: 9324-10-H-2
METAL ENCLOSED SWITCHGEAR
Date.……..: 16.11.2015
TEST REPORT Order No…: 9324
Serial No………….......: 9324-10-H-2 Rated Current..………………...……………...….: 630 A
Type…………….…...…: TG21 - 02 Rated Short-Circuit Breaking Current.……...: 16 kA
Production Year…....: 2015 Rated Frequency………………………...…….….: 50 Hz
Rated Voltage……....: 36 kV Control Supply Voltage………..……...…..…...: 110 V–
Operating Voltage….: 35 kV Motor Supply Voltage…………..……....………: 220 V~
7.102 Mechanical operation test 4. The disconnector could not be closed when earthing switch is closed. O
5. The earthing switch could not be closed ,when disconnector is closed. O
6. Cover of medium voltage compartment could not be opened, when earthing switch is
O
open.
7. When the cover of cable compartment is open it is not be possible to operate the
O
disconnector.
8. Operating at maximum supply voltage for five times. O
Tests on auxiliary and control 9. Operating at maximum supply voltage for five times. O
7.2 and 7.104
circuits 10. Electro mechanical interlocking coil will operate at minimum voltage ( %85 of rated
─
voltage) and at maximum voltage (%110 of rated voltage).
11. Operation of heating and lightning circuits will be checked. O
12. Accuracy of auxiliary contacts positions will be checked O
7.2 Tests on auxiliary and control 13. Construction and earthing connections shall be suitable. O
circuits 14. Operation of live line indicator lamps will be seen when system is closed and phase to
O
earth voltage is applied.
7.5 Design and visual checks
15. If there is a current transformer or/and a voltage transformer,seconder circuit
O
connections will be checked.
16. Appearance and cleanliness of metal enclosed switchgear will be checked. O
17. The resistance between every phase's inlet and outlet.
( Except; resistance of current transformator and ve M.V. fuse )
Measurements of main circuit
7.3 Acceptable maximum resistance Measured Resistance Values O
resistance
value L1 L2 L3
300 µΩ 197 µΩ 195 µΩ 191 µΩ
18. SF6 gas pressure of disconnector will be checked
Ambient Required Measured Pressure Measured Pressure
7.4 Gas Pressure Control O
Temperature Pressure (Disconnector-1) (Disconnector-2)
20 oC 0,40…0,50 bar 0,49 bar - bar
19. Between phases and earth when the system is closed. (1 min) 70 kV O
Dielectric test on the main
7.1 20. Between phases when the system is closed. (1 min) 70 kV O
circuit
21. Across isolating distance when the disconnector is open. (1min) 80 kV O
Tests on auxiliary and control 22. The insulation of the low voltage circuits (except electronic circuits) shall withstand to 1
7.2 O
circuits kV in 1 second.