Professional Documents
Culture Documents
Earthing Systems
In order to ensure protection of persons and continuity of service, conductors and live parts
of electrical installations should be «insulated» from the frames or enclosures connected to the
earth. Insulation is achieved by:
Insulating material which is a non-conducting material that provides electric isolation, it
meets two primary requirements:
o An electrical resistivity and a dielectric strength sufficiently high for the given
application.
o Adequate thermal and mechanical properties.
Clearances (spaces) in gases (e.g. in air) and crawling distances (concerning switchgear, to
prevent flashover on electrical switchgear), (this is the distance from the accessible side of
the electrical equipment enclosure to various wall construction types, or other electrical
equipment).
Insulation is characterized by specified voltages which, in accordance with standards, are
applied to new products and equipment:
Insulating voltage (highest network voltage);
Lightning impulse withstand voltage: overvoltage of external origin (1.2kV/50 µs
wave);
Power frequency withstand voltage: overvoltage of internal origin (2U + 1000 V for
1min).
Example for a LV PRISMA type switchboard:
Insulating voltage: 1,000 V;
Impulse voltage: 12 kV.
When a new installation is produced and commissioned, in accordance with the standards,
the risk of insulation faults is extremely small, as the installation ages, this risk however, increases
(1).
The insulation can be subject to various aggressions which give rise to insulation faults,
for example:
During installation
o mechanical deterioration of a cable insulator
During operation such as:
o dust with a varying degree of conductivity
o thermal ageing of insulators due to excessive temperatures caused by: climate, too
many cables in a duct, a poorly ventilated cubicle, harmonics, overcurrent, etc,
o The electrodynamics forces developed during a short-circuit, which may damage a
cable or reduce a clearance.
o The operating and lightning overvoltage,
o The 50 Hz return overvoltage, resulting from an insulation fault in MV.
Insulation fault normally results from a combination of these primary causes. This fault
can be either:
o Between the live conductors, in which case it becomes a short circuit (for example
phase to phase fault)
o Between live conductors and the exposed conductive parts or earth. A fault current
then flows in the protection conductor (PE) and/or in the earth.
System earthling arrangements in LV are mainly concerned by the second type of faults
which occur most frequently in loads and cables (1).
Whatever its cause, an insulation fault is a risk to persons, to life property and the
availability of electrical power
Table 2-1: Maximum times for maintenance of contact voltage as in standard IEC
60364 [2]
EENG465-handout Eng. Amani SAIED, Dr. Imane MAATOUK
Page 3
Chapter 2. Earthing Systems
Figure 2-3: Zones time/current of effects of AC current on human body when passing
from left hand to feet (2)
Some serious effects of current on human body are shown in Figure 2-4.
potential). So a level potential difference between the person’s right and left hands appears. Thus
an electric current circulates from its right hand to its left one.
Figure 2-8-a: The neutral point of the transformer is connected the Earth/Ground; the person’s
hand is in direct contact with a hot conductor. Shock current flows from the source through the
line and from person’s hand to the person’s leg through person’s body and find its returning
path to star point (source) through the general mass of earth (because neutral point is earthed).
The person is electrified.
Figure 2-8-b: The neutral is not earthed, but a poor/ broken down insulation ensures connection
to the earth (we are now in the same case as in a.); the person is electrified.
Figure 2-8-c: The neutral is not earthed but line capacitance with respect to the ground ensures
connection to the earth. As in case a. and b., the person is electrified.
Figure 2-8-d: The transformer neutral point is connected to the earth. There is an electric
potential difference between the two conductors (phase A and phase B), current flows from the
person’s hand 1 to the person’s hand 2 through its heart. This case of electric shock is fatal
because the heart is electrified.
Figure 2-8-e: The neutral is earthed; the floor of area is wet and conductive, the person’s hand
is in touch with a faulty appliance due to a bad insulation, current flows from the person’s hand
to the person’s leg, through person’s body, and return to the source through the earth. The
person is electrified.
Figure 2-8-f: The floor of the area is insulated but the connection to the earth is made by other
conductive material (ex: earthed tap). Current flows through the heart of person and find its
return path to the source through the conductive material. This case of electric shock is fatal
because the heart is electrified.
It is becoming increasingly vital to be more aware of this hazard. If the part in fault is
automatically disconnected to eliminate the fault, it can result in a risk for persons, for example:
Sudden absence of lighting,
Placing the equipment required for safety purposes out of service,
Economic Impact due to production loss. This risk must be overcome especially in
industrial facilities where some of the machines take long time to start and could be
costly to start.
Moreover, if the fault current is high, it can inflict damage, in the installations or the
loads, which in effect can lead to tardiness and maintenance costs
It can disturb sensitive equipment in case of a phase to earth faults, especially if they
are part of a low current system
Disconnecting over-voltages and/or the eruption of the phenomena of electromagnetic
radiation may lead to the malfunctioning or even the damage of some sensitive
equipment.
This is known to be the accidental contact of persons with a live conductor (phase or
neutral) or a normally live conductive element as explained in section 2.2.3.1. Two complementary
measures are commonly used as protection against the dangers of direct contact:
The physical prevention of contact with live parts by barriers, insulation,
inaccessibility, etc. (see Figure 2-9)
EENG465-handout Eng. Amani SAIED, Dr. Imane MAATOUK
Page 9
Chapter 2. Earthing Systems
Additional protection in the event that a direct contact occurs, despite or due to failure
of the above measures. This protection is based on residual-current operating device
with a high sensitivity (IΔn ≤ 30 mA) and a low operating time. These devices are
highly effective in the majority of case of direct contact, (see Figure 2-10).
Figure 2-9: example of physical prevention of contact with live parts (2)
As explained in section 2.2.3.1, electric shock occurs due to an indirect contact of a person
with accidentally energized metal frames. This accidental energizing is the result of an insulation
fault. A fault current flows and creates a potential rise between the frame and the earth, thus
causing a fault voltage to appear which is dangerous if it exceeds voltage U L (refer to section
2.2.3.1). Two levels of protective measures exist for this case:
While the terms are similar, each method, in fact, provides surge and lightning protection in its
own specific way.
2.4.1. Earthing
Under fault conditions the dead metal parts (the parts which does not carry current under
normal conditions) of an electrical installation such as frames, enclosures, supports, fencing etc.
may attain high potential with respect to ground. So that any person or stray animal touching these
or approaching these will be subjected to potential difference which may result in the flow of a
current through the body of the person or the animal of such a value as may prove fatal.
To avoid this, non-current carrying metal parts of the electrical system are connected to the
general mass of earth by means of an earthing system comprising of earth conductors to conduct
the fault currents safely to the ground. It is normally achieved by inserting ground rods or other
electrodes deep inside earth. So earthing means, connecting the dead parts of the installation to the
earth. Generally green wire is used for this. Electricity flows to earth via the path of least
resistance. If there is a fault in an electrical appliance and a live wire comes into contact with a
part of the appliance, this can cause a very dangerous situation. If you touch the machine, electric
current will flow from the electrified part of the machine through you as it follows its path to earth.
This can cause serious injury or even death. Earthing prevents this risk by the electrical current
with an alternative path in the event of an accident. This is the concept used when deploying
lightning rods to offer protection to tall buildings and structures in the event of a lightning strike.
2.4.2. Grounding
2.4.3. Bonding
Bonding is simply the act of joining two electrical conductors together. These may be two
wires, a wire and a pipe, or these may be two equipment. Bonding has to be done by connecting
of all the metal parts that are not supposed to be carrying current during normal operations to
bringing them to the same electrical potential. Bonding ensures that these two things which are
bonded will be at the same electrical potential. That means we would not get electricity building
up in equipment or between two different equipment. No current flow can take place between two
bonded bodies because they have the same potential.
Bonding, itself, does not protect anything. However, if one of those boxes is earthed there
can be no electrical energy build-up. If the grounded box is bonded to the other box, the other box
is also at zero electrical potential. Thus the primary reason for bonding is personnel safety, so
someone touching two pieces of equipment at the same time does not receive a shock by becoming
the path of equalization if they happen to be at different potentials.
The Second reason has to do with what happens if a phase conductor may be touched an
external metal part. The bonding helps to create a low impedance path back to the source. This
will force a large current to flow, which in turn will cause the breaker to trip. In other words,
bonding is there to allow a breaker to trip and thereby to terminate a fault. Bonding to electrical
earth is used extensively to ensure that all conductors (person, surface and product) are at the same
electrical potential.
When all conductors are at the same potential no discharge can occur. Bonding is achieved
by cad welding (exothermically welded connections to create a permanent bond) or bonding
connectors are attached to the appropriate parts, which mean that voltage is transferred via these
connectors rather than through you in the event of an accident. Bonding is shown in Figure 2-12.
In the Figure 2-13, the earthing of the appliance is broken. When the person touches the
faulty appliance, the fault current will circulate in two paths through the person body. Because the
man’s hand is connected to an earthed metal conductive, there is a level potential difference
between the man’s hand and both the man’s leg and other hand. The person is shocked.
Figure 2-13: Example of an electric shock in case of a broken ground of the appliance
Suppose now that the ground of the appliance is fixed, how it will protect the person against
the electric shock? (See Figure 2-14).
Under earthing system measures, metal covering bodies and enclosures of all equipment
are connected to each other as a grid by means of appropriate conductors to establish an equal zero
potential reference level among all points which may come in contact with persons.
Metal conduits and pipework (not part of the electrical installation) for water, gas,
heating, compressed-air, etc. and metal materials associated with them
5. Bonding conductor: A protective conductor providing equipotential bonding
6. Main earthing terminal: The terminal or bar provided for the connection of protective
conductors, including equipotential bonding conductors, and conductors for functional
earthing, if any, to the means of earthing.
7. The removable link: allows an earth-electrode-resistance check.
The LV earthing system characterizes the earthing mode of the secondary of the MV/LV
transformer and the means of earthing the installation frames. Identification of the system types is
therefore defined by means of 2 letters:
The first one is for the transformer neutral connection (2 possibilities):
o T for "connected" to the earth,
o I for "isolated" from the earth;
The second one is for the type of application on the frame connection (2 possibilities):
o T for "directly connected" to the earth,
o N for "connected to the neutral" at the origin of the installation, which is connected
to the earth.
The combination of these two letters gives three possible configurations:
TT: transformer neutral earthed, and frame earthed,
TN: transformer neutral earthed, frame connected to neutral,
IT: unearthed transformer neutral, earthed frame.
Note 1:
The TN system, as in IEC 60364 includes several sub-systems:
TN-C; if the N and PE neutral conductors are one and the same (PEN);
TN-S: if the N and PE neutral conductors are separate;
TN-C-S: use of a TN-S downstream from a TN-C (the opposite is forbidden, i.e. TN-
S-C). TN-S is compulsory for networks with conductors of a cross-section <10 mm2
Cu.
Note 2:
EENG465-handout Eng. Amani SAIED, Dr. Imane MAATOUK
Page 18
Chapter 2. Earthing Systems
Each earthing system can be applied to an entire LV electrical installation; however several
earthing systems may be included in the same installation (2).
2.4.8.1. TT system
i. Definition
One point at the supply source is connected directly to earth. All exposed- and extraneous-
conductive-parts are connected to a separate earth electrode at the installation as shown in Figure
2-17. This electrode may or may not be electrically independent of the source electrode. The two
zones of influence may overlap without affecting the operation of protective devices (2).
iv. Example:
Suppose that the resistance of the earth electrode of substation neutral Rn is 10 Ω and the
resistance of the earth electrode of the installation RA is 20 Ω.
a) Calculate the fault current Id
b) Calculate the fault voltage Uf
c) Calculate the maximum sensitivity of the RCD to be installed
Solution:
230
a) 𝐼𝑑 = 10+20=7.7A
230
b) 𝑈𝑓 = 20 × 20+10 = 20 × 7.7 = 154𝑉
50
c) 𝐼∆𝑛 = 20 = 2.5
So that a standard 300 mA RCD will operate and clear the fault with less than 1s (exact
operation time is specified by the standard) where a fault voltage exceeding appears on an
exposed-conductive-part.
2.4.8.2. TN system
i. Definition
The source is earthed as for the TT system (above). In the installation, all exposed and
extraneous-conductive-parts are connected to the neutral conductor. The several versions of TN
systems are shown below:
TN-C system (see Figure 2-19)
The neutral conductor is also used as a protective conductor and is referred to as a PEN
(Protective Earth and Neutral) conductor. This system is not permitted for conductors of less than
10 mm2 or for portable equipment. The PEN conductor is both the neutral conductor and at the
same time carries phase unbalance currents as well as 3rd order harmonic currents (and their
multiples) (2).
Caution: In the TN-C system, the “protective conductor” function has priority over the
“neutral function”. In particular, a PEN conductor must always be connected to the earthing
terminal of a load and a jumper is used to connect this terminal to the neutral terminal (2).
It is a dangerous voltage since it exceeds the limit safety voltage, even in dry atmospheres
(𝑈𝐿 = 50𝑉). The installation or part of the installation must then be automatically and promptly
de-energized (2).
iv. Example:
Suppose we have the system below shown in Figure 2-23, where the phase to neutral
voltage is equal to 230V.
a) Calculate ZS
b) Calculate the fault current Id
c) Calculate the fault voltage Uf
Solution:
a) The fault loop impedance ZS= ZAB+ZBC+ZCD+ZDE+ZEN+ZNA, if ZBC and ZDE
are the predominant, these are the impedances of two cables of 35m2 section and 50m
long so:
𝜌×𝐿
𝑍𝑆= 2 × = 64.3𝑚Ω
𝑆
b) The “instantaneous” magnetic trip unit adjustment of the circuit-breaker protecting this
circuit must be less than this short-circuit value so that positive operation in the shortest
time possible is assured.
230
𝐼𝑑 = = 3576𝐴
0.0643
Some authorities base such calculations on the assumption that a voltage drop of 20%
occurs in the impedance loop thus the fault current will be:
230
𝐼𝑑 = 0.8 × = 2860.8A
0.0643
230
c) 𝑈𝑓 = = 115𝑉
2
Figure 2-23: Example for a fault current calculation in case of a TN system (2)
2.4.8.3. IT system
i. Definition
IT system (isolated neutral)
No intentional connection is made between the neutral point of the supply source and earth
(see Figure 2-24). Exposed- and extraneous-conductive-parts of the installation are connected to
an earth electrode.
EENG465-handout Eng. Amani SAIED, Dr. Imane MAATOUK
Page 24
Chapter 2. Earthing Systems
The reasons for this form of power-source earthing are to fix the potential of a small
network with respect to earth (Zs is small compared to the leakage impedance) and to reduce the
level of overvoltage, such as transmitted surges from the MV windings, static charges, etc. with
respect to earth (2).
Figure 2-28: Fault current path for a first fault in IT system (2)
First Fault:
The first fault current will be then equal to:
0.8 × 𝑈𝑜
𝐼𝑑 = + 𝐼𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑖𝑣𝑒
𝑍𝐶
Where:
– 𝑈𝑜 = phase to neutral voltage
– 𝑍𝐶 = impedance of the circuit fault-current loop
– I capacitive is the vector sum of the capacitive currents in the two healthy phases. The
voltages of the healthy phases have (because of the fault) increased to √3 the normal
phase voltage, so that the capacitive currents increase by the same amount. These
currents are displaced, one from the other by 60°, so that when added vectorially, this
amounts to 3x capacitive current.
Second Fault:
On the appearance of a second fault, on a different phase, or on a neutral conductor, a rapid
disconnection becomes imperative. This will be similar to a phase to phase fault, the two circuits
involved in this short-circuit are assumed to be of equal length, with the same cross sectional area
conductors, the PE conductors being the same cross sectional area as the phase conductors. In such
a case, the impedance of the circuit loop will be twice that calculated for one of the circuits in the
TN case.
If one of the two faulty conductors is the neutral so the fault current will be:
0.8𝑈𝑜
𝐼𝑑 =
2 × 𝑍𝐶
Where:
– Uo = phase to neutral voltage
EENG465-handout Eng. Amani SAIED, Dr. Imane MAATOUK
Page 27
Chapter 2. Earthing Systems
Figure 2-29: Circuit breaker tripping on double fault situation when exposed-
conductive-parts are
connected to a common protective conductor (2)
While when exposed conductive parts are earthed either individually (each part having its
own earth electrode) or in separate groups (one electrode for each group), it is then possible for
the second earth fault to occur in a different group or in a separately earthed individual apparatus.
Additional protection to that described above for the first case, is required, and consists of a RCD
placed at the circuit breaker controlling each group and each individually-earthed apparatus.
The reason for this requirement is that the separate-group electrodes are bonded through
the earth so that the phase to phase short-circuit current will generally be limited when passing
through the earth bond by the electrode contact resistances with the earth, thereby making
protection by overcurrent devices unreliable. The more sensitive RCDs are therefore necessary,
but the operating current of the RCDs must evidently exceed that which occurs for a first fault (see
Figure 2-30). For a second fault occurring within a group having a common earth-electrode system,
the overcurrent protection operates, as described above for case 1.
iv. Example
An electrical installation is realized according to the following diagram:
Solution:
a) IT earthing scheme
b)
380
𝐼𝑑1 = = 0.315 = 315𝑚𝐴
1010
𝑈𝑑1 = 0.315 × 10 = 3.15𝑉
The maintenance department should eliminate this fault. To detect the fault use
permanent insulator monitor.
c)
d) Id2 is very high (limited by a very low resistance value (resistance of conductors).
Interruption must be done through circuit breaker.
In terms of the protection of persons, the three system earthing arrangements (SEA) are
equivalent if all installation and operating rules are correctly followed. Consequently, selection
does not depend on safety criteria. It is by combining all requirements in terms of regulations,
continuity of service, operating conditions and the types of network and loads that it is possible to
determine the best system(s). Selection is determined by the following factors:
Above all, the applicable regulations which in some cases impose certain types of SEA.
Secondly, the decision of the owner if supply is via a private MV/LV transformer (MV
subscription) or the owner has a private energy source (or a separate-winding transformer).
If the owner effectively has a choice, the decision on the SEA is taken following
discussions with the network designer (design office, contractor). The discussions must cover:
First of all, the operating requirements (the required level of continuity of service) and the
operating conditions (maintenance ensured by electrical personnel or not, in-house
personnel or outsourced, etc.)
Secondly, the particular characteristics of the network and the loads.
The scope of the TT distribution scheme is mainly located in public networks because of
the length of lines bound to a small section and, secondly, because it dispenses the distributor of
permanent control of earth among subscribers.
The field of application of the IT and TN systems is in the industrial networks. The TN
system combines clarity in all situations with the simplicity of the means used. This results in
EENG465-handout Eng. Amani SAIED, Dr. Imane MAATOUK
Page 31
Chapter 2. Earthing Systems
greater ease in meeting protective measures. The cost price of its installation remains lower than
other types of network. Operational maintenance is easy.
v. Examples:
TT Earthing scheme: very large network with high-quality earth electrodes for exposed
conductive parts (10 ohms max), secondary schools, LV distribution network, etc…
IT Earthing scheme: The need for a continuous power supply is constantly increasing in
hospitals, on ships, in manufacturing plants, process plants, data centers, control rooms,
airports, railway systems, transport systems, heating systems, cooling systems, etc. In
tunnels and below ground, lighting and ventilation must work faultlessly; submarine crews
as well as astronauts in space equally depend on a reliable power supply.
TN Earthing scheme: Distributed area (storms) (e.g. television or radio transmitter),
Network with high leakage currents (>500mA), very large network with low-quality earth
electrodes for exposed conductive parts (30 ohms)
i. Buried ring:
The ring (see Figure 2-32) should be buried around the perimeter of the excavation made
for the foundations. It is important that the bare conductor be in intimate contact with the soil. At
least four (widely-spaced) vertically arranged conductors from the electrode should be provided
for the installation connections and, where possible, any reinforcing rods in concrete work should
be connected to the electrode. The electrode must be at least 50 cm below the hard-core or
aggregate base for the concrete foundation. Neither the electrode nor the vertical rising conductors
to the ground floor should ever be in contact with the foundation concrete. For existing buildings,
the electrode conductor should be buried around the outside wall of the premises to a depth of at
least 1 meter. As a general rule, all vertical connections from an electrode to above-ground level
should be insulated for the nominal LV voltage (600-1000 V) (2).
It is often necessary to use more than one rod, in which case the spacing between them
should exceed the depth to which they are driven, by a factor of 2 to 3. The total resistance is then
equal to the resistance of one rod, divided by the number of rods in question. The approximate
resistance R obtained is:
1 𝜌
𝑅= ×
𝑛 𝐿
Where:
– L = the length of the rod in meters
– ρ = resistivity of the soil in ohm-meters (see “Influence of the type of soil” below)
– n = the number of rods
Table 2-3: Average resistivity (Ωm) values for approximate earth-elect (2)
2.4.10. How the current propagate in the earth:
Consequently, outside the region closest to the electrode (called resistance area), all the ground is
at the same potential (see Figure 2-34).
Due to the fact that earthing is a system designed to guarantee safety, its effectiveness
should be verified. The diffusion resistance value is the parameter normally considered to be the
most relevant one to test grounding system quality and its capacity to carry out its function
properly. The earth’s ground resistance impacts the effectiveness of shunting high voltage surges
from lightning and other sources to the earth. The generally accepted practice is to have the earth’s
ground resistance not exceed 25 ohms. However, to protect communication systems (cell phone
sites) and sensitive electronic installations (computers), the voltage dissipation capability of the
earth (earth ground resistance) might be required to be less than 3 ohms and in some cases less
than 1 ohm. Earth Resistance is the resistance existing between the electrically accessible part of
a buried electrode and another point of the earth, which is far away (see Figure 2-37). There must
always be removable links which allow the earth electrode to be isolated from the installation, so
that periodic tests of the earthing resistance can be carried out. To make such tests, two auxiliary
electrodes are required, each consisting of a vertically driven rod (2).
Ammeter method
Applied as shown in the Figure 2-38:
𝑈 1 1 1
𝑅𝑇 = ( + − )
2 𝑖1 𝑖3 𝑖2
Figure 2-39: Measurement of the resistance to the mass of earth of electrode (X) using
an earth electrode- testing ohmmeter (2)
D must be at least four to five times the longest dimension of the system under test. One or more
voltage probes are placed at a distance from the center of the system under test equal to 0.62 times
D. The meter displays the ratio of the probe voltage (with respect to the grounding system under
test over the injected current.
Lebanese case the maximum voltage to ground on ungrounded conductors must not exceed 240
volts. Below are listed some of the sections of this article.
Residential wiring system supplied by a grounded alternating current service must have a
grounding electrode conductor connected to the grounded service conductor (6).
Grounded (neutral) conductor of a residential service must run to the service disconnecting
means and be bonded (attached) to the disconnecting means enclosure (see Figure 2-53) (6).
Section 250.52 (A) includes the details and descriptions of grounding electrodes that are
required to be used for the grounding electrode systems (when present) as shown in Figure 2-54(6).
(A)(1) Metal underground water pipe in direct contact with the earth for 10 ft. or
more (3.0 m or more).
(A)(2) Metal frame of a building or structure, where effectively grounded, can be
used as a grounding electrode.
(A)(3) Concrete-encased electrode; it is an excellent choice
(A)(4) Ground ring encircling the house, in direct contact with the earth, consisting
of at least 20 feet (6.0 m) of bare copper conductor (at least 2 AWG) must be used.
(A)(5) Rod and pipe electrode commonly called “ground rods,” can be used.
(A)(6) Other listed electrodes
(A)(7) Plate electrodes can be used, but rarely are used in residential work.
(A)(8) Other local metal underground systems or structures.
The following systems and materials shall not be used as grounding electrodes (6):
Metal underground gas piping systems
Aluminum
If a ground ring is installed as the grounding electrode, bury it at least 30” (750 mm) deep.
Install rod and pipe electrodes so that at least 8 feet (2.44 m) of length is in contact with
the soil.
Bury plate electrodes at least 30” (750 mm) below the surface of the earth (6).
A single rod, pipe or plate shall be supplemented by an additional electrode of the type
listed in 250.52 (A). NEC provides an exception: If a single rod, pipe or plate electrode has a
resistance to earth of 25 ohms or less, the supplemental electrode shall not be required (6).
The electrode shall be installed such that at least 2.44 m (8 ft) of length is in contact with
the soil. It shall be driven to a depth of not less than 2.44 m (8 ft) except that, where rock bottom
is encountered, the electrode shall be driven at an oblique angle not to exceed 45 degrees from the
vertical or, where rock bottom is encountered at an angle up to 45 degrees, the electrode shall be
permitted to be buried in a trench that is at least 750 mm (30 in.) deep. The upper end of the
electrode shall be flush with or below ground level unless the aboveground end and the grounding
electrode conductor attachment are protected against physical damage as specified in other
sections. Figure 2-55 shows grounding rods installation (6).
Augment a single electrode that is a rod, pipe, or plate and does not have a resistance to
ground of 25 ohms or less, by one additional electrode of a type specified in 250.52 (A)(4) through
A(8) (see Figure 2-56) (6).
Install grounding electrode conductor in one continuous length without a splice. Splicing
is allowed only by irreversible compression-type connectors listed for the purpose or by the
exothermic (CAD Weld) welding process (see Figure 2-57) (6).
It specifies how to determine the size of the grounding electrode conductor. Table 250.66
of NEC (refer to Table 2-4) is used to size the grounding electrode conductor of a grounded AC
system and is based on the largest size service entrance conductor (6).
2.6. Conclusion
In this chapter we have studied about earthing system which is an essential element for the
electrical system security and safety. It is required to allow for protective devices to be activated
when there is an insulation fault. It ensures equipotentiality of conductive parts that can be accessed
simultaneously, with the potential in the surrounding soil in order to prevent people from being
exposed to hazardous voltages. Earthing system also helps to reduce electromagnetic interferences
and allows the lightning strike energy to be safely dissipated. Thus protection of person and
property is achieved as per the recommendations of the electric standards and regulations.
References
1. Electric, Schneider. Earthing System How To Choose The Right System Earthing Arragement.
France : Schneider Electric Industries SAS, 2009.
3. Dalziel, Professor C.F. Deleteriouis Effects of Electric Sosk. Geneva : s.n., 1961.
4. http://www.duncaninstr.com/Gr_article.htm. [Online]
5. http://www.ap-concepts.com/win_sgm_func.htm. [Online]