is complete.
United States: 800-536-1800
Note: Do not turn off power while the ECM is
being reprogrammed. Canada: 425-881-1800
14 Push in the red Emergency Stop button and All other locations 001-425-881-1800
disconnect the CAT5 cable from the GCON.
15 Secure the diagnostic port cover using the
retaining fasteners removed in step 3. Do not
over tighten.
16 Perform function test. Refer to the Operator's
Manual on your machine.
17 Return the machine to service.