You are on page 1of 21

Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10

Base Station Installation Site Requirements

7 Power requirements

7.1 Site earth and BTS grounding requirements


Site earthing and site equipment grounding considerations and recommendations.

BTS site grounding is divided into two contexts: site earthing and site equipment
grounding.
To protect the BTS from damaging over voltages through antenna equipment,
communication cables, or power supply lines, grounding cabling must be planned and
installed before the installation of the base station. To avoid interference, it is
recommended that large grounding systems are designed case-specifically.
The function of the site earth is to convoy the lethal and hazardous voltages and electric
currents from the site main grounding point (main grounding busbar) to the earth.
The impedance of the earth connection should be as low as possible:

• The earthing (grounding) resistance target of the BTS site is ≤10 Ω. If it is not
possible to reach this target because of the difficult conditions, for instance in areas
such as solid rocks or dry desert, the earthing (grounding) resistance can be max.
150 Ω.
• The cross-sectional area of the Main Earthing Conductor should not be smaller than
live (L) and neutral never less than 6 mm2 (10 AWG), recommended size is 16 mm2
(6 AWG). For NEBS installations, 16 mm2 (6 AWG) or higher is required.

Site equipment grounding is required to ensure personnel safety and to avoid


electrostatic discharge which can damage the equipment.
An AC power plug with a protective earth (PE) connection is not sufficient. Grounding
must have a fixed, non-removable connection.
BTS DC power input must be floating -48 VDC, or positive grounded. Negative
grounding is not allowed. Note that the fuse protection does not work with negative
grounding. Note also that surge and lightning protection may not work properly with
negative grounding.
In a +24 VDC system, a Flexi Power DC/DC Module (FPDA) or a similar safety-approved
DC/DC converter must be used to convert the negative grounded +24 VDC to floating
-48 VDC

g Note: Follow local requirements for earthing (grounding). The principles and
requirements vary in different countries.

Observe the following recommendations when planning the BTS grounding:

• Grounding cable cross-section has to be more than any of AC or DC power feeding


cable cross-section.
• The grounding cable is connected with screws to the BTS mains grounding point.
• The grounding cable must be connected to a main grounding busbar with a minimum
of 6 mm2 (10 AWG) grounding cable.

78 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

• Route the grounding cables as directly as possible from the equipment to the
grounding point. Avoid unnecessary loops and sharp bending of the grounding cable.
The grounding cables should not be run parallel with power cables.
• The external antenna feeders must also be grounded according to the local
legislation if the antennas are exposed to lightning.
• The BTS is suitable for installation in a Common Bonding Network (CBN), Isolated
Bonding Network (IBN) or both.
• For NEBS locations, the BTS is suitable for installation in networks
telecommunications facilities, locations where the NEC (National Electric Code)
applies, and OPS (Outside Plant) environments.

7.2 Mains power requirements


Mains power considerations and permitted operating voltages.

f WARNING! Warning
Danger of lethal voltages.
Make sure that the mains power breaker is off, and that the cabinet is properly earthed
(grounded), before connecting or removing any mains power supply cables from the
BTS cabinet.

At the site there must be a main switch for disconnecting the BTS mains power. The
disconnecting device should disconnect both input supply poles simultaneously.

Table 42 Permitted operating voltage

Property Nominal operating voltage Permitted operating voltage

DC voltage 48 VDC 40.5 to 57.0 VDC

AC voltage with 200 - 240 VAC 184 to 276 VAC (45 - 66 Hz)
optional FPMA

DC voltage with 24 VDC 18 to 32 VDC


optional DC Module

DC return connections can be isolated DC return (DC-I) or common DC return (DC-C).


Check the power consumption. If the power demand exceeds 30A and you use a 30A
source such as an integrated power distribution unit (PDU) or System Module Power
Output port with 30A output capability, then it is recommended to use the dual power
cable FPCA (472806A) with the PDU or System Module Power Output port.
See Cabling Flexi Multiradio BTS [technology] for instructions on how to connect the dual
power cable.

g Note: Note that there are some variations in input voltages between different RF
variants. For more information, see
Flexi Multiradio BTS RF Module and Remote Radio Head Description.

Issue: 08D DN0951839 79


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

7.2.1 Circuit breakers


Guidelines for selecting circuit breakers and a table listing minimum recommended sizes.

General guidelines for circuit breakers are provided below. Recommended sizes are
provided in the table below.

• Medium delay type (B or C) is recommended to avoid tripping in rush current or


minor lightning surges.
• Circuit breaker interrupt rating is recommended for exceeding maximum short circuit
(breaking) capacity expected from the power source.
• Voltage rating for overvoltage protection device should also be considered.

Table 43 Minimum recommended sizes for circuit breakers


Unit Battery back- Constant 55V
up, 36V DC DC @ source,
Configuration after feeder 48V after 110 V AC (A) 230 V AC (A)
@ Radio (A) feeder @ FPAD/FPAE FPAD/FPAE
Radio (A)
2TX 120W RRH
FRGY, FRCG, 2 x 60 W 20 16 10 6
FHDB, FHEB,
2 x 40 W 16 13 6 6
FHEF, FHEG
2 x 30 W 13 10 6 6
2 x 20 W 13 10 6 6
4TX 160W RRH
FHFB,FRBE, 4 x 40 W 32 25 13 6
FRBF,FRBG,
FHED, FRHG, 4 x 30 W 25 20 10 6
FRNC, FHEH 4 x 20 W 20 16 10 6
4TX 120W RRH
FRIG, FRHC, 4 x 30 W 32 25 13 6
FRHD, FHGB
4 x 20 W 25 20 10 6
2TX 80W RRH
FHDA, FHEA 2 x 40 W 16 13 6 6
FRHB, FRMB 2 x 30 W 13 10 6 6
FRAA, FRCC 2 x 20 W 13 10 6 6

6TX 360W RF Module


FXED 6 x 60 W 50 40 - -
FRGU 6 x 40 W 40 32 - -
FRMF 6 x 30 W 32 25 - -
FRSA
6 x 20 W 25 20 - -

6TX 240W RF Module

80 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

Table 43 Minimum recommended sizes for circuit breakers (Cont.)


Unit Battery back- Constant 55V
up, 36V DC DC @ source,
Configuration after feeder 48V after 110 V AC (A) 230 V AC (A)
@ Radio (A) feeder @ FPAD/FPAE FPAD/FPAE
Radio (A)
FRMC, FRME 6 x 40 W 40 32 - -
FRPA, FRPB 6 x 30 W 32 25 - -
FRHC, FRHF 6 x 20 W 25 20 - -

3TX 240W RF Module


FXCB, FXDB 3 x 80 W 40 32 - -
FXEB, FXFC 3 x 60 W 32 25 - -
FXJB, FRGT 3 x 40 W 25 20 - -
FRGS 3 x 30 W 25 20 - -
FXEE
3 x 20 W 20 16 - -

3TX 180W RF Module


FXCA, FXDA, 3 x 60 W 32 25 - -
FXEA, FXFA
FXFB, FXDJ, 3 x 40 W 32 20 - -
FRGP, FRMA
3 x 30 W 25 20 - -
FRMD, FRBA
FRHA, FRIE 3 x 20 W 25 20 - -

8TX 160W TDD RRH


FZHM, FZHI 8 x 20 W 32 25 - -
8 x 10 W 25 20 - -
4TX 120W TDD RRH
FZNI 4 x 30 W 32 25 - -
4 x 20 W 25 20 - -
4 x 10 W 25 20 - -
8TX 80W TDD RRH
FZHA 8 x 10 W 25 20 - -
System Modules
ESMB/ESMC FIQB/FIYB 6 6 - -
(no PDU DC
ports in use)

FSME (no FTIB/FTLB 16 13 - -


PDU DC ports
in use)
FSMF (without FTIF 10 8 - -
FPFD PDU)

Issue: 08D DN0951839 81


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

Table 43 Minimum recommended sizes for circuit breakers (Cont.)


Unit Battery back- Constant 55V
up, 36V DC DC @ source,
Configuration after feeder 48V after 110 V AC (A) 230 V AC (A)
@ Radio (A) feeder @ FPAD/FPAE FPAD/FPAE
Radio (A)
FTIF + 1 x 16 13 - -
FBBC
FTIF + 2 x 20 16 - -
FBBC
FSIH - 13 10 - -
1 x FBIH 20 16 - -
2 x FBIH 32 25 - -
Notes:
• 48V includes a 10% tolerance
• AC includes a 10% tolerance and 88% efficiency for AC/DC converter (FPAD/FPAE)
• ALD includes a 10% tolerance and 90% efficiency
• ALD -30W for 2ANT, 60W for 3ANT, 90W for 6ANT
• The commonly available preferred values for the rated current are 6 A, 10 A, 13 A, 16 A, 20
A, 25 A, 32 A and 40 A. If a size is not available, use the next available size.
• The variant with highest power consumption is the representative variant for each type (2x60
RRH, 4x40 RRH, 3x60 RFM, etc.).
• Maximum fuse rating is the highest rated value for each module.

7.2.2 Flexi Power Module (FPMA) battery backup times


Power load considerations and estimated battery backup times.

Flexi BTS uses 48 VDC power. In a BTS site with AC feed only, Flexi Power Module
(FPMA) is required to convert AC to DC. Flexi Power Module (FPMA) consists of
mechanics, AC terminal, and four slots for AC/DC sub-module (FPAA) or battery sub-
module (FPBB).
Two FPMAs can be installed in a stack to support FPAA and FPBB operating in parallel.
Table 44: Battery backup times shows the battery backup times depending on the
configuration and load scenario.

82 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

Table 44 Battery backup times

FPMA Estimated typical battery backup time in 23°C for new battery [min.]

Single FPMA Dual FPMA (stacked)

Power load FPAA 1 x FPBB 2 x FPBB 3 x FPBB 4 x FPBB 5 x FPBB 6 x FPBB


(rectifier) (battery) (battery) (battery) (battery) (battery) (battery)

250 1 32 64 96 128 160 192

500 1 16 32 48 64 80 96

750 1 11 22 33 44 55 66

1000 1 8 16 24 32 40 48

1250 2 - 13 19 26 32 38

1500 2 - 11 16 21 27 32

1750 2 - 9 14 18 23 27

2000 2 - 8 12 16 20 24

2250 3 - - 11 14 18 -

2500 3 - - 10 13 16 -

2750 3 - - 9 12 15 -

3000 3 - - 8 11 13 -

3250 4 - - - 10 - -

3500 4 - - - 9 - -

3750 4 - - - 9 - -

4000 4 - - - 8 - -

g Note: FPBB maximum charge and heating power is 100 W per battery.
The “per battery” charge power needs to be taken into account and subtracted from the
available rectifying capacity, thus reducing the power available for the BTS.
In redundant (n+1) configurations an extra FPAA provides rectifying redundancy and,
additionally, takes care of battery charging.

Issue: 08D DN0951839 83


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

7.2.3 Flexi Power Module (FPMA) AC wiring and fuse


requirements
Fuse and wire cross section requirements for AC connections.

Table 45 Fuse and wire cross section requirements single phase AC


# of FPAA in FPMA Fuse size (A) for single Wire cross section
phase 240 VAC
1 6 3 x 1.5 mm2
2 10 3 x 1.5 mm2
3 16 3 x 2.5 mm2
4 20 3 x 4 mm2

Table 46 Fuse and wire cross section requirements three phase AC


Wire cross section
FPMA Fuse size (A) for 3 phase 240 VAC

FPAA 1 1st phase 10 5 x 1.5 mm2

FPAA 2

FPAA 3 2nd phase 6

FPAA 4 3rd phase 6

Table 47 Fuse and wire cross section requirements three phase AC for dual FPMA
Wire cross
section
dual FPMA #1 dual FPMA #2 Fuse size (A) dual FPMA for 3
phase 240 VAC

FPAA 1 FPAA 5 1st phase 20 5 x 4 mm2

FPAA 2 FPAA 6

FPAA 3 FPAA 7 2nd phase 10

FPAA 4 FPAA 8 3rd phase 10

7.3 RF Module and RRH DC cable requirements


7.3.1 DC cable requirements for 3TX 240W RF Modules
Variant and output power-specific considerations for selecting a DC cable for a 80 W RF
Module.

84 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

A DC cable is not included in the 3TX 240W RF Module delivery. 48 VDC power can be
fed from a System Module or directly from an external power source.
If the cable path between the System Module/external power source and RF Module
exceeds 10 m, then a Flexi System External OVP (FSEC/FSES/FSEP) must be installed
next to the System Module or external power source. For details, see Creating Flexi
Multiradio BTS Site Configurations in respective system documentation.
If a 3TX 240W RF Module is used with FSMC/D/E (FPFB 30A PDU), FSMF (FPFD
A.102 30A PDU) or FPFC A.102 30A PDU then the rules in table DC Cable
Requirements for 3TX 240W RF Modules apply.

g Note: For the enhanced FPFD PDU version A.103/A.204 or FPFC A.203 with 45A/40A
capability a single DC cable is sufficient and a dual DC cable (FPCA) shall not be used.

With ESMB or ESMC, a single cable is sufficient for all 3TX 240W RF Modules as 36A
PDU is used.

Table 48 DC Cable Requirements for 80 W RF Modules

Variant Total Configured RET/MHA Minimum DC Power


output power2) voltage Cable3)

2100/1900/18 <= 180 W Any Any Single


00
(FRGT/FXFC/
FXEB)

2100/1900/18 > 180 W Yes < 46.5 Dual


00
(FRGT/FXFC/
FXEB)

2100/1900/18 > 180 W Yes >= 46.5 Single


00
(FRGT/FXFC/
FXEB)

2100/1900/18 > 180 W No < 41.5 Dual


00
(FRGT/FXFC/
FXEB)

2100/1900/18 > 180 W No >= 41.5 Single


00

2) Total configured output power is the total power for all three branches. For example, a 2+2+2 @ 40 W is
equal to 240 W.
3) The following power cables are available: FPCA 472806A (Dual, 2 m, 6.6 ft), FPCB 472817A (Single, 2 m,
6.6 ft), FPCC 472823A (Single, 2 m, 6.6 ft), FPTA 472246A (Single, 4 m, 13.1 ft). The dual power cable
requires two available PWR outputs on the System Module or PDU (excluding PWR AUX). It is
recommended to use the next available connectors in sequence. The FPCC and FPTA require removing
the connector from one end. Consider future expansion when choosing single or dual power cables.

Issue: 08D DN0951839 85


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

Table 48 DC Cable Requirements for 80 W RF Modules (Cont.)

Variant Total Configured RET/MHA Minimum DC Power


output power2) voltage Cable3)

(FRGT/FXFC/
FXEB)

850/900 <= 180 W Any Any Single


(FXCB/FXDB)

850/900 > 180 W Yes < 40 Dual


(FXCB/FXDB)

850/900 > 180 W Yes < 46.5 Single


(FXCB/FXDB)

850/900 > 180 W Yes >= 46.5 Single


(FXCB/FXDB)

850/900 > 180 W No < 41.5 Single


(FXCB/FXDB)

850/900 > 180 W No >= 41.5 Single


(FXCB/FXDB)

Requirements if power is supplied from an external source


The following requirements apply if power is fed from an external power source:

• The allowed diameter of shielded or jacketed cables is 6-25 mm (0.24-1 in.).


• The allowed cross section of individual DC wires is 6-25 mm2 (10-4 AWG) at the DC
terminal. It is recommended that 25 mm2 (4 AWG) wires are capped to avoid loose
strands. If thicker DC wires are required, then an FSEC/FSES/FSEP or any other
IP65 DC distribution box is required to reduce the cable thickness at the module.
• Recommended DC cable lengths, thicknesses, and type are provided in Feederless
site and Distributed site solution requirements.
• The DC connector has three screw terminals. The outer terminals are for (+) and (-)
wires. The middle terminal is for grounding the shielded DC cable braid.

2) Total configured output power is the total power for all three branches. For example, a 2+2+2 @ 40 W is
equal to 240 W.
3) The following power cables are available: FPCA 472806A (Dual, 2 m, 6.6 ft), FPCB 472817A (Single, 2 m,
6.6 ft), FPCC 472823A (Single, 2 m, 6.6 ft), FPTA 472246A (Single, 4 m, 13.1 ft). The dual power cable
requires two available PWR outputs on the System Module or PDU (excluding PWR AUX). It is
recommended to use the next available connectors in sequence. The FPCC and FPTA require removing
the connector from one end. Consider future expansion when choosing single or dual power cables.

86 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

7.3.2 DC cable requirements for 6TX 240W RF Modules


Variant and output power-specific considerations for selecting a DC cable for a 6TX
240W Module.

A DC cable is not included in the 6TX 240 W RF Module delivery. 48 VDC power can be
fed from an external power source.

• If a 6TX 240W RF Module is used with FSMC/D/E (FPFB 30A PDU), FSMF (FPFD
A.103 30A PDU) or FPFC A.102 30A PDU then the rules in Table 49: DC cable
requirements for 6TX 240W FRMC, FRPA, FRPB Modules and Table 50: DC cable
requirements for 6TX 240W FRHC, FRHF Modules apply:

g Note: For enhanced FPFD PDU version A.103/A.204 or FPFC A.203 with 45A/40A
capability a single DC cable is sufficient and dual DC cable shall not be used.
If the cable path between the System Module/external power source and RF Module
exceeds 10 m, then a Flexi System External OVP (FSES/FSEP) must be installed next
to the System Module or external power source.

Table 49 DC cable requirements for 6TX 240W FRMC, FRPA, FRPB Modules

Total Configured RET/MHA Minimum DC Power Cable


output power Voltage voltage (at
FRM input)

<= 180 W No Any Single

<= 180 W Yes Any Single

> 180 W Yes < 44.3 FPCA

> 180 W Yes > 44.3 Single

> 180 W No < 41.3 FPCA

> 180 W No > 41.3 Single

Table 50 DC cable requirements for 6TX 240W FRHC, FRHF Modules

Total Configured RET/MHA Minimum DC Power Cable


output power Voltage voltage (at
FRM input)

<= 180 W No Any Single

<= 180 W Yes Any Single

> 180 W Yes < 48.2 FPCA

Issue: 08D DN0951839 87


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

Table 50 DC cable requirements for 6TX 240W FRHC, FRHF Modules (Cont.)

Total Configured RET/MHA Minimum DC Power Cable


output power Voltage voltage (at
FRM input)

> 180 W Yes > 48.2 Single

> 180 W No < 45.2 FPCA

> 180 W No > 45.2 Single

Requirements if power is supplied from an external source


The following requirements apply if power is fed from an external power source:

• The allowed diameter of shielded or jacketed cables is 6-25 mm (0.24-1 in.).


• The allowed cross section of individual DC wires is 6-25 mm2 (10-4 AWG) at the DC
terminal. It is recommended that 25 mm2 (4 AWG) wires are capped to avoid loose
strands. If thicker DC wires are required, then an FSEC/FSES/FSEP or any other
IP65 DC distribution box is required to reduce the cable thickness at the module.
• Recommended DC cable lengths, thicknesses, and type are provided in section
Feederless site and Distributed site solution requirements.
• The DC connector has three screw terminals. The outer terminals are for (+) and (-)
wires. The middle terminal is for grounding the shielded DC cable braid.

7.3.3 DC cable requirements for 6TX 360W RF Modules


Considerations for selecting a DC cable for a 6TX 360W RF Module.

A DC cable is not included in the 6TX 360W RF Module delivery. 48 VDC power can be
fed from an external power source.
For the enhanced FPFD PDU version A.103/A.204, a single DC cable is sufficient up to
240W commissioned RF Power under all conditions. An enhanced dual FPCA DC cable
A.203 is needed if more than 240W and up to 360W RF Power is commissioned and
Radio operating voltage drops below 48V in a battery back-up operated site.
If the cable path between the System Module/external power source and RF Module
exceeds 10 m, then a Flexi System External OVP (FSES/FSEP) must be installed next
to the System Module or external power source.
For 6x60 W RF Module variants, the allowed outer diameter of shielded or jacketed
cables is 6-28 mm (0.24-1.1 in.), and the allowed cross section of individual DC wires is
6-35 mm2 (10-2 AWG) at the DC terminal.

7.3.4 DC cable requirements for Remote Radio Heads (RRH)


Considerations for selecting a DC cable for a Remote Radio Head.

88 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

A DC cable is not included in the RRH delivery. 48 VDC power can be fed from a System
Module or an external power supply. If the cable path between the System
Module/external power source and RF Module exceeds 10 m, then a Flexi System
External OVP (FSEC/FSES/FSEP) must be installed next to the System Module or
external power source. For details, see Creating Flexi Multiradio BTS Site Configurations
in respective system documentation.
Requirements if power is supplied from an external source
The following requirements apply if power is fed from an external power source:
• The allowed diameter of shielded or jacketed cables is 6-25 mm (0.24-1 in.).
• The allowed cross section of individual DC wires is 6-25 mm2 (10-4 AWG) at the DC
terminal. It is recommended that 25 mm2 (4 AWG) wires are capped to avoid loose
strands. If thicker DC wires are required, then an FSEC/FSES/FSEP or other IP65
DC distribution box is required to reduce the cable thickness at the module.
• Recommended DC cable lengths, thicknesses, and type are provided in the section
Feederless site and Distributed site solution requirements.
• The DC connector has three screw terminals. The outer terminals are for (+) and (-)
wires. The middle terminal is for grounding the shielded DC cable braid or ground
wire.

7.4 BTS power consumption


Information on where to find power consumption details for various types of modules.

For power consumption of RF Module, Remote Radio Head and System Module
variants, see the following documents:

• Flexi Multiradio BTS RF Module and Remote Radio Head Description


• Flexi Multiradio 10 Base Station System Module Description
• Flexi Multiradio BTS LTE System Module Description
• Flexi Multiradio BTS WCDMA System Module Description

7.4.1 Power consumption of Flexi Outdoor Cabinet fans (FCFA,


FCSA, and FCOS)
Power consumption values for FCFA, FCSA and FCOS fans.

Table 51 Power consumption of Flexi Outdoor Cabinet fans (FCFA, FCSA, and
FCOS)

FCFA FCSA FCOS

60 W clean 34 W at 23 °C 32 W minimum

100 W typical 94 W at 55 °C 43 W typical

180 W dirty 58 W maximum

Issue: 08D DN0951839 89


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

The total power consumption of Flexi Cabinet Site Support Module depends on which
third-party configuration has been installed in the line terminal equipment space.
The estimated maximum heat load can be assumed to be the same as the power
consumption values.

7.5 Lightning surge requirements


Lightning surge requirements for various BTS ports and units.
AC power port
Table 52 Switching and lightning transient requirements for AC power port

Spec Method Requirement

ETSI EN 301 489-1 EN 61000-4-5 ±2 kV line to ground


(common), pulse 1.2/50µs,
Rs=(2Ω+ 10Ω)

±1.0 kV line to line


(differential), pulse 1.2/50µs
(Rs=2Ω)

GR-1089 GR-1089 ±2 kV each phase


conductor to green-wire
ground, pulse 1.2/50µs
(Rs=2Ω)

±2 kV each phase
conductor to neutral
conductor, pulse 1.2/50µs
(Rs=2Ω)

±2 kV between neutral
conductor and green-wire
ground, pulse 1.2/50µs
(Rs=2Ω)

DC power port
Table 53 Surge immunity requirements for DC power port

Spec Method Requirement

- EN 61000-4-5 ±1 kV line to ground, pulse


1.2/50µs (Rs=2Ω)

±0,5 kV line to line, pulse


1.2/50µs (Rs=2Ω)

RF antenna ports

90 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

Table 54 Lightning surge requirements for antenna ports

Spec Method Requirements

EN 61000-4-5 ±50 V…±500 V 1.2/50µs


(Rs=2Ω), pulses at the
center pin of the antenna
connector

IEC 62305-4 ±3 kA, 10/350µs pulses to


the center pin of the
antenna connector

IEC 62305-4 ±20 kA, 10/350µs pulses to


the shield of the antenna
connector

Telecom ports
Table 55 Lightning surge requirements for telecom ports

Spec Method Requirements

ETSI EN 301 489-1 EN61000-4-5 ±1 kV line to ground, pulse


1.2/50µs, Rs = 2Ω for
shielded I/O and
communication lines

EN61000-4-5 ±4 kV line to ground, pulse


1.2/50µs, Rs = 2Ω for
shielded I/O and
communication lines

Use only tested IP65 class cables with seals provided by Nokia.
The cable shielding/drain wire must always be connected to the relevant ground pins
at the Digital Distribution Frame (DDF) or Network Termination Unit (NTU)/Network
Interface Unit (NIU) as close as possible to avoid EMC interfering effects. Make sure
additional country-specific grounding regulations for transmission wiring installations
are followed!
The Flexi BTS Transmission interface is a SELV circuit and must not be directly
connected to TNV circuits.
The Flexi BTS interfaces can be connected to the telecommunication network only
through a Network Terminating Unit (NTU)/Network Interface Unit (NIU) that provides
overvoltage protection and the required isolation.

Alarm and control ports

Issue: 08D DN0951839 91


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

Table 56 Surge requirements for alarm and control ports

Spec Method Requirement

ITU-T K.45 ITU-T K.44 ±1kV, 10/700µs (Rs=25Ω)


between center conductors
and shield
±4 kV, 10/700µs (Rs=25Ω)
between cable shield and
ground

Ethernet ports
Table 57 Lightning surge requirements for Ethernet ports

Spec Method Requirements

ETSI EN 301 489-1 EN61000-4-5 ±1 kV line to ground, pulse


1.2/50µs, Rs = 2Ω for
shielded I/O and
communication lines

EN61000-4-5 ±4 kV line to ground, pulse


1.2/50µs, Rs = 2Ω for
shielded I/O and
communication lines

Use only tested IP65 class cables with seals provided by Nokia.
The cable shielding/drain wire must always be connected to the relevant ground pins
at the Digital Distribution Frame (DDF) or Network Termination Unit (NTU)/Network
Interface Unit (NIU) as close as possible to avoid EMC interfering effects. Make sure
additional country-specific grounding regulations for transmission wiring installations
are followed!
The Flexi BTS IuB/Abis Transmission interface is a SELV circuit and must not be
directly connected to TNV circuits.
The Flexi BTS IuB/Abis transmission interfaces can be connected to the
telecommunication network only through a Network Terminating Unit (NTU)/Network
Interface Unit (NIU) that provides overvoltage protection and the required isolation.

Flexi Multimode System Module (FSMF)

Table 58 Lightning surge requirements for Flexi Multimode System Module (FSMF)

Spec Method Requirements

ETSI EN 301 489-1 Sec EN61000-4-5 4 kV between shield and


9.8 ground, pulse 1.2/50µs,
RS=2Ω

DC power port with FSEC/FSES/FSEP box (OVP box)

92 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

Flexi System External Over Voltage Protection (OVP) for Feederless


(FSEC/FSES/FSEP)
The FSEC/FSES/FSEP gives Class II (C, T2) protection for both common and differential
mode disturbance. The following levels should be fulfilled:

• Protection level UP (Line - Line) < 500 V (at IN, 8/20 µs)
• Protection level UP (Line - Ground) < 1000 V (at IN, 8/20 µs)

Protection devices should fulfil following standard IEC 61643-1 and IEC 60364-4-443.
Nominal voltage is -48.0 VDC according to ETSI EN 300 -132-2.

Table 59 Lightning surge requirements for FSEC/FSES/FSEP


Common mode protection Class II (C, T2) requirements

Voltage protection level, UP max. 1 kV

Nominal discharge current (8/20), IN 15 kA

Max discharge current, Imax 30 kA

Response time, tA < 25 ns

Differential mode Class II (C, T2) requirements

FSEC FSES/FSEP

Voltage protection level, UP max. 500 V

Nominal discharge current (8/20), IN 15 kA 5 kA

Max discharge current, Imax 30 kA 6.5 kA

Response time, tA < 25 ns

Note: Voltage should be measured from all of the output ports


and it should not rise above 500 V line to line.

Flexi Power Distribution and Fuses (FPFD)


Flexi Power Distribution and Fuses (FPFD) has surge voltage protection integrated on
input and supports the following requirements:

Table 60 Lightning surge requirements (DC power port) FPFD

Spec Method Requirements

EN61000-4-5 1 kV line to ground, pulse


1.2/50µs, RS=12Ω

500V line to line, pulse


1.2/50µs, RS=2Ω

Issue: 08D DN0951839 93


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

Table 60 Lightning surge requirements (DC power port) FPFD (Cont.)

Spec Method Requirements

Note: Voltage should be measured from all of the output ports and it should not rise
above 100 V line to line.

Flexi Power Distribution and Fuses (FPFC)


Flexi Power Distribution and Fuses (FPFC) has surge voltage protection integrated on
DC input and supports the following requirements:
FPFC gives Class II (C, T2) DC input protection for both common and differential mode
disturbance. The following levels should be fulfilled:

• Protection level UP (Line - Line) < 500 V (at IN, 8/20 µs)
• Protection level UP (Line - Ground) < 1000 V (at IN, 8/20 µs)

Enhanced FPFC (A.203) gives Class II (C, T2) output port protection for both common
and differential mode Disturbance (10kA/15kA).
Protection devices should fulfil following standard IEC 61643-1 and IEC 60364-4-443.
Nominal voltage is -48.0 VDC according to ETSI EN 300 -132-2.

Table 61 Lightning surge requirements for FPFC


Common mode protection Class II (C, T2) requirements

Voltage protection level, UP max. 1 kV

Nominal discharge current (8/20), IN 15 kA/30kA DC Input

10 kA/15 kA DC Output ports*)

Max discharge current, Imax 30 kA

Response time, tA < 25 ns

Differential mode Class II (C, T2) requirements

Voltage protection level, UP max. 500 V

Nominal discharge current (8/20), IN 15 kA/30kA DC Input

10 kA/15 kA DC Output ports*)

Max discharge current, Imax 30 kA

Response time, tA < 25 ns

g Note: Voltage should be measured from all of the output ports and it should not
rise above 500 V line to line.

94 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

*) for Enhanced FPFC (A.203 or newer)


When using an FPFC, it must be plus grounded in order to provide surge protection for
the site.
Flexi Power AC/DC Submodule (FPAD/FPAE)
Protection devices should fulfil the standards IEC 61643-1 and IEC 60364-4-443.
Nominal voltage is -48.0 VDC according to ETSI EN 300 -132-2.

Table 62 (AC) Lightning surge requirements for FPAD/FPAE

Spec Method

IEC 62305-4 IEC 61643-1

Class II (Class C): nominal discharge surge current 5kA,


pulse 8/20µs, line to ground, line to line

External AC surge protection devices might be needed for FPAC and FPAA rectifiers.
Follow country-specific local regulations.
Selected RF Modules
Table 63 Lightning surge requirements for selected RF Modules

RF Module Method Requirements

FRBB (760) (3x40 W) EN 61000-4-5 ±1 kV line to ground

FRGP (2100) (3x60 W) EN 61000-4-5 ±1 kV line to ground

FRGP_B (2100) (3x60 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRGT (2100) (3x80 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRHA (2600) (3x60 W) EN 61000-4-5 ±1 kV line to ground

FRHC (2600) (6x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRHE (2600) (6x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRIE (2100/1700) (3x60 W) EN 61000-4-5 ±1 kV line to ground

FRMA (800) (3x60 W) EN 61000-4-5 ±1 kV line to ground

FRMC (800) (6x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRMD (800) (3x60 W) EN 61000-4-5 ±1 kV line to ground

FRPA (700) (6x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRPB (700) (6x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

Issue: 08D DN0951839 95


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

Table 63 Lightning surge requirements for selected RF Modules (Cont.)

RF Module Method Requirements

FXCA (850) (3x60 W) EN 61000-4-5 ±1 kV line to ground

FXCB (850) (3x80 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FXDA (900) (3x60 W) EN 61000-4-5 ±1 kV line to ground

FXDB (900) (3x80 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FXEA (1800) (3x60 W) EN 61000-4-5 ±1 kV line to ground

FXEB (1800) (3x80 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FXFB (1900) (3x60 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FXFC (1900) (3x80 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FXED (1800) (6x60 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRGU (2100) (6x60 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FXJB (900) (3x80 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FXEE (1800) (3x80 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRME (800) (6x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FZNC (2300) (6x10 W) OVP IEC 62305-4: Class II integrated, up to 15 kA

Selected Remote Radio Heads


Table 64 Lightning surge requirements for selected RRHs

RRH Method Requirements

FHDA (900) (2x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FHDB (900) (2x60 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FHEA (1800) (2x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FHEB (1800) (2x60 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FHFB (1900) (4x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRGQ (2100) (2x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRGY (2100) (2x60 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

96 DN0951839 Issue: 08D


Flexi Multiradio Base Station and Flexi Multiradio 10 Power requirements
Base Station Installation Site Requirements

Table 64 Lightning surge requirements for selected RRHs (Cont.)

RRH Method Requirements

FRHB (2600) (2x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRHD (2600) (4x30 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRHE (2600) (4x30 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRIG (2100/1700) OVP IEC 62305-4: Class II integrated, up to 5 kA


(4x30W/2x60 W)

FRMB (800) (2x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRCG (850) (2x60 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRCC (850) (2x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRNC (2300) (4x30 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FRBG (720/730) (4x40 W OVP IEC 62305-4: Class II integrated, up to 5 kA


(B12: 2x40 W, B29: 2x40 W)

FRBE (720/750) (B13: 2x40 OVP IEC 62305-4: Class II integrated, up to 5 kA


W, B29: 2x40 W)

FRBF (760) (4x40 W) OVP IEC 62305-4: Class II integrated, up to 5 kA

FZNI (2300) (4x30 W) OVP IEC 62305-4: Class II integrated, up to 15 kA

FZHA (2600) (8x10 W) OVP IEC 62305-4: Class II integrated, up to 15 kA

FZHM (2600) (8x20 W) OVP IEC 62305-4: Class II integrated, up to 20 kA

FZHI (2600) (8x20 W) OVP IEC 62305-4: Class II integrated, up to 20 kA

FZHJ (2600) (8x20 W) OVP IEC 62305-4: Class II integrated, up to 20 kA

Selected Remote Radio Heads (AC power)

Table 65 Lightning surge requirements for selected RRHs (AC power)

RRH Method Requirements

FHGB (2100) (2x5 W) OVP IEC 62305-4: Class II integrated, up to 5 kA line


to ground

FHDG 900J (2x5 W) OVP IEC 62305-4: Class II integrated, up to 5 kA line


to ground

Issue: 08D DN0951839 97


Power requirements Flexi Multiradio Base Station and Flexi Multiradio 10
Base Station Installation Site Requirements

Table 65 Lightning surge requirements for selected RRHs (AC power) (Cont.)

RRH Method Requirements

FHEI 1800LB (2x5 W) OVP IEC 62305-4: Class II integrated, up to 5 kA line


to ground

FZQB 3500 (4x2 W) OVP IEC 62305-4: Class II integrated, up to 4 kA line


to ground

98 DN0951839 Issue: 08D

You might also like