Sprinkler Placement
Obstruction Rules
© Fire Smarts LLC. All rights reserved.
Instructor
Ralph E. Bless, P.E., SET, CFPS
Vice President, Telgian
Ralph has more than 38 years experience in fire
protection including a broad range of water based
and special hazard system design, code consulting
and fire protection engineering services. Ralph is
licensed as a Professional Engineer in six states, a
Certified Fire Protection Specialist, Level IV NICET
senior fire sprinkler layout technician and holds
three additional NICET certifications, as well as
eight state licenses. Ralph chairs the NFPA technical
committee for Record Storage, NFPA 232, and
serves on the NFPA technical committees for Water
Spray Systems, NFPA 15 as well as the NFPA 13
Installation Technical Committee and Correlating
Committee.
© Fire Smarts LLC. All rights reserved.
DISCLAIMER
This seminar and its content is not a formal interpretation issued pursuant to
NFPA regulations. Any opinion expressed is the personal opinion of the
author and presenter and does not necessarily present the official position of
the NFPA and its Technical Committees. Furthermore, this presentation is
neither intended, nor should be relied upon, to provide professional
consultation or services.
© Fire Smarts LLC. All rights reserved.
Obstructions – Big Picture
© Fire Smarts LLC. All rights reserved.
Obstructions Big Picture
Two Objective Components
Basic Requirements.
Sprinklers must be positioned and located so as to
provide satisfactory performance with respect to
activation time and distribution.
1 2
8.1.1(3)
© Fire Smarts LLC. All rights reserved.
Activation Time
Ceiling/Roof Construction Impacts Activation Time
Unobstructed Construction – Do not impede heat flow or
water discharge in a manner that materially affects the
ability of the sprinkler to control/suppress the fire
Obstructed Construction – Does impede heat flow or
water discharge in a manner that materially affects the
ability of the sprinkler to control/suppress the fire
© Fire Smarts LLC. All rights reserved.
Activation Time
Ceiling/Roof Construction Impacts Activation Time
Differing ceiling/roof construction configurations limit the
allowable sprinkler spacing (As) – Generally More
Obstructed – Lower As
Differing ceiling/roof construction configurations limit the
allowable distance below the ceiling/roof for the sprinkler
deflector
© Fire Smarts LLC. All rights reserved.
NFPA 13 – 2013/2016 Edition
Obstruction Rules
© Fire Smarts LLC. All rights reserved.
NFPA 13 – 2019 Edition
References??
© Fire Smarts LLC. All rights reserved.
Water Distribution
Anything Between the Sprinkler Position and the
Fire Location that Interferes with the Distribution of
Water Must Follow the Rules:
General Rules (8.5)
Standard Spray Sprinklers
(8.6‐Upright/Pendent 8.7‐Sidewall)
Extended Coverage Sprinklers
(8.8‐Upright/Pendent 8.9‐Sidewall)
Residential Sprinklers (8.10)
CMSA Sprinklers (8.11) Apply the Obstruction Rules from
ESFR Sprinklers (8.12) Sections 8.5 and 8.6 to 8.12 as
Applicable
© Fire Smarts LLC. All rights reserved.
Water Distribution
EXCEPT
A.8.1.1(3)
© Fire Smarts LLC. All rights reserved.
Shadow Areas
Pendent or Upright
Spr
Shadow Area
Shadow Area
© Fire Smarts LLC. All rights reserved.
Shadow Areas
Sidewall Spr
© Fire Smarts LLC. All rights reserved.
Basic Obstruction Rule
DO NOT OBSTRUCT THE
SPRINKLER
© Fire Smarts LLC. All rights reserved.
Basic Obstruction Rule
© Fire Smarts LLC. All rights reserved.
Detailed Obstruction Rule
DO NOT OBSTRUCT THE SPRINKLER IN A
MANNER THAT:
UNACCEPTABLY IMPACTS
CONTROL/SUPPRESSION EFFECTIVENESS
OF THE SPRINKLER
© Fire Smarts LLC. All rights reserved.
General Obstruction Rules 8.5.5
General Format
8.5.5.1 Performance Objectives
8.5.5.2 Obstructions to Discharge Pattern
Development
8.5.5.3 Prevent Discharge from Reaching the Hazard
(4 ft Rule)
8.5.6 Clearance (18”/36” Rule)
© Fire Smarts LLC. All rights reserved.
8.5.5 Obstructions to Sprinkler Discharge
General Two Zone Criteria
© Fire Smarts LLC. All rights reserved.
Spray Pattern
Varies With Different
Sprinklers
© Fire Smarts LLC. All rights reserved.
Spray Pattern
Varies With Applied
Pressure
© Fire Smarts LLC. All rights reserved.
8.5.5.2 Obstructions to
Sprinkler Discharge Pattern Development
Continuous and noncontinuous obstructions ≤18 in.
below the sprinkler deflector that prevent the
discharge pattern from developing must comply with
8.5.5.2.
1 A Beam Rule / Times Rule
8.5.5.2.1
© Fire Smarts LLC. All rights reserved.
8.5.5.2 Obstructions to
Sprinkler Discharge Pattern Development
Sprinklers must be positioned in accordance with the minimum
distances and special requirements of Section 8.6 through 8.12
so that they are sufficiently away from obstructions such as truss
webs and chords, pipes, columns and fixtures.
Also Sends User to 8.6 through 8.12
for Specific Rules – Note: CMSA and ESFR Rules 8.5.5.2.2
extend this depth to 24 to 36 in.
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
Continuous or noncontinuous obstructions that interrupt the
water discharge in a horizontal plane more than 18 in. below the
sprinkler deflector in a manner to limit the distribution from
reaching the protected hazard must comply with 8.5.5.3
B
2
8.5.5.3 Provides Some General Rules 8.5.5.3
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
Sprinklers must be installed under fixed obstructions >4 ft in
width.
Be Careful, General Rules of 8.5.5
are Modified for CMSA and ESFR
8.5.5.3.1
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
Roof
Floor
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
Roof
Floor
4’-2”
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
Roof
OK?
Floor
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
Roof
OK?
Floor
© Fire Smarts LLC. All rights reserved.
Multiple Adjacent Obstructions
Many Small Obstructions on
One Large One?
Only Addressed for ESFR Sprinklers (8.12.6.3.3 in the
2016 Edition) – Must Separate Individual Components
by 3X the Width of the Adjacent Individual
Components OR Consider as a Single Obstruction
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
Exceptions:
Sprinkler are not be required under noncombustible
obstructions >4 ft wide where the bottom of the obstruction
is ≤24 in. above the floor or deck. (New to the 2016 Edition,
8.5.5.3.1.4)
Sprinklers are not required under obstructions that are not
fixed in place, such as conference tables.
8.5.5.3.2
© Fire Smarts LLC. All rights reserved.
8.5.5.3 Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
Is this an obstruction that needs sprinklers
beneath it?
© Fire Smarts LLC. All rights reserved.
Obstructions that Prevent Discharge from
Reaching the Hazard
Is this something that needs
sprinklers in it?
© Fire Smarts LLC. All rights reserved.
Open Grid Ceiling
≥1/4” openings in least dimension
Depth of material ≤ the least dimension
70% open
Light Hazard Clearance
≤10 ft x 10 ft Clearance of ≥18 in.
≤10 ft x 12 ft Clearance of ≥ 24 in.
>10 ft x 12 ft Clearance of ≥ 36 in.
Ordinary Hazard Clearance
≤10 ft x 10 ft Clearance of ≥24 in.
>10 ft x 10 ft Clearance of ≥36 in.
8.15.14
© Fire Smarts LLC. All rights reserved.
Drop Out Ceiling
Listed
Not allowed beneath QR or EC sprinklers
unless specifically Listed for such
application
8.15.15
© Fire Smarts LLC. All rights reserved.
In‐Rack Exception
Exceptions:
Obstructions to In‐Rack Sprinkler Discharge – In‐rack sprinklers
are not be required to meet the obstructions criteria and
clearance from storage requirements of 8.5.
In‐rack sprinklers do have requirements for distance above
storage, below beam and spacing from the support upright in
the storage criteria Chapters
8.13.5
© Fire Smarts LLC. All rights reserved.
Small Closet/Compartment Exception
Exceptions:
Closets – In all closets and
compartments, including those
closets housing mechanical
equipment, that are not larger than
400 ft3 in size, a single sprinkler at
the highest ceiling level is sufficient
without regard to obstructions or
minimum distance to the wall.
8.5.5.4
© Fire Smarts LLC. All rights reserved.
HVLS Fans
HVLS fans permitted and not be considered an obstruction if:
≤24 ft diameter
Hub centered approximately between 4 sprinklers
Vertical clearance of ≥3 ft
Fans interlocked to shutdown within 90 sec of water flow
11.1.7/12.1.4.1
© Fire Smarts LLC. All rights reserved.
Sprinkler Frame Arms
8.3.1.3
© Fire Smarts LLC. All rights reserved.
Head Guards
Guards utilized to protection sprinklers from
mechanical injury must be listed for use with the
sprinkler
6.2.8
© Fire Smarts LLC. All rights reserved.
General Clearance to
Storage Rules
Clearance Req’d from the Top of Storage to the Sprinkler
Deflector
≥18 in.
Greater clearance when required by another Standard
≥36 in. for Special Sprinklers (CMSA/ESFR)
<18 in. if proven by large‐scale fire test
≥36 in. for Rubber Tire Storage
8.5.6
© Fire Smarts LLC. All rights reserved.
SSU/SSP&ECU/ECP Obstruction Rules
8.6.5/8.8.5 General Format
8.6.5.1/8.8.5.1 Performance Objectives (Beam/Soffit Rules)
8.6.5.2/8.8.5.2 Impaired Discharge Pattern Development
(3X/4X) and Suspended/Floor Mounted Obstruction Rules)
8.6.5.3/8.8.5.3 Prevent Discharge from Reaching the Hazard
(4 ft Rule)
8.6.6/8.8.6 Clearance (18” Rule)
© Fire Smarts LLC. All rights reserved.
8.6.5.1 – SSU/SSP Beam Rule
Ceiling
B
Obstruction
8.6.5.1.2(1)
Figure 8.6.5.1.2(a) and Table 8.6.5.1.2
© Fire Smarts LLC. All rights reserved.
8.6.5.1 – SSU/SSP Beam Rule
% of Flow
© Fire Smarts LLC. All rights reserved.
8.8.5.1 – ECU/ECP Beam Rule
Ceiling
B
Obstruction
8.8.5.1.2(1)
Figure 8.8.5.1.2(a) and Table 8.8.5.1.2
© Fire Smarts LLC. All rights reserved.
8.8.5.1 – ECU/ECP Beam Rule
80
70
30 40 50 60
Pressure
Driven Flow
© Fire Smarts LLC. All rights reserved.
8.6.5.1 – SSU/SSP Beam Rule
8.8.5.1 – ECU/ECP Beam Rule
Ceiling
Obstruction
≤ 4 ft
≤1/2 S ≤1/2 S
CL
8.6.5.1.2(2)
8.8.5.1.2(2)
© Fire Smarts LLC. All rights reserved.
8.6.5.1 – SSU/SSP Soffit Rule
8.8.5.1 – ECU/ECP Soffit Rule
Soffit
Obstruction
Ceiling
A D A D 8 in. B
D 30 in.
8.6.5.1.2(3)
Wall
Figure 8.6.5.1.2(b)
8.8.5.1.2(3)
Figure 8.8.5.1.2(b)
© Fire Smarts LLC. All rights reserved.
8.6.5.1 – SSU/SSP Soffit Rule
8.8.5.1 – ECU/ECP Soffit Rule
Soffit
Obstruction
Ceiling
≤24 in.
≤1/2 S
Wall
½ of 4 ft Rule
8.6.5.1.2(4)
Figure 8.6.5.1.2(c)
8.8.5.1.2(4)
Figure 8.8.5.1.2(c)
© Fire Smarts LLC. All rights reserved.
8.6.5.2 – SSP/SSU 3X Rule
Ceiling
8.6.5.2.1.3
Figure 8.6.5.2.1.3(b)
© Fire Smarts LLC. All rights reserved.
8.8.5.2 – ECP/ECU 4X Rule
Ceiling
NOTE:
EC Sprinklers Are Only Permitted With Truss/Bar 8.8.5.2.1.3
Joist That Have Web Members ≤1 in. Unless Figure 8.8.5.2.1.3(b)
Truss/Bar Joist Are Spaced >7½ ft O/C – 8.4.3(3)
© Fire Smarts LLC. All rights reserved.
8.6.5.2 – SSP/SSU 3X Rule
Vertical Obstruction
A 3C or 3D
Sprinkler
C Use Greater of C or D
No Max. for A
D A
8.6.5.2.1.3
Figure 8.6.5.2.1.3(a)
© Fire Smarts LLC. All rights reserved.
8.8.5.2 – ECP/ECU 4X Rule
Vertical Obstruction
A 4C or 4D
Sprinkler
C Use Greater of C or D
No Max. for A
D A
8.8.5.2.1.3
Figure 8.8.5.2.1.3(a)
© Fire Smarts LLC. All rights reserved.
8.6.5.2 – SSP/SSU 3X Rule
Ceiling
A 3C or 3D
Don’t Forget to Check the
Use Greater of C or D Web Member
8.6.5.2.1.3
Figure 8.6.5.2.1.3(B)
© Fire Smarts LLC. All rights reserved.
8.8.5.2 – ECP/ECU 4X Rule
Ceiling
A 4C or 4D
Don’t Forget to Check the
Use Greater of C or D Web Member
8.8.5.2.1.3
Figure 8.8.5.2.1.3
© Fire Smarts LLC. All rights reserved.
8.6.5.2 – SSP/SSU 3X Rule
8.8.5.2 – ECP/ECU 4X Rule
The rules of known as the “Three/Four Times Rule” have been
written to apply to obstructions where the sprinkler can be
expected to get water to both sides of the obstruction without
allowing a significant dry shadow on the other side of the
obstruction. This works for small non‐continuous obstructions
and for continuous obstructions where the sprinkler can throw
water over and under the obstruction, such as the bottom chord
of an open truss or joist. …
A.8.6.5.2.1.3
A.8.8.5.2.1.3
© Fire Smarts LLC. All rights reserved.
Exceptions to SSP/SSU 3X Rule
For light and ordinary hazard occupancies, structural
members only are required to be considered when
applying the requirements of 8.6.5.2.1.3.
Allowance Not Included For Any Other
Sprinkler Types
8.6.5.2.1.4
© Fire Smarts LLC. All rights reserved.
Exceptions to SSP/SSU 3X Rule
The intent of 8.6.5.2.1.4 to exempt nonstructural
elements in LH and OH occupancies from the
obstruction criteria commonly known as the “Three
Times Rule”. However, the other obstruction rules,
including the “Beam Rule” (8.6.5.1.2) and “Wide
Obstruction Rule” (8.6.5.3.3) still apply. If the
obstruction is so close to a sprinkler that water cannot
spray on both sides, it is effectively a continuous
obstruction as far as the sprinkler is concerned and the
Beam Rule should be applied.
A.8.6.5.2.1.4
© Fire Smarts LLC. All rights reserved.
Exceptions to
SSP/SSU 3X&ECU/ECP 4X Rules
Open Web Steel or
Wood Truss
Ceiling
≤1/2 S ≤1/2 S
CL
8.6.5.2.1.5
8.8.5.2.1.4
© Fire Smarts LLC. All rights reserved.
Exceptions to
SSP/SSU 3X&ECU/ECP 4X Rules
Y ≥24 in.
Ceiling O/C
X ≥20 in.
apart
X/2
CL Open Truss with ≤4 in.
Member Dimensions
Typical 2x4 Truss
8.6.5.2.1.6
8.8.5.2.1.5
© Fire Smarts LLC. All rights reserved.
Exceptions to
SSP/SSU 3X 4X Rules
Open Truss/Bar Joist
Ceiling
≥6 in. C
D
CL A 3C or 3D
≤8 in.
Use Greater of C or D
8.6.5.2.1.7
© Fire Smarts LLC. All rights reserved.
Exceptions to
ECU/ECP 4X Rules
Open Truss/Bar Joist
Ceiling
≥6 in. C
D
CL A 4C or 4D
≤8 in.
Use Greater of C or D
8.8.5.2.1.6
© Fire Smarts LLC. All rights reserved.
Exceptions to
SSU 3X & ECU 4X Rules
The 3X and 4X rules do not apply to sprinkler system
piping less than 3 in. in diameter
Upright
≤3 in. (nominal)
8.6.5.2.1.8
8.8.5.2.1.7
© Fire Smarts LLC. All rights reserved.
SSU Sprig Length
What is the required sprig length needed?
Apply 3X Rule: Apply Bottom Chord of Truss
3 x 4 in. = 12 in. Rule = 6 in.
Apply 3X Rule:
?
3 x 4.5 in. = 13.5 in.
4 in Pipe
© Fire Smarts LLC. All rights reserved.
Exceptions to
SSP/SSU 3X ECU/ECP 4X Rules
The 3X and 4X rules do not apply to sprinklers
positioned with respect to obstructions in accordance
with 8.6.5.1.2/8.8.5.1.2 (Beam/Soffit Rule).
Acceptable if Arrangement Complies with
the Beam/Soffit Rules
8.6.5.2.1.9
8.8.5.2.1.8
© Fire Smarts LLC. All rights reserved.
Exceptions to
SSP/SSU 3X ECU/ECP 4X Rules
Sprinklers are permitted to be placed without regard to
blades of ceiling fans less than 60 in. in diameter,
provided the plane view of the fan is at least 50% open.
8.6.5.2.1.10
8.8.5.2.1.9
© Fire Smarts LLC. All rights reserved.
SSP/SSU&ECU/ECP Suspended or Floor
Mounted Vertical Obstructions
Ceiling
B
A
Applies Only to Light
Hazard Occupancies
Floor
Freestanding Obstruction –
Privacy Curtains, Freestanding
Partitions, Room Dividers, Etc.
8.6.5.2.2
Figure 8.6.5.2.2, Table 8.6.5.2.2
8.8.5.2.2
Figure 8.8.5.2.2, Table 8.8.5.2.2
© Fire Smarts LLC. All rights reserved.
SSP/SSU&ECU/ECP Suspended or
Floor Mounted Vertical Obstructions
≥70% Open Mesh
Ceiling
?
≥22 in.
Floor
Suspended Obstruction –
Privacy Curtains, Freestanding
Partitions, Room Dividers, Etc.
8.6.5.2.2.1
Figure 8.6.5.2.2
8.8.5.2.2.1
Figure 8.8.5.2.2
© Fire Smarts LLC. All rights reserved.
SSP/SSU & EC Obstructions that Prevent
Discharge from Reaching the Hazard
4 ft Rule
Roof
>18 in.
≤4 ft
Floor
The Same As General
Rules in 8.5.5.3
8.6.5.3
8.8.5.3
© Fire Smarts LLC. All rights reserved.
SSU/SSP & ECU/ECP
Clearance to Storage Rules
Use General Rules +
Storage on shelves against a wall can extend to <18
in. below the deflector provided the sprinkler is not
directly above the storage
The allowance for application of such with EC
sprinklers is through reference back to 8.6.6.2 in
A.8.8.6.
8.6.6
8.8.6
© Fire Smarts LLC. All rights reserved.
Shelf Storage Against a Wall
<18 in. Clearance
≤1/2 S Roof
Roof
Storage
Shelf Storage Against the Wall
Against the Wall
Floor
Floor ?
≤30” – Shelf Storage Definition?
© Fire Smarts LLC. All rights reserved.
SSW/ECSW Obstruction Rules 8.7.5/8.9.5
General Format
8.7.5.1/8.9.5.1 Performance Objectives (Beam/Soffit
Rules)
8.7.5.2/8.9.5.2 Impaired Discharge Pattern Development
(3X/4X and Suspended/Floor Mounted Obstruction Rules)
8.7.5.3/8.9.5.3 Prevent Discharge from Reaching the
Hazard (4 ft Rule)
8.7.6/8.9.6 Clearance (18” Rule)
Rules Are the Similar to Upright and
Pendent Sprinklers – In the Interest of
Time We’ll Only Look at a Few Items
© Fire Smarts LLC. All rights reserved.
SSW Clearance to Storage Rules
Use General Rules +
Storage on shelves against a wall can extend to <18
in. below the deflector provided the sprinkler is not
directly above the storage through reference back to
8.6.6.2 in A.8.7.6
No specific rules in 8.9 for ECSW for clearance
8.7.6
© Fire Smarts LLC. All rights reserved.
Residential Obstruction Rules 8.10.6
General Format
8.10.6.1 Performance Objectives (Beam/Soffit Rules)
8.10.6.2 Impaired Discharge Pattern Development (4X
Rules Are the Same As Indicated for EC
and Suspended/Floor Mounted Obstruction Rules)
Upright, Pendent and Sidewall Sprinklers
8.10.6.3 Prevent Discharge from Reaching the Hazard
(4 ft Rule) Additionally, Always Check the
Manufactures Installation Guide and Listing
No Storage Clearance Rules
Criteria
© Fire Smarts LLC. All rights reserved.
CMSA Obstruction Rules 8.11.5
General Format
8.11.5.1 Performance Objectives (Beam Rules)
8.11.5.2 Impaired Discharge Pattern Development (3X
Rule)
8.11.1.1 Indicates that the Manufacturer’s
8.11.5.3 Prevent Discharge from Reaching the Hazard
Installation Instructions are to be used if different
(4 ft Rule) than Section 8.11.
© Fire Smarts LLC. All rights reserved.
8.11.5.1 – CMSA Beam Rule
Ceiling
B
Obstruction
8.11.5.1.2
Figure 8.11.5.1.2 and
Table 8.11.5.1.2
© Fire Smarts LLC. All rights reserved.
CMSA Obstructions that Prevent
Discharge from Reaching the Hazard
(>2 ft Rule)
Cannot Extend Above
Sprinkler
Roof
B
Obstruction Entirely
Below Sprinkler
A >24 in.
Since B is Measured to the Bottom of the
Obstruction and It Can’t Extend Above the
Sprinkler B=Max. Obstruction Depth As Well
8.11.5.3.2 and
Figure 8.11.5.3.2
© Fire Smarts LLC. All rights reserved.
CMSA Obstructions that Prevent Sprinkler
Discharge from Reaching the Hazard
(>2 ft Rule)
Comparison to Beam Rule
Ceiling
8” 6”
35” 35”
How Can This Be RIGHT?
© Fire Smarts LLC. All rights reserved.
CMSA Obstructions that Prevent Sprinkler
Discharge from Reaching the Hazard
Roof
(2 ft Rule)
≤24 in.
>24 in.
≤12 in.
>18 in.
½S ½S
CL
Storage
8.11.5.3.4 and
Figure 8.11.5.3.4
© Fire Smarts LLC. All rights reserved.
CMSA Obstructions that Prevent Sprinkler
Discharge from Reaching the Hazard
(1 ft Rule)
Roof
≤6 in.
CL
8.11.5.3.5 and
Figure 8.11.5.3.5
© Fire Smarts LLC. All rights reserved.
CMSA Obstructions that Prevent
Discharge from Reaching the Hazard
(1 ft & 2 ft Rules)
Roof
24
24 in.
C
L
36 in.
12 12
CL
© Fire Smarts LLC. All rights reserved.
8.11.6 CMSA Clearance
to Storage Rules
Use General Rules +
The clearance between the deflector and the top of
storage must be 36 in. or greater.
8.11.6
© Fire Smarts LLC. All rights reserved.
ESFR Obstruction Rules 8.12.5
General Format
8.12.5.1 Obstructions at or Near Ceiling (Beam Rule)
8.12.5.2 Isolated Obstructions Below Sprinklers
8.12.5.3 Continuous Obstruction Below Sprinklers
8.12.6 Clearance (36” Rule)
8.12.5.1.3, 8.12.5.2(5) and 8.12.5.3.6 all indicate
that special obstruction rules are to be applied in
accordance with the listing of the sprinkler which
may be different than 8.12.5
© Fire Smarts LLC. All rights reserved.
8.12.5.1 – ESFR Beam Rule
Ceiling
B
Obstruction
8.12.5.1.1
Figure 8.12.5.1.1 and
Table 8.12.5.1.1
© Fire Smarts LLC. All rights reserved.
Continuous vs Noncontinuous
Obstructions
Continuous Obstructions An obstruction at or below
the level of the sprinkler deflector that affects the
discharge pattern of two or more sprinklers.
Noncontinuous Obstructions An obstruction at or
below the level of the sprinkler deflector that affects
the discharge pattern of a single sprinkler.
3.3.18.1
3.3.18.2
© Fire Smarts LLC. All rights reserved.
8.12.5.2 – ESFR Isolated Obstructions
Below Sprinkler
Cannot Extend Above
Sprinkler
Roof
≥12” ≤24”
8.12.5.2(2)
© Fire Smarts LLC. All rights reserved.
ESFR Isolated/Continuous Obstructions
Below Sprinklers
Roof
≥24 in.
≤2 in.
8.12.5.2(4)
8.12.5.3(2)
© Fire Smarts LLC. All rights reserved.
8.12.5.3.2 – ESFR Bottom Chord of Bar
Joist/Truss Rule
Ceiling
≥12”
Does not apply for Upright
ESFR where directly over the
bottom chord that is ≤4 in. 8.12.5.3.2
© Fire Smarts LLC. All rights reserved.
8.12.6 ESFR Clearance to Storage Rules
Use General Rules +
Clearance to Storage. (ESFR Sprinklers) The clearance
between the deflector and the top of storage shall be
36 in. or greater.
8.12.6
© Fire Smarts LLC. All rights reserved.
Example
24” Wide Light Fixture
Clearly Less than 24 in.
Non Compliant
© Fire Smarts LLC. All rights reserved.
Example
The position of the sprinkler w/respect
to the obstruction
AND
The positon of the protected materials
w/respect to the obstruction
BOTH MATTER
© Fire Smarts LLC. All rights reserved.
Another Example
The position of the sprinkler w/respect to
the obstruction
AND
The positon of the protected materials
w/respect to the obstruction
AND
The arrangement and type of protected
materials
IT ALL MATTERS
© Fire Smarts LLC. All rights reserved.
Conclusion
© Fire Smarts LLC. All rights reserved.
Questions and Comments