3 INSTALLATION & WIRING 5 TC-01 OPERATION

1. Direct mounting to the expansion slot in the MPU of 2. Connecting to DVP 1. Switch the DU-01 to TC-01
TC-01
the EP/EH series series PLC via accessory mode (please see the back of
cable the DU-01), and select RD (to Indication of the connected MPU model
read P, D and F in the MPU of
Indication of internal data storage model
PLC) or WR (to write the data

DVPDU-01 Digital Setup Display in P, D, F of DU-01 to the MPU


of PLC).
Note: P: Program, D: Data register, F: File register
Instruction Sheet 2. TC-01 Password Key Setting
1 WARNING Password key setting of TC-01 can be set via WPLSoft. The purpose is to read/write to the key-locked
PLC as long as the password setting matches with the one in PLC. To unlock the password key
Please power down the MPU of the Please power down the PLC MPU prior to install the DU-01,
setting, please use WPLSoft as well.
PLC prior to install the DU-01, which which is connected via a high-density connector. Also please
a) Password Key Setting
is connected via a high-density refer to the figures above for proper operation. Put the
In RD or WR mode, press ESC button and hold for 3 seconds or
connector. Also please read the face-up DU-01 slantly in the extension slot, then push it down
more to enter password setting. See the figure on the right:
figures on the right for operation in arrow direction. DO NOT push it down vertically to prevent
(No need to shut down the MPU) Open WPLSoft [Setting] [TC-01 password key setting].
correctly to prevent damage. damage. Select [Enter TC-01 password key], and operate as instructed.
After setting, display shows the figure on the right. (KEY SET),
4 TS-01 OPERATION then press ESC to exit.
2 INTRODUCTION 1. Switch DU-01 to TS-01 mode. (Please see the back of the DU-01) b) TC-01 has password key setting, therefore, only if the PLC has no password protection or with the
2. Main Process same password with TC-01 can process the writing. It also writes the password to the PLC for
DU-01 Digital Setup Display has two operation modes, TS-01 and
added protection.
TC-01. The mode selection switch locates at the back of the
Time Mode c) Password key clear (KEY CLR): Same as the operation above. Open WPLSoft, select [TC-01
DU-01. Factory setting is TS-01 mode. The current operation
password key clear], and operate as instructed.
mode will be displayed every time when power up. ESC Press and hold for 3 sec.
TS-01 TC-01
Operation Mode
3. Clear P, D, F of TC-01: select the device (P, D or F) to be cleared, press + simultaneously,
then press ESC.
ESC Auto Save
Back of the DU-01 4. RD mode description:
YY-MM-DD
OK Press and hold for 3 sec.

1. In TS-01 mode, DU-01 (specified as TS-01 hereof) has the following functions:
Display
Selection
RD read mode
• Read/Write both the internal devices of PLC (e.g. perpetual calendar, bit devices (X, Y, M, S) HH-MM-SS +
ESC No Save
and word devices (T, C, D)) and the Control Register (CR) inside the extension units.
• Support the read/write 32-bit data register. P,D,F selection
OK Confirm & update time
• Set Start-up display and power save mode.
• Monitor the devices. Confirm
ESC
Device
• If connect the accessory cable to ES-series without perpetual calendar, the Time Display will
start from 00-00-00 calculated by the microprocessor of DU-01 (timing error may occur). Device
Selection
• Give RUN-STOP command to PLC. Device Selection
X, Y, M, S
2. In TC-01 mode, DU-01 (specified as TC-01 hereof) has the following functions for DVP all series: T, C, D

• Read/write the program P, data register D and file register F from PLC. CR P(Program) D (Data Register) F (File Register)
DD(32-bit)
• Copy program and data.
• Support the PLC password protection.
ESC OK
Specify a number
Overview of the Product - Names of Parts
Device
P: program area indication Monitor
1 Press and hold for 3 sec. OK
(TC-01) Number Selection Force On/Off setting
OK OK
2 W: write (WR) indication (TC-01) Bit Device confirm Monitor status of 8 consecutive
Device devices from the specified number
1 5 3 R: read (RD) indication (TC-01) ESC ESC
Setting reading range.
Reading P (Program). Reading F (file register)
4 “In communication” indication (default start & end
2 6 D: Data Register indication
Press OK to complete entering & return
You can press ESC to
addresses are latched You can press ESC to
5 pause reading. pause reading.
(TC-01) area range. User can
3 7 Number Selection OK
Enter a number
Press and hold for 3 sec.
F: File Register indication OK OK
re-set it.)
6 Word Specified No.
(TC-01) Device confirm Enter Set Value
4 8 7
CR: Control Register indication
Device
ESC ESC
Display
ESC
Enter start address
Finish reading.
(Extension Module)
d1EC is the CHKSUM 2746 is the CHKSUM
8 ER: Error message display of writing program of writing data
9 9 Display Area 3. Start-up display mode setting (press + buttons simultaneously)

10 Enter button indication Monitor


Mode Press + + Enter end address
ESC OK K (Decimal), H (Hexadecimal) Any mode* Finish reading Finish reading
11 Time & device
DU-01
indication Until shows
Contacts & coils of timer / content
12
counter indications
Word devices T, C, D, DD (32-bit) Sleep mode activated if no button is pressed
13
indication within 30 seconds Reading processing...
14 Bit devices X, Y, M, S indication You can press ESC to
pause reading.
15 Digit backspace / Run (TC-01)
Sleep mode
16 Back to previous status
17 Enter number or select device
*Note: not include system operation mode setting Finish reading
18 Confirm
19 Enter number or select device 4. Please see the back page for detail information about the process of each mode.
4. WR mode description: Various process for operation modes under TS-01 mode
WR writing mode
Sleep mode setting (On: activate, Off: deactivate)
+ Fill 0 setting (fill 0 before number or not) (On: not to display 0, Off: display 0)
Start-up display setting (On: allow to customize start-up display,
P,D,F selection System operation Off: Default time display)
mode setting Auto Save setting

Device Confirm R W P D F CR ER

Time display mode


K H X Y M S T C D DD

ESC + OK
Mode selection On/Off

P (Program) D (Data Register) F (File Register)


Select yy-mm-dd/hh-mm-ss
PLC calendar setting
R W P D F CR ER
Confirm & update the time

OK Time display mode


K H X Y M S T C D DD
Blink alternatively

ESC + OK
Field selection
Set the contents ESC
for setting

Writing to P (Program) Writing to F


The right four digits show 8 consecutive

in PLC. Start + End (File Register) in PLC.


displays/settings that starts from Y10
The left four digits show device 's number
You can press ESC You can press ESC W P D F CR ER

Setting reading range. Y10 Y11 Y12 Y13


to pause writing during to pause writing during W P D F CR ER

(default start & end TC-01->PLC. Y14 Y15 Y16 Y17


TC-01-> PLC. K

addresses is latched Device select mode K


Y10,Y12,Y15,Y17 are On
(Depends on actual output of the PLC)
area range. User can
Press and hold for 3 sec.until the blinking cursor shows
K

change it.)
W P D F CR ER

Finish writing. Finish writing.


OK Device status display OK OK
d1EC is the CHKSUM d1EC is the CHKSUM K

of writing data. Finish writing of writing data.


Move the bit to
Move to the Forced On/Off
d1EC is the CHKSUM Select device confirm device Set device's number desired device's
digit to be set setting
of writing data. number
X, Y, M, S ESC
ESC
Finish writing Finish writing
Use to switch between K (decimal) / H (hexadecimal) display mode.
Finish writing W P D F CR ER For 32-bit registers, use to move to display the two left-most digits.
At this time, indicator will light up.

Device select mode DD stands for 32-bit data register K

K Both timer and counter have coils & contacts monitor.


W P D F CR ER

Current value
OK OK OK
6 DIMENSIONS & ACCESSORY display
K
(Press and hold for 3 sec.)
Connecting to Move to the
DVP-PLC COM1 Word device Select device Confirm device Set the number ESC
digit to be set
(RS-232 Port) T, C, D, DD

ESC ESC

ESC OK For example:


Display two left-most digits
DU-01 Enter Set Value & return for 32-bit register.
W P D F CR ER
(Press and hold for 3 sec.)
to monitor mode
Current value
Enter Set Value mode
W P D F CR ER
OK OK
display
K

Move to the digit


K

Enter Set Value ESC Device number setting


to be set
Expansion
COM Port T, C, D, DD
ESC

CR number Expansion unit number (0,1,2...7)

The accessory cable connects the DU-01 (the extension COM port of figure above) and
K
DVP-series PLC COM1 (RS-232) port. Therefore, the DU-01 can be connected to ES/SS/EX W P D F CR ER (Press and hold for 3 sec.)
or SA/SX models via the cable, as well as direct installation in the extension slot of EP/EH Specify the expansion Current value
OK Specify CR number OK OK Enter Set Value mode
models. unit number display
K

7 ERROR CODE TABLE select device confirm CR


32-bit 16-bit
Code Code Explanation & Troubleshooting
ESC
P-read error. PLC is password-locked while the TC01 has wrong or no password
Error-00 ESC
key. Need unlock the password setting on PLC or set password in TC-01 via WPL.
P-write error. PLC is password-locked while the TC01 has wrong or no password
Error-01
key; or the source model unmatched the destination model. Device select mode
D-read error. Illegitimate read range (read range only available for the general data
Error-02 R W P D F CR ER

registers of each models, not include special D)


Device select mode
Error-03 D-write error. The source model unmatched the destination model. K H X Y M S T C D DD

Error-04 F-read error. ES series does not have file registers. ESC + OK

PLC status display PLC status switch Time display mode


Error-05 F-write error. The source model unmatched the destination model.
Error-06 PLC is running. Writing to P is not permitted.