Professional Documents
Culture Documents
ANCHORING SYSTEMS
FOR DESIGNERS
Hilti. Meets the highest demands.
Anchor Systems
Hilti. Outperform. Outlast.
HILTI mechanical anchors overview
Name Picture Available diameters and materials Application Base material Loads Approval Price*
HSA zinced (min. 5 µm) Ø6, Ø8, Ø10, Ø12, Ø16, Ø20 Torque controlled expansion anchor.
HSA-F - hot-dip galvanized (min. 35 µm) Fastening columns, beams, facade brackets and channels. Concrete (C20/25 - C50/60) Static 0,71 EUR
HSA Ø6, Ø8, Ø10, Ø12, Ø16, Ø20 Approved for hammer and diamond core drilling. Not approved for cracked concrete Quasi static
ETA-11/0374
M12x115
HSA-R - stainless steel (SS316) Ø6, Ø8, Ø10, Ø12, Ø16, Ø20 Reaction to fire A1.
HUS3-H zinced (min. 5 µm) Ø8, Ø10, Ø14 Steel and metal structures base frame mounting on concrete surface.
Railings and balustrades, architectural metal, structural steel. Static 0,88 EUR
HUS3-H HUS3-HF - hot-dip galvanized (F-coating min. 14 µm) Ø8, Ø10,
Hexagonal head with built-in washer offers outstanding incorporation, through their attachment to Quasi static 8x85
Ø14
the structure. Concrete (C20/C25 - C50/C60) Seismic (C1, C2)
ETA-13/1038
Approved to unscrew the screw-repeated 2 times up to 10 mm with no load drop Approved for cracked concrete Fire resistance to
Smaller minimum distances between the anchors and the distance from the edge. R120 0,92 EUR
HUS3-C zinced (min. 5 µm) HUS3-C Ø8, Ø10 Reaction to fire A1. 8x85
Tested for fire resistance.
Strengthen the profile directly to the ceiling through the ventilation tube or wire assembly.
HUS3-H 6 Railing, fencing and other decorative steel structures strengthening.
Static
ETA approval for hollow-core slabs also for use in cracked concrete. HUS3-P
HUS3-P Concrete (C20/C25 - C50/C60) Quasi static ETA- 10/0005
zinced (min. 5 µm) Ø6 Higher productivity - less drilling time and fewer steps than using conventional anchors. 0,34 EUR
HUS3-I Approved for cracked concrete Fire resistance to ETA-13/1038
Smaller minimum distance between the anchors and distance from the edge. 6x40
R120
HUS3-A Reaction to fire A1.
Tested for fire resistance.
Medium-duty loads with anchor bolts and threaded rods, e.g. suspension systems for pipes, air
Static
ducts, sprinkler systems, etc. Concrete (C20/C25 - C50/C60)
Quasi static
HKD - zinced (min. 5 µm) Ø6, Ø8, Ø10, Ø12, Ø16, Ø20 "Intelligent” stepped expansion cone allows easy, correct setting even in harder materials. Cracked concrete: M6-M16 ETA-06/0047 0,48 EUR
HKD HKD-SR - stainless steel (SS316) Ø6, Ø8, Ø10, Ø12, Ø16, Ø20 Available in a variety of sizes for maximized coverage of applications. Uncracked concrete: M6-M16
Fire resistance to
ETA-02/0032 10x40
R120
Reaction to fire A1. Uncracked concrete: M8-M20
Tested for fire resistance.
Release: 2017 3
Hilti chemical anchors review
HIT-RE 500 V3 HIT-HY 200-A HIT-HY 170 concrete HIT-HY 170 masonry HIT-HY 270 masonry HIT-ICE HIT-CT 1
Concrete C12/15 to C50/60 Concrete C12/15 to C50/60 Concrete C20/25 to C50/60 Concrete C20/25 to C50/60 Concrete C20/25 to C50/60
Basic material Solid and hollow masonry Solid and hollow masonry
Cracked and uncracked concrete Cracked and uncracked concrete Cracked and uncracked concrete Uncracked concrete only Uncracked concrete only
Hammer drilling Hammer drilling
Hammer drilling Solid bricks - hammer mode, Solid bricks - hammer mode, Hammer drilling Hammer drilling
Drilling method Diamond core drilling Diamond core drilling (only HIT-Z)
Diamond core driling + TE-YRT Hollow bricks - rotation mode Hollow bricks - rotation mode Diamond core driling + TE-YRT Diamond core driling + TE-YRT
Diamond core driling + TE-YRT Diamond core driling + TE-YRT
Ø8, Ø10, Ø12, Ø14, Ø16, Ø20, Ø25,
Ø8, Ø10, Ø12, Ø14, Ø16, Ø20, Ø25,
Rebar Ø26, Ø28, Ø30, Ø32, Ø36, Ø40 Ø8, Ø10, Ø12, Ø14, Ø16, Ø20, Ø25 - - Ø8, Ø10, Ø12, Ø14, Ø16, Ø20, Ø25 Ø8, Ø10, Ø12, Ø14, Ø16, Ø20, Ø25
Ø26, Ø28, Ø30, Ø32
HILTI Technical document up to Ø80
HIT-V, M8, M12, M16 HIT-V, M8, M12, M16
M8, M10, M12, M16, M20, M24, M27, Cracked concrete: M10, M12, M16
HIT-V threaded rod M8, M10, M12, M16, M20, M24, M27, HIT-IC M8, M10, M12 HIT-IC M8, M10, M12
M30, M33, M36, M39 Uncracked concrete: M8, M10, M12, M8, M10, M12, M16, M20, M24 M8, M10, M12, M16, M20, M24
M30 in hollow masonry: in hollow masonry:
HILTI Technical document up to M80 M16, M20, M24
HIT-SC 16, 18, 22 HIT-SC 16, 18, 22
HIT-Z threaded rod - M8, M10, M12, M16, M20 - - - - -
Solid masonry Solid masonry
+ 5 ° C - + 40 ° C + 5 ° C - + 40 ° C
Temperature range - 5°C - + 40°C - 10°C - + 40°C - 5°C - + 40°C - 23°C - + 32°C - 5°C - + 40°C
hollow masonry hollow masonry
- 5 ° C - + 40 ° C " - 5 ° C - + 40 ° C "
Anchor insertion time: Solid masonry - 3 min. Solid masonry - 4min.
30 min. 4 min. 3 min. 10 min.
(Base material t = 20 ° C) hollow brick masonry - 3min. " hollow brick masonry - 4min. " Base material t = 18 ° C
Anchor insertion time: Solid masonry - X. Solid masonry - X. Working time: 1.5 hours.
2 h. 25 min. 10 min. Curing time: 24 hours. 40 min.
(Base material T = 0 ° C) hollow brick masonry - 10min. " hollow brick masonry - 10min. "
Curing time *: Solid masonry - 45min. Solid masonry - 30min. Base material t = -23 ° C
7 h. 30 min. 45 min. 75 min.
(Base material t = 20 ° C) hollow brick masonry - 45min. " hollow brick masonry - 30min. " Working time: 1.5 hours.
Curing time *: Solid masonry - X. Solid masonry - X. Curing time: 36 hours.
48 h. 2 h. 5 h. 3 h.
(Base material T = 0 ° C) hollow brick masonry - 5h. " hollow brick masonry - 4h. "
ETA-11/0493 rebar ETA-15/0297
ETA Technical Approval ETA-16/0143 ETA 15/0197 ETA-13/1036 - ETA-11/0354
HIT-Z ETA-12/0006 HIT-V ETA-14/0457
HILTI PROFIS Anchor, HILTI PROFIS Anchor HILTI PROFIS Anchor HILTI PROFIS Anchor
PROFIS - - HILTI PROFIS Anchor
HILTI PROFIS Rebar HILTI PROFIS Rebar (masonry module) HILTI PROFIS Rebar
SAFEset technology with hollow drills SAFEset technology with hollow drills
SAFEset technology with hollow drills
SAFEset technology TE-CD,TE-YD, TE-CD,TE-YD, - - - -
TE-CD, TE-YD
SAFEset technology with TE-YRT SAFEset technology with TE-YRT
Standard hybrid mortar for use in Standard hybrid mortar for use in Hybrid mortar with best performance.
Epoxy mortar with best performance. Hybrid mortar with best performance.
concrete and masonry. Mild steel concrete and masonry. It provides a Intended for all masonry materials. Hilti Clean Technology
Slow curing time, best suited for deep Universal chemistry with a perfect This mortar is specially designed
construction connection, such as steel strong, secure and easy-mounted Suitable for use indoors and outdoors, Ecological chemistry with good
Assignment installations with large diameter rods. bearing capacity. Aproved for dynamic elements of reinforced concrete at low
columns, beams, etc., anchoring. fastening masonry materials. Could be as well as dry and wet holes. Could be loading capacity. Suitable for dry and
Could be used in dry and wet concrete, loads with some rods like HIT-Z-D. ambient temperature.
Suitable for use indoors and outdoors, used with HIT-S and HIT-SC sleeves in used with HIT-S and HIT-SC sleeves in wet concrete holes
water-filled holes and underwater. Suitable for dry and wet concrete holes.
as well as dry and wet holes. hollow materials. hollow materials.
330ml 27,56 28,02 17,56 17,56 35,47** 35,82** 300ml plastic pack 40,57**
Regular price
buying 20pcs 500ml 34,50 35,88 20,50 20,50 45,66** - 48,04**
w/o VAT, EUR
1400ml 106,94** - - - - - -
Note: * - data on the curing time in dry concrete anchors. Wet concrete curing time doubled
** - prices depends on quantity and are set individually with customer
The table is for information only. In case of questions, please contact Hilti technical advisor.
Release: 2017 4
HILTI threaded rods
Suitable for fastenings in concrete and masonry in Suitable for internally-threaded fastenings in NO CLEANING REQUIRED, MAXIMUM SAFETY Suitable for fastenings in cracked concrete. HVZ Wide viarity of applications: concrete foundation
Features a chisel tip to cut and mix the Hilti HVU
Application combination with the relevant Hilti HIT injectable concrete in combination with various Hilti Highest loads in cracked concrete, approved only combines highest performance in chemical construction, beams and wall construction, road
capsule, suitable for fastenings only in concrete
adhesive mortar injectable adhesive mortars, HVU capsules. with Hilti HIT-HY 200. anchors with an unparalleled level of safety. and bridge construction;
One system for many applications thanks to a wide range of adhesive capsules, anchor rods and internally threaded sleeves in various diameters and lengths
HVU capsules
Pre-portioned foil capsule, no waste
HVU-TZ capsules Heavy-duty fastenings in cracked concrete and for dynamic loading (steel structures, machinery, crash and noise barriers, curtain wall structures, railings.)
1000mm threaded rod 8.8 (min. 5 µm) washers, 8.8 HILTI Roughening tool TE-YRT
AM6, AM8, AM10, AM12, AM16, AM20, AM24, AM27, AM30, AM33, AM36, AM39 6,4/12, 8,4/16, 10,5/20, 13/24, 17/30, 21/37, 25,44 d18, d20, d22, d25, d28, d30, d32, d35
1000mm threaded rod 8.8 HDG (min. 45 µm) washers, F, 8.8 Mesh sleeves HIT-SC:
AM10, AM12, AM16, AM20, AM24, AM27, AM30, AM33, AM36, AM39 8,4/16, 10,5/20, 13/24, 17/30 12x50, 12x85, 16x50, 16x85, 18x50, 18x85, 22x50, 22x85, 26x125
2000mm threaded rod 4.8 (min. 5 µm) washers, A4 1000mm sleeves HIT-S:
AM6, AM8, AM10, AM12, AM16, AM20, AM24 6,4/12, 8,4/16, 10,5/20, 13/24, 17/30, 21/37, 25,44 M12, M16, M22
2000mm threaded rod 4.8 F (min. 45 µm) washers, DIN 522 Threaded sleeve HIT-IC:
AM10, AM12, AM16, AM20 6,4/28, 8,4/28, 10,5/28, 8,4/40, 10,5/40, 13/40, 17/40 M8x80, M8x50, M10x50, M10x80, M12x50, M12x80
2000mm threaded rod A4-70 washers, F, DIN9021
AM8, AM10, AM12, AM16, AM20, AM24 8,4/24, 10,5/30, 13/37, 17/50
washers, A4, DIN9021
Hilti bolts: 8,4/24, 10,5/30, 13/37, 17/50
bolts washers, DIN 125B
M6, M8, M10, M12, M16, M20, M24, M27, M30, M33, M36, M39 M24, M27, M30, M33, M36
bolts, F washers, F, DIN 125B
M8, M10, M12, M16, M20 M20
bolts, F DIN 934
M24, M27, M30, M33, M36
bolts, A4
M6, M8, M10, M12, M16, M20, M24
Release: 2017 5
Hilti HIT-HY 200
system
Applications
Advantages
Highlights
Release: 2017 6
Hilti HIT-HY 200
system
No cleaning required.
Set anchor rods reliably.
The new Hilti HIT-Z rod with its cone-shaped helix works as a non-cleaning bonded expansion anchor. This means that
because of their shape, HIT-Z anchor rods are unsusceptible to uncleaned holes in dry or water-saturated concrete. The
benefit is obvious: extremely high robustness and reliability. Engineers are always on the safe side when designing
applications with Hilti HIT-Z.
ETA-12/0006
ETA-11/0493
ETA-11/0492
This bonded expansion anchor system takes up the highest
Watch the video
possible loads in cracked concrete with no drop in
and download
technical infor- performance under demanding conditions such as diamond
mation: cored holes.
www.hilti.com/
HY200
HIT-Z is the first non-cleaning bonded expansion anchor of its
kind designed for everyday use and to replace standard
threaded rods in a whole range of applications.
HIT-Z anchor rod with Hilti HIT-HY 200 Threaded rod with injectable mortar
injectable mortar
The new HIT-Z anchor rod forms part of a bonded expansion When a threaded rod is set in conventional injection adhesive
adhesive expansion anchor system. It’s capable of taking up mortar the load it’s capable of taking up may be very low if
extremely high loads in cracked concrete without loss of the hole is inadequately cleaned after drilling.
performance in dry or water saturated concrete.
Release: 2017 7
Anchoring systems
Size Max. height Drilling Anchor Drilling Designation Product No. Product No. Product No. Product No.
Fastening d0 length depth HSA HSA-F HSA-R HSA-R2
[mm] Hot-dip Stainless Stainless
[mm] [mm] [mm] Galvanized
galvanized steel A4 steel A2
min 5 m min 45 m (1.4401) (1.4301)
① ② ③ ① ② ③
tfix,1 tfix,2 tfix,3 tfix,1 tfix,2 tfix,3
M6 5 - - 6 50 42 - - HSAM6x50 5/-/- 2036084 2036310 2036314 -
M6 20 10 - 6 65 42 52 - HSAM6x65 20/10/- 2036085 2036311 2036315 -
M6 40 30 10 6 85 42 52 72 HSA M6 x 85 40/30/10 2036086 - 2036316 -
M6 55 45 25 6 100 42 52 72 HSA M6x10055/45/25 2036087 - - -
M8 5 - - 8 55 44 - - HSAM8x55 5/-/- 2004122 2004113 2004197 -
M8 20 10 - 8 70 44 54 - HSAM8x70 20/10/- 2004123 2004114 2004198 2004218
M8 35 25 - 8 85 44 54 - HSAM8x85 35/25/- 2004124 2004115 2004199 -
M8 55 45 15 8 105 44 54 84 HSA M8x10555/45/15 2004125 2004116 2004200 -
M8 80 70 40 8 130 44 54 84 HSA M8x13080/70/40 2004126 2004117 - -
M10 5 - - 10 68 55 - - HSAM10x68 5/-/- 2004127 2004118 2004201 -
M10 20 10 - 10 83 55 65 - HSA M10x8320/10/- 2004128 2004119 2004202 2004219
M10 35 25 - 10 98 55 65 - HSA M10x9835/25/- 2004129 2004170 2004203 -
M10 50 40 10 10 113 55 65 95 HSA M10x11350/40/10 2004150 2004171 2004204 -
M10 70 60 30 10 133 55 65 95 HSA M10x13370/60/30 2004151 - 2004205 -
M10 90 80 50 10 153 55 65 95 HSA M10x15390/80/50 2004152 - 2004206 -
M10 105 95 65 10 168 55 65 95 HSA M10x168105/95/65 2004153 - - -
M12 5 - - 12 85 72 - - HSA M12x85 5/ -/- 2004154 2004172 2004207 -
M12 20 5 - 12 100 72 87 - HSA M12x10020/5/- 2004155 2004173 2004208 2004220
M12 35 20 - 12 115 72 87 - HSA M12x11535/20/- 2004156 2004174 2004209 2004221
M12 65 50 15 12 145 72 87 122 HSA M12x14565/50/15 2004157 2004175 2004210 -
M12 95 80 45 12 175 72 87 122 HSA M12x17595/80/45 2004158 - 2004211 -
M12 125 110 75 12 205 72 87 122 HSA M12x205125/110/75 2004159 - 2004212 -
M12 145 130 95 12 225 72 87 122 HSA M12x225145/130/95 2004160 2004176 2004213 -
M16 5 - - 16 102 85 - - HSA M16x1025/-/- 2004161 2004177 2004214 -
M16 20 5 - 16 117 85 100 - HSA M16x11720/5/- 2004162 - 2004215 -
M16 40 25 - 16 137 85 100 - HSA M16x13740/25/- 2004163 2004178 2004216 2004222
M16 85 70 30 16 182 85 100 140 HSA M16x18285/70/30 2004164 2004179 2004217 -
M16 135 120 80 16 232 85 100 140 HSA M16x232135/120/80 2004165 - - -
M20 10 - - 20 125 98 - - HSA M20x12510/-/- 2036088 2036312 2036317 -
M20 55 30 - 20 170 98 123 - HSA M20x17055/30/- 2036089 2036313 2036318 -
Release: 2017 8
Anchoring systems
Release: 2017 9
Anchoring systems
Depth of
Drilling ∅ Length Sales pack Product designation Product No.
the anchor casting HUS3-C
d0 [mm] ls [mm] quantity
[mm] Galvanized
[ks]
hnom1 hnom2 hnom3
8 65 50 - - 50 HUS3-C 8x65 15/-/- 2079931
8 75 50 60 70 50 HUS3-C 8x75 25/15/- 2079932
8 85 50 60 70 50 HUS3-C 8x85 35/25/15 2079933
Release: 2017 10
Anchoring systems
Release: 2017 11
Anchoring systems
Product No.
Depth of Packing unit Product No. Product No.
Length Drilling∅ HKD-SR
Thread borehole standard / Designation HKD HKD
[mm] do [mm] Stainless
h1 [mm] large Galvanized Galvanized
steel A4
M6 25 8 27 100/1000 HKD 6x25 376 894 376 956 247 951
M8 25 10 27 100/ 500 HKD 8x25 376 957 376 958 -
M8 30 10 33 100/ 500 HKD 8x30 376 959 376 960 247 952
M8 40 10 44 50 /500 HKD 8x40 376 961 376 962 -
M10 25 12 27 100/ 500 HKD 10x25 376 963 376 964 -
M10 30 12 33 100/ 500 HKD 10x30 376 965 376 966 -
M10 40 12 44 50/ 500 HKD 10x40 376 967 378 430 247 953
M12 25 15 27 100/ 250 HKD 12x25 378 431 378 432
M12 50 15 55 50/ 250 HKD 12x50 378 544 378 533 247 954
M16 65 20 70 25 HKD 16x65 382 941 - 247 955
M20 80 25 85 25 HKD 20x80 382 955 - 247 956
Release: 2017 12
Anchoring systems
Drilling ∅ Lenght Maximum height of fixation Depth of the anchor Sales pack Designation Product No.
d0 [mm] ls [mm] tfix1) [mm] casting [mm] quantity HUS-CR
[ks] Stainless
hnom1 hnom2 hnom3 hnom1 hnom2 hnom3 steel A4
Release: 2017 13
Anchoring systems
HRD-H 10
Material: polyamide PA 6, carbon steel
Cordless Screwdriver / Screw Terminal SW 13
Max. fastening Max. fastening Lenght Designation Sales pack quantity Product No.
heigh tfix1 heigh tfix2 [mm]
10 mm - 60 mm HRD-H 10x60 Frame anchor 50pc 423870
30 mm 10 mm 80 mm HRD-H 10x80 Frame anchor 50pc 423871
50 mm 30 mm 100 mm HRD-H 10x100 Frame anchor 50pc 423872
70 mm 50 mm 120 mm HRD-H 10x120 Frame anchor 50pc 423873
90 mm 70 mm 140 mm HRD-H 10x140 Frame anchor 50pc 423874
110 mm 90 mm 160 mm HRD-H 10x160 Frame anchor 50pc 423875
130 mm 110 mm 180 mm HRD-H 10x180 Frame anchor 50pc 423876
150 mm 130 mm 200 mm HRD-H 10x200 Frame anchor 50pc 423877
HRD-HR 10
Material: polyamide PA 6, stainless steel, class III. (A4)
Cordless Screwdriver / Screw Terminal SW 13
Max. fastening Max. fastening Lenght Designation Sales pack quantity Product No.
heigh tfix1 heigh tfix2 [mm]
10 mm - 60 mm HRD-HR 10x60 Frame anchor 50pc 423888
30 mm 10 mm 80 mm HRD-HR 10x80 Frame anchor 50pc 423889
50 mm 30 mm 100 mm HRD-HR 10x100 Frame anchor 50pc 423890
90 mm 70 mm 140 mm HRD-HR 10x140 Frame anchor 50pc 423891
HRD-HR2 10
Material: polyamide PA 6, stainless steel, class II. (A2)
Cordless Screwdriver / Screw Terminal SW 13
Max. fastening Max. fastening Lenght Designation Sales pack quantity Product No.
heigh tfix1 heigh tfix2 [mm]
10 mm - 60 mm HRD-HR2 10x60 Frame anchor 50pc 423897
30 mm 10 mm 80 mm HRD-HR2 10x80 Frame anchor 50pc 423898
50 mm 30 mm 100 mm HRD-HR2 10x100 Frame anchor 50pc 423899
70 mm 50 mm 120 mm HRD-HR2 10x120 Frame anchor 50pc 423900
90 mm 70 mm 140 mm HRD-HR2 10x140 Frame anchor 50pc 423901
HRD-HF 10
Material: polyamide PA 6, hot-dip galvanized, 45μm
Cordless screwdriver / screwdriver SW 13
Max. fastening Max. fastening Lenght Designation Sales pack quantity Product No.
heigh tfix1 heigh tfix2 [mm]
10 mm - 60 mm HRD-HF 10x60 Frame anchor 50pc 423909
30 mm 10 mm 80 mm HRD-HF 10x80 Frame anchor 50pc 423910
50 mm 30 mm 100 mm HRD-HF 10x100 Frame anchor 50pc 423911
70 mm 50 mm 120 mm HRD-HF 10x120 Frame anchor 50pc 423912
90 mm 70 mm 140 mm HRD-HF 10x140 Frame anchor 50pc 423913
110 mm 90 mm 160 mm HRD-HF 10x160 Frame anchor 50pc 423914
130 mm 110 mm 180 mm HRD-HF 10x180 Frame anchor 50pc 423915
Release: 2017 14
Anchoring systems
HRD-C 10
Material: polyamide PA 6, carbon steel
Cordless screwdriver / screw terminal T40
Max. Max. Lenght Designation Sales pack quantity Product No.
fastening fastening [mm]
heigh tfix1 heigh tfix2
10 mm - 60 mm HRD-C 10x60 Frame anchor 50pc 423859
30 mm 10 mm 80 mm HRD-C 10x80 Frame anchor 50pc 423860
50 mm 30 mm 100 mm HRD-C 10x100 Frame anchor 50pc 423861
70 mm 50 mm 120 mm HRD-C 10x120 Frame anchor 50pc 423862
90 mm 70 mm 140 mm HRD-C 10x140 Frame anchor 50pc 423863
110 mm 90 mm 160 mm HRD-C 10x160 Frame anchor 50pc 423864
130 mm 110 mm 180 mm HRD-C 10x180 Frame anchor 50pc 423865
150 mm 130 mm 200 mm HRD-C 10x200 Frame anchor 50pc 423866
180 mm 160 mm 230 mm HRD-C 10x230 Frame anchor 50pc 423867
220 mm 200 mm 270 mm HRD-C 10x270 Frame anchor 50pc 423868
260 mm 240 mm 310 mm HRD-C 10x310 Frame anchor 50pc 423869
HRD-CR 10
Material: polyamide PA 6, stainless steel, class III. (A4)
Cordless screwdriver / screw terminal T40
Max. Max. Lenght Designation Sales pack quantity Product No.
fastening fastening [mm]
heigh tfix1 heigh tfix2
10 mm - 60 mm HRD-CR 10x60 Frame anchor 50pc 423885
50 mm 30 mm 100 mm HRD-CR 10x100 Frame anchor 50pc 423886
90 mm 70 mm 140 mm HRD-CR 10x140 Frame anchor 50pc 423887
HRD-CR2 10
Material: polyamide PA 6, stainless steel, class II. (A2)
Cordless screwdriver / screw terminal T40
Max. Max. Lenght Designation Sales pack quantity Product No.
fastening fastening [mm]
heigh tfix1 heigh tfix2
10 mm - 60 mm HRD-CR2 10x60 Frame anchor 50pc 423892
30 mm 10 mm 80 mm HRD-CR2 10x80 Frame anchor 50pc 423893
50 mm 30 mm 100 mm HRD-CR2 10x100 Frame anchor 50pc 423894
70 mm 50 mm 120 mm HRD-CR2 10x120 Frame anchor 50pc 423895
90 mm 70 mm 140 mm HRD-CR2 10x140 Frame anchor 50pc 423896
Release: 2017 15
Anchoring systems
Release: 2017 16
Anchoring systems
Note:The standard portfolio of HIT-V screws is up to M24. An extended portfolio of HIT-C anchor bolts can also be used - see pages 88-89. Threaded rods may also be used.
The material quality of the HIT-C anchor bolt or threaded rods, including the nut and washer, must be at least the same as the HIT-V anchor bolt used in the anchor design,
eg. PROFIS Anchor - see the relevant ETA approvals.
Release: 2017 17
Anchoring systems
M12 28 160 110 14 20 HAS-E M12x110/28 332221 333148 259952 229 506
M12 88 220 110 14 10 HAS-E M 12x110/88 333102 333149 259953
M12 128 260 110 14 10 HAS-E M 12x110/128 333103 333150 259758
M12 168 300 110 14 10 HAS-E M 12x110/168 333104 333151 259759
M12 368 500 110 14 20 HAS-E M 12x110/368 88641
M16 38 190 125 18 20 HAS-E M 16x125/38 332222 333153 259954 229 507
M16 108 260 125 18 10 HAS-E M 16x125/108 333106 333154 259955
M16 148 300 125 18 10 HAS-E M 16x125/148 333107 333155 259760
M16 198 350 125 18 10 HAS-E M 16x125/198 333108 333156 259956
M16 348 500 125 18 10 HAS-E M 16x125/348 333109 333157
HAS-E-R
M20 48 240 170 24 10 HAS-E M 20x170/48 332223 333158 333135 229 508
M20 68 260 170 24 10 HAS-E M 20x170/68 333110 333159
M20 108 300 170 24 10 HAS-E M 20x170/108 333111 333160 333136
M20 158 350 170 24 10 HAS-E M 20x170/158 333112 333161
M20 208 400 170 24 10 HAS-E M 20x170/208 333113 333162
M20 308 500 170 24 10 HAS-E M 20x170/308 88907
M24 54 290 210 28 10 HAS-E M 24x210/54 332224 333163 333137 229 509
M24 124 360 210 28 10 HAS-E M 24x210/124 77210
M24 264 500 210 28 5 HAS-E M 24x210/264 4040
Filling set
Insertion pad, spherical washer, hexagonal socket
Thread of Salespack Designation Product No. Product No. Product No.
anchor quantity Galvanized Hot-dip Stainless steel
shaft [ks] galvanized A4
Release: 2017 18
Anchoring systems
Release: 2017 19
Anchoring systems
Release: 2017 20
HSA Stud anchor
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical approval a) DIBt, Berlin ETA-11/0374 / 2016-08-08
Release: 2017 21
HSA Stud anchor
Precalculated values
Design resistance calculated according ETAG 001, Annex C and Hilti technical data. All data applies to concrete C
20/25 – fck,cube =25 N/mm².
Recommended loads can be calculated by dividing the design resistance by an overall partial safety factor
for action = 1,4. The partial safety factors for action depend on the type of loading and shall be taken from national
regulations.
Design resistance
Single anchor, no edge effects
Anchor size M6 M8 M10
Effective anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
Min. base material thickness hmin [mm] 100 100 120 100 100 120 100 120 160
Tensile NRd
HSA, HSA-BW, 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
HSA-R2, HSA-R [kN] 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
HSA-F 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
Shear VRd, without lever arm
HSA, HSA-BW 5,2 5,2 5,2 5,5 8,5 8,5 15,1 15,1 15,1
HSA-R2, HSA-R [kN] 5,5 5,8 5,8 5,5 9,8 9,8 18,1 18,1 18,1
HSA-F 5,2 5,2 5,2 5,5 8,5 8,5 15,1 15,1 15,1
Release: 2017 22
HSA Stud anchor
Release: 2017 23
HSA Stud anchor
Release: 2017 24
HSA Stud anchor
Materials
Mechanical properties
Anchor size M6 M8 M10 M12 M16 M20
HSA
Nominal
HSA-BW
tensile 650 580 650 700 650 700
HSA-F [N/mm²]
strength
HSA- R2
fuk,thread 650 560 650 580 600 625
HSA-R
HAS
HSA-BW
Yield strength 520 464 520 560 520 560
HSA-F [N/mm²]
fyk,thread
HSA-R2
520 448 520 464 480 500
HSA-R
HAS
Stressed
HSA-BW
cross- 20,1 36,6 58,0 84,3 157,0 245,0
HSA-R2 [mm²]
Section As,thread
HSA-R
HAS
HSA-BW
Moment of
HSA-R2 12,7 31,2 62,3 109,2 277,5 540,9
resistance W
HSA-R [mm³]
HSA-F
HAS
HSA-BW 9,9 21,7 48,6 91,7 216,4 454,4
Char. bending
HSA-F [Nm]
resistance M0Rk,s
HSA-R2
9,9 21,0 48,6 76,0 199,8 405,7
HSA-R
Material quality
Type Part Material Coating
Bolt Carbon-steel
HSA Sleeve Carbon-steel
HSA-BW HSA: Carbon-steel, Galvanized (≥5 µm)
Carbon Steel Washer
HSA-BW: Carbon-steel
Hexagon nut Steel, strength class 8
Bolt Stainless steel A2, 1.4301 or 1.4162 M6 – M20 coated
HSA-R2
Sleeve Stainless steel A2, 1.4301 or 1.4404 -
Stainless Steel Washer Stainless steel grade A2 -
Grade A2
Hexagon nut Stainless steel grade A2 M6 – M20 coated
Bolt Stainless steel grade A4, 1.4401 or 1.4362 M6 – M20 coated
HSA-R
Sleeve Stainless steel A2, 1.4301 or 1.4404 -
Stainless Steel Washer Stainless steel grade A4 -
Grade A4
Hexagon nut Stainless steel grade A4 M6 – M20 coated
Sleeve Stainless steel A2 1.4301 -
Stainless steel A2 1.4301
HSA-F Bolt
Carbon steel, Rupture elongation A5 ˃ 8% Hot dip galvanized
Carbon Steel (≥42 µm)
Washer HSA: carbon steel
Hexagon nut Steel, strength class 8
Release: 2017 25
HSA Stud anchor
Setting details
Anchor size M6 M8 M10
Nominal anchorage
hnom [mm] 37 47 67 39 49 79 50 60 90
depth
Minimum base
hmin [mm] 100 100 120 100 100 120 100 120 160
material thickness
Minimum spacing smin [mm] 35 35 35 35 35 35 50 50 50
Minimum edge
cmin [mm] 35 35 35 40 35 35 50 40 40
distance
Nominal diameter of
do [mm] 6 8 10
drill bit
Cutting diameter of
dcut ≤ [mm] 6,4 8,45 10,45
drill bit
Depth of drill hole h1 ≥ [mm] 42 52 72 44 54 84 55 65 95
Diameter of clearance
df ≤ [mm] 7 9 12
hole in the fixture
Torque moment Tinst [Nm] 5 15 25
Width across SW [mm] 10 13 17
One anchor length for different fixture thickness tfix and the corresponding setting positions
Release: 2017 26
HSA Stud anchor
Design parameters
Anchor size M6 M8 M10
Nominal anchorage
hnom [mm] 37 47 67 39 49 79 50 60 90
depth
Effective anchorage
hef [mm] 30 40 60 30 40 70 40 50 80
depth
Critical spacing for
scr,sp [mm] 100 120 130 130 180 200 190 210 290
splitting failure
Critical edge distance
ccr,sp [mm] 50 60 65 65 90 100 95 105 145
for splitting failure
Critical spacing for
scr,N [mm] 90 120 180 90 120 210 120 150 240
concrete cone failure
Critical edge distance
for concrete cone ccr,N [mm] 45 60 90 45 60 105 60 75 120
failure
For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to be
reduced.
Release: 2017 27
HST3
Metal expansion anchor
European CE PROFIS FM
Technical conformity Anchor design approved
Assessment software
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical approval a) DIBt, Berlin ETA-98/0001 / 2015-11-06
Fire test report DIBt, Berlin ETA-98/0001 / 2015-11-06
a) All data for HST3 in concrete strength class C20/25 to C50/60 given in this section according to ETA-98/0001,
issue 2015-11-06. Data for other concrete strength classes according to Hilti Technical Data assessment.
Release: 2017 28
HST3
Metal expansion anchor
Precalculated values
Design resistance calculated according ETAG 001, Annex C and data given in ETA-98/0001, issue 2015-11-06. All
data applies to concrete C 20/25 – fck,cube =25 N/mm².
Recommended loads can be calculated by dividing the design resistance by an overall partial safety factor
for action = 1,4. The partial safety factors for action depend on the type of loading and shall be taken from national
regulations.
Design resistance for a single anchor, with min. edge distance (c = cmin)
Anchor size M8 M10 M12 M16 M20 M24
Effective anchorage
hef [mm] 47 40 60 50 70 65 85 101 125
depth
Minimum base material
hmin [mm] 80 80 100 120 100 120 140 120 140 160 160 200 250
thickness
Min. edge distance in 170a)
cmin [mm] 40 50 60 50 60 60 55 65 65 65 120 80
Non-cracked concrete 150b)
Min. edge distance in
cmin [mm] 40 45 60 45 55 60 55 65 65 65 120 80 125
cracked concrete
Tensile NRd
Non-cracked concrete
HST3/HST3-BW [kN] 7,4 6,0 11,7 10,5 8,9 13,5 12,9 12,7 17,0 17,0 24,6 20,0 40,0
HST3-R/HST3-R-BW [kN] 7,4 6,0 11,7 10,5 8,9 13,5 12,9 12,7 17,0 17,0 17,0 24,7 39,8
Cracked concrete
HST3/HST3-BW [kN] 3,9 2,8 6,7 5,7 5,1 8,2 7,8 7,8 11,2 11,2 20,5 16,0 25,2
HST3-R/HST3-R-BW [kN] 3,9 2,8 6,7 5,7 5,1 8,2 7,8 7,8 11,2 11,2 20,5 16,0 25,2
Shear VRd, without lever arm
Non-cracked concrete
HST3/HST3-BW [kN] 3,4 4,5 6,2 4,9 6,2 6,6 5,9 6,6 8,1 8,1 19,1 11,4 32,6
HST3-R/HST3-R-BW [kN] 3,4 4,5 6,2 4,9 6,2 6,6 5,9 6,6 8,1 8,1 19,1 11,4 27,5
Cracked concrete
HST3/HST3-BW [kN] 2,4 2,8 4,4 3,0 3,9 4,7 4,2 5,4 5,7 5,7 13,5 8,1 15,4
HST3-R/HST3-R-BW [kN] 2,4 2,8 4,4 3,0 3,9 4,7 4,2 5,4 5,7 5,7 13,5 8,1 15,4
a) For HST3/HST3-BW
b) For HST3-R/HST3-R-BW
Release: 2017 29
HST3
Metal expansion anchor
Design resistance for double anchor, without edge effects, with min. spacing (s= smin)
Anchor size M8 M10 M12 M16 M20 M24
Effective anchorage depth hef [mm] 47 40 60 50 70 65 85 101 125
Minimum base material
hmin [mm] 80 80 100 120 100 120 140 120 140 160 160 200 250
thickness
Min. spacing in Non-
smin [mm] 35 50 40 40 55 50 60 75 80 65 120 90 125
cracked concrete
Min. spacing in cracked
smin [mm] 35 40 40 40 50 50 50 65 80 65 120 90 125
Concrete
Tensile NRd
Non-cracked concrete
HST3/HST3-BW [kN] 6,8 5,5 9,6 9,6 7,8 12,2 12,7 12,0 17,3 16,6 22,4 21,1 31,4
HST3-R/HST3-R-BW [kN] 6,8 5,5 9,6 9,6 7,8 12,2 12,7 12,0 17,3 16,6 22,4 21,1 31,4
Cracked concrete
HST3/HST3-BW [kN] 3,5 2,8 5,5 5,5 4,2 7,4 7,4 6,9 11,4 10,9 17,0 15,8 22,4
HST3-R/HST3-R-BW [kN] 3,5 2,8 5,5 5,5 4,2 7,4 7,4 6,9 11,4 10,9 17,0 15,8 22,4
Shear VRd, without lever arm
Non-cracked concrete
HST3/HST3-BW [kN] 11,0 16,1 25,5 18,9 22,6 33,9 28,3 41,7 59,1 44,2 76,3 67,1 62,7
HST3-R/HST3-R-BW [kN] 12,6 16,1 20,2 20,2 22,6 29,4 29,4 38,9 50,9 50,9 76,3 70,9 78,4
Cracked concrete
HST3/HST3-BW [kN] 9,3 7,6 14,6 14,6 11,8 20,6 20,6 23,6 39,0 37,2 54,4 50,6 55,9
HST3-R/HST3-R-BW [kN] 9,3 7,6 14,6 14,6 11,8 20,6 20,6 23,6 39,0 37,2 54,4 50,6 55,9
Release: 2017 30
HST3
Metal expansion anchor
Fire resistence
All data in this section applies to:
- Correct setting (See setting instruction)
- No edge distance and spacing influence
- Steel failure
- Minimum base material thickness Concrete C 20/25, fck,cube = 25 N/mm²
- Hilti Technical Data for concrete strength class C55/67 to C80/95: for a structural element that fulfills the
requirements according to DIN EN 1992-1-2 the fire resistences of C20/25 could be assumed.
- partial safety factor for resistence under fire exposure M,fi=1,0 (in absence of other national regulations)
Design resistence
Anchor size M8 M10 M12 M16 M20 M24
Eff. Anchorage depth
[mm] 47 40 60 50 70 65 85 101 125
hef
Fire Exposure R30
Tensile NRd,fi
HST3/HST3-BW [kN] 0,9 1,5 2,4 2,3 5,0 4,4 7,1 9,1 12,6
HST3-R/HST3-R-BW [kN] 1,9 1,8 3,0 3,2 5,0 4,7 7,1 9,1 12,6
Shear VRd,fi
HST3/HST3-BW [kN] 0,9 1,5 2,4 2,3 5,2 4,4 9,7 15,2 21,9
HST3-R/HST3-R-BW [kN] 4,9 4,7 11,8 8,9 17,1 16,9 31,9 37,0 62,8
Fire Exposure R120
Tensile NRd,fi
HST3/HST3-BW [kN] 0,6 0,8 0,9 0,8 1,3 1,5 2,4 3,8 5,4
HST3-R/HST3-R-BW [kN] 1,5 1,5 2,4 2,5 4,0 3,8 5,6 7,3 10,1
Shear VRd,fi
HST3/HST3-BW [kN] 0,6 0,8 0,9 0,8 1,5 1,5 2,4 3,8 5,4
HST3-R/HST3-R-BW [kN] 1,7 2,0 3,3 3,3 4,8 6,2 9,0 14,1 20,3
Mechanical properties
Anchor size M8 M10 M12 M16 M20 M24
HST3/HST3-BW [N/mm²] 800 800 800 720 700 530
Nominal tensile strength fuk,thread
HST3-R/HST3-R-BW [N/mm²] 720 710 710 650 650 650
HST3/HST3-BW [N/mm²] 640 640 640 576 560 450
Yield strength fyk,thread
HST3-R/HST3-R-BW [N/mm²] 576 568 568 520 520 500
Stressed cross-section As [mm²] 36,6 58,0 84,3 157 245 353
Moment of resistance W [mm³] 31,2 62,3 109 277 541 935
HST3/HST3-BW [Nm] 30 60 105 240 457 595
Char. bending resistance M0Rk,s
HST3-R/HST3-R-BW [Nm] 27 53 93 216 425 730
Release: 2017 31
HST3
Metal expansion anchor
Setting instructions
Setting details
Anchor size M8 M10 M12 M16 M20 M24
Nominal diameter of drill bit do [mm] 8 10 12 16 20 24
Cutting diameter of drill bit dcut ≤ [mm] 8,45 10,45 12,5 16,5 20,55 24,55
hnom,1 [mm] - 48 60 78 - -
Nominal anchorage depth
hnom,2 [mm] 54 68 80 98 116 143
hef,1a) [mm] - 40 50 65 - -
Effective anchorage depth
hef,2b) [mm] 47 60 70 85 101 125
Depth of drill hole h1,1h [mm] - 53 68 86 - -
(hammer drilled holes) h1,2h [mm] 59 73 88 106 124 151
Depth of drill hole h1,1d [mm] - 58 70 88 - -
(diamond drilled holes) h1,2d [mm] 64 78 90 108 - -
Diameter of clearance hole in
df ≤ [mm] 9 12 14 18 22 26
the fixture
Torque moment Tinst [Nm] 20 45 60 110 180 300
Width across SW [mm] 13 17 19 24 30 36
Setting details: depth of drill hole h1 and effective anchorage depth hef
hmin
h1
hnom
tfix hf
Release: 2017 32
HUS3
Screw anchor
Concrete Tensile Solid brick Autoclaved Seismic Small edge Fire Sprinkler European CE DIBt PROFIS
zone aerated ETA-C1 distance resistance approved Technical conformity Approval Anchor design
concrete and spacing Approval Reusability software
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical assessment a) DIBt, Berlin ETA-13/1038 / 2015-08-27
DIBt approval (Reusability) DIBt, Berlin Z-21.8-2018 / 2014-04-01
a) All data given in this section according ETA-13/1038, issue 2015-08-27.
Release: 2017 33
HUS3
Screw anchor
Precalculated values
Design resistance calculated according ETAG 001, Annex C and data given in ETA-13/1038 issue 2015-08-27.
All data applies to concrete C 20/25 – fck,cube =25 N/mm².
Design resistance
Release: 2017 34
HUS3
Screw anchor
Release: 2017 35
HUS3
Screw anchor
Fire resistance
The following technical data are based on: ETA-13/1038 issue 2015-08-27.
Release: 2017 36
HUS3
Screw anchor
Materials
Anchor size 6 8 10 14
Type HUS3 H, C, A, I, P, PS H, C, HF H, C, HF H, HF
Nominal tensile strength fuk [N/mm²] 930 810 805 730
Yield strength fyk [N/mm²] 750 695 690 630
Stressed cross-section As, [mm²] 26,9 48,4 77,0 131,7
Moment of resistance W [mm³] 19,6 47 95 213
Char, bending
[Nm] 21 46 92 187
resistance M0Rk,s
Material quality
Type Material Coating
HUS3- H, C, A, I, P, PS Carbon-steel Galvanized (≥5 µm)
HUS3-HF Carbon-steel Multilayer coating (≥14 µm)
Head configuration
HUS3-C
Countersunk head
HUS3-A
External thread
M8 or M10
HUS3-I
Internal threads
M8 and M10
HUS3-P
Pan head
HUS3-PS
Pan head (small)
Release: 2017 37
HUS3
Screw anchor
Anchor dimensions
Dimensions
Anchor size 6 8 10 14
Type HUS3 H, C, A, I, P, PS H, C, HF H, C, HF H, HF
Threaded
dt [mm] 7,85 10,30 12,40 16,85
outer diameter
Core diameter dk [mm] 5,85 7,85 9,90 12,95
Shaft diameter ds [mm] 6,15 8,45 10,55 13,80
Stressed section As [mm2] 26,9 48,4 77,0 131,7
10 : screw diameter
45/25/15 : maximum thickness fixture
tfix1/tfix2/tfix3 related to the embedment
depth hnom1/hnom2/hnom3 (see Annex B3)
Design parameters
Anchor size 6 8 10 14
Type HUS3- H, C, A, I, P, PS H, C, HF H, C, HF H, HF H
Nominal anchorage
hnom [mm] 50 50 60 70 55 75 85 65 85 115
depth
Effective anchorage
hef [mm] 42 40 46,4 54,9 41,6 58,6 67,1 49,3 66,3 91,8
depth
Minimum base
100 100 100 120 100 130 140 120 160 200
material thickness hmin [mm]
Minimum spacing smin [mm] 35 40 50 50 50 50 60 60 75 75
Minimum edge
cmin [mm] 35 50 50 50 50 50 60 60 75 75
distance
Critical spacing for
scr,sp [mm] 126 120 140 170 130 180 220 170 200 280
splitting failure
Critical edge distance
ccr,sp [mm] 63 60 70 85 65 90 110 85 100 140
for splitting failure
Critical spacing for
scr,N [mm] 126 120 140 170 130 180 202 150 200 280
concrete cone failure
Critical edge
distance for concrete ccr,N [mm] 63 60 70 85 65 90 101 75 100 140
cone failure
For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to be
reduced.
Release: 2017 38
HUS3
Screw anchor
Drilling:
• Holes in Mz and KS drilled with TE rotary hammers drilled with hammering mode
• Holes in PPW drilled with TE rotary hammers drilled without hammering mode
Installation:
• The anchor is correct mounted, if there is neither a turn-through or spinning of the screw in the drill hole nor that
an easy turning of the screw is possible after the installation procedure when the head of the screw has touched
the fixture
• The recommended setting tool is Hilti SFH 22A
Edge distance and spacing influences:
• Distance to free edge free edge to solid masonry (Mz and KS) units cmin,free ≥ 200 mm
• Distance to free edge free edge to solid masonry (autoclaved aerated gas concrete) units cmin,free ≥ 170 mm
• The minimum distance to horizontal and vertical mortar joint cmin,h and cmin,v is stated in drawing below
• Minimum anchor spacing in one brick/block is smin = 80 mm
The minimum edge distance to vertical mortar join for aerated gas concrete is 100mm
Recomended loads
Hilti
Anchor size 6
Type HUS3- A, H, I, C, P, PS
Base material hnom [mm] 55
Compressive Frec a) [kN]
[N/mm²]
strength class Tensile and Shear
Solid clay brick ≥8 0,6
≥ 10 0,7
Mz 2,0-2DF
≥ 12 0,8
DIN V 105-100 / EN 771-1
LxWxH [mm]: 240x115x113 ≥ 16 0,9
hmin [mm]: 115 ≥ 20 0,9
Solid sand-lime brick ≥8 0,8
≥ 10 0,9
KS 2,0-2DF
≥ 12 1,0
DIN V 106-100 / EN 771-2
LxWxH [mm]: 240x115x113 ≥ 16 1,1
hmin [mm]: 115 ≥ 20 1,2
Release: 2017 39
HUS3
Screw anchor
Aerated concrete
PPW -0,65
DIN 4165/ EN 771-4 ≥6 0,4
LxWxH [mm]: 499x240x249
hmin [mm]: 240
Recommended loads
Hilti
Anchor size 8 10
Type HUS3 H, C, HF H, C, HF
Base material hnom [mm] 60 75
Compressive Frec a) [kN]
[N/mm²]
strength class Tensile and Shear
Solid clay brick ≥ 12 1,1 1,4
Mz 2,0-2DF
DIN V 105-100 / EN 771-1 ≥ 20 1,6 2,0
[mm]: 240x115x113
hmin [mm]: 115
Solid sand-lime brick ≥ 12 1,3 1,4
KS 2,0-2DF
DIN V 106-100 / EN 771-2 ≥ 20 1,7 2,1
LxWxH [mm]: 240x115x113
hmin [mm]: 115
Aerated concrete
PPW 6-0,4
0,7 0,9
DIN 4165 / EN 771-4 ≥6
LxWxH [mm]: 499x240x249
hmin [mm]: 240
a) Recommended load for tension, shear or combined tension and shear loading.
The characteristic resistance is valid for single anchor or for a group of two or four anchors with spacing
equal or larger than the minimum spacing smin according to specification.
Load values:
• The technical data for the HUS3 anchors are reference loads for MZ 12 2,0-2DF, KS 12 2,0-2DF and PPW 6-0,4.
• The load Values are valid for non-structural applications.
• Due to the natural variation of stone solid bricks, on site anchor testing is recommended to validate technical data.
• The HUS3 anchor was installed and tested in the center area of solid bricks as shown considering minimal edge
and space distances.
• The HUS3 anchor was not tested in the mortar joint between solid bricks or in hollow bricks; however a load
reduction is expected.
• For brick walls where anchor position in brick cannot be determined, 100% anchor testing is recommended.
Release: 2017 40
HUS3
Screw anchor
Limitations of loads:
• All data is for redundant fastening for not structural applications
• Plaster, graveling, lining or leveling courses are regarded as non-bearing and may not be taken into account for
the calculation of embedment depth
• The decisive resistance to tension loads is the lower value of Nrec (brick breakout, pull out) and Nmax,pb (pull out of
one brick)
Nmax,pb brick breadth bbrick [mm] Nmax,pb brick breadth bbrick [mm]
[kN] 80 120 200 240 300 360 [kN] 80 120 200 240 300 360
brick 240 1,1 1,6 2,7 3,3 4,1 4,9 brick 240 0,8 1,2 2,1 2,5 3,1 3,7
length length
300 1,4 2,1 3,4 4,1 5,1 6,2 300 1,0 1,5 2,6 3,1 3,9 4,6
lbrick lbrick
[mm] 500 2,3 3,4 5,7 6,9 8,6 10,3 [mm] 500 1,7 2,6 4,3 5,1 6,4 7,7
Nmax,pb
lbrick bbrick
Basic loading data for single anchor in Hollow core slab: Basic loading data
All data in this section applies to
-Correct setting (See setting instruction)
-No edge distance and spacing influence
-Ratio core width / web thickness w/e ≤ 4,2
-Concrete C 30/37 to C 50/60
Characteristic resistance
Anchor size 8 10
Type HUS3 C, H, HF C, H, HF
Bottom flange thickness db ≥ [mm] 30 30
All load directions FRk [kN] 2,0 2,0
Release: 2017 41
HUS3
Screw anchor
Design resistance
Anchor size 8 10
Type HUS3 C, H, HF C, H, HF
Bottom flange thickness db ≥ [mm] 30 30
All load directions FRd [kN] 1,3 1,3
Recommended loads
Anchor size 8 10
Type HUS3 C, H, HF C, H, HF
Bottom flange thickness db ≥ [mm] 30 30
All load directions a) Frec [kN] 0,95 0,95
a) With overall partial safety factor for action = 1,4. The partial safety factors for action depend on the type
of loading and shall be taken from national regulations.
a) The value for maximum design load of actions per fastening point NSd is valid in general that means all
fastening points are considered in the design of the redundant structural system. The value NSd may be
increased if the failure of one (= most unfavourable) fixing point is taken into account in the design
(serviceability and ultimate limit state) of the structural system e.g. suspended ceiling.
Release: 2017 42
HSL-3 Heavy duty anchor
carbon steel
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical approval a) CSTB, Paris ETA-02/0042 / 2015-09-07
ICC-ES report incl. seismic ICC evaluation service ESR 1545 / 2014-02-01
Shockproof fastenings in civil Federal Office for Cicil Protection, BZS D 08-601 / 2008-06-30
defence installations Bern
Fire test report IBMB, Braunschweig UB 3041/1663-CM / 2004-03-22
Assessment report (fire) warringtonfire WF 327804/A / 2013-07-10
a) All data given in this section according ETA-02/0042, issue 2015-09-07.
Release: 2017 43
HSL-3 Heavy duty anchor
carbon steel
Precalculated values
Design resistance calculated according ETAG 001, Annex C and data given in ETA-02/0042, issue 2015-09-07. All
data applies to concrete C 20/25 – fck,cube =25 N/mm². HSL-3-SK and HSL-3-SH is only available up to M12.
Recommended loads can be calculated by dividing the design resistance by an overall partial safety factor
for action = 1,4. The partial safety factors for action depend on the type of loading and shall be taken from national
regulations.
Design resistance
Release: 2017 44
HSL-3 Heavy duty anchor
carbon steel
Materials
Material quality
Part Material
Bolt, threaded rod steel strength 8.8, galvanised to min. 5 µm
Anchor dimensions
Release: 2017 45
HSL-3 Heavy duty anchor
carbon steel
Setting
Setting details: depth of drill hole h1 and effective anchorage depth hef
Anchor
M8 M10 M12 M16 M20 M24
version HSL-3
Anchor version
M8 M10 M12 M16 M20 M24
HSL-3-G
Release: 2017 46
HSL-3 Heavy duty anchor
carbon steel
Anchor version
M12 M16 M20 M24
HSL-3-B
Anchor version
M8 M10 M12
HSL-3-SH
Anchor version
M8 M10 M12
HSL-3-SK
Release: 2017 47
HSL-3 Heavy duty anchor
carbon steel
Setting parameters
Anchor size M8 M10 M12 M16 M20 M24
Minimum base
hmin [mm] 120 140 160 200 250 300
material thickness
smin [mm] 60 70 80 100 125 150
Minimum spacing
for c ≥ [mm] 100 100 160 240 300 300
Minimum edge cmin [mm] 60 70 80 100 150 150
distance for s ≥ [mm] 100 160 240 240 300 300
Critical spacing for
scr,sp [mm] 230 270 300 380 480 570
splitting failure
Critical edge distance
ccr,sp [mm] 115 135 150 190 240 285
for splitting failure
Critical spacing for
scr,N [mm] 180 210 240 300 375 450
concrete cone failure
Critical edge distance
for concrete cone
ccr,N [mm] 90 105 120 150 187,5 225
failure
For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to be
reduced.
Critical spacing and critical edge distance for splitting failure apply only for non-cracked concrete. For cracked
concrete only the critical spacing and critical edge distance for concrete cone failure are decisive.
Release: 2017 48
Hilti HIT-RE 500 V3
with HIT-V rod
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European Technical Assessment CSTB ETA-16/0143 / 2016-11-30
Fire test report MFPA Leipzig GS 3.2/15-361-4 / 2016-08-04
a) All data given in this section according to ETA-16/0143, issue 2016-11-30.
Release: 2017 49
Hilti HIT-RE 500 V3
with HIT-V rod
Combined tension and shear loading for hammer drilling or Hilti hollow drill bit
Precalculated values
Recommended loads can be calculated by dividing the design resistance by an overall partial safety factor for
action = 1,4. The partial safety factors for action depend on the type of loading and shall be taken from national
regulations.
Release: 2017 50
Hilti HIT-RE 500 V3
with HIT-V rod
Release: 2017 51
Hilti HIT-RE 500 V3
with HIT-V rod
Release: 2017 52
Hilti HIT-RE 500 V3
with HIT-V rod
Release: 2017 53
Hilti HIT-RE 500 V3
with HIT-V rod
Setting
M8 10 - 10 - 10 -
M10 12 - 12 - 12 12
M12 14 14 14 - 14 14
M16 18 18 18 18 18 18
M20 22 22 22 22 22 22
M24 28 28 28 28 28 28
M27 30 - 30 30 30 30
M30 35 35 35 35 35 35
d0 [mm]
d0 [mm] size
Nominal measured
18 17,9 to 18,2 18 18
20 19,9 to 20,2 20 20
22 21,9 to 22,2 22 22
25 24,9 to 25,2 25 25
28 27,9 to 28,2 28 28
30 29,9 to 30,2 30 30
32 31,9 to 32,2 32 32
35 34,9 to 35,2 35 35
Release: 2017 54
Hilti HIT-RE 500 V3 mortar
with rebar (as anchor)
Concrete Concrete Static/quasi- Seismic Hammer drilled Diamond Hilti SafeSet Small edge
(uncracked) (cracked) static ETA-C1/C2 holes drilled technology distance
holes and spacing
European CE PROFIS
Technical conformity Anchor design
Assessment software
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European Technical Assessment CSTB ETA-16/0143 / 2016-04-18
Release: 2017 55
Hilti HIT-RE 500 V3 mortar
with rebar (as anchor)
d0 [mm]
d0 [mm] size
Nominal measured
18 17,9 to 18,2 18 18
20 19,9 to 20,2 20 20
22 21,9 to 22,2 22 22
25 24,9 to 25,2 25 25
28 27,9 to 28,2 28 28
30 29,9 to 30,2 30 30
32 31,9 to 32,2 32 32
35 34,9 to 35,2 35 35
Release: 2017 56
Hilti HIT-RE 500 V3 mortar w/
rebar (as post-installed conn.)
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical assessment CSTB, Marne la Vallée ETA-16/0142 / 2016-04-18
European technical assessment CSTB, Marne la Vallée ETA-16/0143 / 2016-04-18
Fire evaluation CSTB, Marne la Vallée MRF 1526054277/B / 2016-04-12
a)
All data given in this section according to the approvals mentioned above ETA-16/0142 issue 2016-04-18 and
ETA-16/0143 issue 2016-03-29.
Release: 2017 57
Hilti HIT-RE 500 V3 mortar w/
rebar (as post-installed conn.)
Materials
Properties of reinforcement
Product form Bars and de-coiled rods
Class B C
Characteristic yield strength f yk or f0,2k (MPa) 400 to 600
≥ 1,15
Minimum value of k = (f t/fy)k ≥ 1,08
< 1,35
Characteristic strain at maximum force, uk (%) ≥ 5,0 ≥ 7,5
Bendability Bend / Rebend test
Maximum deviation from Nominal bar size (mm)
nominal mass ≤8 ± 6,0
(individual bar) (%) >8 ± 4,5
Bond: Nominal bar size (mm)
Minimum relative rib area, 8 to 12 0,040
fR,min > 12 0,056
Solutions can be calculated according Eurocode 2 using HILTI PROFIS REBAR design program
Release: 2017 58
Hilti HIT-HY 200 mortar
with HIT-Z rod
Concrete Tensile zone Seismic ETA- Fire Corrosion No cleaning Hilti SafeSet
(uncracked) C1/C2 resistance resistance required for with hollow drill
approved loads bit
European CE PROFIS
Technical conformity Anchor design
Approval software
Approvals / certificates
Description Authority / Laboratory No. / date of issue
ETA-12/0006 / 2015-08-
27 (HIT-HY 200-A)
European technical approval a) DIBt, Berlin
ETA-12/0028 / 2015-08-
27 (HIT-HY 200-R)
Fire test report IBMB, Brunswick 3501/676/13 / 2012-08-03
a) All data given in this section according ETA-12/0006 and ETA-12/0028, issue 2015-08-27.
Release: 2017 59
Hilti HIT-HY 200 mortar
with HIT-Z rod
Shear VRd: single anchor, min. edge distance (c = cmin) , without lever arm
Non-cracked concrete
cmin [mm] 40 80 115 110 165
HIT-Z [kN] 3,5 9,2 12,8 16,3 26,0
HIT-Z-R [kN] 3,5 9,2 12,8 16,3 26,0
Cracked concrete
cmin [mm] 40 80 115 110 165
HIT-Z [kN] 2,5 6,5 9,1 11,6 18,4
Release: 2017 60
Hilti HIT-HY 200 mortar
with HIT-Z rod
Release: 2017 61
Hilti HIT-HY 200 mortar
with HIT-Z rod
Release: 2017 62
Hilti HIT-HY 200 mortar
with HIT-Z rod
Release: 2017 63
Hilti HIT-HY 200 mortar
with HIT-Z rod
Minimum edge and spacing geometrical requirements are determined by testing the installation conditions in which
two anchors with a given spacing can be set close to an edge without forming a crack in the concrete due to
tightening torque.
The HIT-Z boundary conditions for edge and spacing geometry can be found in the tables to the left. If the
embedment depth and slab thickness are equal to or greater than the values in the table, then the edge and
spacing values may be utilized.
PROFIS Anchor software is programmed to calculate the referenced equations in order to determine the
optimized related minimum edge and spacing based on the following variables:
Cracked or uncracked concrete For cracked concrete it is assumed that a reinforcement is present which
limits the crack width to 0,3 mm, allowing smaller values for minimum edge
distance and minimum spacing
Anchor diameter For smaller anchor diameter a smaller installation torque is required,
allowing smaller values for minimum edge distance and minimum spacing
Slab thickness and embedment Increasing these values allows smaller values for minimum edge distance
depth and minimum spacing
Release: 2017 64
Hilti HIT-HY 200 mortar
with HIT-Z rod
Release: 2017 65
Hilti HIT-HY 200 mortar
with HIT-V rod
Concrete Tensile Seismic Small edge Variable Fire Approved Hilti SafeSet
(uncracked) zone ETA-C1 distance embedment resistance automatic with hollow
and spacing depth cleaning drill bit
while drilling
Approvals / certificates
Description Authority / Laboratory No. / date of issue
ETA-11/0493 / 2015-04-
European technical approval a) DIBt, Berlin 15 (Hilti HIT-HY 200-A)
ETA-12/0084 / 2015-04-14
(Hilti HIT-HY 200-R)
Fire test report IBMB, Brunswick 3501/676/13 / 2012-08-03
Release: 2017 66
Hilti HIT-HY 200 mortar
with HIT-V rod
Recommended loads can be calculated by dividing the design resistance by an overall partial safety factor for
action = 1,4. The partial safety factors for action depend on the type of loading and shall be taken from national
regulations.
Release: 2017 67
Hilti HIT-HY 200 mortar
with HIT-V rod
Release: 2017 68
Hilti HIT-HY 200 mortar
with HIT-V rod
Release: 2017 69
Hilti HIT-HY 200 mortar
with HIT-V rod
a)
Design resistance: concrete C 20/25 – fck,cube = 25 N/mm² - embedment depth = 12 d
Anchor size M8 M10 M12 M16 M20 M24 M27 M30
Embedment depth hef = 12 d a) [mm] 96 120 144 192 240 288 324 360
Base material thickness h = hmin [mm] 126 150 174 228 284 344 384 430
Tensile NRd: single anchor, no edge effects
Non-cracked concrete
HIT-V 5.8 [kN] 12,0 19,3 28,0 52,7 82,0 118,0 153,3 187,3
HIT-V 8.8 [kN] 19,3 30,7 44,7 84,0 125,2 164,5 196,3 230,0
HIT-V-R [kN] 13,9 21,9 31,6 58,8 92,0 132,1 80,4 98,3
HIT-V-HCR [kN] 19,3 30,7 44,7 84,0 125,2 117,6 152,9 187,1
Cracked concrete
HIT-V 5.8 [kN] 12,0 18,8 28,0 52,7 82,0 117,3 140,0 163,9
HIT-V 8.8 [kN] 12,1 18,8 30,8 54,7 85,5 117,3 140,0 163,9
HIT-V-R [kN] 12,1 18,8 30,8 54,7 85,5 117,3 80,4 98,3
HIT-V-HCR [kN] 12,1 18,8 30,8 54,7 85,5 117,3 140,0 163,9
Shear VRd: single anchor, no edge effects, without lever arm
Non-cracked concrete
HIT-V 5.8 [kN] 7,2 12,0 16,8 31,2 48,8 70,4 92,0 112,0
HIT-V 8.8 [kN] 12,0 18,4 27,2 50,4 78,4 112,8 147,2 179,2
HIT-V-R [kN] 8,3 12,8 19,2 35,3 55,1 79,5 48,3 58,8
HIT-V-HCR [kN] 12,0 18,4 27,2 50,4 78,4 70,9 92,0 110,3
Cracked concrete
HIT-V 5.8 [kN] 7,2 12,0 16,8 31,2 48,8 70,4 92,0 112,0
HIT-V 8.8 [kN] 12,0 18,4 27,2 50,4 78,4 112,8 147,2 179,2
HIT-V-R [kN] 8,3 12,8 19,2 35,3 55,1 79,5 48,3 58,8
HIT-V-HCR [kN] 12,0 18,4 27,2 50,4 78,4 70,9 92,0 110,3
a) d = element diameter
Release: 2017 70
Hilti HIT-HY 200 mortar
with HIT-V rod
a)
Design resistance: concrete C 20/25 – fck,cube = 25 N/mm² - embedment depth = 12 d
(load values are valid for single anchor)
Anchor size M8 M10 M12 M16 M20 M24 M27 M30
Embedment depth hef = 12 d a) [mm] 96 120 144 192 240 288 324 360
Base material thickness h = hmin [mm] 126 150 174 228 284 344 384 430
Spacing s = smin [mm] 40 50 60 75 90 115 120 140
Tensile NRd: double anchor, no edge effects, min. spacing (s = smin)
Non-cracked concrete
HIT-V 5.8 [kN] 12,0 19,3 28,0 48,7 67,8 89,5 106,2 124,9
HIT-V 8.8 [kN] 17,3 24,2 31,8 48,7 67,8 89,5 106,2 124,9
HIT-V-R [kN] 13,9 21,9 31,6 48,7 67,8 89,5 80,4 98,3
HIT-V-HCR [kN] 17,3 24,2 31,8 48,7 67,8 89,5 106,2 124,9
Cracked concrete
HIT-V 5.8 / 8.8
[kN] 8,1 12,4 19,5 33,2 49,8 66,5 78,6 92,6
HIT-V-R / -HCR
Shear VRd: double anchor, no edge effects, min. spacing (s = smin) , without lever arm
Non-cracked concrete
HIT-V 5.8 [kN] 7,2 12,0 16,8 31,2 48,8 70,4 92,0 112,0
HIT-V 8.8 [kN] 12,0 18,4 27,2 50,4 78,4 112,8 147,2 179,2
HIT-V-R [kN] 8,3 12,8 19,2 35,3 55,1 79,5 48,3 58,8
HIT-V-HCR [kN] 12,0 18,4 27,2 50,4 78,4 70,9 92,0 110,3
Cracked concrete
HIT-V 5.8 [kN] 7,2 12,0 16,8 31,2 48,8 70,4 92,0 112,0
HIT-V 8.8 [kN] 12,0 18,4 27,2 50,4 78,4 112,8 147,2 179,2
HIT-V-R [kN] 8,3 12,8 19,2 35,3 55,1 79,5 48,3 58,8
HIT-V-HCR [kN] 12,0 18,4 27,2 50,4 78,4 70,9 92,0 110,3
a) d = element diameter
Release: 2017 71
Hilti HIT-HY 200 mortar
with rebar (as anchor)
Concrete Tensile zone Seismic Small edge Variable Approved Hilti SafeSet
(uncracked) ETA-C1 distance and embedment automatic with hollow
spacing depth cleaning while drill bit
drilling
European CE PROFIS
Technical conformity Anchor design
Approval software
Approvals / certificates
Description Authority / Laboratory No. / date of issue
ETA-11/0493 / 2015-04-
European technical approval a) DIBt, Berlin 15 (Hilti HIT-HY 200-A)
ETA-12/0084 / 2015-04-
14 (Hilti HIT-HY 200-R)
a) All data given in this section according ETA-11/0493 and ETA-12/0084
Release: 2017 72
Hilti HIT-HY 200 mortar
with rebar (as anchor)
Precalculated values
Recommended loads can be calculated by dividing the design resistance by an overall partial safety factor for
action = 1,4. The partial safety factors for action depend on the type of loading and shall be taken from national
regulations.
Release: 2017 73
Hilti HIT-HY 200 mortar
with rebar (as anchor)
Release: 2017 74
Hilti HIT-HY 200 mortar
with rebar (as anchor)
Release: 2017 75
Hilti HIT-FY 200 mortar w/
rebar (as post-installed conn.)
Approvals / certificates
Description Authority / Laboratory No. / date of issue
ETA-12/0083 / 2013-06-05
a)
(HIT-HY 200-R)
European technical approval DIBt, Berlin ETA-11/0492 / 2013-06-05
(HIT-HY 200-A)
Fire test report CSTB, Paris 26033756
a) All data given in this section according ETA-12/0083, issued 2013-06-05 and ETA-11/0492,
issued 2013-06-05.
Release: 2017 76
Hilti HIT-FY 200 mortar w/
rebar (as post-installed conn.)
Electrical Conductivity
HIT-HY 200 in the hardened state is not conductive electrically. Its electric resistivity is 15,5109 ∙cm (DIN
IEC 93 – 12.93). It is adapted well to realize electrically insulating anchorings (ex: railway applications, subway).
Drilling diameters
Drill bit diameters d0 [mm]
Rebar (mm)
Hammer drill (HD) Compressed air drill (CD)
8 12 (10 a)) -
10 14 (12 a)) -
12 16 (14 a)) 17
14 18 17
16 20 20
18 22 22
20 25 26
22 28 28
24 32 32
25 32 32
26 35 35
28 35 35
30 37 35
32 40 40
a) Max. installation length I = 250 mm.
Release: 2017 77
Hilti HIT-HY 170 mortar
with HIT-V rod
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European Technical Approval a) DIBt, Berlin Germany ETA-14/0457 / 2015-03-10
a) All data given in this section according to ETA-14/0457, issued 2015-03-10.
Release: 2017 78
Hilti HIT-HY 170 mortar
with HIT-V rod
Recommended loads can be calculated by dividing the design resistance by an overall partial safety factor for
action = 1,4. The partial safety factors for action depend on the type of loading and shall be taken from national
regulations.
Release: 2017 79
Hilti HIT-HY 170 mortar
with HIT-V rod
Release: 2017 80
Hilti HIT-HY 170 mortar
with HIT-V rod
Release: 2017 81
Hilti HIT-HY 170 mortar
with HIT-V rod
Release: 2017 82
Hilti HIT-HY 170 mortar
with HIT-V rod
a)
Design resistance: concrete C 20/25 – fck,cube = 25 N/mm² - embedment depth = 12 d
Anchor size M8 M10 M12 M16 M20 M24
Embedment depth hef = 12 d a) [mm] 96 120 144 192 240 288
Base material thickness h = hmin [mm] 126 150 174 228 284 344
Edge distance c = cmin [mm] 40 50 60 80 100 120
Tensile NRd: single anchor, min. edge distance (c = cmin)
Non-cracked concrete
HIT-V 5.8 [kN]
HIT-V 8.8 [kN]
9,6 14,9 21,5 38,3 56,0 73,6
HIT-V-R [kN]
HIT-V-HCR [kN]
Cracked concrete
HIT-V 5.8 [kN]
HIT-V 8.8 [kN]
- 8,2 11,8 21,0 - -
HIT-V-R [kN]
HIT-V-HCR [kN]
Shear VRd: single anchor, min. edge distance (c = cmin) , without lever arm
Non-cracked concrete
HIT-V 5.8 [kN]
HIT-V 8.8 [kN]
3,9 5,7 7,8 12,9 18,9 25,9
HIT-V-R [kN]
HIT-V-HCR [kN]
Cracked concrete
HIT-V 5.8 [kN]
HIT-V 8.8 [kN]
- 4,0 5,5 9,1 - -
HIT-V-R [kN]
HIT-V-HCR [kN]
a) d = element diameter
a) The curing time data are valid for dry base material only. In wet base material, curing times must be doubled.
Release: 2017 83
Hilti HIT-HY 170 mortar
with HIT-V rod
a)
Design resistance: concrete C 20/25 – fck,cube = 25 N/mm² - embedment depth = 12 d
(load values are valid for single anchor)
Anchor size M8 M10 M12 M16 M20 M24
Embedment depth hef = 12 d a) [mm] 96 120 144 192 240 288
Base material thickness h = hmin [mm] 126 150 174 228 284 344
Spacing s = smin [mm] 40 50 60 80 100 120
Tensile NRd: double anchor, no edge effects, min. spacing (s = smin)
Non-cracked concrete
HIT-V 5.8 [kN]
HIT-V 8.8 [kN]
11,2 17,2 24,5 42,5 64,9 89,9
HIT-V-R [kN]
HIT-V-HCR [kN]
Cracked concrete
HIT-V 5.8 [kN]
HIT-V 8.8 [kN]
- 9,7 13,9 24,3 - -
HIT-V-R [kN]
HIT-V-HCR [kN]
Shear VRd: double anchor, no edge effects, min. spacing (s = smin) , without lever arm
Non-cracked concrete
HIT-V 5.8 [kN] 7,2 12,0 16,8 31,2 48,8 70,4
HIT-V 8.8 [kN] 12,0 18,4 27,2 50,4 78,4 112,8
HIT-V-R [kN] 8,3 12,8 19,2 35,3 55,1 79,5
HIT-V-HCR [kN] 12,0 18,4 27,2 50,4 78,4 70,9
Cracked concrete
HIT-V 5.8 [kN] - 12,0 16,8 31,2 - -
HIT-V 8.8 [kN] - 15,7 22,7 40,3 - -
HIT-V-R [kN] - 12,8 19,2 35,3 - -
HIT-V-HCR [kN] - 15,7 22,7 40,3 - -
a) d = element diameter
Setting details
Marking of the
embedment depth
Release: 2017 84
Hilti HIT-HY 170 mortar
with HIT-V rod
Setting details
Anchor size M8 M10 M12 M16 M20 M24
Nominal diameter of
d0 [mm] 10 12 14 18 22 28
drill bit
Eff. embedment hef and hef,min [mm] 60 60 70 80 90 96
drill hole depth range h0a)
for HIT-V hef,max [mm] 96 120 144 192 240 288
Minimum base hef + 30 mm
hmin [mm] hef + 2 d0
material thickness ≥ 100 mm
Max. diameter of
clearance hole in the 9 12 14 18 22 26
df [mm]
fixture
Max. torque moment Tmaxb) [Nm] 10 20 40 80 150 200
Minimum spacing smin [mm] 40 50 60 80 100 120
Min. edge distance cmin [mm] 40 50 60 80 100 120
Critical spacing for
scr,sp [mm] 2 ccr,sp
splitting failure
For spacing (or edge distance) smaller than critical spacing (or critical edge distance) the design loads have to be
reduced.
a) Embedment depth range: hef,min ≤ hef ≤ hef,max
b) Maximum recommended torque moment to avoid splitting failure during installation with minimum spacing
and/or edge distance.
c) h: base material thickness (h ≥ hmin), hef: embedment depth
d) The critical edge distance for concrete cone failure depends on the embedment depth hef and the design bond
resistance. The simplified formula given in this table is on the save side.
Release: 2017 85
Hilti HIT-HY 270 mortar
for masonry
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European Technical Assessment DIBt, Berlin ETA-13/1036 / 2014-12-15
Fire test report MFPA, Leipzig PB 3.2/14-179-1 / 2014-09-05
Release: 2017 86
Hilti HIT-HY 270 mortar
for masonry
Release: 2017 87
Hilti HIT-HY 270 mortar
for masonry
Design
Anchorages are designed under the responsibility of an engineer experienced in anchorages and masonry work.
Verifiable calculation notes and drawings are prepared taking account of the loads to be anchored. The position
of the anchor is indicated on the design drawings (e. g. position of the anchor relative to supports, etc.).
Anchorages under static or quasi-static loading are designed in accordance with: ETAG 029, Annex C, Design
method A
ℎ
Failure of the metal part 𝑁𝑆𝑑 ≤ 𝑁𝑅𝑘,𝑠 /𝛾𝑀𝑠
ℎ
Pull-out failure of the anchor 𝑁𝑆𝑑 ≤ 𝑁𝑅𝑘,𝑝 /𝛾𝑀𝑚
Release: 2017 88
Hilti HIT-HY 270 mortar
for masonry
ℎ
Failure of the metal part 𝑉𝑆𝑆 ≤ 𝑉𝑅𝑅,𝑠 /𝛾𝑀𝑠
Notice that loads are affected by a series of factors such as visibility/filling of joints, factors for anchor groups,
spacing and edge distance.
For other applications not covered in this FTM, use Hilti PROFIS Anchor software.
Release: 2017 89
Hilti HIT-HY 270 mortar
for masonry
w/w d/d
hef fb
Load type Anchor size Ta Tb Ta Tb
[mm] [N/mm²]
Loads [kN]
NRd,p = NRd,b HIT-V M8, M10, M12, M16 w/ HIT-SC 50 16 1,0(1,2*) 1,0(1,2*) 1,0(1,2*) 1,0(1,2*)
(ccr = 100mm) HIT-IC M8, M10, M12 w/ HIT-SC 80 16 1,4(1,8*) 1,4(1,8*) 1,4(1,8*) 1,4(1,8*)
HIT-V M8, M10 w/ HIT-SC 50 16 2,6 2,6 2,6 2,6
HIT-V M12, M16 w/ HIT-SC 50 16 3,2 3,2 3,2 3,2
VRd,b
HIT-V M8, M10 w/ HIT-SC 80 16 3,2 3,2 3,2 3,2
(ccr = 100mm)
HIT-V M12, M16 w/ HIT-SC
80 16 4,8 4,8 4,8 4,8
HIT-IC M8,M10, M12 w/ HIT-SC
Release: 2017 90
Hilti HIT-HY 270 mortar
for masonry
w/w d/d
hef fb
Load type Anchor size Ta Tb Ta Tb
[mm] [N/mm²]
Loads [kN]
NRd,p = NRd,b HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 12 - - 2,4 2,0
all
(ccr = 115mm) HIT-IC M8, M10, M12 w/ or w/o HIT-SC 28 - - 3,6 3,0
VRd,b HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 12 - - 2,4 2,4
all
(ccr = 115mm) HIT-IC M8, M10, M12 w/ or w/o HIT-SC 28 - - 3,6 3,6
12 - - 1,6 1,2
≥ 80
20 - - 2,2 1,8
HIT-V M8, M10, M12, M16 w/ HIT-SC
NRd,p = NRd,b 12 - - 2,0 1,6
≥ 130
(ccr = 50mm) 20 - - 3,0 2,4
12 - - 1,6 1,2
HIT-IC M8, M10, M12 w/ HIT-SC 80
20 - - 2,2 1,8
12 2,4 2,4 2,4 2,4
HIT-V M8 w/ HIT-SC ≥ 80
20 3,6 3,6 3,6 3,6
NRd,p = NRd,b HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 4 1,8 1,4 2,0 1,6(1,8*)
≥ 80
(ccr = 115mm) HIT-IC M8, M10, M12 w/ or w/o HIT-SC 6 2,2 1,8 2,4(2,6*) 2,0(2,2*)
4 2,4 2,0 2,6(2,8*) 2,2(2,4*)
≥ 100
6 3,0 2,4 3,2 (3,4*) 2,6(2,8*)
Release: 2017 91
Hilti HIT-HY 270 mortar
for masonry
w/w d/d
hef fb
Load type Anchor size Ta Tb Ta Tb
[mm] [N/mm²]
Loads [kN]
VRk,b HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 80 3 1,6 1,6 1,6 1,6
(ccr = 115mm) HIT-IC M8,M10, M12 w/ or w/o HIT-SC 80 3 1,0 1,0 1,0 1,0
NRd,p = NRd,b HIT-V M10 w/o HIT-SC 80 4 1,6 1,2 1.8 1,4(1,6*)
(ccr = 115mm) HIT-V M12 w/o HIT-SC 80 4 1,8 1,6 2,0 1,8
HIT-V M16 w/o HIT-SC 80 4 2,2 1,8 2,4(2,6*) 2,0(2,2*)
Release: 2017 92
Hilti HIT-HY 270 mortar
for masonry
w/w d/d
hef fb
Load type Anchor size Ta Tb Ta Tb
[mm] [N/mm²]
Loads [kN]
NRd,p = NRd,b HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 6 1,2 1,0 1,2 1,0
all
(ccr = 115mm) HIT-IC M8,M10, M12 w/ or w/o HIT-SC 16 2,2 1,8 2,2 1,8
VRd,b HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 6 1,6 1,6 1,6 1,6
all
(ccr = 115mm) HIT-IC M8,M10, M12 w/ or w/o HIT-SC 16 2,6 2,6 2,6 2,6
NRd,p = NRd,b
HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 50 14 2,2 1,8 2,2 1,8
(ccr = 115mm)
VRd,b
HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 50 14 4,2 4,2 4,2 4,2
(ccr = 115mm)
HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 50 14 2,2 1,8 2,2 1,8
NRd,p = NRd,b
(ccr = 115mm) HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC
80 14 2,2 1,8 2,2 1,8
HIT-IC M8,M10, M12 w/ or w/o HIT-SC
HIT-V M8, M10, M12, M16 w/ or w/o HIT-SC 50 14 4,2 4,2 4,2 4,2
VRd,b HIT-V M8, M10 w/ or w/o HIT-SC 80 14 4,2 4,2 4,2 4,2
(ccr = 115mm)
HIT-V M12, M16 w/ or w/o HIT-SC
80 14 4,8 4,8 4,8 4,8
HIT-IC M8,M10, M12 w/ or w/o HIT-SC
VRd,b HIT-V M8, M10, M12, M16 w/ HIT-SC HIT-IC 4 1,4 1,4 1,4 1,4
all
(ccr = 200mm) M8, M10, M12 w/ HIT-SC 10 2,4 2,4 2,4 2,4
Release: 2017 93
Hilti HIT-HY 270 mortar
for masonry
Design tension and shear resistance – Pull out / Pushing out of one brick failure modes
2
σd = design compressive stress perpendicular to the shear (N/mm )
fvko = initial shear strength according to EN 1996-1-1, Table 3.4
Jobsite test
For other bricks in solid or hollow masonry, not covered by the Hilti HIT-HY 270 ETA or this technical data manual,
the characteristic resistance may be determined by job site tension tests (pull-out tests or proof-load tests), according
to ETAG029, Annex B.
For the evaluation of test results, the characteristic resistance may be obtained taking into account the factor, which
considers the different influences of the product.
The factor for the brick types covered by the Hilti HIT-HY 270 ETA is provided on the following table:
Release: 2017 94
Hilti HIT-HY 270 mortar
for masonry
*Ta / Tb, w/w and d/d anchorage parameters, as defined on Table page 8
Applying the factor from the table above, the characteristic tension resistance NRk can be obtained. Characteristic
shear resistance VRk can also be directly derived from NRk. For detailed procedure consult ETAG 029, Annex B.
Setting
Installation instructions
Anchor installation should be carried out by appropriately qualified personnel and under the supervision of the person
responsible for technical matters of the site.
Hole drilling If no significant resistance is felt over the entire depth of the hole when drilling
(e.g. in unfilled butt joints), the anchor should not be set at this position.
Hammer drilling
Release: 2017 95
Hilti HIT-HY 270 mortar
for masonry
Drill hole cleaning Just before setting an anchor, the drill hole must be free of dust and debris.
Inadequate hole cleaning = poor load values.
Manual Cleaning (MC) or Compressed air cleaning (CAC) for hollow and solid bricks
Blow 2 times from the back of the hole (if needed with nozzle extension) over the
hole length with hand pump (drill hole diameter d0 ≤ 18 mm and drill hole depth
up to h0 = 100 mm) or oil-free compressed air (min. 6 bar at 6 m³/h; drill hole
depth up to h0 = 300 mm) until return air stream is free of noticeable dust.
Brush 2 times with the specified brush by inserting the steel brush Hilti HIT-RB to
the back of the hole (if needed with extension) in a twisting motion and removing it.
The brush must produce natural resistance as it enters the drill hole (brush Ø ≥ drill
hole Ø) - if not the brush is too small and must be replaced with the proper brush
diameter.
Blow again with hand pump or compressed air 2 times until return air stream is
free of noticeable dust.
Injection preparation in masonry with holes or voids: installation with sieve sleeve HIT-SC
Release: 2017 96
Hilti HIT-HY 270 mortar
for masonry
Control amount of injected mortar. Adhesive has to protrude into the lid.
Loading the anchor: After required curing time tcure the anchor can be loaded.
The applied installation torque shall not exceed the values Tmax.
Release: 2017 97
Hilti HIT-HY 270 mortar
for masonry
For installing HIT-V and HIT-IC with embedments of 50 and 80 mm, a single sieve sleeve is used.
Hollow brick with threaded rod HIT-V or internal threaded sleeve HIT-IC and single sieve sleeve HIT-SC
Installation parameters of threaded rod HIT-V with sieve sleeve HIT-SC in hollow and solid brick
HIT-V M6 M8 M10 M12 M16
with HIT-SC 12x85 16x50 16x85 16x50 16x85 18x50 18x85 22x50 22x85
Nominal diameter of drill bit d0 [mm] 12 16 16 16 16 18 18 22 22
Drill hole depth h0 [mm] 95 60 95 60 95 60 95 60 95
Effective embedment depth hef [mm] 80 50 80 50 80 50 80 50 80
Maximum diameter of
df [mm] 7 9 9 12 12 14 14 18 18
clearance hole in the fixture
Minimum wall thickness hmin [mm] 115 80 115 80 115 80 115 80 115
Brush HIT-RB - [-] 12 16 16 16 16 18 18 22 22
Number of strokes HDM - [-] 5 4 6 4 6 4 8 6 10
Nr. of strokes HDE 500-A - [-] 4 3 5 3 5 3 6 5 8
Maximum torque moment for
all brick types except Tmax [Nm] 3 3 3 4 4 6 6 8 8
“parpaing creux”
Maximum torque moment
Tmax [Nm] 2 2 2 2 2 3 3 6 6
for “parpaing creux”
Installation parameters of internal threaded sleeve HIT-IC with HIT-SC in hollow and solid brick
HIT-IC M8x80 M10x80 M12x80
with HIT-SC 16x85 18x85 22x85
Nominal diameter of drill bit d0 [mm] 16 18 22
Drill hole depth h0 [mm] 95 95 95
Effective embedment depth hef [mm] 80 80 80
Thread engagement length df [mm] 8…75 10…75 12…75
Maximum diameter of
hmin [mm] 9 12 14
clearance hole in the fixture
Minimum wall thickness - [mm] 115 115 115
Brush HIT-RB - [-] 16 18 22
Number of strokes HDM - [-] 6 8 10
Number of strokes HDE-500 Tmax [-] 5 6 8
Maximum torque moment Tmax [Nm] 3 4 6
Release: 2017 98
Hilti HIT-HY 270 mortar
for masonry
Applications for hollow and solid bricks with sieve sleeves (cont.)
For installing HIT-V with embedments of 130 and 160 mm, two attached sleeves are used.
Hollow brick with threaded rod HIT-V and two sieve sleeves HIT-SC for deeper embedment depth
Installation parameters of threaded rod HIT-V with two HIT-SC in hollow and solid brick for deeper
embedment depth
HIT-V M8 M10 M12 M16
16x50 16x85 16x50 16x85 16x50 16x85 22x50 22x85
with HIT-SC + + + + + + + +
16x85 16x85 16x85 16x85 16x85 16x85 22x85 22x85
Nominal diameter of drill bit d0 [mm] 16 16 16 16 18 18 22 22
Drill hole depth h0 [mm] 145 180 145 180 145 180 145 180
Effective embedment depth hef [mm] 130 160 130 160 130 160 130 160
Maximum diameter of
clearance hole in the df [mm] 9 9 12 12 14 14 18 18
fixture
Minimum wall thickness hmin [mm] 195 230 195 230 195 230 195 230
Brush HIT-RB - [-] 16 16 16 16 18 18 22 22
Number of strokes HDM - [-] 4+6 6+6 4+6 6+6 4+8 8+8 6+10 10+10
Number of strokes HDE-500 - [-] 3+5 5+5 3+5 5+5 3+6 6+6 5+8 8+8
Maximum torque moment Tmax [Nm] 3 3 4 4 6 6 8 8
Release: 2017 99
Hilti HIT-HY 270 mortar
for masonry
Applications for hollow and solid bricks with sieve sleeves (cont.)
For through fastenings with HIT-V, two attached sleeves are used.
Hollow and solid brick with threaded rod HIT-V with two sieve sleeves HIT-SC for setting through the fixture and/or
through the non-loadbearing layer
Installation parameters of threaded rod HIT-V with two sieve sleeves HIT-SC for setting through the fixture
and/or through the non- loadbearing layer in hollow and solid brick)
HIT-V M8 M10 M12 M16
16x50 16x85 16x50 16x85 18x50 18x85 22x50 22x85
with HIT-SC + + + + + + + +
16x85 16x85 16x85 16x85 18x85 18x85 22x85 22x85
Nominal diameter of drill bit d0 [mm] 16 16 16 16 18 18 22 22
Drill hole depth h0 [mm] 145 180 145 180 145 180 145 180
Effective embedment depth hef,min [mm] 80 80 80 80 80 80 80 80
Max. thickness of non-
loadbearing layer and hp,max [mm] 50 80 50 80 50 80 50 80
fixture (through setting)
Max. diameter of clearance
hole in the fixture (pre-
df1 [mm] 9 9 12 12 14 14 18 18
setting)
Max. diameter of clearance
hole in the fixture (through df2 [mm] 17 17 17 17 19 19 23 23
setting)
Minimum wall thickness hmin [mm] hef+65 hef+70 hef+65 hef+70 hef+65 hef+70 hef+65 hef+70
Brush HIT-RB - [-] 16 16 16 16 18 18 22 22
Number of strokes HDM - [-] 4+6 6+6 4+6 6+6 4+8 8+8 6+10 10+10
Number of strokes HDE-
- [-] 3+5 5+5 3+5 5+5 5+8 8+8 5+8 8+8
500
Max. torque moment for all
brick types exept “parpaing Tmax [Nm] 3 3 4 4 6 6 8 8
creux”
Max. torque moment for
Tmax [Nm] 2 2 2 2 3 3 6 6
“parpaing creux”
Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only be installed without
sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
be rough enough
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Possible drilling
methods'')
Characteristic HIT-RE 500 V3 bond
5 tRk [N/mm2] 8,5 14 9,5 14 9,5 14 9,5 14 10 14 10 13 11 11 20 11 8 11 - 10 - 8,5
resistance
6 60 [mm] 10,6 15,6
7 70 [mm] 12,4 19,7 14,0 19,7 Possible driling methods:
- Temperature range I (min. base material temperature -40°C, max.
- Rebar BSt 500S fuk = 550 [N/mm2], fyk = 500 [N/mm2] according
- No edge distance and spacing influence (calculations according
8 80 [mm] 14,2 23,4 17,1 24,0 17,1 24,0 17,1 24,0 Hammer drilling
long term/short term base material temperature: +24°C/40°C)
9 90 [mm] 16,0 26,3 20,4 28,7 20,4 28,7 20,4 28,7 20,4 28,7
10 100 [mm] 17,9 29,4 23,8 33,6 24,0 33,6 24,0 33,6 24,0 33,6 24,0 33,6
11 120 [mm] 21,3 30,7 28,6 42,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2
Effective anchorage depth
12 140 [mm] 24,9 30,7 33,4 42,2 38,9 55,7 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7
- Installation temperature range -5°C to +40°C
13 160 [mm] 28,4 30,7 38,2 44,2 44,5 60,7 48,5 68,1 48,5 68,1 48,5 68,1 48,5 68,1 48,5 68,1 48,5 68,1 - 56,7 - 56,7
14 180 [mm] 30,7 30,7 42,8 44,2 50,1 60,7 57,3 79,2 57,9 81,3 57,9 81,3 57,9 81,3 57,9 81,3 57,9 81,3 - 67,7 - 67,7 Drilling with HILTI TE-CD or TE-YD hollow dril bits
- Concrete C 20/25, fck,cube = 25 N/mm²
- Correct setting (See setting instruction)
15 200 [mm] 30,7 30,7 44,2 44,2 55,7 60,7 63,6 79,2 67,8 95,2 67,8 95,2 67,8 95,2 67,8 95,2 67,8 95,2 - 79,3 - 79,3
hef
All data in this section applies to:
16 220 [mm] 44,2 44,2 60,7 60,7 70,0 79,2 78,3 109,8 78,3 109,8 78,3 109,8 78,3 109,8 78,3 109,8 - 91,5 - 91,5
17 240 [mm] 44,2 44,2 60,7 60,7 76,4 79,2 89,2 123,5 89,3 125,1 89,2 125,1 89,2 125,1 89,2 125,1 - 104,3 - 104,3
ETAG Bond design method)
18 260 [mm] 60,7 60,7 79,2 79,2 100,7 123,5 100,6 141,1 100,6 141,1 100,6 141,1 100,6 141,1 - 117,6 - 117,6
19 280 [mm] 60,7 60,7 79,2 79,2 112,4 123,5 112,4 157,7 112,4 157,7 112,4 157,7 112,4 157,7 - 131,4 - 131,4
20 300 [mm] 79,2 79,2 123,5 123,5 124,7 174,9 124,7 174,9 124,7 174,9 124,7 174,9 - 145,7 - 145,7
21 400 [mm] 123,5 123,5 192,0 192,8 192,0 242,1 192,0 269,3 192,0 269,3 - 224,4 - 224,4
(ETA-16/0143)
22 500 [mm] 192,8 192,8 242,1 242,1 268,3 277,1 268,3 315,7 - 313,6 - 296,7
23 600 [mm] 277,1 277,1 315,7 315,7 - 376,9 - 356,0
24 700 [mm] - 400,0 - 415,3
25 800 [mm] - 474,7 Diamond coring with roughening tool TE-YRT
hef + 30mm;
26 Minimum base material thickness hmin [mm] hef + 2d0
≥100mm
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
be rough enough
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Possible drilling
methods'')
Characteristic HIT-RE 500 V3 bond
5 tRk [N/mm2] 6,5 18 7,5 18 8 17 8 17 8 15 8 15 8 14 8 13 - 11 - 10 - 10
resistance
6,5 12,2 9,4 15,6 HIT-V Hilti cutted rod with nut and washer
- Temperature range I (min. base material temperature -40°C, max.
6 60 [mm]
- No edge distance and spacing influence (calculations according
8 80 [mm] 8,7 12,2 12,5 19,3 16,0 24,0 17,1 24,0 Possible driling methods:
9 90 [mm] 9,8 12,2 14,1 19,3 18,0 28,1 20,4 28,7 20,4 28,7 Hammer drilling
10 100 [mm] 10,8 12,2 15,7 19,3 20,1 28,1 24,0 33,6 24,0 33,6 24,0 33,6
12,2 12,2 18,8 19,3 24,1 28,1 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2
Effective anchorage depth
11 120 [mm]
- Installation temperature range -5°C to +40°C
12 140 [mm] 12,2 12,2 19,3 19,3 28,1 28,1 37,5 52,3 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7 - 46,4
13 160 [mm] 12,2 12,2 19,3 19,3 28,1 28,1 42,8 52,3 48,5 68,1 48,5 68,1 48,5 68,1 48,5 68,1 - 56,7 - 56,7 - 56,7
- Concrete C 20/25, fck,cube = 25 N/mm²
- Correct setting (See setting instruction)
14 180 [mm] 19,3 19,3 28,1 28,1 48,2 52,3 57,9 81,3 57,9 81,3 57,9 81,3 57,9 81,3 - 67,7 - 67,7 - 67,7
All data in this section applies to:
hef
15 200 [mm] 19,3 19,3 28,1 28,1 52,3 52,3 67,0 81,6 67,8 95,2 67,8 95,2 67,8 95,2 - 79,3 - 79,3 - 79,3 Drilling with HILTI TE-CD or TE-YD hollow dril bits
16 220 [mm] 28,1 28,1 52,3 52,3 73,7 81,6 78,3 109,8 78,3 109,8 78,3 109,8 - 91,5 - 91,5 - 91,5
ETAG Bond design method)
17 240 [mm] 28,1 28,1 52,3 52,3 80,4 81,6 89,2 117,6 89,2 125,1 89,2 125,1 - 104,3 - 104,3 - 104,3
according (ETA-16/0143)
18 260 [mm] 52,3 52,3 81,6 81,6 100,6 117,6 100,6 141,1 100,6 141,1 - 117,6 - 117,6 - 117,6
19 280 [mm] 52,3 52,3 81,6 81,6 112,4 117,6 112,4 153,0 112,4 157,7 - 131,4 - 131,4 - 131,4
20 300 [mm] 52,3 52,3 81,6 81,6 117,6 117,6 124,7 153,0 124,7 174,9 - 145,7 - 145,7 - 145,7
21 400 [mm] 81,6 81,6 117,6 117,6 153,0 153,0 187,0 187,0 - 224,4 - 224,4 - 224,4
22 500 [mm] 153,0 153,0 187,0 187,0 - 231,3 - 272,3 - 313,6
23 600 [mm] 187,0 187,0 - 231,3 - 272,3 - 325,3
24 700 [mm] - 272,3 - 325,3
hef + 30mm;
25 Minimum base material thickness hmin [mm] hef + 2d0
≥100mm Diamond coring with roughening tool TE-YRT
Overall partial safety factor for recommended loads γ = 1,4 should be applied.
The partial safety factors for action depend on the type of loading and shall be taken from national regulations.
For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to be reduced.
a) hef,min ≤ hef ≤ hef,max (hef: embedment depth)
b) h: base material thickness (h ≥ hmin)
c) The critical edge distance for concrete cone failure depends on the embedment depth hef and the design bond resistance. The simplified formula given in this table is on the save side.
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
be rough enough
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Possible drilling
methods'')
Characteristic HIT-RE 500 V3 bond
5 tRk [N/mm2] 6,5 18 7,5 18 8 17 8 17 8 15 8 15 8 14 8 13 - 11 - 10 - 10
resistance
6 60 [mm] 6,5 15,6 9,4 15,6 HIT-V Hilti cutted rod with nut and washer
- Temperature range I (min. base material temperature -40°C,
8 80 [mm] 8,7
- No edge distance and spacing influence (calculations
9 90 [mm] 9,8 19,5 14,1 28,7 18,0 28,7 20,4 28,7 20,4 28,7 AM Hilti metric rod with nut and washer seperately
10 100 [mm] 10,8 19,5 15,7 30,9 20,1 33,6 24,0 33,6 24,0 33,6 24,0 33,6
19,5 18,8 30,9 24,1 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2 Possible driling methods:
Effective anchorage depth
12 140 [mm] 15,2 19,5 21,9 30,9 28,1 44,9 37,5 55,7 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7 - 46,4 Hammer drilling
- Correct setting (See setting instruction)
13 160 [mm] 17,4 19,5 25,1 30,9 32,1 44,9 42,8 68,1 48,5 68,1 48,5 68,1 48,5 68,1 48,5 68,1 - 56,7 - 56,7 - 56,7
according ETAG Bond design method)
14 180 [mm] 28,2 30,9 36,1 44,9 48,2 81,3 57,9 81,3 57,9 81,3 57,9 81,3 57,9 81,3 - 67,7 - 67,7 - 67,7
[N/mm2] according (ETA-16/0143)
All data in this section applies to:
hef
15 200 [mm] 30,9 30,9 40,2 44,9 53,6 83,7 67,0 95,2 67,8 95,2 67,8 95,2 67,8 95,2 - 79,3 - 79,3 - 79,3
16 220 [mm] 44,2 44,9 58,9 83,7 73,7 109,8 78,3 109,8 78,3 109,8 78,3 109,8 - 91,5 - 91,5 - 91,5
17 240 [mm] 44,9 44,9 64,3 83,7 80,4 125,1 89,2 125,1 89,2 125,1 89,2 125,1 - 104,3 - 104,3 - 104,3
18 260 [mm] 69,7 83,7 87,1 130,6 100,6 141,1 100,6 141,1 100,6 141,1 - 117,6 - 117,6 - 117,6 Drilling with HILTI TE-CD or TE-YD hollow dril bits
19 280 [mm] 75,0 83,7 93,8 130,6 112,4 157,7 112,4 157,7 112,4 157,7 - 131,4 - 131,4 - 131,4
20 300 [mm] 80,4 83,7 100,5 130,6 120,6 174,9 124,7 174,9 124,7 174,9 - 145,7 - 145,7 - 145,7
21 400 [mm] 130,6 130,6 160,8 188,2 180,9 244,8 192,0 269,3 - 224,4 - 224,4 - 224,4
+24°C/40°C)
Overall partial safety factor for recommended loads γ = 1,4 should be applied.
The partial safety factors for action depend on the type of loading and shall be taken from national regulations.
For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to be reduced.
a) hef,min ≤ hef ≤ hef,max (hef: embedment depth)
b) h: base material thickness (h ≥ hmin)
c) The critical edge distance for concrete cone failure depends on the embedment depth hef and the design bond resistance. The simplified formula given in this table is on the save side.
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
hole
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Drilling method'')
11 120 [mm]
- Installation temperature range -5°C to +40°C
12 140 [mm] - 21,9 - 26,3 - 30,7 - 30,1 - 37,6 - 39,8 - 39,8 - 39,8 - 39,8
- Correct setting (See setting instruction)
13 160 [mm] - 25,1 - 30,1 - 35,1 - 34,4 - 43,0 - 48,6 - 48,6 - 48,6 - 48,6
according ETAG Bond design method)
14 180 [mm] - 28,2 - 33,9 - 39,5 - 38,7 - 48,4 - 58,0 - 58,0 - 58,0 - 58,0
All data in this section applies to:
hef
15 200 [mm] - 30,7 - 37,6 - 43,9 - 43,0 - 53,8 - 67,3 - 68,0 - 68,0 - 68,0
16 220 [mm] - 41,4 - 48,3 - 47,3 - 59,2 - 74,0 - 78,4 - 78,4 - 78,4
17 240 [mm] - 44,2 - 52,7 - 51,7 - 64,6 - 80,7 - 89,4 - 89,4 - 89,4
according (ETA-16/0143)
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
hole
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Drilling method'')
11 120 [mm]
- Installation temperature range -5°C to +40°C
12 140 [mm] - 12,2 - 19,3 - 28,1 - 39,8 - 39,8 - 39,8 - 39,8 - 39,8
- Correct setting (See setting instruction)
13 160 [mm] - 12,2 - 19,3 - 28,1 - 45,9 - 48,6 - 48,6 - 48,6 - 48,6
according ETAG Bond design method)
hef
Overall partial safety factor for recommended loads γ = 1,4 should be applied.
The partial safety factors for action depend on the type of loading and shall be taken from national regulations.
For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to be reduced.
a) hef,min ≤ hef ≤ hef,max (hef: embedment depth)
b) h: base material thickness (h ≥ hmin)
c) The critical edge distance for concrete cone failure depends on the embedment depth hef and the design bond resistance. The simplified formula given in this table is on the save side.
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
hole
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Drilling method'')
8 80 [mm] -
- No edge distance and spacing influence (calculations
9 90 [mm] - 15,0 - 18,8 - 22,6 - 20,5 - 20,5 AM Hilti metric rod with nut and washer seperately
10 100 [mm] - 16,7 - 20,9 - 25,1 - 24,0 - 24,0 - 24,0
19,5 - 25,1 - 30,1 - 31,6 - 31,6 - 31,6 - 31,6 - 31,6 Driling method:
Effective anchorage depth
11 120 [mm] -
- Installation temperature range -5°C to +40°C
12 140 [mm] - 19,5 - 29,3 - 35,1 - 39,8 - 39,8 - 39,8 - 39,8 - 39,8 Diamond coring
- Correct setting (See setting instruction)
13 160 [mm] - 19,5 - 30,9 - 40,2 - 45,9 - 48,6 - 48,6 - 48,6 - 48,6
according ETAG Bond design method)
hef
Overall partial safety factor for recommended loads γ = 1,4 should be applied.
The partial safety factors for action depend on the type of loading and shall be taken from national regulations.
For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to be reduced.
a) hef,min ≤ hef ≤ hef,max (hef: embedment depth)
b) h: base material thickness (h ≥ hmin)
c) The critical edge distance for concrete cone failure depends on the embedment depth hef and the design bond resistance. The simplified formula given in this table is on the save side.
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
be rough enough
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Possible drilling
methods'')
Characteristic HIT-HY 200 bond
5 tRk [N/mm2] - 12 5 12 7 12 7 12 7 12 7 12 7 12 7 12 7 12 7 12 7 12
resistance
6 60 [mm] - 12,0 6,2 15,0
7 70 [mm] - 14,0 7,3 17,5 12,3 19,7 Possible driling methods:
- Temperature range I (min. base material temperature -40°C, max.
- Rebar BSt 500S fuk = 550 [N/mm2], fyk = 500 [N/mm2] according
- No edge distance and spacing influence (calculations according
8 80 [mm] - 16,0 8,3 20,1 14,0 24,0 16,4 24,0 17,1 24,0 Hammer drilling
long term/short term base material temperature: +24°C/40°C)
9 90 [mm] - 18,0 9,4 22,6 15,8 27,1 18,4 28,7 20,4 28,7 20,4 28,7
10 100 [mm] - 20,0 10,4 25,1 17,5 30,1 20,5 33,6 23,4 33,6 24,0 33,6 24,0 33,6
11 120 [mm] - 20,0 12,5 30,1 21,1 36,1 24,6 42,2 28,1 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2
Effective anchorage depth
12 140 [mm] - 20,0 14,6 30,7 24,6 42,2 28,7 49,2 32,8 55,7 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7 - - 39,7 55,7
- Installation temperature range -10°C to +40°C
13 160 [mm] - 20,0 16,7 30,7 28,1 44,2 32,8 56,2 37,5 64,3 46,9 68,1 48,5 68,1 48,5 68,1 48,5 68,1 - - 48,5 68,1
14 180 [mm] 18,8 30,7 31,6 44,2 36,9 60,7 42,2 72,3 52,7 81,3 57,9 81,3 57,9 81,3 57,9 81,3 - - 57,9 81,3 Drilling with HILTI TE-CD or TE-YD hollow dril bits
- Concrete C 20/25, fck,cube = 25 N/mm²
- Correct setting (See setting instruction)
15 200 [mm] 20,9 30,7 35,1 44,2 41,0 60,7 46,9 79,2 58,6 95,2 67,8 95,2 67,8 95,2 67,8 95,2 - - 67,8 95,2
hef
All data in this section applies to:
16 220 [mm] 38,7 44,2 45,1 60,7 51,6 79,2 64,5 109,8 78,3 109,8 78,3 109,8 78,3 109,8 - - 78,3 109,8
17 240 [mm] 42,2 44,2 49,2 60,7 56,2 79,2 70,3 120,6 87,9 125,1 89,2 125,1 89,2 125,1 - - 89,2 125,1
ETAG Bond design method)
18 260 [mm] 53,3 60,7 60,9 79,2 76,2 123,5 95,2 141,1 99,1 141,1 100,6 141,1 - - 100,6 141,1
19 280 [mm] 57,4 60,7 65,6 79,2 82,1 123,5 102,6 157,7 106,7 157,7 112,4 157,7 - - 112,4 157,7
20 300 [mm] 70,3 79,2 87,9 123,5 109,9 174,9 114,3 174,9 123,1 174,9 - - 124,7 174,9
21 400 [mm] 117,2 123,5 146,6 192,8 152,4 208,5 164,2 242,1 - - 187,6 269,3
(ETA-11/0493)
22 500 [mm] 183,2 192,8 190,5 208,5 205,2 242,1 - - 234,5 315,7
23 600 [mm] - - 281,4 315,7
24 700 [mm]
25 800 [mm] Diamond coring with roughening tool TE-YRT
hef + 30mm;
26 Minimum base material thickness hmin [mm] hef + 2d0
≥100mm
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
be rough enough
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Possible drilling
methods'')
Characteristic HIT-HY 200 bond
5 tRk [N/mm2] 7,5 18 7,5 18 8,5 18 8,5 18 8,5 18 9 18 9 18 9 18
resistance
6 60 [mm] 7,5 12,0 9,4 15,6 HIT-V Hilti cutted rod with nut and washer
- HILTI HIT-V (F) 5.8 rod fuk = 500 [N/mm2], fyk = 400 [N/mm2]
- Temperature range I (min. base material temperature -40°C,
9 90 [mm] 11,3 12,0 14,1 19,3 19,2 28,0 20,4 28,7 20,4 28,7 Hammer drilling
10 100 [mm] 12,0 12,0 15,7 19,3 21,3 28,0 24,0 33,6 24,0 33,6 24,0 33,6
- Installation temperature range -10°C to +40°C
11 120 [mm] 12,0 12,0 18,8 19,3 25,6 28,0 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2
12 140 [mm] 12,0 12,0 19,3 19,3 28,0 28,0 39,7 52,6 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7
- Correct setting (See setting instruction)
13 160 [mm] 12,0 12,0 19,3 19,3 28,0 28,0 45,5 52,6 48,5 68,1 48,5 68,1 48,5 68,1 48,5 68,1
according ETAG Bond design method)
14 180 [mm] 19,3 19,3 28,0 28,0 51,2 52,6 57,9 81,3 57,9 81,3 57,9 81,3 57,9 81,3
All data in this section applies to:
hef
15 200 [mm] 19,3 19,3 28,0 28,0 52,6 52,6 67,8 82,0 67,8 95,2 67,8 95,2 67,8 95,2 Drilling with HILTI TE-CD or TE-YD hollow dril bits
16 220 [mm] 28,0 28,0 52,6 52,6 78,3 82,0 78,3 109,8 78,3 109,8 78,3 109,8
17 240 [mm] 28,0 28,0 52,6 52,6 82,0 82,0 89,2 118,0 89,2 125,1 89,2 125,1
according (ETA-11/0493)
18 260 [mm] 52,6 52,6 82,0 82,0 100,6 118,0 100,6 141,1 100,6 141,1
19 280 [mm] 52,6 52,6 82,0 82,0 112,4 118,0 112,4 153,3 112,4 157,7
20 300 [mm] 52,6 52,6 82,0 82,0 118,0 118,0 124,7 153,3 124,7 174,9
21 400 [mm] 82,0 82,0 118,0 118,0 153,3 153,3 187,3 187,3
+24°C/40°C)
Overall partial safety factor for recommended loads γ = 1,4 should be applied.
The partial safety factors for action depend on the type of loading and shall be taken from national regulations.
For spacing (or edge distance) smaller than critical spacing (or critical edge distance) the design loads have to be reduced.
a) Embedment depth range: hef,min ≤ hef ≤ hef,max
b) Maximum recommended torque moment to avoid splitting failure during installation with minimum spacing and/or edge distance.
c) h: base material thickness (h ≥ hmin), hef: embedment depth
d) The critical edge distance for concrete cone failure depends on the embedment depth h ef and the design bond resistance. The simplified formula given in this table is on the safe side.
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
Uncracked
be rough enough
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
concrete
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
Cracked
(please look at
,,Possible drilling
methods'')
Characteristic HIT-HY 200 bond
5 tRk [N/mm2] 7,5 18 7,5 18 8,5 18 8,5 18 8,5 18 9 18 9 18 9 18
resistance
6 60 [mm] 7,5 15,6 9,4 15,6 HIT-V Hilti cutted rod with nut and washer
- Temperature range I (min. base material temperature -40°C,
8 80 [mm] 10,0
- No edge distance and spacing influence (calculations
9 90 [mm] 11,3 19,3 14,1 28,7 19,2 28,7 20,4 28,7 20,4 28,7 AM Hilti metric rod with nut and washer seperately
10 100 [mm] 12,5 19,3 15,7 30,6 21,3 33,6 24,0 33,6 24,0 33,6 24,0 33,6
Possible driling methods:
- Installation temperature range -10°C to +40°C
11 120 [mm] 15,0 19,3 18,8 30,6 25,6 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2 31,5 44,2
12 140 [mm] 17,5 19,3 21,9 30,6 29,9 44,6 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7 39,7 55,7 Hammer drilling
- Correct setting (See setting instruction)
13 160 [mm] 19,3 19,3 25,1 30,6 34,1 44,6 45,5 68,1 48,5 68,1 48,5 68,1 48,5 68,1 48,5 68,1
according ETAG Bond design method)
14 180 [mm] 28,2 30,6 38,4 44,6 51,2 81,3 57,9 81,3 57,9 81,3 57,9 81,3 57,9 81,3
All data in this section applies to:
hef
15 200 [mm] 30,6 30,6 42,7 44,6 56,9 84,0 67,8 95,2 67,8 95,2 67,8 95,2 67,8 95,2
16 220 [mm] 44,6 44,6 62,6 84,0 78,3 109,8 78,3 109,8 78,3 109,8 78,3 109,8
17 240 [mm] 44,6 44,6 68,3 84,0 85,4 125,1 89,2 125,1 89,2 125,1 89,2 125,1
18 260 [mm] 74,0 84,0 92,5 130,6 100,6 141,1 100,6 141,1 100,6 141,1 Drilling with HILTI TE-CD or TE-YD hollow dril bits
19 280 [mm] 79,7 84,0 99,6 130,6 112,4 157,7 112,4 157,7 112,4 157,7
20 300 [mm] 84,0 84,0 106,8 130,6 124,7 174,9 124,7 174,9 124,7 174,9
21 400 [mm] 130,6 130,6 180,9 188,0 192,0 244,6 192,0 269,3
+24°C/40°C)
Overall partial safety factor for recommended loads γ = 1,4 should be applied.
The partial safety factors for action depend on the type of loading and shall be taken from national regulations.
For spacing (or edge distance) smaller than critical spacing (or critical edge distance) the design loads have to be reduced.
a) Embedment depth range: hef,min ≤ hef ≤ hef,max
b) Maximum recommended torque moment to avoid splitting failure during installation with minimum spacing and/or edge distance.
c) h: base material thickness (h ≥ hmin), hef: embedment depth
d) The critical edge distance for concrete cone failure depends on the embedment depth h ef and the design bond resistance. The simplified formula given in this table is on the safe side.
Latvia
+371 67600673 / www.hilti.lv
HILTI Center Latvia
Address Opening hours
Mukusalas 42a Mon - Fr: 800 AM – 500 PM
1026, Riga E-mail
T +371 67600673 online.lv@hilti.com
F +371 67628821
Estonia
+372 6260080 / www.hilti.ee
HILTI Center Estonia
Address Opening hours
Mustamae tee 46 Mon - Fr: 800 AM – 500 PM
10621, Tallinn E-mail
T +372 6260080 online.ee@hilti.com
F +372 6260080
Technical product specifications are constantly improving and changing for improvement. Although the preparation of this catalog has been given maximum
care, some changes may not be made and can only occur after the publication of this catalog. Please verify your details with your nearest dealer. Hilti accepts
no responsibility for any errors and mistakes. Therefore, the information contained in this catalog is subject to change without notice. Published by Hilti Lithuania
in 2017.