You are on page 1of 87

Allen Tan, ABB MY, SA Products, Indonesia Oct 2011

RED670
Line Differential protection IED
Line Differential Protection RED670

ƒ Application Areas
ƒ Multi-terminal lines with
communication to 4 remote line
ends
ƒ Multi-terminal lines with
transformers in the protected zone
ƒ Tapped lines
ƒ Tapped lines with transformers
ƒ Short lines
ƒ Cables and Long lines with
charging current compensation
ƒ Series compensated lines
Line Differential Protection RED670
Simple line differential protection application

Protected zone

RED RED
670 Comm. Channel 670

Conventional two terminal application


Line Differential Protection RED670
Differential and Bias quantities
Fundamental frequency current phasors
I1 I2

RED RED
670 670

RED
670 I3

Differential and Bias currents in phase L1:

I DiffL1 = I1L1 + I 2 L1 + I 3 L1
I Bias = max( I 1L1 , I 1L 2 , I 1L 3 , I 2 L1 , I 2 L 2 , I 2 L 3 , I 3 L1 , I 3 L 2 , I 3 L 3 )
Application examples

Power transformers can be applied within the protected zone

Id> Id > „ Small power transformers


without a line differential terminal
„ Time delayed differential function
Id > gives selective tripping for
secondary side faults
„ Instantaneous differential
function for faults on the line

Id > Id >
Application examples tapped lines
Two terminal applications
2-winding power transformer with connected
small delta tertiary load. Two lines (cables).
CB 1 CB 2
Line 1 Line 2
D

2-winding power transformer on tapped line.


Two lines (cables).

CB 1 CB 2
Line 1

Line 2

Passive load
Application examples multicircuit lines
Three terminal application.
3-winding power transformer with small delta tertiary. Three lines (cables).

CB 3
CB 1 Line 3
Line 1
Line 2
D
CB 2

Four terminal application.


2-winding power transformer, small delta tertiary.
Four lines (cables).
CB 1 CB 3
Line 1 Line 4

Line 2 Line 3
D
CB 2 CB 2
Line Differential Protection RED670
Biased Differential Protection Characteristic
Differential protection principle
Differential
Time tagged
Protection
instantaneous
algorithm
sampled values

Remote Line end E


Line end D
iin Σ I= O + iout
Communication Line end C
charging
Line end B current
Local anlogue Line end A2
inputs Line end A1

id
All currents iin , iout & id are calculated from
phase current values from all line ends
Differential protection principle

Remote Time tagged


Communication instantaneous
sampled phase
Local anlogue
currents values
inputs

Fourier Current Start


filter differential Trip
Transformer
inrush blocking
- second harmonic Transformer
Symmetrical
- wave block components interturn fault on
- 5 th harmonic -negative sequence off
2-20% of I base

Block
Block Trip
Line Differential Protection RED670
Double breaker switchyard application

Protected zone

RED RED
670 670

RED Communication
670

No external current summation gives secure application!


RED670, Application with up to 5 ends
Line Differential Protection RED670
Application with power transformer in the
protected zone
Protected zone

RED RED
670 670

RED
670 Communication

ƒ Considered phenomena:
ƒ Phase shift of the current through the transformer at different vector groups
ƒ The inability of many transformers to transform zero sequence currents
ƒ The inrush current, appearing at the energization of a transformer, will be detected
as a differential current it the transformer is within the protected zone
ƒ Deviation of tap changer position will cause false differential current to the
protection, if not compensated for
Line Differential Protection RED670
Application with power transformer in the
protected zone

Protected zone

RED RED
670 670
Communication

Often required application


Line Differential Protection RED670
Differential protection – Tap-off to small transformer
Protected zone instantaneous function

RED RED
Comm. Channel
670 IF 670

Protected zone delayed function


IF
50/51-1

IF
Line Differential Protection RED670
Negative sequence current
ƒ Negative sequence currents will occur during all types of
faults, also for a transient period during three phase short
circuits
ƒ The fault point will serve as a source for negative sequence
current
ƒ Negative sequence current can be seen as normal phase
currents but with reverse phase rotation
ƒ In normal operation, under balance conditions, the negative
sequence current components are zero
Line Differential Protection RED670
Negative Sequence Source at Fault Point

Internal Fault
Protected zone

Fault Point

RED RED
670 Communication 670
I-

External Fault
Protected zone

Fault Point

RED RED
670 Communication 670

I-
Line Differential Protection RED670
Negative Sequence Current Fault Discriminator
I- Remote 1 I- Local

RED RED
I- Remote = I- Remote 1 + I- Remote 2 670
670

Studied
Terminal

90

RED 120 60
670
I- Remote 2

ƒ If the two currents flow 150 30


in the same direction,
the fault is internal. External Fault Zone Internal Fault Zone
ROA
ƒ If the two currents flow 180

in opposite directions,
the fault is external. Minimum Operation I- Local I- : Reference

210
330

240 300

270
Line Differential Protection RED670
Negative Sequence Current Fault Discriminator

ƒ Calculation of negative Trajectory of local (Current Terminal 1) contribution to total neg. seq. diff. current

sequence current from No directional


90
120 60
fundamental phase test done:
neither
Excursion
current per CT grope external,
nor internal 150 15ms 30 from 0 deg
fault due to
gives stability against declared
26ms
transient
ct saturation
CT saturation 180
8ms
0

External 0.1
Internal
fault fault
region 0.2
210 330 declared
0.3 kA here 8 ms
after fault
0.4 kA
240 300
270
Local contribution to total negative sequence diff. current
Directional limit (within ± 60 degrees is an internal fault)
Line Differential Protection RED670
Transformer Inrush Current
current
in pu phase L3 current
10.0

5.0 CB
closes
iL1
iL2
0.0
iL3

-5.0

phase L1 current

0 20 40 60 80 100
time in ms

If Transformer in the zone: Inrush Current: Differential Current

Detection: 2nd Harmonic and 5th Harmonic

As in normal transformer differential protection


Line Differential Protection RED670
Transformer Overexcitation

If Transformer in the zone: Overexcitation: Differential Current

Detection: 5th Harmonic

As in normal transformer differential protection


Line Differential Protection RED670
Current Transformer Saturation

Primary Current

Secondary Current

High Degree of Harmonics (2nd and 5th)


Line Differential Protection RED670
Negative sequence discriminator - Functional Logic

ƒ Negative Sequence Fault Discriminator: Internal Fault


ƒ 2nd and 5threstrain function are overridden
ƒ The biased differential function operates without delay
(start)
ƒ Exception: Inrush current of transformer in the protected
zone: Special logic will detect this
ƒ Negative Sequence Fault Discriminator: External Fault
ƒ 2nd and 5th harmonic restrain is active, with cross blocking
function. This means that harmonics also in non-faulted
phase will block the function.
ƒ Temporarily (as long as external fault is declared plus 100
ms) the limit of differential current for operation will be
increased to the value of “IdminHigh”.
ƒ Negative Sequence Fault Discriminator: No Operation
ƒ Normal differential protection function with 2nd and 5th
harmonic restrain
Line Differential Protection RED670
Time synchronization

90deg

360 o
Time coordination error ≤ 1 ms = 18 o ms
20ms
Line Differential Protection RED670
Time synchronizing with the echo method
T2 T3
A

B
T1 T4

(T2 − T1 ) + (T4 − T3 )
Time delay: Td =
2
Provided that send
(T1 + T4 ) − (T2 + T3 ) and receive delay
Clock difference: Δt = times are equal
2
Line Differential Protection RED670
LDCM communication parameters
Only one clock may
exist in the
communication
network
“CommSync”.
With G.703 this is
normally in the MUX
Analogue values are
sent as a 8 bit word
(256) based on setting:
“CompRange”
This means accuracy
will depend on current
level and the setting.
Around 3% is normal.
Line Differential Protection RED670
LDCM communication supervision

Communication in MUX have with bad arrangement showed many repeated


incorrect messages with substitution (say 4 per 100 ms). With normal delays the
alarm is not picking up these problems. Above logic should be used, set time to
alarm e.g. 30 seconds and reset time 3-5 minutes.
Line Differential Protection RED670
Time synchronizing with the echo method

Virtual error in Ampere at different time deviation


(Synchronization error)

3000
2500
2000 Time error=0.4 ms
1500 Time error=0.2 ms
1000 Time error=0.1 ms
500
0
0 5 10 15 20 25
Fault current at external faults (kA)
Line Differential Protection RED670
Time synchronizing with the echo method

Virtual error in Ampere at different time deviations


(Synchronization error)
7000
6000
5000 Time error=1 ms
4000
Time error=0.8 ms
3000
2000 Time error=0.6 ms
1000
0
0 5 10 15 20 25
Fault current at external faults (kA)
Line Differential Protection RED670
Charging Current

Ic1 Idiff,false = Ic1 + Ic2 Ic2

RED Communication RED


670 670
Line Differential Protection RED670
Charging Current Compensation

ƒ Continuous estimation of differential current at no-fault


condition: Charging current
ƒ Pre-fault charging current estimation kept during faults
ƒ Subtraction of the false pre-fault differential currents
ƒ At low resistance faults the fault current is large:
dominating over the charging current: Error in the
charging current compensation has minor influence
ƒ At high resistive faults the voltage is maintained and
the charging current is close to the non-faulted case
Line Differential Protection RED670
Route switched networks with delay symmetry
ƒ The echo method allows for route switching with equal delay times for
send and receive

A B

Maximum transmission time


Td < 40 ms
Line Differential Protection RED670
Route switched network without delay symmetry
ƒ GPS system required for set up
ƒ GPS loss tolerated with:
ƒ Free-wheeling IED clocks
ƒ Fall back to the echo method

D GPS
clock
GPS GPS
clock clock
A C
B

GPS
Maximum transmission time clock
Td < 40 ms
Line Differential Protection RED670
Communication principle

5-terminal line with master-master system

Protected zone

RED RED
670 670

Comm. Channels

RED RED RED


670 670 670
Line Differential Protection RED670
Communication principle

5-terminal line with master-slave system

Protected zone

RED RED
670 670

Comm. Channels

RED RED RED


670 670 670
Line Differential Protection RED670

Differential Trip Security


ƒ Sampled values collected every ƒ Trip enabled with 5
ms consecutive sample sets
calculated to trip
ƒ Communication message sent
every 5 ms ƒ 1 or 2 messages required
depending on fault incidence
ƒ Each communication message
point
contains 5 sets of sampled values

0 0 0 0 0 T 0 0 0 T 0 0 0
1 3
2 4
3 5
4 1
5 2
5 ms
Line Differential Protection RED670
Differential Protection function block
Pre-processing
Function blocks

Differential function
Remote current 1 DR

Analogue outputs
for DR channels
Remote current 2 DR 31-40
Line Differential Protection RED670
Local Criteria for security at communication problems
Startup element based on
• Phase-phase current variation
• Zero sequence current criterion
• Low voltage criterion
• Low current criterion

IEC 61850 identification STSGGIO, ANSI device no 11

ΔIΦΦ> TIVD
0

I0> TZD Local side start-up


0 Send signal to remote side
≥1
ULow< TUD
& 0
Remote side
start-up

IΦ< TID
0
Trip
Trip from the main &
protection logic
Line Differential Protection RED670
Local Criteria for security at communication problems
Features for the security logic (start up element):

High sensitivity to detect abnormal status


No influence on the operate speed of the main protection
Detect power swings (even when started without fault)
Detect evolving faults, high impedance faults and three phase faults on the
weak side
Detects the switch onto fault case of unloaded line when the voltage input is
taken from the bus bar
It is possible to block each sub function of start-up element
Startup output signal has a settable pulse time
Line Differential Protection RED670
Local Criteria for security at communication problems
Phase-phase current variation
Line Differential Protection RED670
Local Criteria for security at communication problems

Zero sequence current criterion


Line Differential Protection RED670
Local Criteria for security at communication problems

Low voltage criterion


Line Differential Protection RED670
Local Criteria for security at communication problems

Low current criterion


Line Differential Protection RED670
Local Criteria for security at communication problems
Setting parameters
Line Differential Protection RED670
Communication hardware solutions
LDCM with direct fiber (multi mode)
LDCM with direct fiber (single mode)
- 1310 nm medium range
- 1550 nm long range
LDCM with electrical X21 interface. Can be used
with RAD ASMi-52L on pilot wires

Max 3 resp 70-90 resp 90-120


km
Line Differential Protection RED670
Communication hardware solutions
LDCM with an external optical to galvanic converter and a multiplexer

Multiplexer Multiplexer
Telecom. Network

*) *)

*) Converting optical to galvanic G.703 or V.35 alternatively


Line Differential Protection RED670
Communication hardware solutions
LDCM with an external optical to optical converter for direct connection to a
telecommunications network

G.703.E1 G.703.E1
Telecom. Network

64kbit/s 64kbit/s
Line Differential Protection RED670
Redundant communication channels
2-terminal line with single breaker connected to route switched
network via multiplexer, redundant channels

Telecom. Network

Telecom. Network

Primary channel
Secondary redundant channel
With redundant channels the primary channel normally is in operation.
If the primary channel becomes faulty the operation is switched over
to the redundant channel. If the primary is OK again it will take over
the operation after a time delay.
RED670 Functions
Sensitive directional EF protection (SDE)
for non-direct earthed systems

„ Measuring mode selectable


„ 3I0*cosΦ
„ 3I0*3U0*cosΦ
„ 3I0 and cosΦ
„ Sensitivity down to 0.25%
IF „ Undirectional function (3I0) available
with Definite- or Inverse time delay.
„ Cable CT for the most sensitive
applications
UL1+UL2+UL3
or Open delta
„ Neutral point voltage release and a
separate trip step
„ Directional polarizing from calculated
IN> UL1+UL2+UL3 or by an external Open
Æ delta to a separate Analogue input.
RED670 Functions
Broken Conductor BRC (BRCPTOC, 46)

Detects:
IL1=0
„ broken line conductors
L1
L2 „ open poles of circuit
L3
breakers
BRC
„ Now with a supervision that
IL1=2*ILoadL1 one phase is low (<50% of Ip>)
L1
L2 to avoid problem on healthy
L3
parallel line taking over the
missing load
BRC
„ Function is programmable to:
„ trip a circuit breaker (normally avoided)
„ alarm the abnormal condition
RED670 Functions
4-step Earth fault protection (TEF)

„ Four stage Earth overcurrent.


„ Each stage can be set Off, Non-
directional, Forward or Reverse
IF
„ Each stage can be Definite- or Inverse
time delayed.
„ Taylor made curve is available
„ Each stage can be blocked from
second harmonic inrush currents.
„ Directional polarizing from calculated
UL1+UL2+UL3 or by external Open delta
UL1+UL2+UL3 to a separate Analogue input.
IN>
Æ
4
RED670 Functions
Primary verification of DEF direction

IF „ To manage direction when connected to IN


and UN inputs we need to:
- Short circuit two currents on load
- Create –Up by deleting voltages
- Check and understand direction with the
load situation at the test.
„ With modern relays with high measuring
accuracy down to small levels the DEF can
be connected to residual sum and the
direction can be tested from phase relays
UL1+UL2+UL3
e.g. Distance protection function
IN>
Æ
4
Comparison between external and internal UN/IN
generation

Current difference 1%. Rated I 1 A L1 increased 10 mA voltage decreased


0.5V. Injection with FREJA. 1200/1 A Current transformers
Comparison between external and internal UN/IN
generation

Current difference 5%. Rated I 1 A L1 increased 50 mA voltage decreased


0.5V. Injection with FREJA. 1200/1 A Current transformers
Comparison between external and internal UN/IN
generation

A small increase of amplitude and angle error can be noticed with 1% setting.
The difference is minor and has no practical impact of the operating value.
RED670 hardware
Design of analogue channels
Delta sigma A/D converters
1 bits Æ 14 bit
Low
Mhz Æ6kHz
TRM
channel Low pass filter +
Supervision +
I1 6Khz Æ1.2kHz
Choice of branch
=> 20 bits
High A/D
Mhz Æ6kHz

Resulting frequency
response curve
IED670 Series - Fault locator
• Available information for the recorded disturbances:
– distance to fault
– phasors of currents and voltages
» before the fault
» during the fault
• Distance to fault can be recalculated for different
conditions (changing fault-loop or system parameters)
• Phasors of currents and voltages during the normal
operation (V, A meters)
• Additional information
¤ non-load compensated algorithm was used
E error, fault outside phase selectors
> fault located beyond the line, forward direction
IED670 Fault locator – Load compensation

l
ZL
Load import
F

RSA+XSA A p*ZL (1-p)ZL B RSB+XS


IA B

I
F
R p
UA F

Load export

• Load compensation is essential for correct


measurement in two end infeed systems.
• Source data is used for calculation of fault
current distribution
• Measured pre-fault current (load) is used for
calculation of angles between sources
• Distribution and angle difference gives possibility
to calculate the correct value at resistive faults
IED670 Fault locator – Mixed lines

F
•Example on values per km
RSA+XSA A
IA
p*ZL (1-p)ZL (1-p)ZL B RSB+XS •OHL
B
• X1= 0.02+j0.45 ohm/km
I
F • X0= 0.8+j1.34 ohm/km
UA
R
F •Cable
• X1= 0.08+j0.23 ohm/km
• X0= 0.2+j0.18 ohm/km

• Mixed lines with OHL and Cable sections


will not measure correct distance due to the
very different data for the sections
• Set the OHL line end on OHL line data
• Note! You can recalculate with new settings
• Cable end can be used for location on cables
but accuracy is never accaptable due to the exact
location required.
IED670 Fault locator – Configuration

• Fault locator is configured to use analogue inputs


in the Disturbance Recorder.
• The currents and voltages and on top of this the
neutral current from possible parallel line is
connected to the DR and the respective channel is
set under parameter settings.
IED670 Fault locator – Configuration

• Start and Phase selection is required for all


faults on the own line.
• The distance to fault is sent over IEC61850
and is part of the Disturbance report
• The setting under
General/Settings/Monitoring ”Zero angle ref”
must be set to preferable voltage channel R
phase.
IED670 Fault locator – Parameter setting

• Settings is done of the line and source data in primary ohms


• Line length can be set in km, miles or percentage as preferred.
• The source values shall be typical values of the sources from the back for a fault on
the line. Recalculation can be done under the Disturbance records with the correct
source data for a fault if the service was special and the fault was high resistive.
• The sources are set to allow calculation of the angle between the stations due to the
transmitted load. This allows calculation back of resistive faults to give a high accuracy.
• Normally total accuracy should be around 2-3% including CT and CVT/VT errors.
• The accuracy of 670 is improved compared to 500 series due to considerable improved
accuracy of analogue channels (e.g. 20 bit A/D converter compared to 16 bit).
• Strongest side gives the best accuracy.
High resistive ground faults
ƒ Ground faults are normally consisting
of Arc resistance according to
Warring ton formula:
L3 L1
ƒ Rarc=28700*a/ I1.4

L1 L2 ƒ After the arc over the insulator the


current will flow through the tower foot
L2 L3 resistance. Typically less than 10 ohms
are added.
ƒ However, with fault to vegetation much
higher fault resistances can occur.
ƒ A capability to detect very high fault
resistances can then be and
advantage, specially if faulty phase
only can be tripped.
GF Phase selection for high resistance faults on OHL
ƒ Three GF function blocks with
directional comparison per phase
X(ohm)
(over LDCM):
Measure UL1-IN, UL2-IN,
UL3-IN High resistive
Select Icosα&U fault
rca=-0-30 deg Operating
roa=45-60 deg area
R(ohm)
ƒSensitivity far better than DEF, Diff
and Distance protection.
ƒFailure to operate will give three
phase tripping as today
Î only improvement is achieved
ƒOperation only outside Distance
protection operation when Z<
Phase selection fails.
GAPC Phase Direction comparison scheme
Extreme capability to detect high resistive earth faults.

GFL1 GFL1
L L
GFL2 D D GFL2

GFL3 C C GFL3
M M
IN IN

ƒ We can compare over three of the eight channels in LDCM


ƒ Setting of Multi-purpose function:
ƒ ROA 0 deg
ƒ RCA 60 deg
ƒ Sum IN=5-10%
ƒ Function measures ULx – Sum of IN from both sides
ƒ Gives RF detection even much better than differential function
GAPC Phase Direction comparison scheme

GF TRIP GF TRIP GF TRIP GF TRIP GF TRIP GF TRIP


. . . . . GF PHL1 GF PH L2 GF PH L3 L1 L2 L3 GTRIP GF PHL1 GF PH L2 GF PH L3 L1 L2 L3 GTRIP

1 200 999 999 200 62.7 999 999 77.4 999 999 74.2 60.2 999 999 83.8 999 999 79.4

2 300 999 999 300 65.3 999 999 90.9 999 999 86.4 72.3 999 999 87.7 999 999 83.8

3 325 999 999 325 68.5 999 999 83.2 999 999 80 66.6 999 999 90.2 999 999 86.4

4 350 999 999 350 62.7 999 999 87.7 999 999 83.2 66.6 999 999 84.5 999 999 80

5 375 999 999 375 63.4 999 999 87 999 999 83.8 69.8 999 999 85.1 999 999 81.3

6 400 999 999 400 68.5 999 999 86.4 999 999 83.2 66.6 999 999 91.5 999 999 87

ƒ Detection of 800 ohms fault resistance on a 400 kV system


with 35 deg between sources due to load flow.
RED670 Functions
Fuse Failure Supervision
„ Measuring quantities are selectable
between:
IL „ zero sequence voltage and
current:
„ U0 > Uref and I0 = 0
„ negative sequence voltage and
current:
„ U2 > Uref and I2 = 0
„ Sudden change in current and
voltage:

>Z „ DI/Dt and DU/Dt


„ Programmable influence on the
operation of zone measuring elements
RED670 Functions
Breaker Failure Protection
Current level Iset 0,1 – 2 * Ibase
Retrip of actual breaker -No retrip
-With current check
-Without current check

Current check mode 1 out of 3


1 out of 4 or 2 out of 4
Retrip delay, one per phase t1 0.000 – 60.000 s
BFP Back up trip delay, one timer
I> per phase t2 0.000 – 60.000 s
Back-up trip 2 t3 0.000 – 60.000 s
t1
Trip pulse tp 150 ms (settable)
t2
RED670 Functions
BFP in Multi-breaker Applications
ƒ Up to six instances in one IED
BUS A BFP ƒ Optional retrip of own breaker:
START L1
I>
START L2 ƒ With current check
START L3 t1
START 3ph ƒ Without current check
t2
ƒ Increased security for back-up trip
BFP ƒ 1 out of 3 operating mode

All associated
I>
START L1
1 out of 4 operating mode

breakers
START L2 t1 ƒ
START L3
START 3ph t2
ƒ 2 out of 4 operating mode
ƒ Different back-up trip times for
BFP
I> single and multi-pole faults
START L1
START L2 t1
START L3
START 3ph t2
BUS B
RED670 functions
Breaker Failure Protection (BFP) – Fast reset

Pre-filter
„ Adaptive current
Post-filter
0.5 * detection ASD
Stab zone
„ No false operation in
case of saturated CT
„ Maximum reset time
approx 1/2 cycle to
allow short back-up
tripping times.
ASD output

RMS output
RED670 functions – Auto Recloser
Input signals – typical
connections

CB ready
CB closed

From high priority AR


RED670 functions – Synchronizing/Synchro check
Energizing Check
UA
UB
B
A ILoad

Inductive and Capacitive


charging of dead line

Uhigh
27
SC/VC ƒ The dead line and Live bus
Ulow conditions are checked.
ƒ Uhigh and Ulow are verified
RED670 functions – Synchronizing/Synchro check

Synchronizing / Parallelling Check


UA
UB
B
A ILoad

UAL Icap

25

SC/VC
dU
ƒ Paralleling (synchronism conditions are
checked
ƒ Δφ, Δf, ΔU and Uhigh are within set values
ƒ Synchronizing of asynchronous networks
is included
RED670 functions – Synchronizing/Synchro check
Setting parameters
U-Bus
U-Line
Energizing check
ΔU High voltage U> 50-120% of Ub
Low voltage U< 10- 80% of Ub
Operate time 80 ms (typical)
Δφ
Paralleling (Synchronism) Check
Frequency difference Δf < 3-1000mHz
Voltage difference ΔU < 2 - 50 % of Ub
Phase difference Δφ < 5 - 90o
Operate time 80 ms (typical)

Syncronizing
SYNC MaxFrequency diff Δf < 3-1000mHz
U-Bus
MinFrequency diff Δf < 3-1000mHz
Voltage difference ΔU < 2 - 50 % of Ub
Line
reference
Breaker closing time tBreaker 0.000-60.000 sec
Fuse fail
BLOCK voltage Accuracy of closing angle <2 deg
Accuracy of frequency measurement
about 0,5 mHz!
RED670 functions – Synchronizing/Synchro check
Synchrocheck – Voltage selection
1U B1Q B2Q
1U
UB1 UB2

SYN1

ULN1

3U

1U
1U
IED
UB1 UB2

SYN1 SYN2

ULN1

LN1Q

3U
RED670 Functions
Measurements
REx670
SVRx- XPx-
CVMMXU RANGE_XP
P HIGHHIGH
Q HIGH
NORMAL
S
AIM Preproc
I
LOW
LOWLOW
U

IEC 61850-8-1
CPx-
f For each value:
cos φ CMMXU .mag (magnitude
IL1 of reported
IL2 value)
AIM Preproc IL3 .range (normal
3I0 |high|low
VPx- Izs |high-high
Ins |low-low)
VMMXU
UL1L2
UL2L3
AIM Preproc UL3L1
3U0
Uzs
Uns
RED670 functions
Metering of Energy (MMTR)
REx670
SVRx-
CVMMXU MMTR
Pinst EAF
P EAR
Qinst ERF
AIM Preproc
Q ERR
S MaxDmd

IEC 61850-8-1
I MDP
U MDQ
f
cos φ

„ High accuracy metering


„ Presentation on LHMI
„ Sent to SA system
„ Energy plus maximum demand of
power in all quadrants
„ Can be site calibrated.
RED670 Functions
Out of step protection
ƒ Basic concept ƒ Considering the typical case, we
have:
δ1= Arccot(2R1/ZAB)
δ2= Arccot(2R2/ZAB)
A ZA ZL ZB B δ=ωt=2π fs t

EA U EB fs= 1/( π dt) (Arccot(2R1/ZAB)-Arccot(2R2/ZAB))


I
ϕ

Suppose: EA=EB=E This means that it is possible


I ZAB =2 E Sin(δ/2) to measure the slipping
Ucosϕ=Ecos(δ/2) and frequency by detecting
R=U cosϕ /I=(ZAB/ 2) cot(δ/2) U cosϕ .
RED670 Functions
Out of step protection
Equivalent two-machine system

δ
RED670 functions
Out of step protection - 78

ƒ Operation based on U.cos(φ) principle


ƒ Minor improvements
ƒ can measure the positive
sequence quantities
ƒ U.cos(φ), slip f & slip Z
as service values
ƒ Available in other 670 products as
option
δ (i.e. in REL 670)

Measured
Impedance at
this instant of
time
RED670 functions
Out of step protection - 78

ƒ Pole slip protection based on ABB REG216 implementation


ƒ Improved by positive sequence calculations
ƒ Main features:
ƒ Detection of slip frequencies in relation to PS of 0.2 to 8Hz

ƒ Alarm before the first slip (rotor angle pick-up setting)

ƒ Discrimination between generating and motoring directions of rotor phase-


angle
ƒ Discrimination between local and external power swing centre

ƒ Trip after a set number of slips

ƒ Trip within a set rotor angle


RED670 functions
Out of step protection
RED670 functions
Out of step protection
Line Differential Protection RED670
Errors in current measurement:
Saturation

Phase- and amplitude faults


Line Differential Protection RED670
CT Requirements
Close-up faults
I sn ⎛ 0.25 ⎞
Eal ≥ Ealreq = I k max ⋅ ⋅ ⎜⎜ RCT + RL + 2 ⎟⎟
I pn ⎝ Ir ⎠
Through line faults
I sn ⎛ 0.25 ⎞
Eal ≥ Ealreq = 2 ⋅ I t max ⋅ ⋅ ⎜⎜ RCT + RL + 2 ⎟⎟
I pn ⎝ Ir ⎠

Through 1 ½ CB bay faults


I sn ⎛ 0.25 ⎞
Eal ≥ Ealreq = I tfdb ⋅ ⋅ 2 ⋅ ⎜⎜ RCT + RL + 2 ⎟⎟
I pn ⎝ Ir ⎠

Through in-zone transformers faults


I sn ⎛ 0.25 ⎞
Eal ≥ Ealreq = 30 ⋅ I nt ⋅ ⋅ ⎜⎜ RCT + RL + 2 ⎟⎟
I pn ⎝ Ir ⎠
Line Differential Protection RED670
CT Requirements – Formula to be used

You might also like