You are on page 1of 95

Fire 

Sprinkler Placement 
Obstruction Rules

© Fire Smarts LLC.  All rights reserved.  
Instructor
Ralph E. Bless, P.E., SET, CFPS
Vice President, Telgian
Ralph has more than 38 years experience in fire 
protection including a broad range of water based 
and special hazard system design, code consulting 
and fire protection engineering services. Ralph is 
licensed as a Professional Engineer in six states, a 
Certified Fire Protection Specialist, Level IV NICET 
senior fire sprinkler layout technician and holds 
three additional NICET certifications, as well as 
eight state licenses. Ralph chairs the NFPA technical 
committee for Record Storage, NFPA 232, and 
serves on the NFPA technical committees for Water 
Spray Systems, NFPA 15 as well as the NFPA 13 
Installation Technical Committee and Correlating 
Committee.

© Fire Smarts LLC.  All rights reserved.  
DISCLAIMER
This seminar and its content is not a formal interpretation issued pursuant to
NFPA regulations. Any opinion expressed is the personal opinion of the
author and presenter and does not necessarily present the official position of
the NFPA and its Technical Committees. Furthermore, this presentation is
neither intended, nor should be relied upon, to provide professional
consultation or services.

© Fire Smarts LLC.  All rights reserved.  
Obstructions – Big Picture

 Minimize the impact of obstructions on sprinkler


discharge and resultant fire control/suppression.
 Limit operational delay of sprinklers.
 Prevent uncontrolled fires from overwhelming the
fire sprinkler system.
 Prevent excessive numbers of sprinklers opening
during a fire.

© Fire Smarts LLC.  All rights reserved.  
Obstructions Big Picture
Two Objective Components
 Basic Requirements. 
Sprinklers must be positioned and located so as to
provide satisfactory performance with respect to
activation time and distribution.
1 2

8.1.1(3)

© Fire Smarts LLC.  All rights reserved.  
Activation Time

 Ceiling/Roof Construction Impacts Activation Time
 Unobstructed Construction – Do not impede heat flow or
water discharge in a manner that materially affects the
ability of the sprinkler to control/suppress the fire
 Obstructed Construction – Does impede heat flow or
water discharge in a manner that materially affects the
ability of the sprinkler to control/suppress the fire

© Fire Smarts LLC.  All rights reserved.  
Activation Time

 Ceiling/Roof Construction Impacts Activation Time
 Differing ceiling/roof construction configurations limit the
allowable sprinkler spacing (As) – Generally More
Obstructed – Lower As
 Differing ceiling/roof construction configurations limit the
allowable distance below the ceiling/roof for the sprinkler
deflector

© Fire Smarts LLC.  All rights reserved.  
NFPA 13 – 2013/2016 Edition
Obstruction Rules

© Fire Smarts LLC.  All rights reserved.  
NFPA 13 – 2019 Edition 
References??

© Fire Smarts LLC.  All rights reserved.  
Water Distribution

 Anything Between the Sprinkler Position and the 
Fire Location that Interferes with the Distribution of 
Water Must Follow the Rules:
 General Rules (8.5)
 Standard Spray Sprinklers
(8.6‐Upright/Pendent 8.7‐Sidewall)
 Extended Coverage Sprinklers
(8.8‐Upright/Pendent 8.9‐Sidewall)
 Residential Sprinklers (8.10)
 CMSA Sprinklers (8.11) Apply the Obstruction Rules from 
 ESFR Sprinklers (8.12) Sections 8.5 and 8.6 to 8.12 as 
Applicable

© Fire Smarts LLC.  All rights reserved.  
Water Distribution
EXCEPT

Not withstanding the obstruction rules provided in Chapter 8, it


is not intended or expected that water will fall on the entire
floor space of the occupancy.

When obstructions or architectural features interfere with the


sprinkler’s spray pattern, such as columns, angled walls, wing
walls, slightly indented walls, and various soffit configurations,
shadowed areas can occur. Where small shadowed areas are
formed on the floor adjacent to their referenced architectural
features, those shadowed areas are purely on paper and do not
take into account the dynamic variables of sprinkler discharge.

A.8.1.1(3)
© Fire Smarts LLC.  All rights reserved.  
Shadow Areas

Pendent or Upright
Spr
Shadow Area

Shadow Area

© Fire Smarts LLC.  All rights reserved.  
Shadow Areas

Shadow Area Shadow Area

Sidewall Spr

© Fire Smarts LLC.  All rights reserved.  
Basic Obstruction Rule

DO NOT OBSTRUCT THE 
SPRINKLER

© Fire Smarts LLC.  All rights reserved.  
Basic Obstruction Rule

© Fire Smarts LLC.  All rights reserved.  
Detailed Obstruction Rule

DO NOT OBSTRUCT THE SPRINKLER IN A 
MANNER THAT:
UNACCEPTABLY IMPACTS 
CONTROL/SUPPRESSION EFFECTIVENESS 
OF THE SPRINKLER

© Fire Smarts LLC.  All rights reserved.  
General Obstruction Rules 8.5.5
General Format
 8.5.5.1 Performance Objectives
 8.5.5.2 Obstructions to Discharge Pattern 
Development
 8.5.5.3 Prevent Discharge from Reaching the Hazard 
(4 ft Rule)
 8.5.6 Clearance (18”/36” Rule)

© Fire Smarts LLC.  All rights reserved.  
8.5.5 Obstructions to Sprinkler Discharge
General Two Zone Criteria

1 18” A Beam Rule / Times


Sprinkler Rule

2 B Below Sprinkler Rule

© Fire Smarts LLC.  All rights reserved.  
Spray Pattern

Varies With Different 
Sprinklers
© Fire Smarts LLC.  All rights reserved.  
Spray Pattern

Varies With Applied 
Pressure
© Fire Smarts LLC.  All rights reserved.  
8.5.5.2 Obstructions to 
Sprinkler Discharge Pattern Development
Continuous and noncontinuous obstructions ≤18 in. 
below the sprinkler deflector that prevent the 
discharge pattern from developing must comply with 
8.5.5.2. 
1 A Beam Rule / Times Rule

8.5.5.2.1
© Fire Smarts LLC.  All rights reserved.  
8.5.5.2 Obstructions to 
Sprinkler Discharge Pattern Development
Sprinklers must be positioned in accordance with the minimum 
distances and special requirements of Section 8.6 through 8.12 
so that they are sufficiently away from obstructions such as truss 
webs and chords, pipes, columns and fixtures.

1 A Beam Rule / Times Rule

Also Sends User to 8.6 through 8.12
for Specific Rules – Note: CMSA and ESFR Rules  8.5.5.2.2
extend this depth to 24 to 36 in.
© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard
Continuous or noncontinuous obstructions that interrupt the 
water discharge in a horizontal plane more than 18 in. below the 
sprinkler deflector in a manner to limit the distribution from 
reaching the protected hazard must comply with 8.5.5.3

B
2

8.5.5.3 Provides Some General Rules 8.5.5.3

© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard
4 ft Rule
Sprinklers must be installed under fixed obstructions >4 ft in 
width.

Be Careful, General Rules of 8.5.5 
are Modified for CMSA and ESFR

8.5.5.3.1

© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard
4 ft Rule

© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard

4 ft Rule
Roof

Wall Wall OK?

Floor

© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard
4 ft Rule
Roof

Wall Wall OK?

Floor

4’-2”

© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard

4 ft Rule

© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard
4 ft Rule
Roof

OK?

Floor

© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard

4 ft Rule
Roof

OK?
Floor

© Fire Smarts LLC.  All rights reserved.  
Multiple Adjacent Obstructions

Many Small Obstructions on 
One Large One?

Only Addressed for ESFR Sprinklers (8.12.6.3.3 in the 
2016 Edition) – Must Separate Individual Components 
by 3X the Width of the Adjacent Individual 
Components OR Consider as a Single Obstruction

© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard
Exceptions:
 Sprinkler are not be required under noncombustible 
obstructions >4 ft wide where the bottom of the obstruction 
is ≤24 in. above the floor or deck. (New to the 2016 Edition, 
8.5.5.3.1.4)
 Sprinklers are not required under obstructions that are not 
fixed in place, such as conference tables.

8.5.5.3.2
© Fire Smarts LLC.  All rights reserved.  
8.5.5.3 Obstructions that Prevent 
Discharge from Reaching the Hazard
4 ft Rule

Is this an obstruction that needs sprinklers 
beneath it?

© Fire Smarts LLC.  All rights reserved.  
Obstructions that Prevent Discharge from 
Reaching the Hazard

Is this something that needs 
sprinklers in it?
© Fire Smarts LLC.  All rights reserved.  
Open Grid Ceiling

 ≥1/4” openings in least dimension
 Depth of material ≤ the least dimension
 70% open
 Light Hazard Clearance
 ≤10 ft x 10 ft Clearance of ≥18 in.
 ≤10 ft x 12 ft Clearance of ≥ 24 in.
 >10 ft x 12 ft Clearance of ≥ 36 in.
 Ordinary Hazard Clearance
 ≤10 ft x 10 ft Clearance of ≥24 in.
 >10 ft x 10 ft Clearance of ≥36 in.

8.15.14
© Fire Smarts LLC.  All rights reserved.  
Drop Out Ceiling

 Listed
 Not allowed beneath QR or EC sprinklers 
unless specifically Listed for such 
application

8.15.15
© Fire Smarts LLC.  All rights reserved.  
In‐Rack Exception
Exceptions:
Obstructions to In‐Rack Sprinkler Discharge – In‐rack sprinklers 
are not be required to meet the obstructions criteria  and 
clearance from storage requirements of 8.5.
In‐rack sprinklers do have requirements for distance above 
storage, below beam and spacing from the support upright in 
the storage criteria Chapters

8.13.5

© Fire Smarts LLC.  All rights reserved.  
Small Closet/Compartment Exception
Exceptions:
Closets – In all closets and 
compartments, including those 
closets housing mechanical 
equipment, that are not larger than 
400 ft3 in size, a single sprinkler at 
the highest ceiling level is sufficient 
without regard to obstructions or 
minimum distance to the wall. 

8.5.5.4

© Fire Smarts LLC.  All rights reserved.  
HVLS Fans
HVLS fans permitted and not be considered an obstruction if:
 ≤24 ft diameter
 Hub centered approximately between 4 sprinklers
 Vertical clearance of ≥3 ft
 Fans interlocked to shutdown within 90 sec of water flow

11.1.7/12.1.4.1

© Fire Smarts LLC.  All rights reserved.  
Sprinkler Frame Arms

Upright sprinklers must have their frame arms installed


parallel to the branch line unless specifically listed for
another orientation

Intended to minimize the obstruction to the discharge


pattern

8.3.1.3

© Fire Smarts LLC.  All rights reserved.  
Head Guards 

Guards utilized to protection sprinklers from 
mechanical injury must be listed for use with the 
sprinkler

6.2.8
© Fire Smarts LLC.  All rights reserved.  
General Clearance to
Storage Rules
Clearance Req’d from the Top of Storage to the Sprinkler 
Deflector
 ≥18 in.
 Greater clearance when required by another Standard
 ≥36 in. for Special Sprinklers (CMSA/ESFR)
 <18 in. if proven by large‐scale fire test
 ≥36 in. for Rubber Tire Storage

8.5.6

© Fire Smarts LLC.  All rights reserved.  
SSU/SSP&ECU/ECP Obstruction Rules 
8.6.5/8.8.5 General Format
 8.6.5.1/8.8.5.1 Performance Objectives (Beam/Soffit Rules)
 8.6.5.2/8.8.5.2 Impaired Discharge Pattern Development 
(3X/4X) and Suspended/Floor Mounted Obstruction Rules)
 8.6.5.3/8.8.5.3 Prevent Discharge from Reaching the Hazard   
(4 ft Rule)
 8.6.6/8.8.6 Clearance (18” Rule)

© Fire Smarts LLC.  All rights reserved.  
8.6.5.1 – SSU/SSP Beam Rule

Ceiling

B
Obstruction

8.6.5.1.2(1)
Figure 8.6.5.1.2(a) and Table 8.6.5.1.2

© Fire Smarts LLC.  All rights reserved.  
8.6.5.1 – SSU/SSP Beam Rule

100% 90% 70% 50% 70% 90% 100%

% of Flow

© Fire Smarts LLC.  All rights reserved.  
8.8.5.1 – ECU/ECP Beam Rule

Ceiling

B
Obstruction

8.8.5.1.2(1)
Figure 8.8.5.1.2(a) and Table 8.8.5.1.2

© Fire Smarts LLC.  All rights reserved.  
8.8.5.1 – ECU/ECP Beam Rule

80
70

30 40 50 60

Pressure 
Driven Flow

© Fire Smarts LLC.  All rights reserved.  
8.6.5.1 – SSU/SSP Beam Rule
8.8.5.1 – ECU/ECP Beam Rule
Ceiling

Obstruction

≤ 4 ft

≤1/2 S ≤1/2 S
CL

8.6.5.1.2(2)
8.8.5.1.2(2)

© Fire Smarts LLC.  All rights reserved.  
8.6.5.1 – SSU/SSP Soffit Rule
8.8.5.1 – ECU/ECP Soffit Rule
Soffit
Obstruction
Ceiling

A D A D 8 in. B

D 30 in.

8.6.5.1.2(3)
Wall
Figure 8.6.5.1.2(b)
8.8.5.1.2(3)
Figure 8.8.5.1.2(b)

© Fire Smarts LLC.  All rights reserved.  
8.6.5.1 – SSU/SSP Soffit Rule
8.8.5.1 – ECU/ECP Soffit Rule
Soffit
Obstruction
Ceiling

≤24 in.

≤1/2 S
Wall
½ of 4 ft Rule
8.6.5.1.2(4)
Figure 8.6.5.1.2(c)
8.8.5.1.2(4)
Figure 8.8.5.1.2(c)

© Fire Smarts LLC.  All rights reserved.  
8.6.5.2 – SSP/SSU 3X Rule

Ceiling

Open Web Steel or A 3C or 3D


Wood Truss
A Use Greater of C or D
≤18 in.
Max. Required A 24 in.
C

8.6.5.2.1.3
Figure 8.6.5.2.1.3(b)

© Fire Smarts LLC.  All rights reserved.  
8.8.5.2 – ECP/ECU 4X Rule

Ceiling

Open Web Steel or A 4C or 4D


Wood Truss
A
≤18 in.
Use Greater of C or D
Max. Required A 36 in.
C

NOTE: 
EC Sprinklers Are Only Permitted With Truss/Bar  8.8.5.2.1.3
Joist That Have Web Members ≤1 in. Unless  Figure 8.8.5.2.1.3(b)
Truss/Bar Joist Are Spaced >7½ ft O/C – 8.4.3(3) 

© Fire Smarts LLC.  All rights reserved.  
8.6.5.2 – SSP/SSU 3X Rule

Vertical Obstruction
A 3C or 3D
Sprinkler
C Use Greater of C or D
No Max. for A
D A

8.6.5.2.1.3
Figure 8.6.5.2.1.3(a)

© Fire Smarts LLC.  All rights reserved.  
8.8.5.2 – ECP/ECU 4X Rule

Vertical Obstruction
A 4C or 4D
Sprinkler
C Use Greater of C or D
No Max. for A
D A

8.8.5.2.1.3
Figure 8.8.5.2.1.3(a)

© Fire Smarts LLC.  All rights reserved.  
8.6.5.2 – SSP/SSU 3X Rule

Ceiling

Open Web Steel or


Wood Truss C
A

A 3C or 3D
Don’t Forget to Check the 
Use Greater of C or D Web Member

8.6.5.2.1.3
Figure 8.6.5.2.1.3(B)

© Fire Smarts LLC.  All rights reserved.  
8.8.5.2 – ECP/ECU 4X Rule
Ceiling

Open Web Steel or


Wood Truss C
A

A 4C or 4D
Don’t Forget to Check the 
Use Greater of C or D Web Member

8.8.5.2.1.3
Figure 8.8.5.2.1.3

© Fire Smarts LLC.  All rights reserved.  
8.6.5.2 – SSP/SSU 3X Rule
8.8.5.2 – ECP/ECU 4X Rule
The rules of known as the “Three/Four Times Rule” have been 
written to apply to obstructions where the sprinkler can be 
expected to get water to both sides of the obstruction without 
allowing a significant dry shadow on the other side of the 
obstruction. This works for small non‐continuous obstructions 
and for continuous obstructions where the sprinkler can throw 
water over and under the obstruction, such as the bottom chord 
of an open truss or joist. …

A.8.6.5.2.1.3
A.8.8.5.2.1.3

© Fire Smarts LLC.  All rights reserved.  
Exceptions to SSP/SSU 3X Rule

For light and ordinary hazard occupancies, structural 
members only are required to be considered when 
applying the requirements of 8.6.5.2.1.3. 

Allowance Not Included For Any Other 
Sprinkler Types

8.6.5.2.1.4

© Fire Smarts LLC.  All rights reserved.  
Exceptions to SSP/SSU 3X Rule

The intent of 8.6.5.2.1.4 to exempt nonstructural 
elements in LH and OH occupancies from the 
obstruction criteria commonly known as the “Three 
Times Rule”. However, the other obstruction rules, 
including the “Beam Rule” (8.6.5.1.2) and “Wide 
Obstruction Rule” (8.6.5.3.3) still apply. If the 
obstruction is so close to a sprinkler that water cannot 
spray on both sides, it is effectively a continuous 
obstruction as far as the sprinkler is concerned and the 
Beam Rule should be applied.
A.8.6.5.2.1.4

© Fire Smarts LLC.  All rights reserved.  
Exceptions to
SSP/SSU 3X&ECU/ECP 4X Rules
Open Web Steel or
Wood Truss
Ceiling

≤1/2 S ≤1/2 S
CL

8.6.5.2.1.5
8.8.5.2.1.4
© Fire Smarts LLC.  All rights reserved.  
Exceptions to
SSP/SSU 3X&ECU/ECP 4X Rules
Y ≥24 in.
Ceiling O/C

X ≥20 in.
apart
X/2

CL Open Truss with ≤4 in. 
Member Dimensions
Typical 2x4 Truss

8.6.5.2.1.6
8.8.5.2.1.5

© Fire Smarts LLC.  All rights reserved.  
Exceptions to
SSP/SSU 3X 4X Rules
Open Truss/Bar Joist
Ceiling

≥6 in. C
D

CL A 3C or 3D

≤8 in.
Use Greater of C or D

8.6.5.2.1.7

© Fire Smarts LLC.  All rights reserved.  
Exceptions to
ECU/ECP 4X Rules
Open Truss/Bar Joist
Ceiling

≥6 in. C
D

CL A 4C or 4D

≤8 in.
Use Greater of C or D

8.8.5.2.1.6

© Fire Smarts LLC.  All rights reserved.  
Exceptions to
SSU 3X & ECU 4X Rules
The 3X and 4X rules do not apply to sprinkler system 
piping less than 3 in. in diameter
Upright

≤3 in. (nominal) Pendent

≤3 in. (nominal)

8.6.5.2.1.8
8.8.5.2.1.7

© Fire Smarts LLC.  All rights reserved.  
SSU Sprig Length
What is the required sprig length needed?
Apply 3X Rule: Apply Bottom Chord of Truss 
3 x 4 in. = 12 in. Rule = 6 in.

Apply 3X Rule:
?
3 x 4.5 in. = 13.5 in.

4 in Pipe

© Fire Smarts LLC.  All rights reserved.  
Exceptions to
SSP/SSU 3X ECU/ECP 4X Rules
The 3X and 4X rules do not apply to sprinklers 
positioned with respect to obstructions in accordance 
with 8.6.5.1.2/8.8.5.1.2 (Beam/Soffit Rule).

Acceptable if Arrangement Complies with 
the Beam/Soffit Rules

8.6.5.2.1.9
8.8.5.2.1.8

© Fire Smarts LLC.  All rights reserved.  
Exceptions to
SSP/SSU 3X ECU/ECP 4X Rules
Sprinklers are permitted to be placed without regard to
blades of ceiling fans less than 60 in. in diameter,
provided the plane view of the fan is at least 50% open.

8.6.5.2.1.10
8.8.5.2.1.9
© Fire Smarts LLC.  All rights reserved.  
SSP/SSU&ECU/ECP Suspended or Floor 
Mounted Vertical Obstructions
Ceiling

B
A
Applies Only to Light
Hazard Occupancies

Floor
Freestanding Obstruction –
Privacy Curtains, Freestanding
Partitions, Room Dividers, Etc.

8.6.5.2.2
Figure 8.6.5.2.2, Table 8.6.5.2.2
8.8.5.2.2
Figure 8.8.5.2.2, Table 8.8.5.2.2
© Fire Smarts LLC.  All rights reserved.  
SSP/SSU&ECU/ECP Suspended or
Floor Mounted Vertical Obstructions
≥70% Open Mesh
Ceiling
?
≥22 in.

Applies Only to Light


Hazard Occupancies –
Intended for Hospitals

Floor
Suspended Obstruction –
Privacy Curtains, Freestanding
Partitions, Room Dividers, Etc.

8.6.5.2.2.1
Figure 8.6.5.2.2
8.8.5.2.2.1
Figure 8.8.5.2.2
© Fire Smarts LLC.  All rights reserved.  
SSP/SSU & EC Obstructions that Prevent 
Discharge from Reaching the Hazard
4 ft Rule
Roof

>18 in.

≤4 ft

Floor

The Same As General 
Rules in 8.5.5.3

8.6.5.3
8.8.5.3
© Fire Smarts LLC.  All rights reserved.  
SSU/SSP & ECU/ECP 
Clearance to Storage Rules
Use General Rules +
 Storage on shelves against a wall can extend to <18 
in. below the deflector provided the sprinkler is not 
directly above the storage
 The allowance for application of such with EC 
sprinklers is through reference back to 8.6.6.2 in 
A.8.8.6.

8.6.6
8.8.6

© Fire Smarts LLC.  All rights reserved.  
Shelf Storage Against a Wall
<18 in. Clearance 
≤1/2 S Roof
Roof

Storage
Shelf Storage Against the Wall
Against the Wall

Floor
Floor ?
≤30” – Shelf Storage Definition?

© Fire Smarts LLC.  All rights reserved.  
SSW/ECSW Obstruction Rules 8.7.5/8.9.5 
General Format
 8.7.5.1/8.9.5.1 Performance Objectives (Beam/Soffit
Rules)
 8.7.5.2/8.9.5.2 Impaired Discharge Pattern Development
(3X/4X and Suspended/Floor Mounted Obstruction Rules)
 8.7.5.3/8.9.5.3 Prevent Discharge from Reaching the
Hazard (4 ft Rule)
 8.7.6/8.9.6 Clearance (18” Rule)

Rules Are the Similar to Upright and 
Pendent Sprinklers – In the Interest of 
Time We’ll Only Look at a Few Items

© Fire Smarts LLC.  All rights reserved.  
SSW Clearance to Storage Rules
Use General Rules +
 Storage on shelves against a wall can extend to <18 
in. below the deflector provided the sprinkler is not 
directly above the storage through reference back to 
8.6.6.2 in A.8.7.6
 No specific rules in 8.9 for ECSW for clearance

8.7.6

© Fire Smarts LLC.  All rights reserved.  
Residential Obstruction Rules 8.10.6 
General Format
 8.10.6.1 Performance Objectives (Beam/Soffit Rules)
 8.10.6.2 Impaired Discharge Pattern Development (4X
Rules Are the Same As Indicated for EC 
and Suspended/Floor Mounted Obstruction Rules)
Upright, Pendent and Sidewall Sprinklers
 8.10.6.3 Prevent Discharge from Reaching the Hazard
(4 ft Rule) Additionally, Always Check the 
Manufactures Installation Guide and Listing 
 No Storage Clearance Rules
Criteria

© Fire Smarts LLC.  All rights reserved.  
CMSA Obstruction Rules 8.11.5
General Format
 8.11.5.1 Performance Objectives (Beam Rules)
 8.11.5.2 Impaired Discharge Pattern Development (3X
Rule)
8.11.1.1 Indicates that  the Manufacturer’s 
 8.11.5.3 Prevent Discharge from Reaching the Hazard
Installation Instructions are to be used if different 
(4 ft Rule) than  Section 8.11.

 8.11.6 Clearance (36” Rule)


Some may indicate the use of ESFR Rules

© Fire Smarts LLC.  All rights reserved.  
8.11.5.1 – CMSA Beam Rule

Ceiling

B
Obstruction

8.11.5.1.2
Figure 8.11.5.1.2 and 
Table 8.11.5.1.2
© Fire Smarts LLC.  All rights reserved.  
CMSA Obstructions that Prevent 
Discharge from Reaching the Hazard
(>2 ft Rule) 
Cannot Extend Above
Sprinkler
Roof

B
Obstruction Entirely
Below Sprinkler
A >24 in.

Since B is Measured to the Bottom of the 
Obstruction and It Can’t Extend Above the 
Sprinkler B=Max. Obstruction Depth As Well 

8.11.5.3.2 and 
Figure 8.11.5.3.2
© Fire Smarts LLC.  All rights reserved.  
CMSA Obstructions that Prevent Sprinkler 
Discharge from Reaching the Hazard

(>2 ft Rule)
Comparison to Beam Rule
Ceiling

8” 6”

35” 35”

How Can This Be RIGHT?

© Fire Smarts LLC.  All rights reserved.  
CMSA Obstructions that Prevent Sprinkler 
Discharge from Reaching the Hazard

Roof
(2 ft Rule) 
≤24 in.
>24 in.

≤12 in.

>18 in.
½S ½S
CL

Storage

8.11.5.3.4 and 
Figure 8.11.5.3.4
© Fire Smarts LLC.  All rights reserved.  
CMSA Obstructions that Prevent Sprinkler 
Discharge from Reaching the Hazard

(1 ft Rule) 
Roof

≥36 in. ≥36 in.

≤6 in.
CL

≤12 in. ≤12 in.

8.11.5.3.5 and 
Figure 8.11.5.3.5

© Fire Smarts LLC.  All rights reserved.  
CMSA Obstructions that Prevent 
Discharge from Reaching the Hazard

(1 ft & 2 ft Rules) 
Roof

24
24 in.
C
L

36 in.
12 12

CL

© Fire Smarts LLC.  All rights reserved.  
8.11.6 CMSA Clearance
to Storage Rules
Use General Rules +
 The clearance between the deflector and the top of 
storage must be 36 in. or greater.

8.11.6

© Fire Smarts LLC.  All rights reserved.  
ESFR Obstruction Rules 8.12.5
General Format
 8.12.5.1 Obstructions at or Near Ceiling  (Beam Rule)
 8.12.5.2 Isolated Obstructions Below Sprinklers
 8.12.5.3 Continuous Obstruction Below Sprinklers
 8.12.6 Clearance (36” Rule)

8.12.5.1.3, 8.12.5.2(5) and 8.12.5.3.6 all indicate 
that special obstruction rules are to be applied in 
accordance with the listing of the sprinkler which 
may be different than 8.12.5

© Fire Smarts LLC.  All rights reserved.  
8.12.5.1 – ESFR Beam Rule
Ceiling

B
Obstruction

8.12.5.1.1
Figure 8.12.5.1.1 and 
Table 8.12.5.1.1
© Fire Smarts LLC.  All rights reserved.  
Continuous vs Noncontinuous
Obstructions
 Continuous Obstructions An obstruction at or below 
the level of the sprinkler deflector that affects the 
discharge pattern of two or more sprinklers.
 Noncontinuous Obstructions An obstruction at or 
below the level of the sprinkler deflector that affects 
the discharge pattern of a single sprinkler.

3.3.18.1
3.3.18.2

© Fire Smarts LLC.  All rights reserved.  
8.12.5.2 – ESFR Isolated Obstructions
Below Sprinkler 
Cannot Extend Above
Sprinkler
Roof

≥12” ≤24”

8.12.5.2(2)
© Fire Smarts LLC.  All rights reserved.  
ESFR Isolated/Continuous Obstructions 
Below Sprinklers
Roof

≥24 in.

≤2 in.

8.12.5.2(4)
8.12.5.3(2)
© Fire Smarts LLC.  All rights reserved.  
8.12.5.3.2  – ESFR Bottom Chord of Bar 
Joist/Truss  Rule
Ceiling

Open Web Steel or


Wood Truss

≥12”

Does not apply for Upright 
ESFR where directly over the 
bottom chord that is ≤4 in. 8.12.5.3.2

© Fire Smarts LLC.  All rights reserved.  
8.12.6 ESFR Clearance to Storage Rules
Use General Rules +
 Clearance to Storage. (ESFR Sprinklers) The clearance 
between the deflector and the top of storage shall be 
36 in. or greater.

8.12.6

© Fire Smarts LLC.  All rights reserved.  
Example
24” Wide Light Fixture

Clearly Less than 24 in.
Non Compliant

6” from Spr to Light Fixture

© Fire Smarts LLC.  All rights reserved.  
Example

The position of the sprinkler w/respect 
to the obstruction
AND
The positon of the protected materials 
w/respect to the obstruction
BOTH MATTER

© Fire Smarts LLC.  All rights reserved.  
Another Example

The position of the sprinkler w/respect to 
the obstruction
AND
The positon of the protected materials 
w/respect to the obstruction
AND
The arrangement and type of protected 
materials 
IT ALL MATTERS

© Fire Smarts LLC.  All rights reserved.  
Conclusion

© Fire Smarts LLC.  All rights reserved.  