You are on page 1of 20

Distance Elements: Linking Theory With Testing

Fernando Calero, Schweitzer Engineering Laboratories, Inc.

Abstract-U nderstanding and testing distance elements Distance elements are used in line protection schemes for
require linking the theory related to their design to the fault their definite reach. Simple overcurrent protection lacks this
voltages and currents used during tests. This paper discusses the property, and its reach is highly dependent on the source
theory, deriving the characteristics of phase and ground distance
elements with a focus on three in particular. The derivation will impedance. A definite reach is highly desired in distance
introduc~ certain concepts, including the impedance plane, elements.
~ource Impedance, forward fault impedance, reverse fault In general, protective relaying elements are implemented
Impedance, fault resistance, and load flow behavior. The discus- by comparing thresholds to measured and/or combined power
sion is based on the use of symmetrical components to under- system quantities. While early electromechanical distance
stand the design, behavior, and characteristics of distance relays used actual magnitude comparisons of the voltage-
elements. This paper also reviews some testing procedural errors.
A confident understanding of the theory allows for an easier produced restraining torque to the current-produced operating
understanding of the testing results obtained. torque [4], distance elements have been preferably imple-
mented by comparing the phase relationship of two vectors.
I. INTRODUCTION The comparison is done with a phase comparator, which can
be implemented with an electromechanical unit (a two-phase
Distance units are the main protection algorithms imple-
motor, for example), a solid-state coincidence timer (measur-
mented in most line protection schemes. Even with line dif-
ing a .quarter-cycle coincidence between square waves), or
fere~tial schemes, distance schemes are used as backup,
numencal comparator [2][3][5]. Regardless of the technology,
keepIng these elements in the protective relaying inventory.
the threshold condition of a phase comparator is described by
While different distance elements have been proposed
(1 ).
according to the requirements and preferences of manufactur-
ers, there are concepts that should be linked from the aca-
demic analysis to the practical testing of these elements. arg(:~) =±90° (1)
Knowing the theory that derives the characteristics of the
The quantities S1 and S2 are phasor quantities, inputs to
element makes it easier to understand the behavior while test-
the P?ase comparator. S1 is normally called the operating
ing the element or comprehending its operation in the field.
quantIty, and S2 is the polarizing quantity or reference. For
Distance units have been traditionally categorized in phase
distance elements, S1 will normally be the assumed voltage
and ground units. They have been designed to detect power
drop (V - Zc I) across the element's replica impedance Zc.
system faults that do not involve the ground return (310) for
Volta~e V is the restraining voltage, and (Zc I) is the operating
phase faults and those that involve the ground return for
quantIty that overcomes the restraining voltage. To compare
gro~nd faults. Phase-to-phase-to-ground faults are a design
whether (Zc I) is larger than V with a phase comparator, a
choIce for manufacturers; generally, these faults will be asso-
reference quantity is required (S2).
ciated with phase fault detection.
S2 is the reference and must be a stable quantity (no
With ten fault types possible, determining the impedance to
significant phase change) during normal and faulted power
the fault is not a simple measurement of voltage and current
system conditions. The choice of S2 may differ from manu-
[1][2][3]. In traditional line protection schemes, six impedance
facturer to manufacturer, and benefits and drawbacks have
units are used, usually identified as AG, BG, CG, AB, BC,
been described in literature [2].
and CA elements. These six elements constitute a protection
zone and should detect all of the ten fault types possible.

978-1-4244-4183-9/09/$25.00 ©2009 IEEE 333


Fig. 1 shows the theoretical operation of S1 and S2 for
faults in the reverse direction (Fig. la), in zone (Fig. Ib), and
out of zone (Fig. 1c) for a distance unit. S2 should be a solid
reference that should not change drastically during fault
conditions.

F1 Fault 81

Trip F2 Fault Fig. 2. Circle Defined by Arbitrary a and b Vectors on the Z Plane

1
82
(a) Fig. 2 illustrates a circle and the graphical proof of (2).
VA
One-half of the circle satisfies the +90 0 requirement; the other
__ ~o~~ r!j-~~+~~~o)Zc half satisfies the -90 0 requirement. The circle is split by the
Tnp 81 •
line connecting the tips of a and b.
F3 Fault An academic and important fact to constantly remember is
(b) that the plot in Fig. 2 represents the circle on the Z plane.
Keeping this concept in mind avoids mixing other or similar
results that are based on different planes.
A simple and generic example of a distance element is used
Trip to demonstrate (2). This element is a self-polarized distance
unit, where:
(c)
SI = V - Zc I (3)
Fig. 1. Distance Relay Operation
S2=V (4)
Protective relaying theory is heavily based on the theory of This distance unit is called self-polarized because the
symmetrical components. The derivation of distance-unit polarizing quantity (S2) is the same as the restraining voltage.
characteristics is no exception. In fact, it is the theory that uses Substituting the SI and S2 values of (3) and (4) into (2)
symmetrical components in the most elegant and ingenious yields:
way.
arg(~~ J= arg(Y -yZC1J = ±90°
II. DESCRIBING A CIRCLE
(5)
Mho distance elements are circles on an impedance plane.
An equation describing a circle should lead to the description
arg( Ii ;Zc) = arg ( Z~ZC J= ±90°
of these distance units. Equation (2) is a vector equation of a
circle [3]. In (5), the a and b vectors can be easily recognized as:

S2
(z-aJ
arg ( -SIJ = arg -:::--== = ±90°
Z-b
(2)
a=Zc
b=O
(6)
(7)

Equation (2), which is an extension of (1), can be readily


visualized in Fig. 2 for an arbitrary set of a and b vectors.

334
The plot of this characteristic is shown in Fig. 3. Zs1 ZL1

-
x _ _ _ Zc = Rc + j Xc
,., " ~

t
.......
......

/
/
/ " "-
"- ,, IR1

VR1
/ \
/ \
I \
I \ Zs1 ZL1

,
I \
I I
,I ~

t
\
\ IR2
I
\ /

,,
\ / VR2
\ /
/
/
"- ,., " ZsO ZLO
" ...... .......
,,"
R
~

Fig. 3. Self-Polarized Distance Element on the Z Plane

III. ANALYSIS OF Two MHo DISTANCE ELEMENTS


VRO t IRO

To support this discussion, two examples of mho distance


Fig. 4. Symmetrical Component Network for a Forward AG Fault
elements are used: a ground distance unit and a phase distance
unit. Both units polarized with positive-sequence voltage The impedance plane for which the analysis will be per-
illustrate the proper development of distance element charac- formed is the positive-sequence impedance in the forward
teristics. The technique is also applicable to other elements direction. The analysis will find the ZL 1 impedances for
found in the industry [3]. The analysis will review the AG and which the unit will operate. Interestingly, the following iden-
Be distance units, which are traditionally the most illustrative tity will allow for an easier analysis:
because they use Phase A symmetrical components. The other
ZLI = VRI- VFI (11)
units are derived in a similar way and are an extension of these IRI
distance units.
Returning to (8), simplify to find a more useful expression
A. Positive-Sequence Polarized AG Ground Distance Unit for SI:
(Forward Characteristics)
SI = (VRI + VR2+ VRO)
This ground distance unit is designed with:
- ZcI (IRI + IR2 + IRO - kcO 3IRO)
SI = VRA - ZcI(IRA - kcO 3IRO) (8) (12)
=(VRI- VFI) + VFI+ VR2+ VRO
S2=VAI (9)
- (ZcI IRI + ZcI IR2 + ZcO IRO)
where:
using:
kcO = ZcO - ZcI (10)
3ZcI VFI =-VF2- VFO
(13)
Zc1 and ZcO are the relay settings. Zc1 is the reach of the =-(VR2-ZLIIR2)-(VRO-ZLOIRO)
ground distance element, and ZcO is implicitly defined in the and:
relay settings when kcO is adjusted for the particular applica-
IRI = IR2 = IRO (14)
tion. These constants are to be visualized as the replica imped-
ances of the line to be protected. Next, simplify (12):
Fig. 4 illustrates the symmetrical component network inter- SI = (VRI- VFI)+ ZLIIRI + ZLOIRI
connection of a source (with its own positive- and zero- (15)
sequence impedance) and an impedance located in the forward ZCOJ
-ZcIIRI ( 2 + -
direction to the distance element location. The distance ZcI
element measurements are denoted by R; these are the vol-
tages and currents that the unit is measuring. The direction of ~=ZLI(2+ ZLOJ-ZCI(2+ ZCOJ (16)
IRI ZLI ZcI
the measurement is clearly shown with the current orienta-
tions.

335
Equation (16) is important in the analysis and is expressed Fig. 5 illustrates a very important concept-the fact that
in terms of ZLI, which is the impedance on which plane the these impedances are all in the forward direction, as derived
characteristic will be derived. from the symmetrical component network interconnection in
Returning to (9), simplify to find a more useful expression Fig. 4. A negative impedance (ZLI =-jX), for example, does
for 82: not mean the fault is in the reverse direction; it means that
ZL 1 is a capacitor in the forward direction.
82 =(VRI- VFI)+ VFI
To contrast the forward fault characteristics of distance
=(VRI- VFI)- VF2- VFO elements, the reverse fault characteristics can be derived.
(17)
={VRI- VFI)+{ZsI+ZLI)IR2 B. Positive-Sequence Polarized AG Ground Distance Unit
+(ZsO+ZLO)IRO (Reverse Characteristics)
The symmetrical component network connection shown in
Using (13) and (14), (17) simplifies to:
Fig. 6 is the network used to derive the reverse fault charac-
~=ZLI(2+ ZLOJ+ZSI(I+ ZSOJ (18)
teristics for the AG element described by 81 and 82 in (8) and
(9). The impedance ZL' is of interest, and the reverse fault
IRI ZLI ZsI
characteristics of this distance unit will be plotted on the ZL l'
The results in (16) and (18) can be used in (2) to find the a
plane. Notice again the directions of the distance-unit current
and b vectors:
measurements are denoted by the current orientations.

a=ZcI
(2+ ZCO
ZcI J
(19)
ZL1' Zs1

(2+ ZLOJ
ZLI ~

f
IR1

(1+ ZSOJ
ZsI
VF1 VR1 f
b = -ZsI (20)
(2+ ZLOJ
ZLI
ZL1' Zs1
The impedance ratio of Zc 1 and ZcO, via kcO in (10),
should equate the line impedance ratio of ZL 1 and ZLO,
~
because these are the replica impedances. Therefore, (19) is
IR2

f
further simplified to:
a = ZcI (21) VR2

Fig. 5 illustrates the derived characteristic on the ZL 1


plane. Any ZLI impedance (with a characteristic ZLO/ZLI
impedance ratio) inside the circle indicates an operating ZLO' ZsO
condition.
x a=Zc1 ~
,,-,:- IRO

f
", ",
/ /
/ /
/ / VRO
/ I
I I ~
I I
,
I
I ,
I
,
,
"1\\
I I
Fig. 6. Symmetrical Component Network for a Reverse AG Fault

Returning to (8), simplify to find a more useful expression


I \
I ' R for 81:
\
, \
, /
/
I
I
81 = (VRI + VR2+ VRO)
\
,, '......
...... _--" ",/
/
I
-ZcI{IRI + IR2+ IRO-kc03IRO)
, ...... ",
/
/
(22)
=(VRI- VFI)+ VFI+ VR2+ VRO
1 ZSOJ ......

~~~J
( ----", [( ZsOJ]
b=-Zs1 + Zs1 - (ZcI IRI + ZcI IR2 + ZcO IRO)
bmem =-Zs1 (::
2+ ZLOJ
( ZL1 using:
VFI = - VF2 - VFO
Fig. 5. Forward Fault Characteristic on the ZLI Plane (23)
= -(VR2 + ZLI 'IRI) - (VRO+ ZLO'IRO)

336
Equation (22) can be simplified to: x
81 = (VR1- VF1) - ZL1'IR1- ZLO'IRI

ZCOJ
-ZclIRl ( 2 + -
(24) a=-ZC1[ (1+~J]
2+ ZLO'J
Zcl (
ZL1' R
using:

b=_ZS1[ (1+~J ]
Zll' = VR1- VFl (25)
(-IR1)

_8_l_=ZL1'(2+ ZLO'J+ZC1(2+ ZCOJ (26)


, (
2+ ZLO'J
ZL1'

(-IRI) ZLI' Zcl \ I

Returning to (9), simplify to find a more useful expression


\
, /
/
"
--" ;I'

for 82:
Fig. 7. Reverse Fault Characteristic on the ZLl' Plane
82 = (VRI- VFI)+ VFI
C. Positive-Sequence Polarized BC Phase Distance Unit
=(VRI- VFI)- VF2- VFO (Forward Characteristics)
(27)
= (VR1- VF1)-(Zsl+ ZL1)IRl The symmetrical component network connection shown in
- (ZsO + ZLO) IRI Fig. 8 is the network used to derive the forward fault charac-
teristic for the BC element described in (31) and (32).
~= ZL1'(2+ ZLOJ+ZS1(1+ ZSOJ (28)
This phase distance unit is defined by:
-IRI ZLI Zsl 81 = (VRB - VRC) -Zcl(IRB - IRC) (31)
The results in (26) and (28) can be used in (2) to find the a 82 = VB1- VCl (32)
and b vectors:
Zs1 ZL1

a=-Zcl
(2+~~~J
~--~ (29) ~
2+ ZLO'J IR1
( ZL1'

b=-Zsl
(1+
~--~
~:~J (30)
(
2+ ZLO'J
ZL1'
Zs1 ZL1

The ground element is mostly directional for all reactive ~


impedances and may encounter problems if capacitances are IR2
located in the reverse direction. Fig. 7 illustrates that there are
impedances on the ZL1' plane (mainly capacitive and with
negative resistance values) for which the element will operate.
This is a desirable distance element characteristic. For security Fig. 8. Symmetrical Component Network for a Forward BC Fault
purposes, most manufacturers will opt to supervise the opera-
tion of distance elements with directional elements to avoid
unwanted operations if the fault impedances in the reverse
direction fall inside the characteristic, as shown in Fig. 7.

337
Following a similar procedure for S1 as that described in ZL1' Zs1
Section III, Subsection A:

t
SI=(a 2 -a)[(VR1- VR2)-Zcl(IRI-IR2)]
(33)
= jJ3[ (VR1- VF1) - VR2- Zcl(2IR1)+ VF1] VR1

~ = jJ3 (2ZLI-IZcl) (34)


IRI ZL1' Zs1
and for S2:

t
S2 = (a 2 -a)(VR1- VFl + VF1) ~

(35) IR2

= jJ3[(VR1- VF1)+ IRl(Zsl+ ZL1)] VR2

(36) ~= jJ3 (2 ZLI-Zsl) Fig. 10. Symmetrical Component Network for a Reverse BC Fault
IRI
Using the results in (34) and (36), the resulting a and b Returning to (31), simplify to find a more useful expression
vectors are: for S1, based on the network shown in Fig. 10:
a=Zcl (37) SI = (a 2 - a)[(VR1- VR2) - Zcl (IR1- IR2)]
b=- Zsl (38) =jJ3[ (VRl- VFl) - VR2 - Zcl (2IRl) + VFlJ (39)
2
The positive-sequence polarized phase distance unit has a = jJ3[(VR1- VF1)- VR2-Zcl(2IR1)
definite reach, given by Vector a. Fig. 9 illustrates the +VR2-ZL'IRI
threshold locus on the ZL 1 plane.
x
~=jJ3(2ZL1+2Zcl) (40)
(-IR1)
,
a =Zc1

",
",,,,--==-
.""
",
.""
........ Returning to (32), simplify to find a more useful expression
/ / ,,~
for S2:
/
/
/
/
":.\.\ ,
/
/
I
/ \\ S2=(a 2 -a)[(VR1- VFl)+ VF1]
\ \ (41)
I I \ \
I I \ \ = jJ3[(VR1- VF1)- IRl(Zsl + ZL1)]
I I
,
I \
I ,
\ I
I \
I ~ = jJ3 (2 ZL1- Zs2) (42)
I \ (-IR1)
\ I 'R Using the results in (40) and (42), the resulting a and b
/ I
\ / vectors are:
/ I
\ / I
\
",
",
/ a=-Zcl (43)
\ /
\ / b =_ Zsl
"" ..... , ",
/
/
2
(44)
' ..... .""
",

x
Fig. 9. Forward Fault Characteristic on the ZL 1 Plane

D. Positive-Sequence Polarized BC Phase Distance Unit R


(Reverse Characteristics)
a =-Zc1
In this section, we will follow a similar procedure as b=- Zs1
described in Section III, Subsection B. Fig. lOis the network 2
used to derive the reverse fault characteristic for the Be phase
distance element. \
,
I
\ I

" ...... _-",


\ /
/

Fig. 11. Reverse Fault Characteristic on the ZL I' Plane

338
E. Phase-to-Phase-to-Ground Faults Using:
An interesting design choice is the detection of phase-to- IR2=-IRI ZsO+ZLO (46)
phase-to-ground faults. These can be considered either as ZsO + ZLO + Zsl + ZLI
ground faults (due to the involvement of the ground return) or
(45) yields:
phase faults (due to their multiphase nature). The choice is a
design choice of the manufacturer.
When single-pole trip, line distance protection schemes are
ZLl(l+ ZsO+ZLO J
~ = jv"3 ZsO+ ZLO+ Zsl + ZLI (47)
designed, phase-to-phase-to-ground faults are to trip the three
poles of the breaker. Only phase-to-ground faults, when IRI -ZCl(l+ ZsO+ZLO J
ZsO + ZLO + Zsl + ZLI
detected, imply the opening of a single pole of the breaker.
This argument, by itself, justifies detecting phase-to-phase-to Returning to (32), derive a more useful expression for 82:
ground faults with the phase elements. Other arguments
82 = jv"3[(VRl- VFl) + VFl] (48)
include the operation of the phase selectors in the overall
scheme. using (46):
The positive-sequence polarized phase distance unit
described by (31) and (32) readily detects phase-to-phase-to- ZLl(1 + ZsO + ZLO J
ground faults. Fig. 12 is the network used to derive the ~ = jv"3 ZsO + ZLO + Zsl + ZLI (49)
forward fault characteristic for the BeG phase distance IRI +Zsl (ZSO+ ZLO J
element. ZsO + ZLO + Zsl + ZLI

Zs1 ZL1 Next, use (47) and (49) to find the a and b vectors:
a = Zcl (50)
~
IR1
b = -ZSI[ ZsO+ ZLO ]
Zsl + ZLI + 2Zs0 + 2ZLO (51 )
= f(ZLl)
While Vector a is well-defined with a very definite and
desired reach, Vector b is a function of ZL 1 but in the nega-
Zs1 ZL1 tive direction. The result indicates that to find the shape
requires an iterative process, because b is not in the same
~
position for two different values of ZL 1. However, what really
IR2 matters is (50) because the element has a definite reach.
F. Three-Phase Faults and Memory in 82
For both the ground distance elements and the phase
distance element, three-phase faults can be shown to present
the same characteristic on the ZL 1 plane. The a and b vectors
ZsO ZLO can be shown to be the ones found for the self-polarized
distance unit, described in (6) and (7).
~ The characteristic plotted in Fig. 3 shows that the circle
IRO boundary passes through at the distance element location.
Neither the ground nor the phase element can detect the fault
due to the lack of any voltage to calculate the positive-
sequence polarizing quantity (82). The distance unit should be
Fig. 12. Symmetrical Component Network for a Forward BCG Fault able to detect these faults.
Returning to (31), derive a more useful expression for 81 In general, memory action is provided, and 82 "remem-
based on the network shown in Fig. 12: bers" the proper polarizing quantity after the fault when all
voltages are zero. In most implementations of modern relays,
81 = jv"3[(VRl- VFl) + VFl- VF2) 82 is implemented with memory for all phase and ground
(45)
- Zcl (IRl- IR2)] distance elements [6]. Besides the benefit associated with
detecting three-phase faults right at the location of the distance
unit, providing memory action enhances the ability of distance
protection schemes to be applied in lines with series capacitors
and increases fault detection ability.

339
For the positive-sequence polarized phase distance unit, a X
modified S2 polarizing vector is: " , . . , - - - - ...... ~G

S2 = VBlmem - VClmem (52) / /


", " ",
/ \
This translates to: / \
I \
S2 = jJ3(Vsl) I \
(53) , I
= jJ3(VRI + Zsl IRl) I ,
\ I
For a three-phase fault: \ I R

~=jJ3(ZL1+Zsl) (54)
IRI
Using (54) together with (37), the memory effect expands
the circle with:
bmem = -Zsl (55) Fig. 13. Response of All Three Ground Distance Elements to an AG Fault
In fact, it can be shown that polarizing the ground and on the ZL 1 Plane
phase distance elements with memory modifies Vector b, Interestingly, the responses of the elements do not over-
resulting in the following values. reach. Therefore, as a protective scheme design choice, the
For the ground distance unit: distance elements can detect all types of faults. The other
choice could be to use a phase selector to enable only the type

bmem=-ZSI[2+~] 2+
ZLO
(56)
of distance unit appropriate for the type of fault. That way,
only the AG element detects AG faults, since the fault detector
ZLI has determined the type of fault.

For the phase distance unit: H Fault Resistance and Load Flow
bmem = -Zsl (57) Fault resistance and load flow are not considered when
describing the characteristics of distance elements. The plots
These results are shown in Fig. 5 and Fig. 9. In the opera-
in Fig. 5 and Fig. 9 are provided and assume a radial system.
tion of these distance elements, the memory has a time
The appendix of this paper provides the complete deriva-
constant, which varies with the design and purpose [6]. In
tions of the impedance plots on the apparent impedance plane,
traditional phase distance relay applications, the time constant
considering these two factors.
should be enough to detect the zero-voltage, three-phase fault.
Fault resistance and load flow are more important in the
Series capacitor applications require a longer time constant
analysis of the operation of distance units. During the testing
and associated logic that changes short and long memory
of the characteristic's distance units, these two factors are
constants.
generally not considered.
When picturing the operation of these units, the b vector
starts at b = bmem, and after a few time constants, its value
IV. ANALYSIS OF A QUADRILATERAL GROUND
approaches that of the "no-memory" mho circle. DISTANCE UNIT
G. Response to Other Fault Types and Phase Selector Quadrilateral distance units are provided in protection
Criteria systems to cover ground faults. While their advantages over
Although not part of this paper, it has been shown else- traditional mho ground distance units and ground overcurrent
where that all distance elements have a response to other types protection are a matter of discussion, these units are present in
of faults [3]. However, with the methodology described protective relays and merit consideration.
previously, these characteristics can be derived. Implementing a quadrilateral element requires a reactance
Fig. 13 is an example of the composite response for an AG element, a resistance element, and a directional element.
fault of all the ground distance elements. There are areas of
A. Reactance Element
the ZL 1 plane where two or three of these elements will oper-
ate. The same is true for phase distance elements and their The reactance element for a ground directional element is
responses to other fault types. defined by the following equations [2][3]:
SI =VRA-Zc(IRA+kcO 310) (58)
jT
S2 = j IR2 e (59)
The polarizing quantity S2 is a current; T is the
"nonhomogeous correction angle" to be described later. It can
be shown that 12 is the better choice when load is considered.
However, 10 and (IA+KO 10) are other possibilities for
obtaining a reactance line.

340
Equation (58) is the same as (8) and can also be simplified Zs1 ZL1
to the expression in (16).
The polarizing quantity 82 is different. To simplify 82, a
~
relatively nonacademic mathematical trick can be used. IR1
82 = 0 (VRl- VFl) + j IRI e jT (60)

~=Q(ZLl+ J
jT
j e (61)
IRI 0 0
Zs1 ZL1
The end result is:

~~~]
~

ZLl- ZCl[ 2 IR2


2_ ZLO
81 ZLI
jT
(62) 3Rt
82 ZLl+ j e
0(2- ZLO]
ZLI ZsO ZLO

Equation (62) is not rigorously correct, but it allows for a


criterion to obtain the expression for Vector b. ~

IRO
-j [90-T+ang (2+ZCO)]
b= 00 e Zcl ( 63)

Vector a is expressed in (19). Fig. 14 illustrates the graphi-


cal result. Vector b is a very large and infinite vector but with Fig. 15. Symmetrical Component Representation of an AG Fault With Fault
Resistance (Rt)
an angle. The reactance line is a circle with infinite radius.
If the protective relay is doing a DFT (discrete Fourier
transform) or cosine filter calculation, the real and imaginary
parts of the vectors are available. It follows that:

1m {VRA [ ZLl(IRA + kcO 310)*]} =


(65)
1m{(If Rf) [ ZLl(IRA + kcO 310)*]}
Z-b
and:

1m{VRA [ Zcl(IRA + kcO 310)*]}


Rf = ---=-----------::~ (66)
Im{[ If (Zcl(IRA + kcO 310)*]}
R
-j[90-T+L(2+ ZeD)] In one design choice [2], the If value was chosen to be:
b =ooe Ze1
If = 3 (IRO + IR2)

Fig. 14.

Reactive Line Component of a Ground Quadrilateral Unit
2
(67)

Equation (66) yields the fault resistance value (Rf), which


B. Resistance Element for a radial system adds to the line impedance. This result is a
The resistive check for a quadrilateral element could be straight calculation of Rf and cannot be plotted on an imped-
implemented with equations similar to (58) and (59), using ance plane. In fact, the directional element that keeps the
82 = IR2 and Zc = R [3]. Another approach is to actually reactance unit from detecting reverse faults cannot be plotted
calculate the resistive component of the fault [1][2]. on the plane. The quadrilateral element is a combination of the
Consider the symmetrical component representation of a reactance line, the resistive check, and a directional element.
ground fault with resistance, as shown in Fig. 15. The follow-
V. TESTING OF DISTANCE ELEMENTS
ing is true:
VFl + VF2 + VFO = If Rf Relay engineers are curious. Most of them want to have a
(64) deep understanding of the devices that are connected to their
VRA - ZLl(IRA + kcO 310) = If Rf power system. When the device fundamentals are understood
analysis and testing are simple. There are three types of testin~
that satisfy different functions of a numerical protective relay:
acceptance, commissioning, and maintenance [7].

341
Acceptance testing involves the study of the protective 1) Apparent Impedance for a Ground Fault
device and its characteristics. Some users qualify protective The network in Fig. 4 is also used to derive the expression
devices over a period of time, studying and testing the for the apparent impedance. Therefore, for the AG fault in
characteristics provided by the device. This test is performed Fig. 4:
in a quiet environment, usually the company's protection VFl + VF2 + VFO = 0
laboratory, with ample time to verify the published character-
(VR1- ZLI IRl)
istics. During this type of testing, the users have an oppor-
tunity to obtain an understanding of the relay principles. +(VR2-ZLI IR2)+(VRO-ZLO IRO) = 0 (68)
Commissioning testing involves the actual installation of VRA + ZLI [IRA + kLO (310)] = 0
the protective device and the testing of the connections to it
Equation (68) simplifies to:
(e.g., polarities and phasing) and of the programmable logic.
Some distance-unit reaches may be verified on the distance ZL1= VRA (69)
elements. The commissioning testing is by no means as IRA + kcO (310)
involved as the acceptance testing, due to the timing and most
where kcO is defined in (10) as a relay setting. It should be
likely the pressure to get the devices installed.
equal to kLO:
Maintenance testing involves a periodic and simple func-
tional evaluation of the protective device. The testing takes kLO = ZLO - ZLI (70)
advantage of the self-check algorithms in numerical protective 3ZLI
relays and also the nature of the hardware design. Since the
2) Apparent Impedance for a Phase-to-Phase Fault
firmware is a software program, it is not expected that the
The following is true for the network in Fig. 8:
features tested in the acceptance testing and the commission-
ing testing have changed. A visual inspection of the enable VF1- VF2 =0
light, confirmation that the metering matches known levels, (VR1- ZLI IRl) - (VR2 - ZLI IR2) = 0 (71)
and testing of auxiliary contacts or devices should suffice. The (VR1- VR2) - ZL1(IR1- IR2) = 0
maintenance testing interval is dependent on the data collected
from the device. If the metering and oscillographic reports are Equation (71) simplifies to:
accessed constantly, the maintenance interval may be longer ZLI = VRB - VRC (72)
than for a device that is totally isolated and not reporting any IRB-IRA
events.
B. Confirming the Distance Unit Characteristic
It is hoped that the information in this section helps in
understanding the actual operation of distance elements and Symmetrical components are used to derive the distance
acceptance testing. The implementation of the distance units element characteristics on the ZL 1 plane. Assuming a radial
has been tested and verified by the manufacturer and users system, this is how the impedance characteristics on the ZL 1
several times, especially if the device is mature in the market- plane are derived. The effect of load flow and fault resistance
place. is neglected; their influence is easier to visualize on the appar-
ent impedance plane when the operation of the unit is studied.
A. Apparent Impedance Symmetrical component theory is fundamental for relay engi-
The term apparent impedance is largely used in protective neers. It makes three-phase power system analysis simple and
relaying literature when discussing distance elements. It is a understandable.
calculation of the impedance in terms of the measured volt- When testing a memory polarized distance unit, the way
ages and currents. For a simple radial system with no load the prefault and faulted voltages are managed affects the test
flow, the apparent impedance can be readily used to verify the results. The memory effect will not be noticeable when the
plots of Fig. 5 and Fig. 9 on the ZLI plane. For load flow and calculated fault voltages are maintained and the calculated
fault resistance in a two-source network, the term is not a fault current is increased until the unit trips. But if the prefault
physical impedance. It is a measurement that implies apparent voltages are healthy and then fault quantities are applied, the
impedance, and it only represents an impedance (ZLI in our memory effect will be noticeable.
discussion) if the system is radial. When fault resistance and
load flow are considered, the apparent impedance is just a
measurement.

342
Memory algorithms may vary among different manufactur- TABLE II
TEST VOLTAGES AND CURRENTS
ers, but the decay of the polarizing memory voltage (82) is,
for most practical purposes, too fast to obtain the memory Point/
Voltages and Currents I
voltage characteristic. Moreover, the filtering of the voltages ZLI
and currents may take some time, and the memory voltage
Va = 63.68LO°, Vb = 71.76L-120.70°,
may have already changed its value. However, by choosing an pI
Vc = 70.81LI22.78° 3.86
impedance point in between the no-memory and "with- 10.00L80°
Ia = 3.84L-74.15°, Ib = 0, Ic = 0
memory" polarization, the behavior can be checked. This will
Va = 64.24LO°, Vb = 72.91L-117.11°,
be illustrated with the phase distance element. p2
Vc = 69.58LI26.03° 4.35
8.95L50°
1) Testing the Ground Distance Unit Ia = 4.32L-44.31 0, Ib = 0, Ic = 0
For illustration, the parameters in Table I were chosen for
Va = 65.36LO°, Vb = 74.34L-ll1.39°,
the model. p3
Vc = 67.59LI31.34° 6.58
6.04L20°
TABLE I Ia = 6.5IL-14.07°, Ib = 0, Ic = 0
GROUND DISTANCE-UNIT MODEL PARAMETERS
Va = 66. 15LO°, Vb = 75.33L-I08.2°,
p4
Parameter Value Description Vc = 66.43LI34.44° 8.23
4.87LI0°
Zcl 10 L80° Positive-sequence reach Ia = 8.15L-14.07°, Ib = 0, Ic = 0

Derived from the setting kcO (10) that Va = 67.41LO°, Vb = 76.79L-I03.58°,


ZcO 30L70° p5
is normally a setting Vc = 64.80LI38.85° 10.73
3.81LO°
Ia = IO.67L6.04°, Ib = 0, Ic = 0
kcO 0.674L-14.93° The actual kcO
Va = 69.69LO°, Vb = 79. 13L-96.90°,
Zsl lL85° Positive-sequence source impedance p6
Vc = 62.34LI45.61 ° 14.87
2.85L-I0°
ZsO 3L80° Zero-sequence source impedance Ia = 14.74LI6.42°, Ib = 0, Ic = 0

Va = 73.67LO°, Vb = 82.72L-87.86°,
Fig. 16 shows the corresponding mho circle derived from p7
Vc = 58.88LI55.35° 21.07
the parameters in Table I. Ten random points were chosen 2.13L-20°
Ia = 20.86L26.80°, Ib = 0, Ic = 0
from the plot, and their impedances were calculated. For each
point, the symmetrical component analysis yielded the corre- p8
Va=62.69LO°, Vb=66.17L-146.27°,
sponding test voltages and currents, as shown in Table II. By Vc = 79.30LI01.14° 13.96
2.71LI70°
fixing the voltages and slowly increasing the current, the trip Ia = 13.92L-164.43°, Ib = 0, Ie = 0
point is found when the distance unit trips. The fault magni- Va = 62.72LO°, Vb = 69.42L-130.35°,
p9
tude listed in Table II corresponds, within the margins of the Vc = 74.06LI14.33° 6.48
5.85LI40°
test equipment error, to the theoretical value, also shown in Ia = 6.45L-133.88°, Ib = 0, Ic = 0
Table II. Va = 63.23LO°, Vb = 70.83L-124.37°,
plO
Vc = 72.05LI19.53°
x a =10L80° 8.80LllO°
4.36
Ia = 4.32L-I04.03°, Ib = 0, Ic = 0

This example illustrates the link between theoretical values


p2
and proper testing. The values in Table II come from the
\
\ symmetrical component analysis of the fault.
\ The source impedance magnitude was not sufficient to
\ make the memory effect noticeable; a larger source impedance
I p3
should be chosen.
p4

\
0

+~
---
( 1 3L80 ]]'"
b=-(1L85°) ' ...........
[ 2+ 30L700]
( 10L80°

Fig. 16. Points on the Ground Distance Characteristic for the Example in
Table I

343
2) Testing the Phase Distance Element TABLE IV
TEST VOLTAGES AND CURRENTS WITH NO MEMORY
To illustrate the phase distance-unit testing, the parameters
from Table III were chosen. Point/
Voltages and Currents I
TABLE III ZLI
PHASE DISTANCE-UNIT MODEL PARAMETERS
Va = 70LO°, Vb = 47.26L-140.11 0,
pI
Parameter Value Description Vc = 45.36L138.07° 3.05
10.00L80°
Ia = 0, Ib = 3.03L-172.63°, Ic = 3.03L7.38°
Zc1 10L80° Positive-sequence reach
Va = 70LO°, Vb = 53.57L-146.19°,
Zsl 10L85° Positive-sequence source impedance p2
Vc = 39.22L130.53° 3.24
9.70L50°
In this example, the source impedance is larger and will Ia = 0, Ib = 3.23L-157.84°, Ic = 3.23L22.16°

allow testing of the memory effect on the distance character- Va = 70LO°, Vb = 60.63L-153.32°,
p3
istics. Vc = 31.49L120.18° 3.87
8.65L20°
Fig. 17 illustrates the plot of the phase distance element Ia = 0, Ib = 3.85L-145.14°, Ic = 3.85L34.86°
based on the parameters in Table III. The inner circle, as dis- Va = 70LO°, Vb = 63.12L-155.97°,
p4
cussed in a previous section, is the characteristic with no- Vc = 28.51Ll15.67° 4.18
memory effect on the polarizing vector (82). 8.23L10°
Ia = 0, Ib = 4.16L-142.04°, Ic = 4.16L37.97°

X a =10L80° Va = 70LO°, Vb = 66.20L-159.41°,


p5
Vc = 24.63L109.02° 4.61
7.74LO°
Ia = 0, Ib = 4.60L-139.55°, Ie = 4.60L40.85°

Va = 70LO°, Vb = 69.46L-163.27°,
p6
Vc = 20.30L99.86° 5.17
7.26L-10°
Ia = 0, Ib = 5.14L-137.19°, Ic = 5.14L42.81 °

p3 Va = 70LO°, Vb = 72.86L-167.64°,
p7
Vc = 15.64L85.70° 5.23
6.82L-20°
Ia = 0, Ib = 5.77L-167.64°, Ic = 5.77L43.78°

Va = 70LO°, Vb = 21.87 L-113.73°,


p8
Vc = 64.39L161.89° 4.83
6.82L170°
Ia = 0, Ib = 4.83L152.17°, Ic = 4.83L-27.84°

Va = 70LO°, Vb = 29.67L-122.89°,
p9
Vc = 59.37L155.19° 3.88
7.74L150°
Ia = 0, Ib = 4.04L157.12°, Ic = 4.04L-22.88°
bmem = -10L85°
Va = 70LO°, Vb = 35.73L-129.06°,
plO
Fig. 17. Phase Distance-Unit Points on the Impedance Plane Vc = 54.99L149.71° 3.53
8.65L130°
Ia = 0, Ib = 3.52L164.21 0, Ic = 3.52L-15.79°
Table IV shows the test voltages and currents used to
confirm the no-memory characteristic. The test voltages are The outer characteristic is related to the memory effect on
constant, while the current is increased until the phase distance 82. It is impractical to test this characteristic. The memory
element trips. The fault current magnitudes correspond to the algorithms in protective relays are constantly updated; the
expected values, within the margins of error of the test equip- filtering behavior of the relays will make the memory value
ment and the device under test. (82) change almost instantly. Therefore, any values calculated
with the outer-circle impedances will not yield any practical
results.

344
Visually, note that the memory polarizing voltage is
changing to the new faulted value and the circle starts from
the outer boundary and decays finally to the inner, no-memory
boundary.
To test this behavior, impedances in between the outer and
inner circle can be chosen. The midpoint impedances shown in
Fig. 17 are good choices. These values are the average of the
two impedances at the same angle from the outer and inner
circles.
~V1mem
Moreover, to test the memory behavior, apply the fault
V1 -+
after healthy voltages have been present for a while. Both fault
Distance Unit
voltages and currents should correspond to the calculated
values.
Table V describes the midpoint impedances and the fault Fig. 18. Typical Fault Sequence Verifying the Voltages and Currents in
Table V
voltages and currents used to verify the memory polarization
of the phase distance element. Healthy prefault voltages and 3) Testing the Ground Reactance Distance Unit
currents start the fault sequence. To illustrate the testing of the ground reactance distance
unit, the parameters in Table I will be used. The setting T
TABLE V
TEST VOLTAGES AND CURRENTS WITH MEMORY compensates for any effect associated with the tilt on the
reactance line.
Point/ The reactance setting T (58) will be set to:
Voltages and Currents
ZLI
p3 Va = 70LO°, Vb = 61.69L-151.70°, Vc = 33.17LI18.19° ( ZCO]
T=arg 2 + - =-6.00
Zcl
(73)
9.51L20° Ia = 0, Ib = 3.69L-143.373°, Ic = 3.69L36.627°
This value makes the reactance line horizontal, as seen in
p4 Va = 70LO°, Vb = 64.71L-153.75°, Vc = 31.01LI12.684°
Fig. 19.
9.32LI0° Ia = 0, Ib = 3.95L-139.25°, Ic = 3.95L40.75°
x
p5 Va = 70LO°, Vb = 68.56L-156.25°, Vc = 24.63LI04.70° Zc=10L80°
9.08LO° Ia = 0, Ib = 4.31L-134.94°, Ic = 4.31L45.06° p1 p2 p3 p4 p5 p6 p7

p6 Va = 70LO°, Vb = 72.77L-158.86°, Vc = 26.329L94.64°


8.84L-I0° Ia = 0, Ib = 4.76L-131.29°, Ic = 4.76L48.71 °

p7 Va = 70LO°, Vb = 78.08L-161.92°, Vc = 24.60L80.10°


8.61L-20° Ia = 0, Ib = 5.35L-127.85°, Ic = 5.35L52.152°

p8 Va = 70LO°, Vb = 25.95L-I07.19°, Vc = 67.08LI58.31°


8.19LI70° Ia = 0, Ib = 4.51LI47.66°, Ic = 4.51L-32.34°

p9 Va = 70LO°, Vb = 31.52L-120.11°, Vc = 60.66LI53.29°


8.66LI50° Ia = 0, Ib = 3.85LI55.09°, Ie = 3.85L-24.91 °

plO Va = 70LO°, Vb = 36.45L-127.95°, Vc = 55.59LI48.86°


9.15LI30° Ia = 0, Ib = 3.43LI63.46°, Ic = 3.43L-16.54°

Fig. 18 illustrates the operation of the distance element and


the fault sequence. Note the effects of the memory action. The R

memory voltage is decaying much slower than the actual Fig. 19. Points on the Reactance Ground Distance Characteristic
positive-sequence voltage. As the polarizing voltage decays,
there will be a point in the decay where there is not enough
polarizing voltage to operate the distance unit. The element
eventually drops out, visualized as the circle dropping from
the full-memory characteristic to the steady-state character-
istic, which is polarized by VI. The memory action, however,
has allowed an expansion of the element.

345
Table VI represents seven points on the reactance line. 3) Use Symmetrical Components When Testing
These impedances lie on the threshold of operation. The The distance element theory is based on symmetrical com-
recorded current in the right-hand column is within the margin ponents. More than any other aspect of power systems,
of error in the test equipment and the protective relay. symmetrical components are the foundation of power system
TABLE VI
protective relaying and, in particular, distance elements. The
TEST VOLTAGES AND CURRENTS FOR FIG. 19 faulted voltages and currents presented earlier were obtained
from symmetrical component analysis of the faults.
Point/
Voltages and Currents I A traditional way to estimate faulted voltages and currents
ZLI for an AG ground fault, for example, is by using a phasor
pI
Va = 64. 15LO°, Vb = 70.34L-140.11 0, diagram, as illustrated in Fig. 20. The faulted voltage is
Ve = 7.200L138.07° 3.75 decreased, and the faulted current is modified according to the
10.38L108.33°
Ia = 3.72L-102.33°, Ib = 0, Ie = 0 impedance magnitude and angle requirement. While this
Va = 63.71LO°, Vb = 70.72L-123.03°, methodology provides a "quick and dirty" way to make an
p2
Ve = 71.83L120.44° 3.87 estimate, it is not based on any theory. The unfaulted voltages
9.98L99.21 °
Ia = 3.85L-93.21 0, Ib = 0, Ie = 0 remain with their healthy values, and the angles between volt-
ages remain constant. This is not what happens in a real power
Va = 63.53LO°, Vb = 71.10L-122.06°,
p3 system.
Ve = 71.56L121.54° 3.91
8.65L20°
Ia = 3.89L-83.59°, Ib = 0, Ie = 0 Moreover, as illustrated in Fig. 20, increasing the faulted
current angle results in the faulted current and the faulted volt-
Va = 63.67LO°, Vb = 71.42L-12 1.00°,
p4 age being in phase. This condition will not occur in a trans-
Ve = 71.21L122.56° 3.86
10L80° mission network. Directional elements will not declare the
Ia = 3.83L-74.00°, Ib = 0, Ie = 0
fault to be in the forward direction because, for ground faults,
Va = 64.08LO°, Vb = 71.65L-120.01°, it is assumed that the source is reactive and not resistive, as
p5
Ve = 70.84L123.38° 3.73 equal angles will suggest.
10.42L70.94°
Ia = 3.70L-64.93°, Ib = 0, Ie = 0

Va = 64.66LO°, Vb = 71.78L-119.l9°, I
p6
Ve = 70.50L123.92° 3.54 ,/
11.076L62.76° ;'
,,
Ia = 3.5IL-56.76°, Ib = 0, Ie = 0 VRA
Va = 65.30LO°, Vb = 71.83L-118.59°,
p7
Ve = 70.21L124.20° 3.32
6.82L-20° If
Ia = 3.29L-49.62°, Ib = 0, Ie = 0
---------------~
C. Comments on the Impedance Testing Results
The results obtained, the description of the testing, and the
theory described in the previous sections allow for discussing
a few interesting issues.
1) The Plot Is on the ZL1 Plane Fig. 20. Fixing Voltages and Changing the Fault Current Does Not
The impedance plots correspond to the ZLI plane. The Accurately Represent Faults in a Power System
characteristics represent actual impedances in a radial network
4) Directional Elements Supervise Distance Units
for which the distance unit will operate. For purposes of test-
If symmetrical components are used to calculate faulted
ing the unit's characteristic, a radial network is assumed.
voltages and currents, the directional units supervising the
Plots that correspond to other planes should not be con-
distance elements will be transparent to the testing procedure.
fused or used together with the distance element characteristic
Directional unit theory is based on symmetrical compo-
plots. For example, the impedance-based ground directional
nents as well. For example, for ground directional elements,
element plots its characteristics on a V2/I2 or VO/IO plane.
the source impedance determines that the direction to the fault
2) The Plot Is for Faults in the Forward Direction is in the forward direction (the measurement is -Zs for a
Fig. 7 and Fig. 11 illustrate the characteristics of distance forward fault).
units for faults in the reverse direction. They represent the The use of symmetrical components and a known source
impedance values on the reverse impedance plane (ZL 1') for impedance ensures that directional elements will not block the
which the element will operate and are a totally different plane operation of distance units.
than the forward fault impedance plane (ZLI) shown in Fig. 5
and Fig. 9.
Reverse fault characteristics are not possible to test in
practice because distance elements are generally supervised by
directional elements that keep distance units operating in the
forward direction only.

346
VI. APPARENT IMPEDANCE, LOAD FLOW,
AND F AULT RESISTANCE
The theory and testing covered in the previous sections
illustrate a radial network and the graphical view of all the
impedances that would make the distance unit operate. Load
flow and fault resistance are factors that are present in all line
IF2
distance protection schemes.
The ZL 1 plane is not the proper plane to visualize the Zs1 mZL1 t (1-m)ZL1 Zr1
3 Rf
operation of the distance units when there is load flow and
fault resistance. The fault resistance is not part of any of the
three symmetrical component networks (positive, negative,
and zero sequence).
VR2 t ~
IR2
VF2 t
The proper plane to use is the apparent impedance plane.
t
IFO
For ground faults, the plane is defined by (69). For phase ZsO mZLO (1-m)ZLO ZrO
faults, the plane is defined by (72). In the appendix of this

t t
paper, the impedance circles are derived for both the ground ~
and phase distance elements. IRO
VRO VFO
It is mathematically very difficult to find the impedance
locus on any plane to describe the distance element
characteristics because the distribution of currents is different
Fig. 22. Two-Source Symmetrical Component Representation of a Ground
depending on the faulted impedance and load flow. With the Fault
use of the equations derived in the appendix, it is simpler to
visualize the location of the apparent impedance measured Solving for m = 1 and Rf= 0, only the load flow effect is
with respect to the distance-unit characteristics. illustrated in Fig. 23. The figure shows a computer-generated
Another important point is that all the information is avail- graph based on the equations derived in the appendix. As
able from the local measurements to calculate the apparent reported in other literature, mho circles adjust appropriately to
impedance. prevent overreach due to the direction of the load flow [3].
To illustrate the plotting on the apparent impedance plane, The pivot point is the unit's reach.
the system in Fig. 21 is used. The end characteristic on the 15r----------~--------.......
left-hand side is plotted, and a large source impedance is x
selected to illustrate the mho circle behavior compared to the Fault
radial characteristics discussed before. ~Location
. .
Zs1 = 10L85°
ZsO = 20L75°
ZL1 = 10L80°
ZLO = 30L70°
Zr1 = 2L85°
ZrO = 2L80°
\
.....

\Forward Load

t
~
J Effect R
IR1 o t-----~-----I------I-~----I
VR1
~Radial
../3"- Characteristic
...... --_ .
Fig. 21. Sample Power System Used to Illustrate the Impedance Plot With
Rf and Load Flow

A. Ground Distance Unit


Using the impedances in Fig. 21 and the network shown in
Fig. 22, circuit analysis techniques can solve for the network.
The distance-unit settings are the same as the ones shown in
-15 "'----------...1....----------'"
-15 o 15
Table I. Fig. 23. Load Flow Effect on the Apparent Impedance Characteristic

347
For the same point (m = 1) and the same load flow but with TABLE VII
TEST VOLTAGES AND CURRENTS FOR APPARENT IMPEDANCES IN
fault resistance (Rf= 0.5 ohms), Fig. 24 illustrates the plot of FIG. 23, FIG. 24, AND FIG. 25
the apparent impedance and the distance-unit characteristics.
In the apparent impedance plane, the Rf component is not a Point/
Voltages and Currents I
straight line, and moreover, the apparent Rf component is ZApp
magnified several times due to the strong remote source. Va = 37.33LO°, Vb = 67.94L-124.33°,
pI Vc = 69.02Ll13.01 °
15r----------~--------..., 2.89
Fault Location X 10.00L80° Ia = 2.88L-71.83°, Ib = 0.53L-143.88°,
Apparent Impedance Ie = 1.67LI06.12°

Ji
. . . . .~. .\.j
Va = 39.57LO°, Vb = 67.77L-112.93°,
p2 Vc = 69.51L124.88° No
R trip
10.47L53.82° Ia = 2.97L-46.46°, Ib = 0.69L-137.72°,
Ic = 1.67L123.59°

Va = 40.94LO°, Vb = 75.50L-I05.75°,
p3 Vc = 72.96L146.88°
Ol--------\T-----#------+--+-----I 3.20
8.63L30.02° Ia = 3.I9L-18.63°, Ib = 1.12L-93.09°,
Ic = 1.08L145.79°

Each point on the apparent impedance plane can be plotted


using the expressions in the appendix; examples are shown in
Fig. 23, Fig. 24, and Fig. 25. Distance units are monitoring the
Forward Load
Radial Effect
power system constantly. When there is a fault, the numerical
Characteristic algorithm calculates the phasor values of the voltages and cur-
-15 10...-
rents. It therefore follows that the impedance trajectory on the
..I000o- .....

-15 o 15
apparent impedance plane can be plotted over time.
Fig. 24. Load Flow and Fault Resistance Apparent Impedance Numerical distance units make calculations in discrete time
periods called processing intervals. It is therefore possible to
The advantage of using a computer program to calculate
evaluate the impedance trajectory to the fault over time. In
the voltages and currents of the network is that a point on the
Fig. 26, a plot of the impedance trajectory is shown. Note that
plot can be found. With this point, the voltages and currents
at each processing interval, the apparent impedance changes.
can be calculated.
The apparently random motion until the impedance stabilizes
15r----------~--------..... to the actual fault apparent impedance is also due to the fil-
X

/
Fault Location tering algorithm used.
Apparent Impedance
15r----------~--------...,
X
...........
""""

o I-- ~----~---__I__+_---R_I

o I-----~----_P_----f+_-----...;.R~

Forward Load
Radial Effect
Characteristic
-15 " " - - - - - - - - - -.........- - - - - - - -.....
-15 o 15

Fig. 25. Boundary Fault at m = 0.5 and Rf= 4.0


- 1 5 1 0 . . . - - - - - - - - -.........- - - - - - - -.....
-15 o 15

Fig. 26. Impedance Trajectory for a Ground Fault at m = 0.25 and Rf= 0.5

348
B. Phase Distance Unit the unit's reach (Zc) with a negative angle for loads in the
The symmetrical component network interconnection for a forward direction (export) and a positive angle for loads in the
phase-to-phase fault is shown in Fig. 27. The system parame- reverse direction (import), as illustrated in Fig. 29.
ters are the ones shown in Fig. 21. The appropriate a and b x Reverse Load Effect
vectors for the fault resistance and load flow are derived in the
appendix. This unit also exhibits a beneficial tilt due to load
flow.

Forward Load Effect

Zs1 mZL1 t IF2

(1-m)ZL1 Zr1
R

Fig. 29. Adaptive Ground Reactance Unit Characteristic

VR2 t ~

1R2 VF2 t Even with the adaptive characteristics described by the


equations derived in the appendix, there is a chance of over-
reaching. The setting T provides perfect adjustment due to
load flow and fault resistance and will adjust for the
Fig. 27. Two-Source Symmetrical Component Representation ofa Phase-to- nonhomogeneity of the negative-sequence network imped-
Phase Fault
ances. The angle T should be the difference between negative-
Fig. 28 illustrates the impedance trajectory for a Be fault. sequence current at the fault (IF2) with respect to the negative-
The expressions (85) and (86), derived in the appendix, sequence current measured at the distance-unit location (used
accurately describe the apparent impedance trajectory. to polarize the reactance line) [7].
At the element's reach (usually Zone 1 is the most critical),
27,..----------r--------------,
the expression for Tis:

T = arg ( Zsl + ZLI + zrlJ (74)


Zrl
The network in Fig. 21 illustrates the adaptability of this
element. The solution of the currents and voltages is obtained
by solving the network in Fig. 22. The fault will be located at
the end of the line (the reach of the element is also set to this
o I-- -+_ _fll--_--I'r-- - -RI
length), and a few Rf values will be used. For the network in
Fig. 21, T = -2.273.
Fig. 30 illustrates selected points used to derive the test
voltages and currents in Table VIII.

-27 1....---------........
-27 o - ----------'27
Fig. 28. Impedance Trajectory for a Phase-to-Phase Fault at m = 0.5 and
Rf= 0.5

C. Ground Reactance Element


The load and fault resistance characteristic equations are
derived in the appendix. The Vector b equation (90) deter-
mines the angle at which the reactance line tilts. The ground
R
reactance line defined by (57) and (58) is an adaptive reac-
tance line because it adjusts its tilt depending on the load flow. Fig. 30. Test Points on the Reactance Line With Different Fault Resistance
Quadrilateral distance units tend to overreach due to load flow Values
and fault resistance. The ground reactance element pivots on

349
TABLE VIII VIII. APPENDIX
TEST VOLTAGES AND CURRENTS FOR APPARENT IMPEDANCES IN FIG. 30
This section introduces how to find the distance element
Point/ characteristics on the apparent impedance plane. On this
Voltages and Currents I
ZApp plane, the graphical characteristics of the distance elements
Va = 44.94LO°, Vb = 67.81L-17.44°, can be observed, along with the influence of load and fault
pI Vc = 69.83L130.92° resistance. Only for radial networks, the ZL 1 plane is equal to
2.91
12.38L35.97° Ia = 2.9IL-29.26°, Ib = 0.83L-130.45°, the apparent impedance plane.
Ic = 1.65L134.07°
A. Positive-Sequence Polarized Ground Distance Unit
Va = 39.57LO°, Vb = 67.77L-112.93°, (Apparent Impedance Plane Forward Characteristics)
p2 Vc = 69.51L124.88°
2.99 Fig. 31 illustrates a simple two-source network and a
10.47L53.82° Ia = 2.97L-46.46°, Ib = 0.69L-137.72°,
Ic = 1.69L123.59° Phase A-to-ground fault. The ground distance unit is
characterized by (8) and (9).
Va = 41. 16LO°, Vb = 68.35L-135.53°,
p3 Vc = 68.53L101.68°
2.61
12.03L106.78° Ia = 2.57L-97.61°, Ib = 0.45L-136.83°, Zs1 ZL1 Zr1
Ic = 1.57 L89.26°
Va = 48.42LO°, Vb = 68.83L-140.44°,
p4 Vc = 68.21L97.40°
16.63L125.50° Ia = 2.I3L-115.07°, Ib = 0.51L-123.08°,
2.12
VRl t VFlt
Ic = 1.44L81.23°

VII. FINAL DISCUSSION


This paper presented a general technique to derive distance
Zs1 ZL1 t IF2
Zr1
3 Rf
elements, as well as deriving the characteristics of three dis- ~ ~
tance units. Knowing the distance element theory allows for IR2 IF1-IR1
the understanding of the units, which in turn facilitates the VR2 t VF2t
acceptance testing sequence.
The distance-unit characteristics are plotted on an imped-
ance plane. The positive-sequence impedance plane represents
the behavior of the units, and a radial system with no fault
resistance or load flow is assumed.
ZsO ZLO t IFO

ZrO

The characteristics imply faults in the forward direction. ~ ~


IRO IFO-IRO
Distance units also have characteristic plots for the reverse
direction. VRO t VFOt
When considering fault resistance and load flow, the
apparent impedance plane describes the measurement with
respect to the impedance characteristic. Fig. 31. AG Fault Symmetrical Component Network Interconnection
Mho distance elements are directional with a desirable
Returning to (8), simplify to find a more useful expression
response in the forward and reverse fault impedance character-
for 81:
istics. Memory action on these units allows for an expansion
larger than the normal expansion due to the source impedance. 81 = VRA - Zc [IRA + kcO (3IRO)] (75)
When the fault voltages are fixed and the fault current is
Equation (75) can be simplified to:
increased until the distance element trips, testing will show the
steady-state (no-memory) characteristics. Using two states 81 VA
Zcl (76)
during the testing, with the prefault state considering only [IA + kcO (310)] [IA + kcO (310)]
healthy voltages, the influence of the memory effect in dis-
tance units can be observed when the fault state is applied.
Quadrilateral distance units are composed of a reactance
unit, a resistance check unit, and a directional element. The
reactance unit presented is a circle of infinite radius. The
directional element and the resistance check of a particular
design cannot be plotted on the apparent impedance plane.
The impedance trajectories can be plotted on the apparent
impedance planes for both the ground and phase distance
units. These plots represent a measurement and not an actual
impedance.

350
Returning to (9), simplify to find a more useful expression Returning to (31), find a more useful expression for 81 :
for 82: 81 = (VRB - VRC) - Zc (IRB - IRC) (81)
82 = VRl+ VR2+ VRO- VR2- VRO
Equation (81) yields:
= VRA - VR2 - VRO (77)
81 = (VRB - VRC) Zc (82)
= VRA + Zsl IR2+ ZsO IRO
(IRB - IRC) (IRB - IRC)
82 VRa Returning to (32), find a more useful expression for 82:
IA + kcO (310) IA + kcO (310) 82= VBl- VCl+ VB2- VB2- VC2+ VC2
(83)

~+~~ ]
(78) = VB- VC- VB2+ VC2
+ZSI[

I~:=~~ zs{ ~J
1+ IR2 + ZcO ZsO
IRI Zcl Zsl
1RBS:IRC 1- (84)
The results in (76) and (78) can be used in (2) to find the a
and b vectors:
Using (82) and (84), the resulting a and b vectors are:
a = Zcl (79)
a = Zcl (85)

b=-ZSI[ ~+~~ ]
1+ IR2 + ZcO ZsO
(80)
b=-ZSI[_1] (86)
IRI Zcl Zsl 1- IAI
IA2
B. Positive-Sequence Polarized Phase Distance Unit
(Apparent Impedance Plane Forward Characteristics) C. Ground Reactance Distance Unit (Apparent Impedance
Fig. 32 is the symmetrical component network intercon- Plane Forward Characteristics)
nection of a two-source power system for a BC fault used to The reactance element is defined by (57) and (58). Finding
analyze the positive-sequence polarized phase distance unit the 81 and 82 vectors on the apparent impedance plane
defined by (31) and (32). follows:
81 VA
Zcl (87)
[IA + kcO (310)] [IA + kcO (310)]
82 = 0 VA + j IR2 e jT (88)

VR1 t VF1 t With 82, a rigorous mathematical procedure is not prac-


tical, as shown in (89).
Rf VA
82 o [IA + kcO (310)]
(89)
[IA + kcO (310)] o . IR2 e jT

Zs1 ZL1
t IF2
Zr1
+ J O[IA + kcO (310)]

The division by zero is infinity, and what matters is the


angle.

VR2 t ~
IR2
VF2 t
~
IF1-IR1
b = 00 e
-Jo[ 90-T+ang(1IAI
+ -lAO
+- ZCO)]
-
IA2 IA2 Zcl (90)

Fig. 32. BC Fault Symmetrical Component Network Interconnection

351
IX. REFERENCES
[1] 1. Roberts, A. Guzman, and E. O. Schweitzer, III, "Z=V/I Does Not
Make a Distance Relay," proceedings of the 20th Annual Western
Protective Relay Conference, Spokane, WA, October 1993. Available:
http://www.selinc.com/techpprs.htm.
[2] E. O. Schweitzer, III and 1. Roberts, "Distance Relay Element Design,"
proceedings of the 46th Annual Conference for Protective Relay
Engineers, College Station, TX, April 1993. Available:
http://www.selinc.com/techpprs.htm.
[3] W. A. Elmore, Protective Relaying Theory and Applications, New York:
Marcel Dekker, Inc., 1994.
[4] Type HZM Distance Relay, Westinghouse Electric Corporation,
Instruction Manual, I.L. 41-412.1K, May 1954.
[5] F. Calero, "Development of a Numerical Comparator for Protective
Relaying: Part I," IEEE Transactions on Power Delivery, Vol. 11, No.3,
pp.1266-1273, July 1996.
[6] D. Hou, A. Guzman, and 1. Roberts, "Innovative Solutions Improve
Transmission Line Protection," proceedings of the 24th Annual Western
Protective Relay Conference, Spokane, WA, October 1997. Available:
http://www.selinc.com/techpprs.htm.
[7] SEL-421 Reference Manual. Available: http://www.selinc.com/
instruction_manual.htm.

X. BIOGRAPHY
Fernando Calero received his BSEE in 1986 from the University of Kansas,
his MSEE in 1987 from the University of Illinois (Urbana-Champaign), and
his MSEPE in 1989 from the Rensselaer Polytechnic Institute. From 1990 to
1996, he worked in Coral Springs, Florida, for the ABB relay division in the
support, training, testing, and design of protective relays. Between 1997 and
2000, he worked for Itec Engineering, Florida Power and Light, and Siemens.
Since 2000, Mr. Calero has been an application engineer in international sales
and marketing for Schweitzer Engineering Laboratories, Inc., providing
training and technical assistance.

20081218· TP6323

352

You might also like