User instructions

COUNTIS E40/E41 GB Three phase kWh meter,


measure via CT 50 to 6000 A
Operating principle
This kilowatt hour meter measures the active and reactive electrical energy used in an electrical
installation.
This device has a digital LCD to display energy used and power.
This device has a total counter and a partial resettable counter.
In case of two tariff levels, the COUNTIS E41 will count separetely the energy used in tariff 1 and in tariff 2.

Product presentation Display of readings


A LCD display. The various datas can be scrolled by pressing
B Key to scroll readings. the Key "Read".
A The Default display will indicate power
C "Prog" key to set up the CT ratio and the type of consumption according to the current tariff.
network.
COUNTIS E40 :
B D Reset to reset the partial counter.
1 1 st pressure : backlight switches ON.
E Metrological LED (1 Wh = 10 impulses). Total active energy consumption (kWh).
C
2 2 nd pressure : partial active energy
D Meter setup consumption (kWh).
3 3 rd pressure : total reactive energy
The following settings have to be made before the consumption (kVAR).
E meter can be put to use : 4 4 th pressure : partial reactive energy
- CT ratio. consumption (kVAR).
- Type of network (single or three-phase).
- Type of three-phase installation (balanced or 5 5 th pressure : instant power consumption
unbalanced). (kW).
1. Press the Prog key during 3 sec. to enter the set- COUNTIS E41 :
up mode. The COUNTIS E41 provides detailed display of the
2. The CT ratio setting is displayed (100A). Press total/partial active energy consumptions accor-
the key "Read" repeatedly to scroll the possible ding to tariff (T1 or T2) and in total (T).
CT values (50, 100, 150, 200, 250, 300, 400, 600,
800… 6000A).
3. Press "Prog" to confirm and switch to the next To reset the partial meter
setting. - Press the scrolling key several times in order
4. The type of network (1L+N, 2L, 3L, 3L+N) is to display partial energy.
displayed. - Press the reset button during 3 sec.
Press the key "Read" repeatedly to scroll the The partial meters (active and reactive energy)
possible values and select the type of network. will be set to zero.
5. Press "Prog" to confirm and switch to the next ERROR message :
setting. In case of bad wiring, an "ERROR" message
6. On three-phase installations, the type of installa- will be displayed.
tion is displayed as "Balanced/Unbalanced" (Bl, - Check for each phase that current (I1, I2, I3)
Unbl). and voltage (L1, L2, L3) are measured on the
Press the key "Read" to scroll the values and right phase.
select the type of installation. - Check the correct wiring of the product (L/N).
7. Press "Prog" to confirm. Note :
8. Press the Prog key during 3 sec. to exit the The information on the display indicates
programming mode. that the corresponding phase (1, 2,3) is under
voltage.
T1/T2 *
+ - U1 U2 U3 N

Technical specifications
Metrological characteristics
4 6 8 10 12 14 16 2 - Characteristic of tariff input COUNTIS E41 :
- Accuracy class B (1%) according to EN50470-3
- Metrological LED : tariff 1 = 0 V, tariff 2 = 230 V +/- 15%
1 pulse = 0.1Wh current transformer ratio - Impulse output characteristics :
e.g. in a installation with a 100/5A C.T., • 1 pulse : 100 Wh
1 pulse = 0.1Wh /20 pulses = 2Wh • Pulse duration : 100 ms
- Starting current : 10 mA • External supply :20 ... 30 V
- Basic current : 5 A
- Max current : 6 A Mechanical characteristics
1 3 5 7 9 11 Technical characteristics - Modular casing 4 M (72 mm)
- Protection degree (casing) : IP20
- Consumption: < 0,6 W et 2,8 VA max per phase - Protection degree noze : IP50/IK03
- Supply : 230/400 V +/- 15% - Insulation class : II
S1 S2 S1 S2 S1 S2 - Frequency : 50/60 Hz +/- 2 Hz
- Savings of measures are made regularly and in Environment
L1 L1 case of power failure in EEPROM
- Storage temperature : -25 °C to +70 °C
L2 L2 Note: - Working temperature : -10 °C to +55 °C
in a unbalanced network, please connect 1 C.T. - Connection capacity :
L3 L3 for each phase. • flexible : 1 à 6 mm 2
if the installation settings is related to a • rigid : 1,5 à 10 mm 2
N N "balanced network", 1 C.T. on the phase 1 has to be
connected
* COUNTIS E41
INTERNATIONAL SALES DEPARTMENT SOCOMEC 1, rue de Westhouse -B.P. 60010 F-67235 Benfeld Cedex - FRANCE Tel. +33 (0)3 88 57 41 41 - Fax +33 (0)3 88 74 08 00
HEAD OFFICE SOCOMEC GROUP S. A. SOCOMEC capital 11 302 300 € R.C.S. Strasbourg B 548 500 149 B.P. 1,rue de Westhouse F-67235 Benfeld Cedex - FRANCE
537204A 11.2009 PAPIER BLANC 70GR PLIAGE 70X75 (marque, nom, vignette en couverture) Web: www.socomec.com