Professional Documents
Culture Documents
Window Shading Strategies: Sun's Path in Winter and Summer
Window Shading Strategies: Sun's Path in Winter and Summer
A high percentage of summer heat gain comes Sun’s Path in Winter and Summer
through windows as solar radiation. Much of the
radiation is diffuse or reflected, and not directly from Dec 21 June 21
noon noon
the sun. As a result, it pays to shade all windows,
regardless of the direction they face. The single Dec 21 June 21
noon noon
exception is passive solar glazings in northern states,
which should have calculated overhangs, as shown in
Chapter 18. Dec 21
sunset
The illustration and table below show the per- June 21
W sunset
centage reductions in heat gain through the entire Noon
Dec 21
sunset
S altitude Noon June 21
cooling season for 4- by 4-foot windows at 30 degree altitude W sunset
north latitude, when shaded by continuous over- Noon
S altitude Noon
hangs of various lengths, L. The reductions are seen altitude N
to be nearly independent of window orientation. Of Dec 21
sunrise E
course, there are reasons other than solar shading for June 21 N
Dec 21 sunrise
building overhangs: sunrise E
June 21
1. A 2-foot overhang protects siding, windows, sunrise
and doors from the weathering effects of rain. In
addition, windows can be left open without worry- Overhang Geometry for Table
ing about sudden showers.
4"
2. A 6- to 8-foot overhang is common for porch L
roofs, which are very common in the South. 4"
492 COOLING
The illustration at right shows an adjustable opaque Adjustable Awning with Sides
window awning with side panels. Both the awnings
and windows measure 4 feet by 4 feet, so at a
90 degree slope, the awning would completely cover
the window. The table below the illustration shows
the cooling-season reductions in heat gain to be
ing
expected through single-glazed windows with differ- Awn gle
a n
ent shading strategies.
As the slope of a shading device increases, visibility 48"
from the window decreases until, at 90-degree slope,
nothing can be seen. Fortunately, much of the shading
benefit is achieved with a slope of only 30 degrees, at
which point the top half of the view is blocked.
Canvas awnings can be rolled up, but the other
shading options would be difficult or impossible to
adjust in different seasons. We therefore need to know
for each the net effect, or cooling-season savings less
reduction in winter solar gain.
Both cooling and heating bills vary with latitude. Net Savings from Awnings, kwhr/sq ft-yr
As latitude increases, cooling bills decrease and heating
bills increase. Net savings from fixed shading devices Window Tinted Silver Charcoal Awning Awning
Facing Glass Film Screen No Side & Sides
therefore vary with latitude. In the South, net savings
Jacksonville, FL, 30.5º N Latitude
are positive; in the North they can be negative.
North 1.5 3.6 3.8 2.9 4.2
The table at right shows how strongly net savings
can vary. Savings in Miami (virtually zero winter heat- East 1.5 3.4 3.6 4.1 4.5
ing load) are nearly three times those in Jacksonville, South 0.4 0.9 1.0 0.4 0.9
only 4.5 degrees to the north. For example, perma- West 2.3 5.4 5.6 5.6 6.8
nent charcoal-colored screens over 100 square feet of Average 1.4 3.3 3.5 3.3 4.1
uniformly distributed glazing would save 1,000 kwhr Miami, FL, 26º N Latitude
in Miami, but only 350 kwhr in Jacksonville. North 3.1 7.4 7.7 5.8 8.6
Shading devices above 30 degrees north latitude East 4.5 10.5 11.0 10.2 13.1
should be of the adjustable variety in order to maxi- South 17 35 47 67 79
mize both summer and winter savings. West 15 32 47 71 83
Average 16 33 46 69 81
Fan Efficiencies
8,000
6,000
t
at
/w
Air flow, cubic feet per minute (cfm)
cfm
t
at
80
/w
g
cfm
ilin
Ce
10
e
us
ho
4,000
le
ho
t
at
W
/w
cfm
30
ow
t
at
ind
/w
W
cfm
2,000
35
ing
lat
cil
Os
0
0 10 20 30 40 50 60
Fan diameter, inches
494 COOLING
Ceiling Fans Ceiling Fan Operation
Air-circulating fans include oscillating, box, and
ceiling fans. The breezes they create can easily allow
air conditioner setbacks of 5°F to 10°F, lowering 10" min
cooling bills by 40 to 80 percent. Portable fans are
best at cooling small areas, such as people sitting at
desks or working in the kitchen. Larger box fans 7' 0" min
can be placed in doorways to move large volumes of for safety
air between rooms. The quietest and most efficient,
however, are ceiling fans. A ceiling fixture can usu-
ally be easily converted to a ceiling fan plus light.
The illustration at right shows required clearances
and proper fan size.
Fans 495
Evaporative Cooling
When water evaporates, it absorbs heat. This is Evaporative coolers are recommended wherever
why you feel so cool when you emerge from swim- the temperature drop (DB − WB ) is over 20°F and
ming on a dry, breezy day. Evaporative coolers (also the cooled air would be below 79°F. The table
known as swamp coolers) utilize this phenomenon below lists these criteria for selected cities. Cities
to lower air temperature. As the illustration on the which meet both criteria appear in italics. To size an
facing page shows, hot, dry air blown through a evaporative cooler, follow these steps:
water-soaked pad emerges as humid, but much 1. Compute the volume of house air.
cooler, air. The temperature drop can be predicted
2. Find the recommended minutes per air change
from the following equation:
for your location.
Temperature drop = E × ( DB − WB ) 3. Divide the house volume by minutes to find the
where E = cooler efficiency, percentage recommended cooler capacity in cfm.
DB = intake air dry bulb temperature 4. If your home is very energy efficient, divide cfm
WB = intake air wet bulb temperature by 2; if not insulated, multiply by 2.
496 COOLING
How an Evaporative Cooler (Swamp Cooler) Works
A B B A
80
75
70
˚F
e,
a tur 65 Line
r
pe s of
Tem B Con
stan
r
Ai 60 t En
thal
py (
Energ
55 y)
50
45 A
H
80 %R
RH
60%
RH
40%
20% RH
0% RH
40 50 60 70 80 90 100
Air Temperature, ˚F
AL
RM
NO
H
G
N HIAN
O FF F
O
W
LO N
FA
The compressor W
LOOL
CO 6 78
turns refrigerant
9 10
AT
ST
1 2
MO
ER
TH
A thermostat senses
that cooling is needed
Refrigerant recycles
to the compressor
Return duct
498 COOLING
If all else fails to cool you into the comfort zone, When you are done, go to the Energy Star site
you have no choice but to air-condition. Air condi- www.energystar.gov. There you will find an up-to-
tioners, powerful but expensive tools, lower humid- date list of all air conditioners, with their rated
ity as well as temperature. cooling capacities and energy efficiency ratios (EER).
What you need first is an estimate of your peak Look for models with the highest EER (the ratio of
cooling load, the number of Btus per hour that Btus removed to watts of electricity consumed) that
need to be removed under the worst conditions of also closely match your load. The most efficient air
the cooling season. The work sheet and tables that conditioner for your purpose will be one that is just
follow allow you to find that load, whether you are capable of supplying the load.
cooling just a bedroom or the entire house, no mat-
ter where you live in the United States.
You may wish to photocopy the work sheet so
that you will be able to calculate the peak cooling
load for a second room.
Read the instructions carefully for each line
before entering any numbers. An example calcula-
tion follows the work sheet.
.70
.70
.80
.75 .75 .70
.75
.90 .80 .75
.90
.80 .90
.90
1.00 1.00
.90
1.10
1.50
1.20
1.20
1.50
1.50
walls. The insulation factor is 0.8 times the nominal Full basement 0.0
R-value of the wall insulation (see Chapter 13 for Unconditioned room 0.9
insulation R-values), or 2.4 if there is none. Ground (slab-on-grade) 0.1
Line 5. Get the floor factor from Table 2; the insu-
lation factor is as in line 4.
Line 6. Enter the total floor area of the cooled
Table 3. Glazing Factors
space. Estimate air changes per hour as 0.4 for the
tightest possible house to 1.3 for a drafty one. Type of Glazing Line 7 Line 8
Line 7. Calculate window areas as height times Single-glazed window 1.0 1.0
width of the sash (the frames holding the glass). Get Double-glazed window 0.5 0.8
the glazing factors from Table 3. Triple-glazed window 0.33 0.65
Line 8. Get the shading factors from Table 1 and
the glazing factors from Table 3.
Line 9. Add the results from lines 1 through 8 and Table 4. Thermal Mass Factors
multiply by the cooling factor for your geographic
Building Construction Factor
area, shown on the map on p. 499.
Light wood frame 1.00
Line 10. Multiply your average monthly spring or
fall kilowatt-hours (get these from your utility bills Solid masonry or wood frame 0.90
with exterior masonry veneer
or by calling your electric utility) by l.4. For the
Wood frame with masonry interior 0.80
average home the result should be about 600 kwhr/ walls, floors, or other mass
month. Earth-sheltered (underground) 0.50
Line 11. Enter the average number of people occu- walls and roof
pying the cooled space during the hot months.
Line 12. Add lines 9, 10, and 11, then multiply
the result by the mass factor from Table 4.
500 COOLING
Work Sheet for Sizing Air Conditioners
Source of Heat Gain Calculations Results
12. Peak cooling load, Btu/hour: sum of lines 9 – 11 x thermal mass factor =