12 SUGAR COGEN PROCESS CONDENSATE TRANSFER PUMP HEAD AND FLOW CALCULATIONS

S.
DESCRIPTION VALUE UNIT REMARKS
No
FLOW

1. Process condensate return 156.75 CM/H As per HMBD

2. No. of pumps 1W+1S

3. Flow per pump 156.75 CM/H

4. Margin considered 10 %

5. Design flow per pump 172.43 CM/H

HEAD

6. Line losses (including fittings, valves, etc.,) 6 mWC

7. Static head 25 mWC

8. Deaerator safety valve set pressure 30 mWC

9. Nozzle losses 10 mWC

10. Flow Element loss (2 No.) 5 mWC

11. Total head 76 mWC

12. Margin on head 5 %

13. Design head 79.8 mWC

CONDENSATE TRANSFER PUMP (SUGAR COGEN)

14. Selected flow per pump 175 CM/H

15. Selected head 80 mWC