You are on page 1of 72

Wind Load: The IBC -2012 and

ASCE 7 -10 Provisions

Mithun Pal
Civil/Structural Engineer

1
Contents

 Objectives
 Important Definitions
 Major Changes in ASCE 7-10 from ASCE 7-05
 Wind Load Calculation Procedure
 Wind Load Calculation as per IBC-2012 and ASCE 7-
10 and Load Combinations
 Conclusion
 Wind Loads for Petrochemical Facilities
 Q&A

2
Objectives

 Explain the design steps for Wind Load calculation as


per IBC-2012 and ASCE 7-10
 To demonstrate the changes made in ASCE 7-10 from
ASCE 7-05
 To explain ASCE guidelines for Wind Load calculation
on Petrochemical Facilities.

3
Important Definitions

 Basic Wind Speed – 3 sec gust speed at 10m above


the ground in Exposure C.
 Gust - A wind gust is a sudden, brief increase in the
speed of the wind followed by a break.
 Gust Factor – Factor to account the dynamics of wind
fluctuation and load amplification by building dynamics.

4
Important Definitions (Cont.)

 Type of buildings
Enclosure Classification
– Open Building – Building having each wall at least 80% open.
Ao > 0.8Ag

– Partially Enclosed Building – Ratio of total area of openings in a


wall receiving positive external pressure and sum of total
openings (roof and wall) is more than 10% and total area of
openings receiving positive pressure is more than 4 sq.ft.
• Ao > 1.10 Aoi, and
• Ao > min[4 sqft , 0.01Ag], and
• Aoi/Agi < 0.20
– Enclosed Building – A building that does not comply with the
requirements for open or partially enclosed building.
5
Important Definitions (Cont.)

 Type of buildings (Cont.)


– Low Rise Building – Enclosed or partially enclosed building
having mean roof height (h) less than or equal to 60 ft (18m) and
mean roof height does not exceed the least horizontal
dimension.
– Simple Diaphragm – A building in which both windward and
leeward wind loads are transmitted by roof and vertical spanning
wall assemblies, through continuous floor and roof diaphragms
to the MWFRS.

 Flexible Structure – Structure having fundamental


natural frequency less than 1 Hz
6
Important Definitions (Cont.)

 Exposure Category – Adequately reflects the


characteristics of ground surface irregularities.
– Exposure A – Deleted in ASCE 7-02 and later.
– Exposure B - Urban and suburban areas, wooded areas, areas with
many closely spaced obstructions.
This category includes terrains with numerous closely spaced
obstruction that extends upto 1500 ft with building of height upto
30 ft and 2600 ft or 20 times the height, whichever is greater, for
building of height more than 30 ft.
– Exposure C - Open terrain with scatter obstructions. Airports, areas
that are generally flat open country.
– Exposure D - Flat, unobstructed areas and water surfaces. This
category includes smooth mud flats, salt flats, and unbroken ice
that extend 5,000 ft or 20 times the building height, whichever is
greater, in the upwind direction. 7
Important Definitions (Cont.)

 Risk Category – A categorization of buildings and other


structures based on the risk associated with
unacceptable performance. (Refer Table 1.5-1).
– Risk Categories replace the Occupancy Categories of ASCE 7-
05
– Risk Category I Occupancy Category I
– Risk Category II Occupancy Category II
– Risk Category III Occupancy Category III
– Risk Category IV Occupancy Category IV

8
Changes in ASCE 7 - 10

 In ASCE 7-05 Wind Load is in Chapter-6, but in ASCE 7-10 Wind


Load is in Chapter -26 to Chapter – 31.
 Removal of the Occupancy Factor (Importance Factor) and
introduction of Risk Category.
 Revised Load Factor for wind in ASD and LRFD load
combinations.
 Revised pressure values for minimum design loads.
 Reinstating applicability of Exposure D in hurricane prone regions.
 Revised wind speed triggers for definition of hurricane prone region
and wind-borne debris region.
 Allowable building height for simplified procedure is increased from
60 ft to 160 ft.
9
Wind Load Calculation Procedures

 Method 1 — Directional Procedure


– Buildings of all height (ASCE 7-10 Chapter 27)
 Method 2 — Envelop Procedure
– For low-rise buildings (ASCE 7-10 Chapter 28) .
 Method 3 — Directional Procedure for Building
Appurtenances
– For building appurtenances (ASCE 7-10 Chapter 29).
 Method 4 — Wind Tunnel Procedure
– For any building (ASCE 7-10 Chapter 31).

10
Wind Load Calculation Procedures (Cont.)

 Directional Procedure –
– Wind direction specific
– External pressure Cp depends on wind direction.
– Cp utilized are based on wind tunnel testing corresponding to wind
direction.

 Envelop Procedure –
– Not dependent on wind direction
– Pseudo-External pressure Cpf is derived from wind tunnel testing to
produce maximum structural actions among all directions.
– Pseudo-External pressure Cpf is lumped together with the gust
factor, G, and GCpf is given for different areas of building.

11
Wind Load Calculation Procedures
(ASCE 7-05)

Wind Load
ASCE 7-05

Simplified Procedure Analytical Procedure Wind Turbine


(For low-rise Procedure
(For all buildings)
diaphragm building) (For all building)
Section 6.5
Section 6.4 Section 6.6

MWFRS C&C Enclosed and Partially Solid Freestanding


Open Building Other Structures
Enclosed Building Walls and Signs
Section 6.4.1.1 Section 6.4.1.2 Section 6.5.13 Section 6.5.15
Section 6.5.12 Section 6.5.14

MWFRS C&C MWFRS C&C


Section 6.5.12.1.3 Section 6.5.12.4 Section 6.5.13.1.2 Section 6.5.13.3

Rigid Buildings of All Low-Rise Building,


Low-Rise Building Building, h > 60ft
Height h<60ft
Section 6.5.12.2.2 Section 6.5.12.4.2
Section 6.5.12.2.1 Section 6.5.12.4.1

Alternation for
Flexible Building Parapet Buildings Parapet
Section 6.5.12.2.3 Section 6.5.12.2.4 60 ft < h < 90ft Section 6.5.12.4.4
Section 6.5.12.4.3

MWFRS – Main Wind Force Resisting System 12


C&C – Components and Cladding
Wind Load Calculation Procedures
(ASCE 7-10)

Wind Load
ASCE 7-10

Envelope Procedure for Directional Method for


Directional Method for MWFRS Building Appurtenances Wind Load on C&C Wind Tunnel Procedure
MWFRS
Section 28 Chapter 29 Chapter 30 Chapter 31
Chapter 27

Part 1: Closed and Part 2: Enclosed Solid


Partially Enclosed Low- Simple Diaphragm Part 1:Directional Method
Part 1: For Enclosed, Partially Freestanding for Enclosed and
Part 2: Enclosed Simple Rise Buildings Low-Rise Buildings Walls and Signs
Enclosed and Open Building Partially Enclosed
Diaphragm Buildings (Analytical Procedure) (Simplified Procedure)
of all heights Section 29.4.1 Buildings h< 60ft
(Analytical Procedure) (Simplified Procedure)
Section 30.4
Low-Rise Solid Attached
Enclosed and Buildings Signs
Walls and Roof Part 2:Simplified
Partially Surfaces Section 28.4.1 Section 29.4.2 Procedure for Enclosed
Enclosed Rigid Sections 27.6.1 Buildings h< 60ft
Buildings
Section 30.5
Section 27.4.1
Roof Overhangs
Roof Overhangs Section 28.4.3 Other Structure Part 3:Directional
Open Buildings Sections 27.6.3 Section 29.5 Method for Enclosed
with Roofs and Partially Enclosed
Section 27.4.3 Buildings h> 60ft
Parapets
Section 30.6
Parapets Sections 28.4.2 Rooftop
Section 27.6.2 Structures and
Parapets equipment for Part 4:Simplified
Section 27.4.5 Buildings with h Procedure for Enclosed
< 60ft Buildings h< 160ft
Section 29.5.1 Section 30.7
Roof Overhangs
Section 27.4.4
Part 5: Directional
Procedure for Open
Enclosed and Building of All Heights
Partially
Section 30.8
Enclosed Flexible
Buildings
Section 27.4.2
Part 6: Directional
Procedure for Building
Appurtenances
Section 30.9
13
ASCE 7-10 Wind Pressures

 The basic form of the pressure equation:

p = qGC
 Where
– p = a wind pressure on a surface
– q = velocity pressure. This is the pressure due to a moving fluid
on a flat plate
– G = gust factor. The gust factor accounts for dynamic
interaction between the flowing air and the structure
– C = pressure coefficient. The pressure coefficient accounts for
varying pressure across a surface.
14
Velocity Pressure, q

See ASCE 7-10 Cl.27.3.2, Cl.28.3.2 and Cl.29.3.2


 qz =Velocity Pressure = 0.613KzKzt KdV2 (N/m2)
= 0.00256KzKzt KdV2 (lb/ft2)
– V = Basic wind speed in mph
– Kz = Exposure Coefficient
– Kzt = Topographical Factor
– Kd = Wind Directionality Factor
 Evaluated at an elevation z:
– qz = 0.00256V2 KzKztKd
 Evaluated at the building mean roof elevation, h:
– qh = 0.00256V2 KhKhtKd 15
Basic Wind Speed, V

See ASCE 7-10 Cl.26.5.1


 Use Fig. 26.5-1A for Risk Category II
 Use Fig. 26.5-1B for Risk Category III & IV
 Use Fig. 26.5-1C for Risk Category I

 Importance Factor, I – Deleted from ASCE 7-10 and


accounted in Basic Wind Speed.

16
Velocity Pressure Exposure
Coefficients, Kz and Kh
See ASCE 7-10 Table 27.3-1, Table 28.3-1 and Table 29.3-1
 Modifies basic wind pressure for heights other than 33
ft and exposures other than exposure C
 Use Table 27.3-1, Table 28.3-1 and Table 29.3-1 for
the value of KZ or Kh
 Compute K directly from equations in the commentary
for any height and/or exposure.

17
Kz & Kh Computation

When z > zg use z = zg K Com putation

When z < 15 use z = 15 ft 2.50

2.00
Table 26.9-1
1.50 Exposure B
K Exposure C
1.00 Exposure D

0.50

0.00
0 500 1000 1500 2000
Elevation, z (ft)

18
Topographical Factor, Kzt

See ASCE 7-10 26.8 & Fig. 26.8-1

 Kzt = 1.0 when:


– H/Lh < 0.2, or
– H < 15' for Exposures C & D, or
– H < 60' for Exposure B.

 Kzt = (1+K1K2K3)2

19
Kzt Constants
See ASCE 7-10 Fig 26.8-1

20
Kzt Multipliers by Equation

See ASCE 7-10 Fig 26.8-1

21
Directionality Factor, Kd

See ASCE 7-10 Cl.26.6 and Table 26.6-1


 This factor shall only be applied when used in conjunction
with load combinations specified in Sections 2.3 and 2.4.

22
Gust Factor, G

See ASCE 7-10 Cl.26.9


 For Rigid structures
– G = 0.85

 For flexible buildings and other structures


– Calculate G as per Cl.26.9 or “by a rational analysis that incorporates
the dynamic properties of the main wind-force resisting system.”

23
Pressure Coefficients, C

 The pressure coefficients are based on


– The enclosure category of the structure
– The location on a structure for which a pressure is to be
computed.

 The pressure coefficients have been determined


experimentally from wind tunnel studies done on
regular shaped structures
 The coefficient represents the ratio between measured
pressure and the computed basic velocity pressure.

24
Location of Pressure

 ASCE 7 provides means for computing forces on


various surfaces.
– The building envelope surfaces experience pressure on both
sides (i.e. external and internal).

25
Internal Pressure Coefficients, GCpi
See ASCE 7-10 Cl.26.11 & Table 26.11-1
 Internal pressure is fairly easy because the air is
relatively stagnant and the shape of the structure does
not affect it’s magnitude.
 As gusting is not a concern internally, the gust factor
and the pressure coefficient are combined.
– GCpi
 The magnitude of the internal pressure coefficient is
strictly dependent on the enclosure classification.
 The pressure can be both positive or negative (i.e.
suction) depending on the direction of the wind relative
to opening for partially enclosed or enclosed buildings.
– Both internal pressures must be considered.
26
Internal Pressure

Table 26.11-1

27
External Pressure Coefficients, Cp
See ASCE 7-10 Table 27.4-1 to 27.4-3 and Table 28.4-1
 As external surfaces are subject to “flowing” air, the
pressure varies considerably on the building surface
depending on structural configuration and direction of
the wind.
 Coefficients also depend on whether the resulting
forces are to be used to design/analyze:
– Main Wind-Force Resisting Systems (MWFRS)
• The structural elements necessary to provide supports and stability
of overall structure (foundation, column, beams, truss, bracing,
wall diaphragm etc.).
– Components & Cladding (C&C)
• Elements of the building envelope that do not qualify as part of the
MWFRS (Windows, doors, curtain walls, roof sheeting
28
and
coverings, overhangs, building attachments etc.).
Directional Procedure

See ASCE 7-10 Chapter 27


 For Wind Load calculation for enclosed, partially
enclosed and open buildings of all height.
 Conditions
– Building shall be of regular shape
– Building does not have response characteristics making it subject
to cross-wind loading, vortex, shedding, instability due to
galloping or flutter or it does not have a location that creates
channelling effect.

 Limitations – Building having unusual shapes or


response.
29
Directional Procedure (Cont.)

See ASCE 7-10 Table 27.2-1


 Part-1: Design Steps for MWFRS (Analytical Procedure)
– Step – 1: Determine risk category (Table 1.5-1)
– Step – 2: Determine Basic Wind Speed
– Step – 3: Determine Wind Parameters (Kd, Exposure Category,
Kzt, G, Enclosure Classification, GCpi)
– Step – 4: Determine velocity pressure exposure coefficient Kz or
Kh (Table 27.3-1)
– Step – 5: Determine velocity pressure qz or qh (Eq. 27.3-1)

30
Directional Procedure (Cont.)

 Part-1: Design Steps for MWFRS (Contd.)


– Step – 6: Determine external pressure coefficient Cp or CN
• Fig. 27.4-1 for walls and flat, gable, hip, monoslope
• Fig. 27.4-2 for domed roofs
• Fig. 27.4-3 for arched roofs
• Fig. 27.4-4 for monoslope roof, open building
• Fig. 27.4-5 for pitched roof, open building
• Fig. 27.4-6 for troughed roof, open building
• Fig. 27.4-7 for along-ridge / valley wind load case for monoslope,
pitched or troughed roof

– Step – 7: Wind pressure, p


• Eq. 27.4-1 for rigid buildings
• Eq. 27.4-2 for flexible buildings
• Eq. 27.4-3 for open buildings 31
Directional Procedure (Cont.)

 Finding Net Pressure


– Wind Loads – Enclosed and partially enclosed Rigid Building
p=qGCp-qi(GCpi ) (lb/ft2)(N/m2) …(Eq. 27.4-1)
– Wind Loads – Enclosed and partially enclosed Flexible Building
p=qGfCp-qi(GCpi ) (lb/ft2)(N/m2) …(Eq. 27.4-2)
– Wind Loads – Open Building with monoslope, pitched or
troughed roofs
p=qGCN (lb/ft2)(N/m2) …(Eq. 27.4-3)
(CN is net pressure coefficient from fig 27-4-4 to 27-4-7)

32
Directional Procedure (Cont.)

 The net pressure is the vector sum of the internal and external
pressure
 Note the sign – positive pressure externally opposes positive
pressure internally (i.e. they act in opposite directions)

33
Directional Procedure (Cont.)

See ASCE 7-10 Table 27.5-1

 Part-2: Design Steps for Diaphragm Building


(h<160ft) (Simplified Procedure)
– Step – 1: Determine risk category (Table 1.5-1).
– Step – 2: Determine Basic Wind Speed.
– Step – 3: Determine Wind Parameters (Kd, Exposure
Category, Kzt, Enclosure Classification).
– Step – 4: Enter Table to determine net pressure on walls at
top and base of building ph and p0 (Table 27.6-1).
– Step – 5: Enter Table to determine net roof pressure pz
(Table 27.6-2).

34
Directional Procedure (Cont.)

 Part-2: Design Steps for Diaphragm Building (h<160ft)


(Simplified Procedure) (Cont.)
– Step – 6: Determine topographical factor, Kzt and apply to wall
and roof pressure.
– Step – 7: Apply loads to walls and roofs simultaneously.

 Diaphragm Flexibility – The design procedure applies to


buildings having either rigid or flexible diaphragms.

35
Directional Procedure (Cont.)

36
Directional Procedure (Cont.)

 Table to Calculate wind Pressure on walls

Table 27.6-1

37
Directional Procedure (Cont.)

 Table to Calculate wind Pressure on roof

Table 27.6-2

38
Directional Procedure (Cont.)

 Minimum Design Wind Loads


– The Load effect of the design wind pressure shall not be less
than a minimum load defined by assuming the pressure, ps, +16
psf for wall and +8 psf for roof onto a vertical plane normal to the
assumed wind direction. Wall and roof loads shall be applied
simultaneously.
– The design pressure for open building shall not be less than 16
psf.

39
Envelope Procedure

See ASCE 7-10 Chapter 28


 For Wind Load calculation for enclosed and partially
enclosed low-rise buildings.
 Condition
– For building of height less than 60 ft
– Building shall be of regular shape
– Building does not have response characteristics making it
subject to cross-wind loading, vortex, shedding, instability due to
galloping or flutter or it does not have a location that creates
channelling effect.

 Limitations – Building having unusual shapes or


response. 40
Envelope Procedure (Cont.)
See ASCE 7-10 Table 28.2-1

 Part-1: Design Steps for MWFRS


– Step – 1: Determine risk category (Table 1.5-1).
– Step – 2: Determine Basic Wind Speed.
– Step – 3: Determine Wind Parameters (Kd, Exposure
Category, Kzt, Enclosure Classification, GCpi).
– Step – 4: Determine velocity pressure exposure coefficint Kz
or Kh using Table 28.3-1.
– Step – 5: Determine velocity pressure qz or qh.
– Step – 6: Determine external pressure coefficient (GCp)
using Fig 28.4-1.
– Step – 7: Calculate wind pressure, p, from Eq. 28.4-1

41
Envelope Procedure (Cont.)

 Design Wind Pressure


– Wind Loads – Enclosed and partially enclosed Rigid Building
p=qh[(GCpf ) - (GCpi )] (lb/ft2)(N/m2) …(Eq. 28.4-1)

 External Pressure Coefficient (GCpf )


– The combined gust effect factor and external pressure
coefficients for low-rise buildings, (GCpf ), are not permitted to be
separated.

42
Envelope Procedure (Cont.)
See ASCE 7-10 Table 28.5-1

 Part-2: Design Steps for Low-Rise Diaphragm Building


(Simplified Procedure)
– Step – 1: Determine risk category (Table 1.5-1).
– Step – 2: Determine Basic Wind Speed.
– Step – 3: Determine Wind Parameters (Exposure Category,
Kzt).
– Step – 4: Enter Table to determine net pressure on walls at top
and base of building ph and p0, Table 27.6-1.
– Step – 5: Enter Table to determine net roof pressure pz, Table
27.6-2

43
Envelope Procedure (Cont.)

 Design Wind Pressure


– Wind Loads – Enclosed and partially enclosed Rigid Building
ps=lKztps30 (lb/ft2)(N/m2) …(Eq. 28.6-1)

l = adjustment factor for building height and exposure from


Fig. 28.6-1
ps30 = Simplified Design Wind Pressure (psf) , Fig. 28.6-1

44
Envelope Procedure (Cont.)

Figure 28.6-1

45
Envelope Procedure (Cont.)

 Minimum Design Wind Loads


– The Load effect of the design wind pressure shall not be less
than a minimum load defined by assuming the pressure, ps, for
zones A and C equal to +16 psf, Zones B and D equal to +8 psf,
while assuming ps for Zones E, F, G and H are equal to 0 psf.

46
Wind Loads on Other Structures and
Building Appurtenances

See ASCE 7-10 Chapter 29


 For Wind Load calculation on building appurtenances
(rooftop structure and equipments) and other
structures of all heights (solid freestanding walls and
solid signs, chimneys, tanks, open signs, lattice
frameworks and trussed tower) using the Directional
Procedure.
 Condition – Same as Directional Procedure.
 Limitations – Same as Directional Procedure.

47
Wind Loads on Other Structures and
Building Appurtenances (Cont.)

See ASCE 7-10 Table 29.1-1

 Design Steps
– Step – 1: Determine risk category (Table 1.5-1).
– Step – 2: Determine Basic Wind Speed.
– Step – 3: Determine Wind Parameters (Kd, Exposure Category,
Kzt and G).
– Step – 4: Determine velocity pressure exposure coefficient Kz
or Kh using Table 29.2-1.
– Step – 5: Determine velocity pressure qz or qh using Eq. 29.4-1

48
Wind Loads on Other Structures and
Building Appurtenances (Cont.)

 Design Steps (Cont.)


– Step – 6: Determination of Force Coefficient Cf
• Fig. 29.4-1 for Solid freestanding signs or wall
• Fig. 29.5-1 for Chimneys, Tanks, Rooftop equipments
• Fig. 29.5-2 for Open Signs, Lattice Frameworks
• Fig. 29.4-3 for Trussed Tower

– Step – 7: Calculate Wind Force, F


• Eq. 29.4-1 for signs and walls
• Eq. 29.5-2 and Eq. 29.5-3 for rooftop structures and equipments
• Eq. 29.5-1 for other structures

49
Wind Loads on Other Structures and
Building Appurtenances (Cont.)

 Design Wind Force


– Wind Loads – Solid freestanding wall and sign
F=qhGCfAs (lb)(N) …(Eq. 29.4-1)
– Wind Loads – Rooftop structures and equipments
(Roof height < 60ft)
Fh=qh(GCr)Af (lb)(N) …(Eq. 29.5-2)
Fv=qh(GCr)Ar (lb)(N) …(Eq. 29.5-3)
– Wind Loads – Other structures
F=qzGCfAf (lb)(N) …(Eq. 29.5-1)

50
Wind Loads on Other Structures and
Building Appurtenances (Cont.)

– qh = the velocity wind pressure at a height h


– G = Gust factor as per Cl.26.9
– Cf = net force coefficient from Fig. 29.4-1, Fig. 29.5-1 to 29.5-3
– As= Gross area of solid freestanding wall and sign
– Af= Projected area normal to the wind.
– Ar= Horizontal projected area of rooftop structure or equipment.
– GCr= 1.9 for rooftop structures and equipments with Af less than
0.1Bh and shall be reduced to 1.9 to 1.0 as 0.1Bh is increased
to Bh
– GCr= 1.5 for rooftop structures and equipments with Ar less than
0.1BL and shall be reduced to 1.5 to 1.0 as 0.1BL is increased
to BL

51
Wind Loads on Other Structures and
Building Appurtenances (Cont.)

 Minimum Design Wind Loads


– Design wind load for other structure shall not be less than 16
lb/ft2.

52
Wind Loads on Components and Cladding
(C&C)

See ASCE 7-10 Chapter 30

 Part-1
• Envelop Procedure for enclosed and partially enclosed
buildings.
• Building has a flat roof, gable roof, stepped roof, hip roof,
monoslope roof or sawtooth roof.
 Part-2
• Envelop Procedure for enclosed buildings.
• Building has a flat, gable or hip shape roofs.

53
Wind Loads on Components and Cladding
(C&C) (Cont.)

 Part-3
• Directional Procedure for enclosed and partially enclosed
buildings having h > 60 ft.
• Building has a flat, pitched, gable, hip, mansard, arched, dome
roofs.
 Part-4
• Directional Procedure for enclosed buildings having h < 160 ft.
• Building has a flat, pitched, gable, hip, mansard, arched, dome
roofs.

54
Wind Loads on Components and Cladding
(C&C) (Cont.)

 Part-5
• Directional Procedure for open building having pitched,
monoslope or troughed roofs.
 Part-6
• Directional Procedure for roof overhangs and parapets of
buildings.

55
Wind Loads on Components and Cladding
(C&C) (Cont.)

 Types of Roofs

56
Wind Loads on Components and Cladding
(C&C) (Cont.)

 Types of Roofs (Cont.)

57
Wind Loads on Components and Cladding
(C&C) (Cont.)

 Types of Roofs (Cont.)

58
Wind Tunnel Procedure

See ASCE 7-10 Chapter 31


 Permitted for any building or structure
 Required for
– Buildings or other structures with unusual shapes
– Buildings or other structures with unusual response
characteristics and thus subject to the following:
– Across-wind loading
– Vortex shedding
– Instability due to galloping or flutter
– Channelling effects
– Buffeting in the wake of upwind obstructions
59
Load Combinations

Design ASCE 7-05 ASCE 7-10


Process
LRFD 1.2D + 1.6(Lr or S or R) + (L or 0.8W) 1.2D + 1.6(Lr or S or R) + (L or 0.5W)

1.2D + 1.6W + L + 0.5(Lr or S or R) 1.2D + 1.0W + L + 0.5(Lr or S or R)

0.9D + 1.6W + 1.6H 0.9D + 1.0W

ASD D +W D + 0.6W

D + 0.75(W) + 0.75L + 0.75(Lr or S or R) D + 0.75(0.6W) + 0.75L + 0.75(Lr or S or R)

0.6D + W 0.6D + 0.6W

60
Conclusion

 Changes in ASCE 7-10 produces greater differences in


design pressure for areas within Hurricane prone regions.
 The changes for other areas don’t produce much change
in wind pressure
Examples-
• Risk Category – II
-ASCE 7-05 Wind Speed = 90 mph (I=1.0) ….(Fig 6-1, ASCE7-05)
-ASCE 7-10 Wind Speed = 115 mph ….(Fig 26.5-1A, ASCE7-10)
-Ratio in wind pressure = 1.0 x 1.6 x 902 / 1152 = 0.98
• Risk Category – III
-ASCE 7-05 Wind Speed = 90 mph (I=1.15) ….(Fig 6-1, ASCE7-05)
-ASCE 7-10 Wind Speed = 120 mph ….(Fig 26.5-1B, ASCE7-10)
-Ratio in wind pressure = 1.15 x 1.6 x 902 / 1202 = 1.035
61
Wind Loads for Petrochemical Facilities
(ASCE 7)

 Wind Loads on Pipe Rack


– Wind Force – Shall be calculated with Directional Procedure as per
Chapter 29 of ASCE 7-10
– Piping Tributary Area
A = L (D+10%W) … (Cl.5.1.1)
– Cable Trays Tributary Area
A = L (h+10%W) … (Cl.5.1.2)

62
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

 Wind Loads on Pipe Rack (Cont.)


– Force Coefficient
• For structural members … (Cl.5.1.3)
– Cf = 1.8 or
– Cf = 2.0 at and below first level and 1.6 for members above
first level
• For Pipes … (Cl.5.1.4)
– Cf = 0.7 as minimum
– Cf = shall be calculated as per Fig. 29.5-1
• For Trays … (Cl.5.1.5)
– Cf = 2.0
63
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

 Wind Loads on Open Structure (Process Structures,


Reactor Operating Structures)
– Frame Load – Shall be as per Eq. 29.5-1 of ASCE 7-10
– Force Coefficient of set of frames –
Cf = CDg / e
CDg= force coefficient for set of frames, from Fig. 5.1
e= effective solid area (As) / gross area of wind-ward frame
(Ag)

64
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

Figure 5.1

N = Number of frames
SF =frame spacing
Figure 5.1
B =Frame width
65
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

 Wind Loads on Open Structure (Process Structures,


Reactor Operating Structures) (Cont.)
– Force Coefficient of Components –

Fig 29.5-1

66
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

 Wind Loads on Open Structure (Process Structures,


Reactor Operating Structures) (Cont.)
– Design Load Cases –
FS = Frame wind load
FT = Frame load + piping wind load + equipment wind load
Design Wind Load = FT+0.5FS

67
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

 Vertical Vessel
– Use Chapter 29 of ASCE 7-10 for velocity pressure calculation
– Gust factor shall be calculated based on empty or operating
vessel frequency (f = 1/T)

68
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

 Vertical Vessel (Cont.)


– For the projected width, add 5 ft (1.52m) to the diameter of the
vessel or add 3 ft (0.91m) plus the diameter of the largest pipe to
the vessel, whichever is greater to account for platforms,
ladders, nozzles and piping below the top tangent line in detail
platform information is not available.
– The vessel height should be increased one vessel diameter to
account for a large diameter pipe and platform attached above
the top tangent, as is the case most tower arrangement.
– The force coefficient Cf shall be determined from ASCE 7 Table
29.5-1

69
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

 Horizontal Vessel
– No check for dynamic properties is required.
– For the projected diameter add 1.5 ft (0.46m) to the insulated
diameter to account for ladders, nozzles and pipe 8 in and
smaller.
– For transverse wind, the for coefficient, Cf, shall be determined
from ASCE 7-10, Figure 29.5-1.
– For longitudinal wind, use Cf of 0.5 for a rounded head and 1.2
for a flat head.
– For platform, use the projected area of the support steel and
force coefficient Cf of 2.0. For handrails use the values in Table
5.1.
– For support, use the actual projected area. Cf should be 1.3 for
concrete pedestals. Steel support shall be same as platforms.
70
Wind Loads for Petrochemical Facilities
(ASCE 7) (Cont.)

 Air Coolers or Fin-Fans


– Use Table 5.3 for Force Coefficient Cf.
– Effective area Ae shall be b x c or b x a.

71
Q&A

72

You might also like