CIRCUIT DRAWN WITH POWER SUPPLY OFF FOR TYPICAL REMOTE CONTROL

M RED
2 BLACK
- DETAILS, SEE DOCUMENT
2 DC
2 WIRE DC
BLACK
4
1
RED
1 +
SUPPLY RWS100
3
6 3
VOLTAGE OPTIONS
5 E
VOLTAGE SIZE
SK5
+ 110VDC 10,12,18,20,25
1 FS1
C2 C1 2 - 48VDC 10,12,18
SK2
24VDC 10
DC-DC 1
CONVERTER
4
REFER TO SHEET 2 FOR NOTES
0VDC
3 4 & OPTION PCB'S IF FITTED
24VDC 6 5
SK14
1

2
SK12 SK10 SK9 SK11
SK4
1 46
2 47
SK1
3
SLEEP
CONTROL 1
5

SK3 SK4
6 CLOSE 9 33
5 STOP/ MAINTAIN 10 34
4
TORQUE 3
OPEN 8 35
2
SENSOR 1
COMMON -VE 1 36
SK8
ESD 12 25
POSITION 10 WAY OPEN INTERLOCK 13 37
SENSOR
CLOSE INTERLOCK 14 38
SK9 COMMON -VE 5 31
BATTERY - 4 SK14
1 42
1 MONITOR RELAY
+ 3 43
FS2 (IF FITTED) 100mA 2 44
SK7
1 6
S1
50% SK6
MAKE AT FULLY SHUT
8 7
2 8
18 WAY MAKE AT FULLY OPEN S2 7 9
CLOSE
STOP 3 10
REMOTE
LOCAL
BREAK AT FULLY SHUT S3
OPEN 6 11
4 12
BREAK AT FULLY OPEN S4 5 13
SK1 SK2
SLOT A SLOT B

Iss Date Chkd Revision Details IQ DC + EXTRA RELAYS S5-S8


1 230813 PJW FIRST ISSUE www. .com
2 240614 MR SHEET 2, NOTE 1 UPDATED
ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: JC1 Circuit Diagram Number Issue Sheet
3 230419 PJW DC Note SHT.2 Corrected BATH, BA1 3JQ ROCHESTER Date : 230813 No
ENGLAND NY 14624, USA
Base WD: 140B0010
Job No : - -
140B0010 3
1
of 2
Tel:01225-733200 Tel:585-247-2304 MI No : - - B1 C1 B2 C2
IQ3
CIRCUIT DRAWN WITH POWER SUPPLY OFF

SLOT A
SK1
SLOT A SK3
EXTRA CHANGE OVER CONTACTS

2 14
FOR OTHER SETTINGS SEE PUB002-038

S5 3
MAKE AT FULLY SHUT 16
DEFAULT SETTINGS SHOWN

1 15
5 17
MAKE AT FULLY OPEN S6 6 19
4 18
8 20
MAKE ON TORQUE
TRIP S7 9 24
7 21
11 30
MAKE WHEN REMOTE
SELECTED S8 12 39
10 41

NOTES
1.FUSES: 3.INDICATION:
-FS1 - 6A anti-surge -For typical position, status and alarm indication see PUB002-041.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%, -“S” contacts are user configurable and are shown in their default
applies for rated torque performance; duty cycle and speed is not setting.
guaranteed. -Refer to PUB002-040 for functions and configuration instructions.
-Monitor Relay indicates actuator availability for remote control (shown
2.REMOTE CONTROL: “unavailable”). It can be configured to exclude local/remote selection.
-For typical remote control circuits refer to: -Refer to PUB002-040 for monitored functions and configuration
-RWS indicated or PUB002-041. instructions.
-For DC and AC control, connect –ve/0V to terminal 36. -Voltage applied to indication contacts must not exceed 150Vac
-(For negative switch / positive common, refer to RWS indicated). -Individual Switch current must not exceed 3.5A inductive, 5A resistive
-Control signal threshold voltages: and no more than 8A in total for all 4 contacts.
-DC: “on” ≥16Vdc / “off” ≤8Vdc, max 60Vdc.
-AC: “on” ≥60Vac / “off” ≤40Vac, max 120Vac. 4.BATTERY:
-Control signal duration to be 300ms minimum. -Battery maintains local and remote “S” contact indication only.
-Maximum current drawn from remote control signals is: -Refer to installation manual for approved replacement battery types.
-8mA at 24Vdc or 12mA at 120Vac.
-Supply provided on terminals 4 & 5:
-Intended for remote control.
-Max external load 5W at 24Vdc / 5VA at 120Vac

5.DC:
-Default for sleep mode is DISABLED.
-Sleep mode can be enabled by moving link LK1 from NORM to SOLAR. (Basic DC solar is 150B0000)
-Actuator will remain powered up at all times while supply is present.
-24VDC will be lost when in sleep mode.
-If customer supply is needed to wake actuator link LK3 must be moved to CUST for maintained customer supply.
Circuit Diagram Number Issue Sheet
No
140B0010 3 2
See Sheet 1 for all Revision details/information of 2