b.4. Environmental
1. Emission
The Contractor shall guarantee that each parameter of
emission resulted from operated power plant comply with CDA
Decree of Minister of Environment, Republic of lndonesia M-093
No. 21 year 2008. Furthermore, time and location of
monitoring also observation method of emission must be
comply with the Decree of BApEDAL principal, Republic of
lndonesia, No. 205 year 199G.
2. Noise
The contractor shall guarantee that noise resulted from
operated power plant shalr comply with the regulation
requirement of the noise level for the local area surrounding
the power plant. The method of measurement, calculation
and evaruation of noise revel, wiil be ruled by Decree of
Minister of Environment, Repubric of rndonesia, No. 4g year
1 996,
Sub-Section 4.3.6 - 7
t
BOOK il
PART 4TECHNICAL REQUIREMENT
Section 4.3 General Technical Requirements
Sub-Section 4.3.6 Performance Testing, Guarantees and First lnspection
a.1. Test schedule will be prepared by the Contractor and the test
shall be conducted in accordance with the "PERFORMANCE
TEST PROCEDURE" submitted by the Contractor and
approved by the Owner and complying with the specified
guarantee conditions.
a.2. The Contractcr shall make the detailed test procedure which
covers all guarantee items based on the ouiline in this
specification, and shall submit it to the Owner for approval.
a.3. The detailed test procedure shall include the following items.
a.7. The Contractor has to repeat any test, if in the opinion the
Owner, the test was not performed properly.
. Test conditions
- The steam generator is operated automatically and maintains
main steam pressure and tenrperature at the specified value.
Other main factors such as excess air ratio, number of
burners, etc., shall be retained at the specified conditions.
- Blow off from steam generator and other parts are entirely
closed.
d. lnstrumentation accuracy
d.1 The high heating values of the fuels shall be determined in the
owner's laboratory and two other laboratories to be chosen
respectively one by the Owner, the other by the Contractor. ln
order to determine the specific consumptions of the plant, the
arithmetical mean value of the high heating values shall be
adopted.
d.? The Net Plant Heat Rate shall be corrected according to the
deviation of the following items to the specified conditions, by
approved correction curves:
^ f- I
"?,
BOOK il
PART 4 TECHNICAL REQUIREMENT
Section 4.3 General Technical Requirements
Sub-Section 4.3.6 Performance Testing, Guarantees and First lnspection
Cb=Gfw+Gss+Grhs
Where as:
e. Environmental Guarantees
General
. Emission
The contractor shall conduct Emission performance Test
on 75 7i, MCR
. Noise
e.2 Standards