COUNTIS E40 / E41 MANU
537204B

Three phase kWh meter,


measure via CT 50 to 6000 A

COUNTIS E40/E41 Operating principle


This kilowatt hour meter measures the active and reactive electrical energy used in an electrical
installation.
This device has a digital LCD to display energy used and power.
This device has a total counter and a partial resettable counter.
In case of two tari levels, the COUNTIS E41 will count separetely the energy used in tari 1 and in tari 2.

Product presentation Display of readings


A LCD display. The various datas can be scrolled by pressing
B Key to scroll readings. the Key «Read».
C «Prog» key to set up the CT ratio and the type The Default display will indicate power
of network. consumption according to the current tari.
D Reset to reset the partial counter.
E Metrological LED (1 Wh = 10 impulses). COUNTIS E40:
1 1st pressure : backlight switches ON.
A Total active energy consumption (kWh).
2 2nd pressure: partial active energy
B Meter setup consumption (kWh).
3 3rd pressure: total reactive energy
C The following settings have to be made before the
consumption (kVAR).
meter can be put to use :
4 4th pressure: partial reactive energy
- CT ratio.
D consumption (kVAR).
- Type of network (single or three-phase).
5 5th pressure: instant power consumption (kW).
- Type of three-phase installation (balanced or
E unbalanced COUNTIS E41:
1. Press the Prog key during 3 sec. to enter the The COUNTIS E41 provides detailed display
setup mode. of the total/partial active energy consumptions
2. The CT ratio setting is displayed (100A). Press according to tari (T1 or T2) and in total (T).
the key «Read» repeatedly to scroll the possible
CT values (50,60,75,100,125,150,160,200,250,3
00,400,500,600,700,750,800,1000,1200,1250,1 To reset the partial meter
500,1600,2000,2500,3000,4000,5000,6000A). - Press the scrolling key several times in order
3. Press «Prog» to conrm and switch to the next to display partial energy.
setting. - Press the reset button during 3 sec.
4. The type of network (1L+N, 2L, 3L, 3L+N) is The partial meters (active and reactive energy)
displayed. Press the key «Read» repeatedly to will be set to zero.
scroll the possible values and select the type of
network. ERROR message:
5. Press «Prog» to conrm and switch to the next In case of bad wiring, an «ERROR» message
setting. will be displayed.
6. On three-phase installations, the type of - Check for each phase that current (I1, I2, I3)
installation is displayed as «Balanced/ and voltage (L1, L2, L3) are measured on the
Unbalanced» (Bl, Unbl). Press the key «Read» right phase.
to scroll the values and select the type of - Check the correct wiring of the product (L/N).
installation.
Note :
7. Press «Prog» to conrm.
The information on the display indicates
8. Press the Prog key during 3 sec. to exit the
that the corresponding phase (1, 2,3) is under
programming mode.
voltage. The information is available only when
the neutral is connected.

T1/T2 *
+ - U1 U2 U3 N Technical specifications
Metrological characteristics -C  haracteristic of tari input COUNTIS E41:
- Accuracy class B (1%) according to EN50470-3 tari 1 = 0 V, tari 2 = 230 VAC +/- 15%
4 6 8 10 12 14 16 2 - Metrological LED: - Impulse output characteristics:
1 pulse = 0.1Wh current transformer ratio • 1 pulse: 100 Wh
e.g. in a installation with a 100/5A C.T., • Pulse duration: 100 ms
1 pulse = 0.1Wh /20 pulses = 2Wh • External supply: 20 ... 30 VDC
- Starting current: 10 mA
- Basic current: 5 A Mechanical characteristics
- Max current: 6 A -M  odular casing 4 M (72 mm)
-P  rotection degree (casing) : IP20
1 3 5 7 9 11 Technical characteristics -P  rotection degree noze: IP50/IK03
- Consumption: < 0,6 W et 2,8 VA max per phase - Insulation class: II
- Supply: 230/400 VAC +/- 15%
- Frequency: 50/60 Hz +/- 2 Hz Environment
S1 S2 S1 S2 S1 S2 -S
 torage temperature: -25 °C to +70 °C
- Savings of measures are made regularly and in
case of power failure in EEPROM -W
 orking temperature: -10 °C to +55 °C
L1 L1 -C
 onnection capacity:
Note: • exible: 1 à 6 mm2
L2 L2
in a unbalanced network, please connect 1 C.T. • rigid: 1,5 à 10 mm2
L3 L3 for each phase. If the installation settings is
related to a "balanced network", 1 C.T. on the
N N
phase 1 has to be connected.
* COUNTIS E41