Professional Documents
Culture Documents
1/2
Nermeen Hammouda
3/4 General Manager - Applied Business, GCC
1/6
Agenda To Reset: Right click on the slide thumbnail and select
‘reset slide’ or choose the ‘Reset’ button on the ‘Home’
ribbon (next to the font choice box)
1/4
• Green Box
2/6
• Variable Speed Technology
Real Numbers ~ Real Value
4/6
3/4
5/6
Variable
• Retrofit Existing chillers with Variable
Speed
Speed Drives
Drives
Central Plant • Provide complete services of a CPO on
Optimization the existing control system
1/2
Nermeen Hammouda
3/4 General Manager - Applied Business, GCC
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
CONDENSER
CONDENSER
CONDENSER
CONDENSER
CONDENSER
CONDENSER
CONDENSER
CONDENSER
03A 04A 05A 06A 07A 08A 09A 10A
VSD CSD CSD CSD CSD CSD CSD CSD
FUTURE FUTURE
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
CONDENSER
CONDENSER
CONDENSER
CONDENSER
CONDENSER
CONDENSER
CONDENSER
CONDENSER
03B 04B 05B 06B 07B 08B 09B 10B
VSD CSD CSD CSD CSD CSD CSD CSD
FUTURE FUTURE
Post the retrofit activities, Client team collected the recorded data critical for
analysis. Amongst the critical parameters recorded, following are the most
important to calculate the performance of the chillers-
The data collected has been processed and analyzed by JCI team to
compare the performance of constant speed chillers to that of variable
speed chillers. Basic engineering calculations and assumptions are
mentioned below
5500
5000
Load, TR
4500
4000
3500
3000
3/1/2019 0:00 3/11/2019 0:00 3/21/2019 0:00 3/31/2019 0:00 4/10/2019 0:00 4/20/2019 0:00 4/30/2019 0:00
Performance Comparison
VSD kW/TR CSD kW/TR
1.000
0.900
0.800
0.700
0.600
SEC, kW/TR
0.500
0.400
0.300
0.200
0.100
Consistently
3/1/2019 0:00
VSD Chillers
3/11/2019 0:00 3/21/2019 0:00 3/31/2019 0:00 4/10/2019 0:00 4/20/2019 0:00 4/30/2019 0:00
are better in
performance!
Data Collected for 8 months. Data collection on going…
Johnson Controls at DC Dialogue 3rd Edition, 2019
Tabulated Data
Sep-18 Oct-18 Nov-18 Dec-18
Description Units
CSD VSD CSD VSD CSD VSD CSD VSD
TR 4,493 3,585 4,728 4,038 4,900 4,583 4,858 4,347
Chiller Pair Delivered Capacity
% 90% 72% 95% 81% 98% 92% 97% 87%
Specific Power Consumption for the
ikW/TR 0.633 0.530 0.614 0.529 0.602 0.522 0.597 0.503
Chiller Pair (SEC)
Energy Consumption for Baseline
kWh 1,399,024 1,170,679 1,197,575 1,033,119 763,181 661,268 1,070,760 901,859
Capacity = Baseline Capacity x SEC
Estimated Energy Savings kWh 228,345 164,457 101,913 168,901
Estimated Monetary Savings AED 68,503 49,337 30,574 50,670
CSD Vs VSD
600,000 6,000
Adjsuted baseline CSD AED Actual VSD AED CSD Avg TR
VSD Avg TR CSD Equi. Load Hrs. VSD Equi. Load Hrs.
500,000 5,000
400,000 4,000
16.3%
AVERAGE TR
13.7% 24.4% 21.9%
300,000 3,000
15.9%
22.7% 28.8%
13.5%
200,000 2,000
100,000 1,000
- 0
Sep-18 Oct-18 Nov-18 Energy
Mar-19 Savings
Dec-18 Jan-19
Apr-19 Feb-19
in 8 months
Savings 68,503 49,337 30,817 51,006 70,271 96,614 101,972 85,833
~ 1.8M kWh
~ AED 554,353
Johnson Controls at DC Dialogue 3rd Edition, 2019
Apprehension’s Mitigated !
! MV Variable Speed Drives are ! MV-VSD costs and size, both have
expensive, with un-attractive reduced with improved technology and its
payback time to evaluate the payback
! District Cooling Plants always ! DCP’s seldom see full Delta T. As such,
operate at Full Load Conditions chillers are loaded between 60% and
90%
! Use for Thermal Storage ! Again, limited by the low Delta T. Also,
means the chillers will always Thermal Storage Tank is always charged
be operating at full design load. at off peak conditions and hence at low
WB temp it will benefit most with VSD
technology.
! Chillers must be evaluated for ! “Real” World conditions will always see
Full Load Efficiency at “Design” reduced ECWT’s and lower loads. Off
Conditions design performance of Chillers is critical.
1/4
2/6
1/2
4/6
3/4
1/4
2/6
1/2
4/6
Johnson Controls
3/4