Dimmable Detector

220~240VAC

Model: UC19

Antenna module 30.2 42.3


sensitivity
LED indication

31.7
hold-time

4.2

45
daylight threshold
stand-by time
stand-by dim level
86.5
93.2
102

25.5
28

daylight sensor + - SYN


13

L’ N N L
1-10V

Product The motion detector can turn on the light based on movement. With this detector built in, light is
Step-dim function
Feature automatically on when needed and dimmed to preset level before it is totally off.

The light keeps off during daytime If there is no more movement, the The light turns off automatically after
even when movement is detected. ambient lux level, the light is light dims to stand-by level after stand-by time.
(Ambient lux level is above preset triggered on by the detector. hold-time.
daylight threshold)

IZUMI LED
ULTRANIK HF motion detector

Synchronized control
Function
Multiple detectors can control the same group of light. No matter which one detects movement, all lights connected
will turn on. Ideal for places such as corridor, show room, meeting room where there are more than one entrances.

Zero-cross relay operation


To protect the relay against the inrush current, control software switches AC load right at the zero-cross points when

Wire loop-in and loop-out


The detector is thoughtfully designed with fast connects for power in and power out to load. Easy to assemble.

N
Wiring L

+ - L N
L N N L’ SYN - + 1-10V
1-10V control gear
- +
UC19

LED

Detection pattern Ceiling mounting (m) Wall mounting (m)


6 5 4 3 2 1 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9
1 2 3 4

1
2
height (m)

height (m)

3
4
4 3 2 1

5
6

high sensitivity area low sensitivity area high sensitivity area low sensitivity area

IZUMI LED
ULTRANIK HF motion detector

Settings 1. Sensitivity I – 100% 1 2


100%
II – 75%
Sensitivity can be adjusted by selecting the combination 75%
III – 50% 50%
on the DIP switches for different applications.
IV – 10% 10%

I – 5s 1 2 3
II – 30s 5s
2. Hold-time III – 1min 30s
IV – 5min 1min
Hold-time refers to the time period that the light remains V – 10min 5min
100% on if no more movement is detected. VI – 20min 10min
20min
VII – 30min
30min

3. Daylight sensor 1 2
I – Disable Disable
Different daylight threshold can be preset on DIP switches. II – 50Lux 50Lux
Light will always turn on upon movement if daylight sensor III – 10Lux 10Lux
IV – 2Lux 2Lux
is disabled.

I – 0s 1 2 3
II – 10s 0s
4. Stand-by time III – 1min 10s
1min
IV – 5min
This is the time period that the light remains at a low level 5min
V – 10min
before it is completely turned off. 10min
VI – 30min 30min
VII – 1h 1h
VIII – + ∞ +∞

1 2
I – 10%
5. Stand-by dim level II – 20%
10%
20%
Light can be dimmed to different levels after hold-time. III – 30%
30%
IV – 50%
50%

Operating voltage 220 ~ 240 VAC 50/60Hz


Rated load Max.800W (capacitive)
Stand-by power <1W
Sensitivity 10% / 50% / 75% / 100%
Hold-time 5s / 30S / 1min / 5min / 10min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞
Stand-by dim level 10% / 20% / 30% / 50%
Daylight sensor 2 ~ 50lux, disable
Microwave frequency 5.8 GHz +/- 75MHz
Transmitting power <0.2mW
Detection range maximum (diameterxheight): 12m x 6m
o o
Detection angle 30 ~ 150
Mounting height maximum 6m
o o
Working temperature -35 C ~ 70 C
IP rating IP20
Semko, CB,CE,SAA