You are on page 1of 6

Mounting Type DVC5010 or DVC6010

Installation Instructions
Digital Valve Controllers on Fisher
November 2004 Type 657 and 667 Actuators
SCREW
(KEY 105)

CONNECTOR
ARM
(KEY 108)
WASHER
(KEY 156)

O-RING
(KEY 60)
CAP SCREW ALIGNMENT PIN
(KEY 120) (KEY 46) CAP SCREW
(KEY 59)
ADJUSTMENT ARM
(KEY 106)

MACHINE SCREW
(KEY 109)
MACHINE SCREW
(KEY 103)

SHIELD
(KEY 102)

PLAIN WASHER PIPE PLUG


(KEY 126) (KEY 61)

LOCK WASHER
(KEY 110)
APPLY LUB, SEALANT
44B1852-C

Figure 1. Type DVC5010 or DVC6010 Digital Valve Controller with Integrally Mounted Filter Regulator
Yoke-Mounted on Type 657/667 Size 30-60 Actuator

Use these instructions to mount a FIELDVUEr Type D Use bypass valves or completely
DVC5010 or DVC6010 digital valve controller on shut off the process to isolate the
Fisher Type 657 and 667 actuators. valve from process pressure. Relieve
process pressure from both sides of
the valve. Drain the process media
WARNING from both sides of the valve.

Avoid personal injury or property D Vent the pneumatic actuator


damage from sudden release of loading pressure and relieve any
process pressure or bursting of parts. actuator spring precompression.
Before performing any maintenance
operations: D Use lock-out procedures to be
sure that the above measures stay in
D Always wear protective clothing effect while you work on the
and eyewear. equipment.
D Disconnect any operating lines
providing air pressure, electric power, D Check with your process or safety
or a control signal to the actuator. Be engineer for any additional measures
sure the actuator cannot suddenly that must be taken to protect against
open or close the valve. process media.
D300925X012 11/2004

www.Fisher.com
Mounting Type DVC5010 or DVC6010
Digital Valve Controllers on Fisher Installation Instructions
Type 657 and 667 Actuators November 2004

SPACER WASHER
(KEY 148) (KEY 149)
CAP SCREW
(KEY 155)

MACHINE SCREW
(KEY 109)

WASHER
ADJUSTMENT ARM (KEY 126)
(KEY 106)
LOCK WASHER
CONNECTOR ARM (KEY 110)
(KEY 108)

27B6723-A

Figure 2. Type DVC5010 or DVC6010 Digital Valve Controller Mounted on Type 657/667 Size 34- 60 Actuator
with Side-Mounted Handwheel

Mounting on Size 30 - 60 Actuators D On actuators without side-mounted handwheel,


refer to figure 1.
Refer to figures 1 and 2 for mounting parts
identification. Refer to the FIELDVUE DVC5000
Series Digital Valve Controllers Instruction Manual - a. Remove one of the stem connector screws.
Form 5335 for DVC5010 digital controller parts Insert one of the cap screws (key 120) included in
identification, and the FIELDVUE DVC6000 Series the kit through the connector arm (key 108) and
Digital Valve Controllers Instruction Manual - Form start it in the stem connector. Tighten the screw
5647 for DVC6010 digital valve controller part so that the stem connector clamps the valve and
identification. Refer to the appropriate actuator actuator stems but still permits the connector arm
instruction manual for actuator installation, to be moved.
operation, maintenance and parts identification.

1. Isolate the control valve from the process line b. Remove the second stem connector screw.
pressure, release pressure from both sides of the Swing the connector arm into place and start the
valve body, and drain the process media from both second screw (key 120) from the kit. Tighten both
sides of the valve. Shut off all pressure lines to the screws.
actuator, releasing all pressure from the actuator.
Use lock-out procedures to be sure that the above
measures stay in effect while you work on the D On actuators with side-mounted handwheel
equipment. refer to figure 2. Loosen the lock nut below the travel
disc. Insert the connector arm beneath the travel
2. Attach the connector arm (key 108) to the valve disc and tighten the lower lock nut against the
stem as follows: connector arm.

2
Mounting Type DVC5010 or DVC6010
Installation Instructions Digital Valve Controllers on Fisher
November 2004 Type 657 and 667 Actuators
3. The parts referenced in this step are part of the 6. Apply lubricant (key 63) to the pin of the
digital valve controller. Refer to the digital valve adjustment arm (key 106). Place the pin into the slot
controller instruction manual for parts identification. of the feedback arm so that the bias spring loads the
Attach the mounting bracket (key 107) to the digital pin against the side of the arm with the valve travel
valve controller housing with screws (key 104). markings.
4. Attach the digital valve controller to the actuator 7. Install the external lock washer (key 110) on the
as follows: adjustment arm. Position the adjustment arm in the
slot of the connector arm (key 108) and loosely
D On actuators without side-mounted handwheel: install the washer (key 126) and screw (key 109).
a. Loosely install a hex flange screw (key 105) in 8. Slide the adjustment arm pin in the slot of the
the right hole of the lower actuator mounting feedback arm until the pin is in line with the desired
boss. valve travel marking. Tighten the screw (key 109).
9. Remove the alignment pin (key 46) and store it in
b. Position the digital valve controller so the hole the module base next to the I/P assembly.
in the mounting pad of the mounting bracket goes
onto the mounting screw (key 105). Slide the 10. Attach the shield (key 102) with two screws (key
digital valve controller to the left to expose the left 103).
hole. Install the left screw (key 105). Tighten both
screws (key 105). For additional information concerning mounting,
setup, calibration and maintenance, refer to the
FIELDVUE DVC5000 Series Digital Valve
D On actuators with side-mounted handwheel:
Controllers Instruction Manual - Form 5335 for
DVC5010 digital controllers, and the FIELDVUE
a. Insert a cap screw (key 155) through a washer
DVC6000 Series Digital Valve Controllers Instruction
(key 149) and spacer (key 148). Loosely install
Manual - Form 5647 for DVC6010 digital valve
the cap screw in the right hole of the lower
controllers.
actuator mounting boss.

b. Position the digital valve controller so the hole


in the mounting pad of the mounting bracket goes
onto the mounting screw (key 155). Be sure the
washer is between the screw head and the
mounting bracket.
Mounting on Size 70 - 100
Actuators
c. Slide the digital valve controller to the left to
align the left hole in the mounting bracket with the Refer to figure 3 for mounting parts identification.
left hole in the actuator yoke. Refer to the FIELDVUE DVC5000 Series Digital
Valve Controllers Instruction Manual - Form 5335
d. Place the second spacer (key 148) between for DVC5010 digital controller parts identification,
the actuator yoke and the mounting bracket. and the FIELDVUE DVC6000 Series Digital Valve
Insert the left screw (key 155) with washer (key Controllers Instruction Manual - Form 5647 for
149) through the hole in the mounting bracket DVC6010 digital valve controller part identification.
and spacer. Tighten both screws (key 155). Refer to the appropriate actuator instruction manual
for actuator installation, operation, maintenance and
parts identification.
Note
1. Isolate the control valve from the process line
The alignment pin (key 46) is stored pressure, release pressure from both sides of the
inside the digital valve controller valve body, and drain the process media from both
housing. It is located above the supply sides of the valve. Shut off all pressure lines to the
pressure gauge. actuator, releasing all pressure from the actuator.
Use lock-out procedures to be sure that the above
5. Set the position of the feedback arm on the digital measures stay in effect while you work on the
valve controller by inserting the alignment pin (key equipment.
46) through the hole on the feedback arm marked
‘‘A’’ for Type 667 actuators or the slot marked ‘‘B’’ for 2. Attach the connector arm (key 108) to the valve
Type 657 actuators. stem connector.

3
Mounting Type DVC5010 or DVC6010
Digital Valve Controllers on Fisher Installation Instructions
Type 657 and 667 Actuators November 2004

SCREW
(KEY 105)

BIAS SPRING
(KEY 78)

ADJUSTMENT O-RING
ARM (KEY 106) (KEY 60)
HEX NUT
(KEY 100) CAP SCREW
(KEY 59)
FEEDBACK ARM
EXTENSION MACHINE SCREW
(KEY 97) (KEY 103)
MACHINE SCREW
MACHINE SCREW (KEY 99)
(KEY 98)
SPACER
LOCK WASHER (KEY 101)
(KEY 110)
SHIELD
MACHINE SCREW (KEY 102)
(KEY 109) PIPE PLUG
(KEY 61)
ALIGNMENT
WASHER CONNECTOR ARM PIN (KEY 46)
(KEY 156) (KEY 108)
LOCK
WASHER (KEY 162)
APPLY LUB, SEALANT PLAIN WASHER
43B8442-C
(KEY 126)

Figure 3. Type DVC5010 Digital Valve Controller with Integrally Mounted Filter Regulator Yoke-Mounted on
Type 657/667 Size 70-100 Actuator

3. Refer to figure 3. If valve travel exceeds 2 inches, Note


a feedback arm extension (key 97) is required.
Remove the bias spring (key 78) for up to 2-inch The alignment pin (key 46) is stored
travel from the feedback arm. Attach the bias spring inside the digital valve controller
(key 78) for up to 4-inch travel to the feedback arm housing. It is located above the supply
extension. Attach the feedback arm extension to the pressure gauge.
feedback arm with screw (key 98), screw (key 99), 6. Set the position of the feedback arm on the digital
spacer (key 101), lock washers (key 162), and hex valve controller by inserting the alignment pin (key
nuts (key 100). Remove the pipe plug from the 46) through the hole on the feedback arm marked
output connection on the back of the housing, apply ‘‘A’’ for Type 667 actuators or the slot marked ‘‘B’’ for
sealant (key 64), and reinstall it in the output Type 657 actuators.
connection on the side of the housing.
7. Apply lubricant (key 63) to the pin of the
4. Loosely install a hex flange screw (key 105) in adjustment arm (key 106). Place the pin into the slot
the right hole of the lower actuator mounting boss. of the feedback arm so that the bias spring loads the
pin against the side of the arm with the valve travel
markings.
5. Position the digital valve controller so the hole in
the mounting pad of the mounting bracket goes onto 8. Install the external lock washer (key 110) on the
the mounting screw (key 105). Slide the digital valve adjustment arm. Position the adjustment arm in the
controller to the left to expose the left hole. Install the slot of the connector arm (key 108) and loosely
left screw (key 105). Tighten both screws (key 105). install the washer (key 126) and screw (key 109).

4
Mounting Type DVC5010 or DVC6010
Installation Instructions Digital Valve Controllers on Fisher
November 2004 Type 657 and 667 Actuators
9. Slide the adjustment arm pin in the slot of the Note
feedback arm until the pin is in line with the desired
valve travel marking. Tighten the screw (key 109). Emerson Process Management does
not assume responsibility for the
10. Remove the alignment pin (key 46) and store it
selection, use, or maintenance of any
in the module base next to the I/P assembly.
product. Responsibility for the
11. Attach the shield (key 102) with two screws (key selection, use, or maintenance of any
103). On Type 657 or 667 size 70-100 actuators, Fisher product remains solely with the
start the screws before installing the shield. purchaser and end-user.
For additional information concerning mounting,
setup, calibration and maintenance, refer to the
FIELDVUE DVC5000 Series Digital Valve
Controllers Instruction Manual - Form 5335 for
DVC5010 digital controllers, and the FIELDVUE
DVC6000 Series Digital Valve Controllers Instruction
Manual - Form 5647 for DVC6010 digital valve
controllers.

5
Mounting Type DVC5010 or DVC6010
Digital Valve Controllers on Fisher Installation Instructions
Type 657 and 667 Actuators November 2004

Fisher and Fisher are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of
Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy,
they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use
or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper
selection, use and maintenance of any Fisher product remains solely with the purchaser and end user.

Emerson Process Management


Fisher
Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
www.Fisher.com

6
EFisher Controls International LLC 1998, 2004; All Rights Reserved Printed in USA