UPOZORENJA KOJA GENERISE INVERTOR

UPOZORENJE RAZLOG STA RADITI


ACS800 TEMP Proverite uslove ambienta
(4210) IGBT temperatura je prekomerna. Proverite protok vazduha I rad
3.08 AW 1 bit 4 ventilatora
Proveriti filtere vazduha

AI < MIN FUNC Analogni signal je ispod minimalne vrednosti Proveriti ozicenje
(8110) zbog pogresnog nivoa signala ili je greska u Proveri nivoe za pravilan analogni
3.09 AW 2 bit 10 ozicenju signal
(programmable
Fault Function
30.01)
BACKUP USED PC stored backup of drive parameters is Sacekati da se preuzimanje podataka
(FFA3) downloaded into use. zavrsi
BATT FAILURE APBU jedinica ima gresku baterije zbog Podesiti S3 na ON
(5581) -nepravilno podesen S3 Zameniti bateriju
3.18 AW 5 bit 15 -napon baterije prenizak
BC OVERHEAT Preopterecenje copera Sacekati da se coper ohladi
(7114) Proveriti podesavanja parametara
3.18 AW 5 bit 3 zastitne funkcije otpornika za
preopterecenje(vidi grupu par. 27
BRAKE CHOPPER).
Proveriti da kocenje zadovoljava
ciklus dozvoljene granice
Proveriti da AC napon nije povisen
BRAKE ACKN Neocekivano stanje resetovanja copera Pogledati grupu parametara 42
(FF74) BRAKE CONTROL
3.16 AW 4 bit 3 Proveriti veze
BR OVERHEAT Kocioni otpor preopterecen Sacekati da se coper ohladi
(7112) Proveriti podesavanja parametara
3.18 AW 5 bit 2 zastitne funkcije otpornika za
preopterecenje(vidi grupu par. 27
BRAKE CHOPPER).
Proveriti da kocenje zadovoljava
ciklus dozvoljene granice
Proveriti da AC napon nije povisen
CALIBRA DONE Kalibracija strujnog transformatora je Nastaviti normalno sa radom
(FF37) zavrsena
UPOZORENJE RAZLOG STA RADITI
CALIBRA REQ Potrbna kalibracija strujnog transformatora
Kalibracija se startuje
(FF36) automatski.Sacekati da se zavrsi
COMM MODULE Ciklicna komunikacija izmedju drajva I Proveri status fieldbus
(7510) mastera je izgubljena komunikacije
3.08 AW 1 bit 12 Proveri parametre 51 I 52
(programmable Proveriti veze
Fault Function
30.18, 30.19)
CUR UNBAL xx Drajv je detektovao neuravnotezenost struja Proveriti kondenzatore za korekciju
(2330) na nekom od nekoliko paralelno vezanih faktora snage
3.08 AW1 bit 14 invertora.To moze biti uzrokovano spoljnom Proveriti motor i kabl do motora
and greskom(zemljospoj,motor,kabl) ili
4.01 inernom greskom(ostecen jedan od
(programmable invertora)
Fault Function
30.17)
DC BUS LIM Ogranicenja momenta zbog previsokog ili Informativni alarm
(3211) preniskog napona medjukola Proveriti Fault Function
3.18 AW5 bit 9 parameters.
(programmable
Fault Function
30.23)
EARTH FAULT Zemljospoj Proveriti kondenzatore za korekciju
(2330) faktora snage
3.08 AW 1 bit 14 Proveriti motor i kabl do motora
(programmable
Fault Function
30.17)
ENC CABLE Nema signala od enkodera Proveriti encoder i ozicenje
(7310)
3.31 AW 6 bit 3
ENCODER A<>B Faze enkodera su pogresne Zameniti fau A i fazu B na enkoderu
(7302)
3.09 AW 2 bit 4
ENCODER ERR Komunikaciona greska izmedju enkodera i Proveriti encoder,veze i interfejs
(7301) drajva modul enkodera i grupu parametara
3.08 AW 1 bit 5 50 ENCODER MODULE
UPOZORENJE RAZLOG STA RADITI
FAN OTEMP Povisena temperatura na izlaznom filteru Zaustavite pogon.Neka se ohladi
(FF83) ventilatora Proverite temperature ambijenta
3.16 AW 4 bit 0 Proveriti da se ventilator okrece u
pravom smeru I da je protok
vazduha nesmetan
HW RECONF RQ Tip invertora je promenjen Wait until alarm POWEROFF!
(FF38) activates and
switch control board power off to
validate
inverter type change.
ID DONE Invertor je izvrsio ID magnetizaciju i moze da Nastaviti normalan rad
(FF32) nastavi normalno sa radom
ID MAGN ID magnetizacija je ukljucena Sacekati da se proces zavrsi
(FF31)
ID MAGN REQ Potrebna je identifikacija.korisnik odlucuje da Startovati magnetizaciju ili ID RUN
(FF30) l ice raditi ID MAGN ili ID RUN
ID N CHANGED ID broj drajva je promenjen iz 1 Vratiti ID broj na 1
(FF68)
ID RUN ID RUN je aktiviran Sacekai da se ID RUN zavrsi
(FF35)
ID RUN SEL ID RUN je izabran i pogon je spreman za start Pritisnuti start dugme za pocetak ID
(FF33) ID RUNa RUNa
IN CHOKE TEMP Povisena temperature Zaustavite pogon.Neka se ohladi
(FF81) Proverite temperature ambijenta
3.18 AW 5 bit 4 Proveriti da se ventilator okrece u
pravom smeru I da je protok
vazduha nesmetan
INV CUR LIM Interna struja invertora ili limit snage je bio Povecati ili smanjiti vreme
(2212) pekoracen ukljucenja opterecenja
3.18 AW 5 bit 8 Proveriti Fault Function
(programmable 30.23
Fault Function Limit inverter actual power or
30.23) decrease lineside
converter reactive power
generation
reference value (parameter 95.06
LCU Q PW
REF).
INV DISABLED DC prekidac je iskljucen dok jedinica radi ili Zatvoriti DC prekidac
(3200) je dat nalog za start Proveriti AFSC-0x Fuse Switch
3.18 AW 5 bit 6 Controller unit.
UPOZORENJE RAZLOG STA RADITI
INV OVERTEMP Temperatura invertora je povisena Proveriti hladjenje
(4290)
3.31 AW 6 bit 0
IO CONFIG Input or output of optional I/O extension or Proveriti Fault Function
(FF8B) fieldbus module has been selected as signal parameters.
(programmable interface in application program but Proveriti parameter group 98
Fault Function communication to appropriate I/O extension OPTION
30.22) module has not been set accordingly. MODULES.
MACRO CHANGE Macro is restoring or User macro is being Sacekati da drajv zavrsi rad
(FF69) saved.
MOD BOARD T Povisena temperature na AINT ploci invertera Proveriti ventilator i tmperaturu
(FF88) ambijenta
09.11 AW 3 bit 14
MOD CHOKE T Povisena temperatura Proveriti ventilator i tmperaturu
(FF89) ambijenta
09.11 AW 3 bit 13
MOT CUR LIM Struja motora je premasila limite definisane u Povecati ili smanjiti vreme
(2300) parametru 20.03 MAXIMUM CURENT ukljucenja opterecenja
3.18 AW 5 bit 10 Povecati limit 20.03
(programmable Proveriti Fault Function
Fault Function parameters
30.23)
MOTOR STALL Motor je ukocen zbog prevelikog opterecenja Proveriti motor i mehanicko
(7121) ili nedovoljne snage motora opterecenje
3.09 AW 2 bit 9 Proveriti Fault Function
(programmable parameters
Fault Function
30.10)
MOTOR STARTS Motor ID RUN se startuje Sacekati da se process zavrsi
(FF34)
MOTOR TEMP Temperatura motora je previsoka zbog Proveriti motor i opterecenje
(4310) preteranog opterecenja,nedovoljne snage Proveriti start-up podatke
3.08 AW 1 bit 3 motora,neadekvatnog hladjenja ili netacnih Proveriti Fault Function
(programmable start-up podataka parametre
Fault Function
30.04.30.09)
MOTOR 1 TEMP Izmerena temperatura je premasila limit koji Proveriti podesavanja parametara
(4312) definise parameter 35.03 Nek se motor ohladi
3.16 AW 4 bit 1 Proveriti da li se motor pravilno
hladi(ventilator,ocistiti rebra za
hladjenje)
UPOZORENJE RAZLOG STA RADITI
MOTOR 2 TEMP Izmerena temperatura je premasila limit koji Proveriti podesavanja parametara
(4313) definise parameter 35.06 Nek se motor ohladi
3.16 AW 4 bit 2 Proveriti da li se motor pravilno
hladi(ventilator,ocistiti rebra za
hladjenje)
MOT POW LIM Limiti snage su premaseni prema limitima Informativni alarm
(FF86) definisanim u parametrima 20.11 , 20.12 Proveriti parametre 20.11,20.12
3.18 AW 5 bit 12 Proveriti Fault Function
(programmable 30.23
Fault Function
30.23)
MOT TORQ LIM Limiti momenta su premaseni racunato I po Informativni alarm
(FF85) limitima minimuma i maksimuma Proveriti parametre 20.13,20.14
3.18 AW 5 bit 11 definisanim u parametrima 20.13,20.14 Proveriti Fault Function
(programmable 30.23)
Fault Function Proveriti parametre motora u
30.23) grupi 99
Proveriti da li je ID RUN uspesno
uradjen
PANEL LOSS Control panel ili DriveWindow izabrani Proveriti veze panela
(5300) kao nacin komuniciranja su prekinuli Proveri Fault Function
3.09 AW 2 bit 13 komunikaciju sa drajvom
(programmable
Fault Function
30.02)
POINTER ERROR Source selection (pointer) parameter Check source selection (pointer)
(FFD0) points to parameter
non existing parameter index. settings.
->POWEROFF! Inverter type (e.g. sr0025_3) has been Switch control board power off to
(FF39) changed. Inverter type is usually changed at validate
factory or during drive implementation inverter type change
PP OVERLOAD Moze biti uzrokovano preteranim Povecati vreme rampe
(5482) opterecenjem na niskim frekvencijama Smanjiti opterecenje
3.18 AW 5 bit 5
REPLACE FAN Vreme rada ventilatora premasilo radni vek Zameniti ventilator
(4280) ventilatora Resetovati brojac rada vent. 01.44
3.18 AW 5 bit 0
SLEEP MODE Sleep function has entered sleeping Vidi grupu parametara 40 PID
(FF8C) mode CONTROL
3.16 AW 4 bit 4
START INHIBI Opciona prevencija neocekivanog starta je Proveriti start inhibit circuit
(FF7A) aktivna (AGPS board).
AW 1 bit 0
UPOZORENJE RAZLOG STA RADITI
START INTERL Nema prijema signala za start Proveriti kolo za start na RMIO karti
(FF8D
SYNCRO SPEED Vrednost nominalne brzine motora u Podesiti pravilno parameter 99.08
(FF87) parametru 99.08 nije dobro podesena
3.18 AW 5 bit 1
TEMP DIF xx y Povisena razlika temperature izmedju Proveriti ventilator
(4380) invertora i nekoliko paralelno p[ovezanih Zameniti ventilator
4.01 FAULTED INT invertora Proveriti protok vazduha
INFO Alarm se javlja kada je razlika preko 15 °c a
greska preko 20 °c
THERMISTOR Temperature motora je povisena. Motor Proveriti optrerecenje motora
(4311) thermal Proveriti start-up podatke
3.08 AW 1 bit 2 protection mode je podesena na Proveriti vezu termistora na DI6
(programmable THERMISTOR
Fault Function
30.04.30.05)
T MEAS ALM Merenje temperature motora je izvan Proveriti kolo za merenje
(FF91) prihvatljivih granica temperature
3.08 AW 1 bit 6
UNDERLOAD Opterecenje motora je prenisko Proveriti pogon
(FF6A) Proveriti Fault Function
3.09 AW 2 bit 1 30.13.30.15)
(programmable
Fault Function
30.13)
Integrisana struja motora premasila Proveriti grupu parametara 72
USER L CURVE opterecenje USER
(2312) Krivulja def. u grupi param. 72 USER LOAD CURVE
3.18 AW 5 bit 13 LOAD CURVE. Nakon vremena hladjena motora
predvidjenog u parametru 72.20
LOAD COOLING TIME greska
se moze resetovati