You are on page 1of 1

B.

SIZING CALCULATION

1 MCW PUMP HEAD AND FLOW CALCULATIONS


S.
DESCRIPTION VALUE UNIT REMARKS
No
FLOW

1. Condenser cooling water requirement for off season 7104 CM/H Siemens HMBD

2. Side stream filter flow 480 CM/H

3. Total Flow 7584 CM/H

4. No. of pumps 2W + 1S

5. Flow per pump 3792 CM/H (3) / 2

6. Margin considered 10 %

7. Design Flow per pump 4171 CM/H (4)*(5)

HEAD

8. Line losses (including fittings, valves, etc.,) 2.7 mWC

9. Static head above pump C/L to hot water inlet 11 mWC

10. Flow Element Loss (1 No.) 2 mWC

11. Condenser pressure drop 8 mWC

12. Total head 23.7 mWC 8+9+10+11

13. Margin on head 5 %

14. Design head 24.89 mWC

MCW PUMP

15. Selected flow per pump 4175 CM/H

16. Selected head 25 mWC

2 SUGAR COGEN ACW PUMP HEAD AND FLOW CALCULATIONS


S.
DESCRIPTION VALUE UNIT REMARKS
No

You might also like