Data Sheet For SINAMICS Power Module PM240-2: Rated Data General Tech. Specifications
Data Sheet For SINAMICS Power Module PM240-2: Rated Data General Tech. Specifications
MLFB-Ordering data
6SL3210-1PE32-1UL0
Figure similar
Output
Ambient conditions
Number of phases 3 AC
Cooling Internal air cooling
Rated voltage 400 V
Rated current (LO) 205.00 A Cooling air requirement 0.153 m³/s (5.403 ft³/s)
Overload capability
1.1 x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s 1.5 × rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s
1.5 × output current rating (i.e., 150 % overload) for 57 s with a cycle time of 300 s 2 × output current rating (i.e., 200 % overload) for 3 s with a cycle time of 300 s
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 1 of 2 Generated Thu Jan 21 12:49:27 CET 2021
Data sheet for SINAMICS Power Module PM240-2
MLFB-Ordering data
6SL3210-1PE32-1UL0
Figure similar
Net weight 61.00 kg (134.48 lb) Conductor cross-section 35.00 ... 120.00 mm² (AWG 2 ... AWG -3)
Depth 357 mm (14.06 in) Conductor cross-section 35.00 ... 120.00 mm² (AWG 2 ... AWG -3)
Comparison with the reference converter (90% / -0.41 % Conductor cross-section 25.00 ... 70.00 mm² (AWG 4 ... AWG -1)
100%)
Cable length 10 m (32.81 ft)
I
1574.3 W (1.11 %) 1872.2 W (1.32 %) 2359.3 W (1.66 %)
PE connection M10 screw studs
100%
Max. motor cable length
853.2 W (0.60 %) 966.3 W (0.68 %) 1127.8 W (0.79 %) Unshielded 450 m (1476.38 ft)
50%
Standards
615.9 W (0.43 %) 665 W (0.47 %)
25%
Compliance with standards UL, cUL, CE, C-Tick (RCM), SEMI F47
50% 90% f
CE marking Low-voltage directive 2006/95/EC
The percentage values show the losses in relation to the rated apparent power of the converter.
The diagram shows the losses for the points (as per standard EN 50598) of the relative torque
generating current (I) over the relative motor stator frequency(f). The values are valid for the basic
version of the converter without options/components.
*converted values
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 2 of 2 Generated Thu Jan 21 12:49:27 CET 2021