Professional Documents
Culture Documents
RED670
Line Differential protection IED
Line Differential Protection RED670
Application Areas
Multi-terminal lines with
communication to 4 remote line
ends
Multi-terminal lines with
transformers in the protected zone
Tapped lines
Tapped lines with transformers
Short lines
Cables and Long lines with
charging current compensation
Series compensated lines
Line Differential Protection RED670
Simple line differential protection application
Protected zone
RED RED
670 Comm. Channel 670
RED RED
670 670
RED
670 I3
I DiffL1 = I1L1 + I 2 L1 + I 3 L1
I Bias = max( I 1L1 , I 1L 2 , I 1L 3 , I 2 L1 , I 2 L 2 , I 2 L 3 , I 3 L1 , I 3 L 2 , I 3 L 3 )
Application examples
Id > Id >
Application examples tapped lines
Two terminal applications
2-winding power transformer with connected
small delta tertiary load. Two lines (cables).
CB 1 CB 2
Line 1 Line 2
D
CB 1 CB 2
Line 1
Line 2
Passive load
Application examples multicircuit lines
Three terminal application.
3-winding power transformer with small delta tertiary. Three lines (cables).
CB 3
CB 1 Line 3
Line 1
Line 2
D
CB 2
Line 2 Line 3
D
CB 2 CB 2
Line Differential Protection RED670
Biased Differential Protection Characteristic
Differential protection principle
Differential
Time tagged
Protection
instantaneous
algorithm
sampled values
id
All currents iin , iout & id are calculated from
phase current values from all line ends
Differential protection principle
Block
Block Trip
Line Differential Protection RED670
Double breaker switchyard application
Protected zone
RED RED
670 670
RED Communication
670
RED RED
670 670
RED
670 Communication
Considered phenomena:
Phase shift of the current through the transformer at different vector groups
The inability of many transformers to transform zero sequence currents
The inrush current, appearing at the energization of a transformer, will be detected
as a differential current it the transformer is within the protected zone
Deviation of tap changer position will cause false differential current to the
protection, if not compensated for
Line Differential Protection RED670
Application with power transformer in the
protected zone
Protected zone
RED RED
670 670
Communication
RED RED
Comm. Channel
670 IF 670
IF
Line Differential Protection RED670
Negative sequence current
Negative sequence currents will occur during all types of
faults, also for a transient period during three phase short
circuits
The fault point will serve as a source for negative sequence
current
Negative sequence current can be seen as normal phase
currents but with reverse phase rotation
In normal operation, under balance conditions, the negative
sequence current components are zero
Line Differential Protection RED670
Negative Sequence Source at Fault Point
Internal Fault
Protected zone
Fault Point
RED RED
670 Communication 670
I-
External Fault
Protected zone
Fault Point
RED RED
670 Communication 670
I-
Line Differential Protection RED670
Negative Sequence Current Fault Discriminator
I- Remote 1 I- Local
RED RED
I- Remote = I- Remote 1 + I- Remote 2 670
670
Studied
Terminal
90
RED 120 60
670
I- Remote 2
in opposite directions,
the fault is external. Minimum Operation I- Local I- : Reference
210
330
240 300
270
Line Differential Protection RED670
Negative Sequence Current Fault Discriminator
Calculation of negative Trajectory of local (Current Terminal 1) contribution to total neg. seq. diff. current
External 0.1
Internal
fault fault
region 0.2
210 330 declared
0.3 kA here 8 ms
after fault
0.4 kA
240 300
270
Local contribution to total negative sequence diff. current
Directional limit (within ± 60 degrees is an internal fault)
Line Differential Protection RED670
Transformer Inrush Current
current
in pu phase L3 current
10.0
5.0 CB
closes
iL1
iL2
0.0
iL3
-5.0
phase L1 current
0 20 40 60 80 100
time in ms
Primary Current
Secondary Current
90deg
360 o
Time coordination error ≤ 1 ms = 18 o ms
20ms
Line Differential Protection RED670
Time synchronizing with the echo method
T2 T3
A
B
T1 T4
(T2 − T1 ) + (T4 − T3 )
Time delay: Td =
2
Provided that send
(T1 + T4 ) − (T2 + T3 ) and receive delay
Clock difference: Δt = times are equal
2
Line Differential Protection RED670
LDCM communication parameters
Only one clock may
exist in the
communication
network
“CommSync”.
With G.703 this is
normally in the MUX
Analogue values are
sent as a 8 bit word
(256) based on setting:
“CompRange”
This means accuracy
will depend on current
level and the setting.
Around 3% is normal.
Line Differential Protection RED670
LDCM communication supervision
3000
2500
2000 Time error=0.4 ms
1500 Time error=0.2 ms
1000 Time error=0.1 ms
500
0
0 5 10 15 20 25
Fault current at external faults (kA)
Line Differential Protection RED670
Time synchronizing with the echo method
A B
D GPS
clock
GPS GPS
clock clock
A C
B
GPS
Maximum transmission time clock
Td < 40 ms
Line Differential Protection RED670
Communication principle
Protected zone
RED RED
670 670
Comm. Channels
Protected zone
RED RED
670 670
Comm. Channels
0 0 0 0 0 T 0 0 0 T 0 0 0
1 3
2 4
3 5
4 1
5 2
5 ms
Line Differential Protection RED670
Differential Protection function block
Pre-processing
Function blocks
Differential function
Remote current 1 DR
Analogue outputs
for DR channels
Remote current 2 DR 31-40
Line Differential Protection RED670
Local Criteria for security at communication problems
Startup element based on
• Phase-phase current variation
• Zero sequence current criterion
• Low voltage criterion
• Low current criterion
ΔIΦΦ> TIVD
0
IΦ< TID
0
Trip
Trip from the main &
protection logic
Line Differential Protection RED670
Local Criteria for security at communication problems
Features for the security logic (start up element):
Multiplexer Multiplexer
Telecom. Network
*) *)
G.703.E1 G.703.E1
Telecom. Network
64kbit/s 64kbit/s
Line Differential Protection RED670
Redundant communication channels
2-terminal line with single breaker connected to route switched
network via multiplexer, redundant channels
Telecom. Network
Telecom. Network
Primary channel
Secondary redundant channel
With redundant channels the primary channel normally is in operation.
If the primary channel becomes faulty the operation is switched over
to the redundant channel. If the primary is OK again it will take over
the operation after a time delay.
RED670 Functions
Sensitive directional EF protection (SDE)
for non-direct earthed systems
Detects:
IL1=0
broken line conductors
L1
L2 open poles of circuit
L3
breakers
BRC
Now with a supervision that
IL1=2*ILoadL1 one phase is low (<50% of Ip>)
L1
L2 to avoid problem on healthy
L3
parallel line taking over the
missing load
BRC
Function is programmable to:
trip a circuit breaker (normally avoided)
alarm the abnormal condition
RED670 Functions
4-step Earth fault protection (TEF)
A small increase of amplitude and angle error can be noticed with 1% setting.
The difference is minor and has no practical impact of the operating value.
RED670 hardware
Design of analogue channels
Delta sigma A/D converters
1 bits Æ 14 bit
Low
Mhz Æ6kHz
TRM
channel Low pass filter +
Supervision +
I1 6Khz Æ1.2kHz
Choice of branch
=> 20 bits
High A/D
Mhz Æ6kHz
Resulting frequency
response curve
IED670 Series - Fault locator
• Available information for the recorded disturbances:
– distance to fault
– phasors of currents and voltages
» before the fault
» during the fault
• Distance to fault can be recalculated for different
conditions (changing fault-loop or system parameters)
• Phasors of currents and voltages during the normal
operation (V, A meters)
• Additional information
¤ non-load compensated algorithm was used
E error, fault outside phase selectors
> fault located beyond the line, forward direction
IED670 Fault locator – Load compensation
l
ZL
Load import
F
I
F
R p
UA F
Load export
F
•Example on values per km
RSA+XSA A
IA
p*ZL (1-p)ZL (1-p)ZL B RSB+XS •OHL
B
• X1= 0.02+j0.45 ohm/km
I
F • X0= 0.8+j1.34 ohm/km
UA
R
F •Cable
• X1= 0.08+j0.23 ohm/km
• X0= 0.2+j0.18 ohm/km
GFL1 GFL1
L L
GFL2 D D GFL2
GFL3 C C GFL3
M M
IN IN
1 200 999 999 200 62.7 999 999 77.4 999 999 74.2 60.2 999 999 83.8 999 999 79.4
2 300 999 999 300 65.3 999 999 90.9 999 999 86.4 72.3 999 999 87.7 999 999 83.8
3 325 999 999 325 68.5 999 999 83.2 999 999 80 66.6 999 999 90.2 999 999 86.4
4 350 999 999 350 62.7 999 999 87.7 999 999 83.2 66.6 999 999 84.5 999 999 80
5 375 999 999 375 63.4 999 999 87 999 999 83.8 69.8 999 999 85.1 999 999 81.3
6 400 999 999 400 68.5 999 999 86.4 999 999 83.2 66.6 999 999 91.5 999 999 87
All associated
I>
START L1
1 out of 4 operating mode
breakers
START L2 t1
START L3
START 3ph t2
2 out of 4 operating mode
Different back-up trip times for
BFP
I> single and multi-pole faults
START L1
START L2 t1
START L3
START 3ph t2
BUS B
RED670 functions
Breaker Failure Protection (BFP) – Fast reset
Pre-filter
Adaptive current
Post-filter
0.5 * detection ASD
Stab zone
No false operation in
case of saturated CT
Maximum reset time
approx 1/2 cycle to
allow short back-up
tripping times.
ASD output
RMS output
RED670 functions – Auto Recloser
Input signals – typical
connections
CB ready
CB closed
Uhigh
27
SC/VC The dead line and Live bus
Ulow conditions are checked.
Uhigh and Ulow are verified
RED670 functions – Synchronizing/Synchro check
UAL Icap
25
dφ
SC/VC
dU
Paralleling (synchronism conditions are
checked
Δφ, Δf, ΔU and Uhigh are within set values
Synchronizing of asynchronous networks
is included
RED670 functions – Synchronizing/Synchro check
Setting parameters
U-Bus
U-Line
Energizing check
ΔU High voltage U> 50-120% of Ub
Low voltage U< 10- 80% of Ub
Operate time 80 ms (typical)
Δφ
Paralleling (Synchronism) Check
Frequency difference Δf < 3-1000mHz
Voltage difference ΔU < 2 - 50 % of Ub
Phase difference Δφ < 5 - 90o
Operate time 80 ms (typical)
Syncronizing
SYNC MaxFrequency diff Δf < 3-1000mHz
U-Bus
MinFrequency diff Δf < 3-1000mHz
Voltage difference ΔU < 2 - 50 % of Ub
Line
reference
Breaker closing time tBreaker 0.000-60.000 sec
Fuse fail
BLOCK voltage Accuracy of closing angle <2 deg
Accuracy of frequency measurement
about 0,5 mHz!
RED670 functions – Synchronizing/Synchro check
Synchrocheck – Voltage selection
1U B1Q B2Q
1U
UB1 UB2
SYN1
ULN1
3U
1U
1U
IED
UB1 UB2
SYN1 SYN2
ULN1
LN1Q
3U
RED670 Functions
Measurements
REx670
SVRx- XPx-
CVMMXU RANGE_XP
P HIGHHIGH
Q HIGH
NORMAL
S
AIM Preproc
I
LOW
LOWLOW
U
IEC 61850-8-1
CPx-
f For each value:
cos φ CMMXU .mag (magnitude
IL1 of reported
IL2 value)
AIM Preproc IL3 .range (normal
3I0 |high|low
VPx- Izs |high-high
Ins |low-low)
VMMXU
UL1L2
UL2L3
AIM Preproc UL3L1
3U0
Uzs
Uns
RED670 functions
Metering of Energy (MMTR)
REx670
SVRx-
CVMMXU MMTR
Pinst EAF
P EAR
Qinst ERF
AIM Preproc
Q ERR
S MaxDmd
IEC 61850-8-1
I MDP
U MDQ
f
cos φ
δ
RED670 functions
Out of step protection - 78
Measured
Impedance at
this instant of
time
RED670 functions
Out of step protection - 78