You are on page 1of 19

This Technical Booklet has been prepared by Products conforming with a European

the Department of the Environment for Council Directive


Northern Ireland and provides for certain
methods and standards of building which, if Any product designed and manufactured to
comply with the requirements of a European
followed, will satisfy the requirements of the
Council Directive does not have to comply with
Building Regulations (Northern Ireland) 2000
any other standard or part of a standard,
("the Building Regulations"). whether British, International or other, which
relates to the same characteristic or specific
There is no obligation to follow the methods or
purpose as the EC Directive.
comply with the standards set out in this
Technical Booklet. CE marked construction products
If you prefer you may adopt another way of Any construction product (within the meaning
meeting the requirements of the Building of the Construction Products Directive) which
Regulations but you will have to demonstrate bears a CE marking shall be treated as if it
that you have satisfied those requirements by satisfied the requirements of any appropriate
other means. British Board of Agrement Certificate, British
Standard or British Standard Code of Practice
Other regulations relating to such a product, where the CE marking
relates to the same characteristic or specific
This Technical Booklet relates only to the purpose as the Certificate, Standard or Code
requirements of Regulations K2 and K3. The of Practice.
work will also have to comply with all other
relevant Building Regulations. Testing of materials and construction
British Standards and European Where for the purposes of this Technical
Technical Specifications Booklet testing is carried out it shall be carried
out by an appropriate organisation offering
In this introduction and throughout this suitable and satisfactory evidence of technical
Technical Booklet any reference to a British and professional competence and
Standard shall be construed as a reference independence. This condition shall be satisfied
to- where the testing organisation is accredited in
(a) a British Standard or British Standard Code a Member State of the European Economic
of Practice; Area in accordance with the relevant parts of
the EN 45000 series of standards for the tests
(b) a harmonised standard or other relevant
standard of a national standards body of any carried out.
Member State of the European Economic Area;
(c) an international standard recognised for
use in any Member State of the European
Economic Area;
(d) any appropriate, traditional procedure of
manufacture of a Member State of the
European Economic Area which has a
technical description sufficiently detailed to
permit an assessment of the goods or
materials for the use specified; or
(e) a European Technical Approval issued in •
accordance with the Construction Products
Directive,
provided that the proposed standard, code of
practice, specification, technical description or
European Technical Approval provides, in use,
equivalent levels of safety, suitability and
fitness for purpose as that provided by the
British Standard.

1
Materials and workmanship Reference
Any work to which a requirement of the Any reference in this Technical Booklet to a
Building Regulations applies must, in publication shall, unless otherwise stated, be
accordance with Part B of the Building construed as a reference to the edition quoted,
Regulations, be carried out with suitable together with amendments, supplements or
materials and in a workmanlike manner. You addenda thereto current at 31 January 1998.
can comply with the requirements of Part 6 by
following an appropriate British Standard or
you may demonstrate that you have complied
with those requirements by other suitable
means, such as an acceptable British Board of
Agrément Certificate, Quality Assurance
Scheme, Independent Certification Scheme or
Accredited Laboratory Test Certificate.

Diagrams
The diagrams in this Technical Booklet
supplement the text. They do not show all the
details of construction and are not intended to
illustrate compliance with any other
requirement of the Building Regulations. They
are not necessarily to scale and should not be
used as working details.

Page
Section 1 General 3

Section 2 Domestic buildings 5

Section 3 Non-domestic buildings 8

Section 4 Ventilation of car parks 11

2
1.1 This Section gives the definitions and Passive stack ventilation (PSV) – a
general provisions relating to the ventilation of ventilation system using a duct from the ceiling
domestic and non-domestic buildings. of a room to a terminal on or above the roof,
which operates by a combination of the natural
Definitions stack effect (i.e. the movement of air due to the
difference in temperature between inside and
1.2 In this Technical Booklet the following
outside) and the effect of wind passing over
definitions apply –
the terminal.
Background ventilation – ventilation by
Rapid ventilation – ventilation by means of a
means of a small adjustable ventilation
large adjustable ventilation opening (e.g. a
opening (e.g. a trickle ventilator) some part of
window), some part of which is not less than
which is not less than 1.75 m above floor level
1.75 m above floor level, and which allows the
and the sole purpose of which is to provide
movement of a substantial volume of air in a
controllable ventilation at a low rate.
short period of time.
Bathroom – a room containing a bath or
Sanitary accommodation – sanitary
shower whether or not it also contains other
accommodation has the meaning assigned to it
sanitary appliances.
by Regulation P1.
Common space – a space in a non-domestic
Utility room – a room used for laundry
building where people are expected to gather
purposes which contains a sink, washing
in large numbers such as shopping malls,
machine, tumble drier or similar moisture
foyers and similar common spaces but shall
producing equipment and which is not entered
not include spaces used solely for circulation.
solely from outside the building.
Enclosed place – a verandah, conservatory or
Ventilation opening – any part of a window, or
similar place which is ventilated directly to the
any hinged panel, adjustable louvre or other
external air.
means of ventilation which opens directly to
the external air or to an enclosed place, but
Habitable room – has the meaning assigned
does not include any opening associated with
to it by Regulation A2 but does not include a
a means of mechanical ventilation.
room intended to be used for the lawful
detention of any person other than a person of
unsound mind.

Mechanical extract ventilation – a system of


ventilation operated by a power driven
mechanism which extracts air from a room and
discharges it only to the external air.

Mechanical supply ventilation – a system of


ventilation operated by a power driven
mechanism which supplies fresh air from
outside the building to a room or space within
the building.

Occupiable room – a room in a non-domestic


building occupied as an office, workroom,
classroom, hotel bedroom or similar room but
does not include a bathroom, utility room,
sanitary accommodation or rooms or spaces
used solely or principally for circulation,
building services plant or storage purposes.

3
Ventilation of sanitary accommodation To minimise the risk of spillage of flue gases,
mechanical extract ventilation –
1.3 Where sanitary accommodation contains a
cubicle or cubicles constructed so as to allow (a) shall not be provided in the same room as
free circulation of air throughout the room or a solid fuel burning appliance;
space, then the provisions shall apply to the (b) shall only be provided in the same room as
room or space as a whole and not to the an oil fired pressure jet appliance when the
cubicle or cubicles separately. installation complies with OFTEC Technical
Information Note TV112. [Technical Information
Interaction of mechanical extract Note TV112 is available from the Oil Fired
ventilation and open-flued heat Technical Association for the Petroleum
producing appliances Industry ( OFTEC ), Century House, 100 High
1.4 Mechanical extract ventilation can cause Street, Banstead, Surrey, SM7 2NN]; and
spillage of flue gases from heat producing (c) extracting at a rate greater than
appliances. The problem is mainly with open- 20 litres/second, shall not be provided in the
flued appliances which rely on natural draughts same room as a gas fired appliance.
for their air supply, but it can also occur with ( BS 5440 : Part 1, Clause 4.3.2.3. both
fan assisted appliances. The installation of recommends and gives a method for a spillage
heat producing appliances is controlled by test for gas fired appliances for use whether or
Part L and they must be able to operate safely not the mechanical extract ventilation and the
whether or not the mechanical extract combustion appliance are in the same or
ventilation is operating. different rooms.)

4
2.1 This Section gives provisions for the Ventilation of rooms direct to external
natural ventilation of rooms in domestic air
buildings and the mechanical ventilation of
2.2 In a domestic building, any habitable room,
internal kitchens, utility rooms, bathrooms and
kitchen, utility room, bathroom and sanitary
sanitary accommodation in an otherwise
accommodation ventilated direct to external air
naturally ventilated domestic building.
shall have ventilation provisions in accordance
with Table 2.1.

Notes to Table
(1) Where a room serves a combined function such as a kitchen-diner, the individual provisions for rapid, background
and mechanical extract ventilation need not be duplicated provided that the greater or greatest provision for the
individual functions in Table 2.1 is made.
(2) As an alternative to the background ventilation provisions listed in Table 2.1, background ventilation openings
equivalent to an average of 6000 mm2 per room may be provided but no room shall have a background ventilation
opening of less than 4000 mm2.
(3) As an alternative to mechanical extract ventilation, passive stack ventilation may be provided. Where passive stack
ventilation is provided it shall be designed and constructed in accordance with BRE Information Paper 13/94 or a
valid BBA Certificate.
(4) Mechanical extract ventilation shall not be provided in a room where there is an open-flued solid fuel burning
appliance (see paragraph 1.4). Mechanical extract ventilation (or passive stack ventilation) need not be provided in a
room with an open-flued appliance which has a flue having a free area at least equivalent to a 125 mm diameter duct
and the appliance’s combustion air inlet and dilution air inlet are permanently open when the appliance is not in use.
(5) This provision is for a domestic size kitchen where the appliances and usage are of a domestic nature. Guidance on
the ventilation required for commercial kitchens is given in CIBSE Guide B, Tables B2.3 and B2.11.
(6) Adjacent to a hob means either –
(a) incorporated within a cooker hood located over the hob; or
(b) located near the ceiling within 300 mm of the centreline of the space for the hob.
(7) As an alternative, mechanical extract ventilation at 6 litres/second may be provided.

5
Ventilation of an internal habitable room 2.5 An enclosed place which provides through
ventilation to a habitable room shall have –
2.3 Where a habitable room cannot be
ventilated in accordance with paragraph 2.2 it (a) a rapid ventilation opening or openings with
shall be ventilated through – an area of not less than 1/20th of the
combined floor areas of the rooms; and
(a) another habitable room in accordance with
paragraph 2.4; or (b) a background ventilation opening or
openings of not less than 8000 mm2.
(b) an enclosed place in accordance with
paragraph 2.5. The habitable room shall have openings for
ventilation to the enclosed place of not less
2.4 A habitable room which provides through than the sizes given in (a) and (b) above.
ventilation to an internal habitable room shall
have – These provisions are shown in Diagram 2.2.
(a) a permanent opening or openings to the
other habitable room with an area of not less
than 1/20th of the combined floor areas of the
rooms;
(b) a rapid ventilation opening or openings with
an area of not less than 1/20th of the
combined floor areas; and
(c) a background ventilation opening or
openings of not less than 8000 mm2.

These provisions are shown in Diagram 2.1.

6
Ventilation of non-habitable internal
rooms
2.6 Any kitchen, utility room, bathroom or
sanitary accommodation which cannot have
ventilation openings in accordance with
paragraph 2.2 shall have mechanical extract
ventilation in accordance with Table 2.2 and a
permanently open air inlet having a minimum
free opening area of 9000 mm2. The
mechanical extract ventilation shall have an
overrun time of not less than 15 minutes and
shall be activated either automatically or
manually (e.g. by the operation of a light
switch).

Notes to Table
(1) As an alternative to mechanical extract ventilation, passive stack ventilation may be provided. Where passive stack
ventilation is provided it shall be designed and constructed in accordance with BRE Information Paper 13/94 or a
valid BBA Certificate.
(2) Mechanical extract ventilation shall not be provided in a room where there is an open-flued solid fuel burning
appliance (see paragraph 1.4). Mechanical extract ventilation (or passive stack ventilation) need not be provided in a
room with an open-flued appliance which has a flue having a free area at least equivalent to a 125 mm diameter duct
and the appliance’s combustion air inlet and dilution air inlet are permanently open when the appliance is not in use.
(3) Adjacent to a hob means either –
(a) incorporated within a cooker hood located over the hob; or
(b) located near the ceiling within 300 mm of the centreline of the space for the hob.

7
3.1 This Section gives the provisions for the Ventilation of rooms direct to external
natural ventilation of rooms in non-domestic air
buildings and the mechanical ventilation of
internal kitchens, bathrooms and sanitary 3.2 In a non-domestic building, any occupiable
accommodation in an otherwise naturally room, kitchen, bathroom and sanitary
ventilated non-domestic building. accommodation shall have ventilation
provisions in accordance with Table 3.1 and
where appropriate paragraphs 3.5, 3.6 and 3.7.

Notes to Table
(1) Where a room serves a combined function, the individual provisions for rapid, background and mechanical extract
ventilation need not be duplicated provided that the greater or greatest provision for the individual functions in
Table 3.1 is made.
(2) For specific rooms where smoking is permitted see paragraph 3.6.
(3) For domestic size facilities passive stack ventilation may be provided in place of mechanical extract ventilation.
Where passive stack ventilation is provided it shall be designed and constructed in accordance with BRE Information
Paper 13/94 or a valid BBA Certificate.
(4) Where an open-flued appliance is provided in a building with mechanical extract ventilation, the spillage of flue gases
could occur. The open-flued appliance needs to be able to operate safely whether or not the fan is running (see
paragraph 1.4).
(5) This provision is for a domestic size kitchen where the appliances and usage are of a domestic nature. Guidance on
the ventilation required for commercial kitchens is given in CIBSE Guide B, Tables B2.3 and B2.11.
(6) Adjacent to a hob means either –
(a) incorporated within a cooker hood located over the hob; or
(b) located near the ceiling within 300 mm of the centreline of the space for the hob.
(7) Where sanitary accommodation in a school or other educational establishment is for use by pupils or students see
paragraph 3.7.
(8) As an alternative, mechanical extract ventilation at 6 litres/second per WC or 3 air changes per hour may be
provided.

8
Ventilation of internal kitchens,
bathrooms and sanitary accommodation
3.3 Where a kitchen, bathroom or sanitary
accommodation is an internal room it shall
have mechanical extract ventilation, to extract
air at a rate of not less than that given in
Table 3.2, and a permanently open air inlet
having a minimum free opening area of
9000 mm2. The mechanical extract ventilation
shall have an overrun time of not less than 15
minutes and shall be activated either
automatically or manually (e.g. by the
operation of a light switch).

Notes to Table
(1) For domestic size facilities passive stack ventilation may be provided in place of mechanical extract ventilation.
Where passive stack ventilation is provided it shall be designed and constructed in accordance with BRE Information
Paper 13/94 or a valid BBA Certificate.

(2) Where an open-flued appliance is provided in a building with mechanical extract ventilation, the spillage of flue gases
could occur. The open-flued appliance needs to be able to operate safely whether or not the fan is running (see
paragraph 1.4).

(3) This provision is for a domestic size kitchen where the appliances and usage are of a domestic nature. Guidance on
the ventilation required for commercial kitchens is given in CIBSE Guide B, Tables B2.3 and B2.11.

(4) Adjacent to a hob means either –


(a) incorporated within a cooker hood located over the hob; or
(b) located near the ceiling within 300 mm of the centreline of the space for the hob.

(5) Where sanitary accommodation in a school or other educational establishment is for use by pupils or students see
paragraph 3.7.

9
Ventilation of common spaces Air supply systems
3.4 A common space shall be ventilated by – 3.8 Where the ventilation of a room in which a
(a) a ventilation opening or openings having an specialist activity is undertaken requires a
area of not less than 1/50th of the floor area of controlled supply of air then –
the common space; or (a) air inlets shall be sited so that they will not
draw contaminated air from any adjacent
(b) mechanical supply ventilation designed to
provide fresh air at a rate of 1 litre/second per source, for example, a flue outlet, exhaust
ventilation outlet or an evaporative cooling
m2 of floor area.
tower, or from an area in which vehicles
manoeuvre; and
Ventilation of rooms in which specialist
activities are undertaken (b) measures shall be taken to avoid legionella
contamination.
3.5 The ventilation provisions in Table 3.1 may
[Guidance on such measures is contained in
not be adequate where specialist activities are
the Health and Safety Executive publication –
undertaken in a room. Additional ventilation
“The control of legionellosis including
should be provided in accordance with, in the
legionnaires’ disease” paragraphs 71 to 89
case of –
which should be read in conjunction with –
(a) fume cupboards in a school or other (i) BS 5720 : 1979 Clauses 2.3.2 and
educational establishment – DFE Design Note 2.3.3; 2.4.2 and 2.4.3; 2.5; 3.2.6; 3.2.8
29; and 5.5.6; or
(b) specific workplaces and work processes – (ii) CIBSE Guide B Sections B2 and B3.]
HSE Guidance Note EH 22;
(c) specific rooms in hospitals – DHSS Activity Ventilation systems
Data Base and Department of Health Building 3.9 Where the ventilation of a room, in which a
Notes 4, 21 and 46 as appropriate; and specialist activity is undertaken, is provided by
(d) building services plant rooms which require a mechanical ventilation system its effective
emergency ventilation to disperse operation shall be ensured by –
contaminating gas releases – HSE Guidance (a) providing adequate access for maintenance
Note EH 22, paragraphs 25 to 27. of the system (see BSRlA Technical Note
10/92 : Sections A5 and D2); and
3.6 Where smoking is permitted in rest rooms,
mechanical extract ventilation at a rate of not (b) commissioning the system in accordance
less than 16 litres/second per person, shall be with a relevant commissioning code. (e.g. a
provided in addition to the provisions in CIBSE Code.)
Table 3.1.

3.7 Where sanitary accommodation in a


school or other educational establishment is for
use by pupils or students, the ventilation
provisions given in Tables 3.1 and 3.2 will be
unable to cope with peak usage e.g. break
times. In these buildings, such sanitary
accommodation shall be ventilated at a rate of
not less than 6 air changes per hour.

10
4.1 This Section gives the provisions for the 4.3 A car park or part of a car park which
ventilation of a car park for light vehicles i.e. cannot have ventilation openings in
cars, motorcycles or passenger or light goods accordance with paragraph 4.2 shall have a
vehicles weighing no more than 2500 kg gross. mechanical extract ventilation system capable
Where the car park also contains other rooms, of –
for example, for attendants or sanitary (a) providing general ventilation of not less
accommodation, such rooms shall be than 6 air changes per hour and local
ventilated in accordance with Section 3. ventilation at exits and ramps, where cars
queue inside the building with engines running,
4.2 A car park which can be ventilated direct to at a rate of not less than 10 air changes per
external air at each car parking level shall have hour; or
either –
(b) ensuring that the concentration of carbon
(a) ventilation openings having a minimum free monoxide is limited so that it does not
opening area not less than 1/20th of the floor exceed –
area at that level, with not less than half of that
area evenly distributed in two opposing walls; (i) 50 parts per million averaged over an
eight hour period; and
(ii) 100 parts per million in any 15 minute
(b) ventilation openings having a minimum free period.
opening area of not less than 1/40th of the
floor area at that level and a mechanical
extract ventilation system capable of not less
than 3 air changes per hour. The ventilation
openings and the extraction points shall be
located to ensure an adequate distribution of
ventilation.

Printed in the UK for the Stationery Office Ltd


Dd 601165 C9 2/99 014567

11
12
Department of Finance
and Personnel

The Building Regulations (Northern Ireland) 2000


Amendments to Technical Booklets C,D,E,F,G,G1,K,L,N and P

Amendments Booklet - AMD 2 December 2000 Page 1 of 5

Introduction (5) Page 19. Paragraphs headed A4 Naturally


occurring contamination -
This document has been prepared by the Delete the existing paragraphs and substitute -
Department of Finance and Personnel and
"Where a dwelling is in an area exposed to a
contains additions and revisions to Technical'
greater than 1 % probability of a radon
Booklets C, D, E, F, G, G1, K, L, N and P
concentration exceeding 200 becquerels per
Technical Booklets D, E, G, L and N are also
cubic metre that dwelling must incorporate
amended by Amendments Booklet - AMD 1:
protective measures [Regulation C2(2)].
December 1998.
Guidance on such measures is given in the
New Technical Booklets H, R and V: following publications'-.
December 2000 replace the previous editions.
(i) DOE(NI) The householder's guide to
Radon;and
(ii) BRE Report BR 413: Radon:
Amendments to Technical Booklet C: 1994 guidance on protective measures for
new dwellings in Northern Ireland.
(1) Front cover - BRE also publish guidance on surveying
Delete the title and substitute "Preparation of existing dwellings and on remedial measures.".
site and resistance to moisture".
(6) Page 23. Publication BRE: Radon -
(2) Page 1. First paragraph - Delete the item and substitute -
Delete "1994" and substitute "2000". "BRE Report BR 413: Radon: guidance on
protective measures for new dwellings in
(3) Page 1. Paragraph headed EC marked Northern Ireland".
construction products -
Delete the heading and existing paragraph
and substitute - Amendments to Technical Booklet D: 1994
"CE marked construction products (as amended)
Any construction product (within the meaning
of the Construction Products Directive) which (1) Page 1. First paragraph -
bears a CE marking shall be treated as if it
satisfied the requirements of any appropriate Delete "1994" and substitute "2000".
British Board of Agrement Certificate, British
Standard or British Standard Code of Practice (2) Page 7. Under the heading Other
relating to such a product, where the CE regulations -
marking relates to the same characteristic or
specific purpose as the Certificate, Standard Delete "Dl and D3." and substitute "Dl
or Code of Practice.". and D2.".

(4) Page 8. Paragraph 2.1 - (3) Page 7. Under the heading CE marked
construction products -
In line 10 delete "C7" and substitute "C5"
In lines 3 and 7 delete "Mark" and substitute
"marking".
Page 2 of 5

Amendments to Technical Booklet D: 1994


(continued)

(4) Page 3. Definition Compartment wall - Any construction product (within the meaning
Delete "E6(3)" and substitute "E43)". of the Construction Products Directive) which
bears a CE marking shall be treated as if it
satisfied the requirements of any appropriate
(5) Page 3. Definition Separating wall - British Board of Agrement Certificate, British
Delete "E6(2)" and substitute "E4(2)". Standard or British Standard Code of Practice
relating to such a product, where the CE
marking relates to the same characteristic or
(6) Page 54. Paragraph 6.1- specific purpose as the Certificate, Standard
Delete "Regulation D5" and substitute "the or Code of Practice.".
publications specified in Table D to Part D in .
Schedule 5 opposite the reference to (4) Page 6. Paragraph 0.9 -
Regulation D2.".
Delete "BS 5588: Part 8: 1988" and substitute
"BS 5588-8: 1999".
(7) Page 54. Paragraph 6.2(a) -
In line 3 delete "Regulation D5." and (5) Page 10. Paragraph 1.17 -
substitute "Table D to Part D in Schedule 5
opposite the reference to Regulation D2.". Delete the existing paragraph and substitute -
"1.17 A dwellinghouse shall be provided with -
(8) Page 54. Paragraph 6.3 -
(a) a self-contained smoke alarm or alarms
Delete the existing paragraph and substitute - complying with BS 5446-1: 2000 installed in
accordance with paragraphs 1.18 to 1.23;
"The design of key elements and protected
members shall comply with the provisions and (b) an automatic fire detection and alarm
relevant recommendations of the publications system complying with BS 5839: Part 6: 1995
specified in Table D to Part D in Schedule 5 of at least Grade D Type LD3 standard; or
opposite the reference to Regulation D2.". (c) an automatic fire detection and alarm
system complying with BS 5839: Part 1: 1988
of at least L3 standard.
Amendments to Technical Booklet E: 1994 However, in a very large dwellinghouse (where
(as amended) the shortest route from any point in one room
to the furthest point in any other room on the
same storey is more than 30 m) self-contained
(1) Page 7. First paragraph - smoke alarms are not adequate and an
Delete "1994" and substitute "2000". automatic fire detection and alarm system
complying with either -
(2) Page 7. Under the heading Other (i) BS 5839: Part 6: 1995 of at least Grade B
regulations - Type LD3 standard; or
Delete "E2, E4, E6, E8 and E10." and (ii) BS 5839: Part 1: 1988 of at least L3
substitute "E2, E3, E4, E5 and E6.". standard,
shall be provided.".
(3) Page 1. Paragraph headed EC marked
construction products - (6) Page 11. Paragraph 1.18 -
Delete the heading and existing paragraph
and substitute - After the last paragraph insert -
"CE marked construction products "The back-up power source to each self-
contained smoke alarm shall be provided by
either -
Page 3 of 5

Amendments to Technical Booklet E: 1994


(continued)

(a) a primary or secondary battery; or "BS 5446: Fire detection and fire alarm
devices for dwellings
(b) a capacitor.".
Part 1: 2000 Specification for smoke
(7) Page 11. Paragraph 1.19- alarms".

Delete the first paragraph and substitute -


(14) Page 96. Publication BS 5588 -
"1.19 Self-contained smoke alarms shall be In Part 8 delete "1988" and substitute "1999".
permanently wired to either -
(a) a regularly used lighting circuit; or (15) Page 96. Publication BS 5839 -
(b) a circuit which - After the last line insert -
(i) is separately fused at the distribution "AMD 9257 August 1996
board;
(ii) serves only self-contained smoke Part 6: 1995 Code of practice for the
alarms; and design and installation of fire detection
and alarm systems in dwellings
(iii) where a residual current device is AMD 9135 April 1996".
used - is not connected to a residual
current device which is also used by
any other circuit.". (16) Page 96 -
After the publication "Fire Services (Northern
(8) Page 14. Table 1.1 - Ireland) Order" insert -
In note (3) delete "in regulation E3 (i)" and "Northern Ireland Firecode as amended
substitute "in Table E to Part E in Schedule November 1999".
5".

(9) Page 30. Paragraph 1.73 -


Amendments to Technical Booklet F: 1998
In the first paragraph delete "BS 5588: Part 8:
1988" and substitute "BS 5588-8: 1999".
(1) Page 1. First paragraph -
(10) Page 41. Table 3.2 - Delete "1994" and substitute "2000".
In note ## delete "NHS Firecode" and
substitute '"Northern Ireland Firecode". (2) Page 1. Under the heading Other
regulations -
Delete "F2, F4 and F6." and substitute "F2, F3
(11) Page 44. Paragraph 3.12 - and F4.".
In sub-paragraph (c) delete "[see regulation
E3(c) and (d)]". (3) Page 1. Under the heading CE marked
construction products -
(12) Page 93. Definition Self-contained In lines 3 and 7 delete "Mark" and substitute
smoke alarm - "marking".
In line 2 delete "or without".

(13) Page 96. Publication BS 5446 -


Delete the item and substitute -
Page 4 of 5

Amendments to Technical Booklet G: 1990 (2) Page 1. Under the heading Other
(as amended) regulations -
Delete "K2 and K4." and substitute "K2 and
(1) Page 1. First paragraph - K3.".
Delete "1994" and substitute "2000".
(3) Page 1. Under the heading CE marked
(2) Page 1. Under the heading CE marked construction products -
construction products - In lines 3 and 7 delete "Mark" and substitute
In lines 3 and 7 delete "Mark" and substitute "marking".
"marking".

Amendments to Technical Booklet L: 1991


Amendments to Technical Booklet G1: 1994 (as amended)

(1) Page 1. First paragraph - (1) Page 1. First paragraph -


Delete "1994" and substitute "2000". Delete "1994" and substitute "2000".

(2) Page 1. Under the heading Other (2) Page 1. Under the heading CE marked
regulations - construction products -
Delete "G4." and substitute "G3.". In lines 3 and 7 delete "Mark" and substitute
"marking".
(3) Page 1. Paragraph headed EC marked
construction products -
Amendments to Technical Booklet N: 1990
Delete the heading and existing paragraph
(as amended)
and substitute -
"CE marked construction products
(1) Page 1. First paragraph -
Any construction product (within the meaning
Delete "1994" and substitute "2000".
of the Construction Products Directive) which
bears a CE marking shall be treated as if it
satisfied the requirements of any appropriate (2) Page 1. Under the heading Other
British Board of Agrement Certificate, British regulations -
Standard or British Standard Code of Practice
Delete "N3, N5 and N7." and substitute "N3,
relating to such a product, where the CE
marking relates to the same characteristic or N4 and N5.".
specific purpose as the Certificate, Standard
or Code of Practice.". (3) Page 1. Under the heading CE marked
construction products •
(4) Page 3. Paragraph 0.2 - In lines 3 and 7 delete "Mark" and substitute
In line 2 delete "G4" and substitute "G3". "marking".

Amendments to Technical Booklet P: 1994


Amendments to Technical Booklet K: 1994

(1) Page 1: First Paragraph -


(1) Page 1. First paragraph -
Delete "1994" and substitute "2000". Delete "1994" and substitute "2000".
Page 5 of 5

Amendments to Technical Booklet P: 1994


(continued)

(2) Page 1. Paragraph headed EC marked


construction products -
Delete the heading and existing paragraph
and substitute -
"CE marked construction products
Any construction product [within the meaning
of the Construction Products Directive) which
bears a CE marking shall be treated as if it
satisfied the requirements of any appropriate
British Board of Agrement Certificate, British
Standard or British Standard Code of Practice
relating to such a product, where the CE
marking relates to the same characteristic or
specific purpose as the Certificate, Standard
or Code of Practice.".

Published by The Stationery Office Limited


and available from:
The Publications Centre
(Mail, telephone and fax orders only)
PO Box 276, London, SW8 5DT
General enquiries 0870 600 55 22
Order through the Parliamentary Hotline Lo-Cull 0845 7 023474
Fax orders 0870 600 5533
Email orders hnnlc-Orders@.theso co.uk
The Stationery Office Bookshops
123 Kingsway, London WC2B 6PQ
020 7242 6393 Fax 020 7242 6394
68-69 Bull Street, Birmingham B4 6AD
0121 236 9696 Fax 0121 236 9699
33 Wine Street, Bristol BS1 2BQ
0117 9264306 Fax 0117 9294515
9-21 Princess Street, Manchester M60 SAS
0161 834 7201 Fax 0161 833 0634
16 Arthur Street, Belfast BT1 4GD
028 9023 8451 Fax 028 9023 5401
The Stationery Office Oriel Bookshop
18-19 High Street, Cardiff CF1 282
029 2039 5548 Fax 029 2038 4347
71 Lothian Road. Edinburgh EH3 9AZ
0870 606 5566 Fax 0870 606 5588
The Parliamentary Bookshop
12 Bridge Street. Parliament Square,
London SW IA 2JX
Telephone orders 020 7119 3890
General enquiries 020 7219 3890
Fax orders 020 7219 3866
Accredited Agents
(see Yellow Pages)
and through good booksellers

You might also like