You are on page 1of 1

Po

Polymer line post


Insulators for distribution
Ins

Ø2 3/8”
Ø2 4/5”
Hot dip 5”
3/


R1
R
galvanized Steel Porcelain

11/10”
1 1/10” Ø1 7/10”

2 3/10”
Ø1 7/10” 10”
2 3/10” 11 3/10”

Ø3” Ø 3.0”
Ø4 2/5” Ø4 2/5”
Ø5 3/5” Ø5 3/5”

PL015 PL015H
STANDARD VERSION *HYBRID VERSION

CATALOG NUMBER PL015 PL015H


ANSI (C29.18)
Class 51-1F
Neck type F
CRITICAL DISTANCES, inches
Arcing distance 6 1/2 6 3/4
Leakage distance 13 7/10 14 7/10

MECHANICAL VALUES, Lb
SCL 5,000 3,000
Maximum density cantilever load 1,348 1,348
Tensile strength 5,000 3,000
ELECTRICAL VALUES,kV
Rated voltage 15 15
Low-frequency dry flashover 85 85
Low-frequency wet flashover 55 55
Critical impulse flashover, positive 150 150
Critical impulse flashover, negative 155 155

RADIO INFLUENCE VOLTAGE DATA


Low-frequency test voltage, RMS to ground, kV 10 10
Maximum RIV at 1,000 kHZ, μV 4 4
DIMENSIONS ACCORDING TO DRAWING
Center hole nominal thread size 3/4” 3/4”
Note1: Dimensions in inches.
* Combines a ceramic head and silicone elastomer housing properties superior leakage distance and reduced unit weight.
Housing: High voltage silicone - High temperature vulcanized (HTV).
Fittings: Hot dip galvanized steel.

Insulators

You might also like