DESCRIPTION OF OPTIONS
Option M12
Configurable I/O extension cards, 13 binary inputs/
4 relay outputs
● Description of option
● Functional description
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com
isenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com Document no.: 4189340699A
14 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com SW version:
Option M12, 4189340699 UK
1. Delimitation
1.1. Scope of option M12..............................................................................................................................3
2. General information
2.1. Warnings, legal information and safety..................................................................................................4
2.1.1. Warnings and notes ......................................................................................................................4
2.1.2. Legal information and disclaimer ..................................................................................................4
2.1.3. Safety issues ................................................................................................................................4
2.1.4. Electrostatic discharge awareness ...............................................................................................4
2.1.5. Factory settings ............................................................................................................................4
3. Description of option
3.1. Option M12.............................................................................................................................................5
3.2. ANSI numbers........................................................................................................................................5
3.3. Terminal descriptions.............................................................................................................................6
3.3.1. Terminal description, AGC.............................................................................................................6
3.3.2. Terminal description, GPU/GPU Hydro.........................................................................................7
4. Functional description
4.1. Digital inputs...........................................................................................................................................8
4.2. Protection/alarm inputs...........................................................................................................................8
4.2.1. Function input................................................................................................................................8
4.3. Relay setup............................................................................................................................................9
4.4. External analogue setpoints...................................................................................................................9
4.4.1. AGC...............................................................................................................................................9
5. Parameters
5.1. Further information ..............................................................................................................................11
1. Delimitation
1.1 Scope of option M12
2. General information
2.1 Warnings, legal information and safety
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in-
jury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-
ranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.
3. Description of option
3.1 Option M12
Option M12 is a hardware option, and therefore an extra PCB is placed in slot #3 in addition to the standard-
installed hardware.
Please refer to the Installation Instructions for detailed description of the wiring of digital in-
puts.
Please refer to the Installation Instructions for detailed description of the wiring of digital in-
puts.
4. Functional description
4.1 Digital inputs
The digital inputs available in this option can be used for two purposes:
1. Protection (alarm) inputs
2. Function inputs
The delay settings are all of the definite time type, i.e. a set time is selected. The delay will be activated if the
input goes ON (or OFF if selected to be N/C). If the input is reset before the delay runs out, the delay will be
reset.
Input Input Input
ON OFF ON
Timer setting
Time
Timer Timer Timer Alarm
start reset start
When the delay runs out, the output will be activated.
The PC utility software is a Windows®-based software, which can be downloaded from our website www.de-
if.com. To adjust the inputs via the PC utility software, a computer must be connected to the controller unit.
Furthermore, the unit parameters must be uploaded to the computer.
Please refer to the Designer’s Reference Handbook for a complete list of the available input
functions.
Each relay has a function and an OFF delay setting as described below.
Function Description
Alarm relay NE When the relay is activated, an alarm is displayed. The relay will remain activated for
as long as the alarm is present and unacknowledged.
Alarm relay ND When the relay is activated, an alarm is displayed. The relay will remain activated for
(GPU/GPU Hydro as long as the alarm is present and unacknowledged.
only)
Alarm/reset The functionality is similar to "Alarm", but with a short-time reset if the relay is ON and
(GPU/GPU Hydro another alarm tries to activate the same relay.
only)
Limit relay When the relay is activated, no alarm message is displayed. After the condition activat-
ing the relay has returned to normal, the relay will deactivate when the "OFF delay"
has expired.
Horn relay When the relay is activated, an alarm message is displayed. The relay will be activated
until the time set in menu 6130 "Alarm horn" has expired or the alarm activating the
relay has been acknowledged.
Siren relay (GPU/ The output activates on all alarms, like “Horn output”. If the relay is ON and another
GPU Hydro only) alarm is active, a short-time reset = 1 s will be activated.
OFF delay The "OFF delay" is used when limit relay is selected. It is the time between the disap-
pearance of the event that caused the relay to activate and the actual deactivation of
the relay.
It is possible to configure the relay outputs to be used for speed and/or voltage regulation.
Please refer to the Designer’s Reference Handbook.
The relays can also be used together with M-logic. Please refer to the help function in the PC
utility software.
4.4.1 AGC
The genset can be controlled from internal as well as from external setpoints. The external setpoints are acti-
vated with a digital signal.
Five inputs can be selected, and their function depends on the mains breaker position.
The controller setpoints will be ignored if the running condition is not present. For instance, it is not possible
to use the frequency controller when paralleling to the mains.
The external setpoints can be used in all genset modes when auto or semi-auto mode is selected.
Only a limited number of digital inputs are available in the standard unit. The unit should be
installed with the sufficient number of options to get the desired digital inputs.
If the option H2 is available in the unit, the external setpoints can be controlled from the control
registers in the Modbus protocol. Please refer to the description of option H2 for further infor-
mation.
5. Parameters
5.1 Further information
For further information, please see the separate parameter list for the Multi-line unit in question: