Professional Documents
Culture Documents
2 Index
Sheet-no.
1 Test Report ............................................................................................................................................... 1
2 Index ......................................................................................................................................................... 2
3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9 .................................................................... 3
4 Drawing of surge arrester body ................................................................................................................ 4
5 Residual voltage tests .............................................................................................................................. 5
5.1 Lightning current impulse residual voltage test (waveform 2/4µs) on single metal-oxide resistors ....5
5.2 Lightning current impulse residual voltage test (waveform 8/20µs) on single metal-oxide
resistors ............................................................................................................................................... 8
5.3 Lightning current impulse residual voltage test (waveform 8/20µs) on SVU ....................................10
5.4 High current impulse residual voltage test ........................................................................................12
5.5 Photographs of test samples (single metal-oxide resistors) .............................................................14
6 Lightning surge operating duty test ........................................................................................................ 15
6.1 Calculation of rated voltage ...............................................................................................................15
6.2 5 impulses +10kA, 8/20µs and simultaneously Ur.............................................................................15
6.3 5 impulses -10kA, 8/20µs and simultaneously Ur .............................................................................20
6.4 Lightning impulse residual voltage measurement at 10kA, 8/20µs ...................................................26
6.5 Oscillograms of the lightning impulse residual voltage .....................................................................26
6.6 Photographs of test samples (single metal-oxide resistors) .............................................................27
7 Technical data of test circuits ................................................................................................................. 28
7.1 Steep current impulse residual voltage test ......................................................................................28
7.2 Lightning impulse residual voltage test on single metal-oxide resistors ...........................................29
7.3 Lightning impulse residual voltage test on complete arrester ...........................................................30
7.4 High current impulse test...................................................................................................................31
7.5 Lightning surge operating duty test ...................................................................................................32
Report No.: HBA 11483 P Sheet: 3
The residual voltage tests (lightning current impulse and high current impulse) were performed on three
typical arrester sections (1 metal-oxide resistor). Additionally the lightning current impulse residual voltage
test with 10kA, 8/20µs has also been carried out on three units (bodys) of SVU 3EV5 144-0LK12-4ZZ9.
According to the KEPCO technical specification, clause 8.1.7 all measured residual voltage values shall
be below the maximum values for one complete SVU (consisting of two units):
5.1 Lightning current impulse residual voltage test (waveform 2/4µs) on single metal-oxide
resistors
The lightning current impulse residual voltage test (waveform 2/4µs) was performed with a current peak
value of 10kA (test circuit see sheet-no. 28).
I Ures Waveform
Sample no. / kA / kV T1 / T2
The tolerances of the specified values for exponential impulse currents are listed in the following table
(according to IEC 62475 (2010):
Report No.: HBA 11483 P Sheet: 6
To determine inductive effects of the voltage measuring circuit a current impulse equal to the discharge
current was applied to a metal block having the same dimensions as the samples. Because the peak
voltage on the metal block was less than 2 % of the peak voltage of the resistor samples, no inductive
correction to the resistor measurements was required.
The maximum lightning current impulse residual voltage for the given complete SVU is calculated from
the lightning current impulse residual voltage of the single metal-oxide resistor multiplied by the scale
factor plus a calculated inductive voltage drop across the complete SVU according IEC 60099-8, clause
8.3.2, procedure b).
fscale = 12 / 1
Ures, sample, max = 15.50kV
L’ = 1µH / m
H = 0.51m
Id = 10kA
Tf = 2µs
The test is passed: The measured residual voltage value of 377kV was lower than the corresponding
maximum specified values for the complete arrester set of 420kV at rated discharge current (10kA,
2/20µs).
5.2 Lightning current impulse residual voltage test (waveform 8/20µs) on single metal-oxide
resistors
The lightning current impulse residual voltage test (waveform 8/20µs) was performed with a current peak
value of 10kA (test circuit see sheet-no. 29).
)
I Ures 1 Waveform Ratio between
The tolerances of the specified values for exponential impulse currents are listed in the table on sheet-no.
5.
5.3 Lightning current impulse residual voltage test (waveform 8/20µs) on SVU
The lightning current impulse residual voltage test (waveform 8/20µs) was performed with a current peak
value of 10kA (test circuit see sheet-no. 30).
)
I Ures 1 Waveform Calculated for
For calculation of the residual voltage at U10kA, 2/20µs the evaluated ratio of f2µs/8µs = 1.046 was used (see
sheet-no. 8). The tolerances of the specified values for exponential impulse currents are listed in the table
on sheet-no. 5.
The test is passed: The maximum residual voltage value of 183.6kV was lower than the corresponding
maximum specified value for the unit of SVU 3EV5 0144-0LK12-4ZZ9 of 420kV/2 = 210kV at rated
discharge current (10kA, 2/20µs).
The high current impulse residual voltage test (waveform 4/10µs) was performed with a current peak
value of 30kA (test circuit see sheet-no. 31).
)
I Ures 1 Waveform
Sample no. / kA / kV T1 / T2
The tolerances of the specified values for exponential impulse currents are listed in the table on sheet-no.
5.
The maximum high current impulse residual voltage for the given complete SVU is calculated from the
lightning current impulse residual voltage of the single metal-oxide resistor multiplied by the scale factor
plus a calculated inductive voltage drop across the complete SVU according IEC 60099-8, clause 8.3.2,
procedure b).
fscale = 12 / 1
Ures, sample, max = 18.15kV
L’ = 1µH / m
H = 0.51m
Id = 30kA
Tf = 4µs
The test is passed: The measured residual voltage value of 443.3kV was lower than the corresponding
maximum specified values for the complete arrester set of 470kV at maximum discharge current (30kA,
4/10µs).
Pass criteria were fulfilled: All measured residual voltage values were lower than the corresponding
maximum specified values for the complete arrester set (consisting of 2 units):
The lightning surge operating duty test was carried out on single metal-oxide resistors (test circuits see
sheet-nos. 29 and 32). While the test samples were energized at rated voltage five nominal discharge
current impulses with waveform 8/20µs were applied 15 ± 15 electrical degrees before the positive peak
of the voltage. Within 10 minutes after the last positive nominal discharge current five more nominal
discharge current impulses with negative peak value were applied 15 ± 15 electrical degrees before the
negative peak of the voltage. The interval between the impulses was 1 minute.
Before and after the test the residual voltage at nominal discharge current 10kA, 8/20µs was measured.
The tolerances of the specified values for exponential impulse currents are listed in the table on sheet-no.
5.
The test is passed: After the test visual inspection of the metal-oxide resistors revealed no evidence of
puncture, flashover or cracking. Change of the residual voltages of all three test samples was far below
the allowed 5%.
Pass criteria were fulfilled: Before and after the test, the residual voltage at nominal discharge current
was measured. The changes between these two measurements was below 5 %.
Inductance µH 1.6
H
CS
I
L Rd TS U1
RSH
TG
RL Re
U2
Uc
Current measurement: i
Shunt RSH = 2.00mΩ (calibration valid until 11/2014)
Oscilloscope Tektronix type TDS 3034C (calibration valid until 11/2014) / PC
Inductance µH 12
L
Uc TG
TS RH
Cs
RSH RN
( Ushunt ) ( RN / (RN+RH)*Ures.OSC )
Voltage measurement: u
Ohmic divider: RH = 3994Ω (calibration valid until 08/2014)
RN = 61.0Ω (calibration valid until 03/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC
Current measurement: i
Shunt RSH = 40.38mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC
Inductance µH 150
L
Uc TG
TS
CH
Cs
CN
RSH
i u
Voltage measurement: u
Capacitive divider: CH = 1.537nF, CN = 1.849µF (calibration valid until 07/2018)
Probe 10:1, Oscilloscope Tektronix TDS 3034 (calibration valid until 01/2015) / PC
Current measurement: i
Shunt RSH = 40.14mΩ (calibration valid until 09/2014)
Probe 10:1, Oscilloscope Tektronix TDS 3034 (calibration valid until 01/2015) / PC
Inductance µH 1
L
Uc TG
TS RH
Cs
RSH RN
i u
Voltage measurement: u
Ohmic divider: RH = 4394Ω (calibration valid until 04/2014)
RN = 61.0Ω (calibration valid until 03/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC
Current measurement: i
Shunt RSH = 10.54mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC
Inductance µH 12
L
Uc BG
TG
SG CH
Cs
RT Tr
TS
CN
RSH2
RSH1
i1 u i2
TG ... Trigger spark gap Tr ... Transformer: 20kV, 12kVA
TS ... Test sample RT ... Trigger resistor
Cs ... Surge capacitor BG ... Blocking gap
L ... Inductance SG ... Spark gap
Uc ... Charge voltage
Voltage measurement: u
Capacitive divider: CH = 256pF, CN = 256nF (calibration valid until 06/2014)
Oscilloscope Tektronix type TDS 3034 (calibration valid until 09/2014) / PC
Rated frequency 60 Hz
5 Vibration test
Date of test: 24.02.2014
Test facility: E T HP AR R&D Ü6b (reference voltage test)
E T HP BSS LAB ME (vibration test)
The vibration test was performed on three complete arrester units (test sample # 26, # 29 and # 31). After
the initial measurements - insulation resistance test (1000V) and reference voltage test (test circuit see
sheet no. 44) - the test samples were exposed to an acceleration of 0.1 g for 500,000 times at its natural
frequency.
Prior to the test itself, the frequency response was determined by a frequency scan. The natural
frequency of the test samples was determined:
natural
Sample-no.
frequency
# 26 40 Hz
# 29 39 Hz
# 31 35 Hz
Depending on this natural frequency, the testing time was calculated: t = 500,000 / (natural frequency)
# 26 12500s
# 29 12821s
# 31 14286s
After that, the insulation resistance (1000V) and reference voltage was measured again.
The arrester unit was fixed with the bottom flange to the vibration table. An acceleration sensor was
installed on both sides of the arrester. The one on the free end of the arrester was removed before the
vibration test; it was only installed to determine the natural frequency.
Report No.: HBA 11496 P Sheet: 6
Pass criteria were fulfilled: There were no change in the appearance and structure of the arrester,
dielectric resistance and the change of action start voltage was within 5% before and after test.
Report No.: HBA 11496 P Sheet: 11
6 Tensile test
Date of test: 24.02.2014 -25.02.2014
Test facility: E T HP AR R&D Ü1/1
The tensile test was performed on three complete arrester units (test samples # 8, #12, #23). The test
sample was mechanically loaded with a tensile force greater than 882 N for more than 60 s.
The arrester unit was fixed horizontally with the bottom flange to the test assembly. The load was applied
by a hydraulic cylinder and measured with a force sensor. Additionally, the elongation was measured by a
distance sensor.
The bending moment test was performed on three complete arrester units and according to paragraph
10.8.9 of IEC 60099-4 with one terminal of the arrester fixed and the other terminal apply to a bending
load of 882N for a duration of 60 s. Thereafter all three test samples were immersed in a vessel, in boiling
3
deionized water with 1 kg/m of NaCl, for 42 h. At the end of the boiling, the arrester was kept in the
vessel until the water had cooled down to 50°C first and then to ambient temperature. For test evaluation
the internal partial discharge test, the measurement of watt losses and the residual voltage measurement
at 10 kA, 8/20µs were performed before and after test.
The samples (# 2, #9, #10) were subjected to a bending moment test with a bending load of 882N within
30 to 60 s. When the test load was reached, it was maintained for 60 s to 90 s. The force was applied by
a hydraulic cylinder and measured by a force transducer. The deflection was measured by a string
potentiometer. After releasing the bending moment the residual deflection was measured over 600 s. The
arrester unit was fixed horizontally with the bottom flange to the test assembly. The load was applied by a
hydraulic cylinder and measured with a force sensor. Additionally, the elongation was measured by a
distance sensor.
Report No.: HBA 11496 P Sheet: 18
The watt losses were measured at continuous operating voltage (test circuit see sheet-no. 44).
Test result: Passed. The change in watt losses was below the required value.
The partial discharge level was measured at 1.05 times the continuous operating voltage before and after
the test (test circuit see sheet-no. 44). The noise level was 0.1 pC.
Test result: Passed. The partial discharge level was below the required level.
Report No.: HBA 11496 P Sheet: 25
The residual voltage was measured at a discharge current of 10 kA, 8/20 µs (test circuit see sheet-no.45).
After the test two successive impulses (50 ... 60 s) at nominal discharge current 10kA were applied.
∆U / %
st
Before the test After test (1 impulse)
Unit-no.
(sample) Waveform Waveform
U / kV I / kA U / kV I / kA ∆U / % required
T1/T2 T1/T2
#2 174.9 10.1 7.4/18.1 174.5 10.0 7.4/18.1 -0.23 ≤5
#9 175.4 10.1 7.4/18.2 173.8 10.1 7.8/18.2 -0.91 ≤5
#10 174.9 10.0 7.4/18.1 175.1 10.0 7.4/18.1 0.11 ≤5
∆U / %
nd
After test (2 impulse)
Unit-no.
(sample) Waveform
U / kV I / kA ∆U / % required
T1/T2
#2 175.2 10.0 7.4/18.2 0.40 ≤5
#9 175.7 10.0 7.4/18.2 1.09 ≤5
#10 176.3 10.1 7.4/18.2 0.69 ≤5
Test result: Passed. The change in residual voltage was below the required value.
Report No.: HBA 11496 P Sheet: 26
Before and after the residual voltage test with two successive impulses the reference voltage was
measured (test circuit see sheet-no. 44).
∆U / %
st nd
Before the 1 impulse After the 2 impulse
Unit-no. (sample) Uref / kV Iref / mA Uref / kV Iref / mA ∆U / % required
#2 67.6 1.0 68.0 1.0 +0.6 ≤2
#9 67.8 1.0 67.9 1.0 +0.1 ≤2
#10 68.1 1.0 68.4 1.1 +0.4 ≤2
7.4.3 Internal partial discharge test, watt losses measurement, reference voltage
measurement
Report No.: HBA 11496 P Sheet: 31
The moisture ingress test was performed on three complete arrester units (test sample # 14, #15, #30).
After initial measurements - consisting of a measurement of the watt losses, a partial discharge test and a
residual voltage test at 10 kA 8/20µs - the test samples were first mechanically preconditioned with the
specified terminal torque for a duration of 30 s and then thermo mechanically preconditioned with the
specified continuous cantilever load. The thermo-mechanical preconditioning was performed by
submitting the test samples to a permanent specified long term load (SLL) in four directions and thermal
variations according to the following sequence and temperature values:
After the thermo mechanical preconditioning all three test samples were immersed in a vessel, in boiling
deionized water with 1 kg/m3 of NaCl, for 42 h. At the end of the boiling, the arresters were kept in the
vessel until the water had cooled down to 50°C first and then to ambient temperature. For verification, all
initial measurements were repeated.
Report No.: HBA 11496 P Sheet: 33
Terminal torque preconditioning was carried with torque moment of 50Nm on all test samples # 14, #15,
#30.
Test samples # 14, #15 and #30 were submitted to the specified long-term load (SLL) of 617 N in four
directions and in thermal variations of + 60 °C, - 25 °C, + 45 °C and - 40 °C.
Report No.: HBA 11496 P Sheet: 34
The watt losses were measured at continuous operating voltage (test circuit see sheet-no. 44).
Test result: Passed. The change in watt losses was below the required value.
The partial discharge level was measured at 1.05 times the continuous operating voltage before and after
the test (test circuit see sheet-no. 44). The noise level was 0.1 pC.
Test result: Passed. The partial discharge level was below the required level.
Report No.: HBA 11496 P Sheet: 39
The residual voltage was measured at discharge current of 10 kA, 8/20 µs (test circuit see sheet-no.45).
After the test two successive impulses (50 ... 60 s) at nominal discharge current 10kA were applied.
∆U / %
st
Before the test After test (1 impulse)
Unit-no.
(sample) Waveform Waveform
U / kV I / kA U / kV I / kA ∆U / % required
T1/T2 T1/T2
# 14 173.7 10.1 7.4/18.1 173.3 10.1 7.9/18.1 -0.23 ≤5
#15 175.0 10.1 7.4/18.2 174.4 10.1 7.7/18.2 -0.34 ≤5
#30 174.4 10.1 7.4/18.1 174.3 10.1 7.6/18.1 -0.06 ≤5
∆U / %
nd
After test (2 impulse)
Unit-no.
(sample) Waveform
U / kV I / kA ∆U / % required
T1/T2
# 14 175.9 10.1 7.6/18.2 1.50 ≤5
#15 176.3 10.0 7.5/18.2 1.09 ≤5
#30 175.8 10.0 7.6/18.2 0.86 ≤5
Test result: Passed. The change in residual voltage was below the required value.
Report No.: HBA 11496 P Sheet: 40
Before and after the residual voltage test with two successive impulses the reference voltage was
measured (test circuit see sheet-no. 44).
∆U / %
st nd
Before the 1 impulse After the 2 impulse
Unit-no. (sample) Uref / kV Iref / mA Uref / kV Iref / mA ∆U / % required
# 14 67.2 1.0 67.7 1.0 +0.7 ≤2
#15 68.1 1.0 68.0 1.0 -0.1 ≤2
#30 67.5 1.0 67.8 1.0 +0.4 ≤2
8.4.2 Photograph of Internal partial discharge test, watt losses measurement, reference
voltage measurement
- The internal partial discharge measured at 1.05 times Uc did not exceed 10 pC
- The increase in watt losses, measured at Uc and at ambient temperature was not more than 20%
- Change of residual voltage measured was not more than 5 % different from the initial
- The difference in voltage between two successive impulses at nominal discharge current did not
exceed 2 %, and the oscillograms of voltage and current did not reveal any partial or full
breakdown of the test sample.
Report No.: HBA 11496 P Sheet: 44
9.1 Internal partial discharge test, watt losses measurement, reference voltage
measurement
TS
C
CM
Tr
ZM
AC PD
RSH
u PDLevel i
Tr ... Transformer
TS ... Test sample
Voltage measurement: u
Capacitive divider: CH = 0.62nF, CN = 29µF (calibration valid until 04/2014)
GLP3
Inductance µH 150
L
Uc TG
TS
CH
Cs
CN
RSH
i u
Voltage measurement: u
Capacitive divider: CH = 1.537nF, CN = 1.849µF (calibration valid until 07/2018)
Probe 10:1, Oscilloscope Tektronix TDS 3034 (calibration valid until 01/2015) / PC
Current measurement: i
Shunt RSH = 40.14mΩ (calibration valid until 09/2014)
Probe 10:1, Oscilloscope Tektronix TDS 3034 (calibration valid until 01/2015) / PC
2 Index
Sheet-no.
1 Test Report ............................................................................................................................................... 1
2 Index ......................................................................................................................................................... 2
3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9 .................................................................... 3
4 Participants of Tests ................................................................................................................................. 4
4.1 Observer: ............................................................................................................................................. 4
4.2 Test engineer: ..................................................................................................................................... 4
5 Dimensional drawings .............................................................................................................................. 5
5.1 Arrester body ....................................................................................................................................... 5
5.2 Arrester accessories (arrester set) ...................................................................................................... 6
6 Visual and structure inspection .............................................................................................................. 10
6.1 Test result Body (based on 8.1.1 KEPCO Specification ITT) ...........................................................10
6.2 Test result Arrester Set (based on 8.2.1 KEPCO Specification ITT) ................................................10
6.3 Photograph of test samples (accessory parts) ..................................................................................11
7 Insulation resistance test ........................................................................................................................ 12
7.1 Test result ..........................................................................................................................................12
7.2 Photographs of test setup .................................................................................................................12
8 Leakage current test............................................................................................................................... 13
8.1 Test result ..........................................................................................................................................13
9 Reference voltage test ........................................................................................................................... 14
9.1 Test result ..........................................................................................................................................14
10 Internal partial discharge test ................................................................................................................. 16
10.1 Internal partial discharge test ............................................................................................................16
11 Discharge withstand current rating test .................................................................................................. 16
11.1 Test results ........................................................................................................................................16
11.2 Photographs of test samples .............................................................................................................21
12 Follow Current Interruption test .............................................................................................................. 22
12.1 Test conditions ..................................................................................................................................22
12.2 Test procedure ..................................................................................................................................23
12.3 Test results ........................................................................................................................................24
13 Technical data of test circuits ................................................................................................................. 35
13.1 Internal partial discharge test, leakage current test, reference voltage measurement .....................35
13.2 Discharge withstand current rating test, Lightning impulse residual voltage test .............................36
13.3 Discharge withstand current rating test, high current impulse test ...................................................37
13.4 Follow current interruption test ..........................................................................................................38
Report No.: HBA 11501 P Sheet: 3
4 Participants of Tests
4.1 Observer:
5 Dimensional drawings
5.2.2 Electrode
Report No.: HBA 11501 P Sheet: 8
MA_D
Report No.: HBA 11501 P Sheet: 9
Appearance and structure of each part of the arrester accessory and bodies have been inspected and the
dimensions have been checked with a slide gauge (500-123UCD15B, calibration valid until 11/14). The
results of the inspection can be seen in the table below. For the dimension indications (EA_A etc.) please
see the attached drawings on sheet no. 5 to 8.
Measured Measured
Body part Required Value Tolerance Measured value
value value
(Drawing No.) / mm / mm / mm
/ mm / mm
(802-61398) #17 #32 #33
-5.3
EA_A 510 510 510 510
+0.7
Pass criteria was fulfilled: The results of the inspection was satisfactory.
6.2 Test result Arrester Set (based on 8.2.1 KEPCO Specification ITT)
Pass criteria was fulfilled: The results of the inspection was satisfactory.
The insulation resistance between both terminals of the arrester body was measured with a 1000V
Megger.
Insulation resistance
Sample
/ Ohm
#17 1.8T
#32 1.7T
#33 1.6T
Pass criteria was fulfilled: The results were higher than 2000 MΩ .
The voltage of peak operation voltage (170kv/√3 / 2) was applied between the arrester body terminals
and the leakage current in a stable condition measured (test circuit see sheet-no. 35).
Pass criteria: Total leakage current Itotal shall be 0.5 mA or less and the resistant leakage current
Iresistive shall be 100 µA or less.
Sample / kVrms / mA / µA
Pass criteria were fulfilled: Total leakage current Itotal was less than 0.5 mA and the resistant leakage
current Iresistive was less than 100 µA.
The reference voltage test was carried out according to paragraph 7.2 of IEC 60099-4. An AC voltage
was applied to the test samples and was increased until the reference current of 1.0 mA was flowing. The
reference voltage Uref,1.0mA was calculated by dividing the voltage peak value by √2. The corresponding
reference voltage at 1 A peak current was calculated from the reference voltage Uref,1.0mA and the voltage-
current characteristic of the arrester according to the following formula (the factor between the reference
voltage at 1.0 mA and 1 A is 1.15): û1A = Uref,1.0mA *√2*nunits*1.15 (test circuit see sheet-no. 35).
Pass criteria: ûref1A ≥ 204kVp (two units in series) equal Uref,1.0mA unit ≥ 62.7 kV
The test was performed on three complete arrester units based on paragraph 8.8 of IEC 60099-4 (Internal
partial discharge test). The partial discharge test was performed at a test voltage of 52.5 kV (= 1.05*Uc*)
on complete arrester units. First the power frequency voltage was increased up to the complete arrester
unit equivalent rated voltage (Ur*) of 62.5 kV. Thereafter the voltage was decrease within 10s to the test
voltage of 52.5 kV and the partial discharge level was measured.
The partial discharge level was measured at 1.05 times the continuous operating voltage before and after
the test (test circuit see sheet-no. 35). The noise level was 0.06 pC.
Pass criteria was fulfilled: The internal partial discharge level did not exceed 10 pC
The discharge withstand current rating test was carried out on three single metal-oxide resistors (test
circuits see sheet-nos. 22 to 37). The test was performed at a maximum discharge current at 30kA,
4/10µs with one positive and one negative impulse. The time between both impulses was 5 minutes.
Before and after the test the residual voltage at nominal discharge current 10kA, 8/20µs was measured.
)
I Ures 1 Waveform
Sample no. / kA / kV T1 / T2
)
I Ures 1 Waveform
Sample no. / kA / kV T1 / T2
Tolerances of the specified values for exponential impulse currents are listed in the following table
(according to IEC 62475 (2010):
All Pass criteria were fulfilled: After the test visual inspection of the metal-oxide resistors revealed no
evidence of puncture, flashover or cracking. Change of the residual voltages of all three test samples was
far below the allowed 5%.
Background: During the follow current interruption test, the externally gapped line arrester (EGLA) has to
show that it has the capability to cut off the follow current after a sparkover due to lightning.
According to the technical specification of KEPCO, the sample has to be under contaminated condition.
Five impulses of lightning voltage have to be applied for each positive and negative polarity and the cutoff
time has to be lower than 1/2 cycle of power frequency. The required AC voltage is 170/√3 = 98.1 kVeff.
Drawing see sheet no. 9
Ambient conditions:
Prior to the test, the silicone surface of the arrester bodies (samples #3 and #21) have been abraded to
roughen their surface. To remove the hydrophobicity of the silicone, kaolin powder has been applied
thoroughly on the whole arrester surface, see photo 12.1.1. This treatment leads to a complete wetting of
the arrester surface when applying the contaminant solution.
The contaminant solution has been prepared according to IEC 60507, clause 13.2 with a salt deposit
density (SDD) of 0.5 mg/cm2, corresponding to a volume conductivity of the contaminant solution of
200 mS/cm. The solution prepared for the test had a volume conductivity of 206 mS/cm
Prior to the test itself, the arresters with the applied kaolin have been mounted to the insulator device and
the gap distances have been adjusted to the specified values (630 mm). Besides the surface treatment,
all components were in a factory new condition and completely assembled as in service.
After installation, the arresters have been sprayed with the contaminant solution, wetting the whole
silicone surface.
After that, the AC voltage has been raised up to the specified value of 98.1 kVeff and the lightning
impulses were applied. For each test, the voltage and current of the test sample have been measured.
All Pass criteria were fulfilled: The test object has passed the follow current interrupting test without
any objection. For each test, including five tests with positive and five with negative polarity, the follow
current cutoff time was far below the required value of 1/2 cycle of the power frequency. The results are
displayed in the following table and the oscillograms on sheets no. 25 to 30.
Applied Applied
polarity
AC lightning cutoff time
Test no. of AC
voltage voltage / ms
voltage
/ kVeff / kVp
POS 1 100 + 900 positive < 1 ms
POS 2 100 + 900 positive < 1 ms
POS 3 100 + 900 positive < 1 ms
POS 4 100 + 900 positive < 1 ms
POS 5 100 + 900 positive < 1 ms
TS
C
CM
Tr
ZM
AC PD
RSH
u PDLevel i
Tr ... Transformer
TS ... Test sample
Voltage measurement: u
Capacitive divider: CH = 0.62nF, CN = 29µF (calibration valid until 04/2014)
GLP3
13.2 Discharge withstand current rating test, Lightning impulse residual voltage test
Inductance µH 12
L
Uc TG
TS RH
Cs
RSH RN
( Ushunt ) ( RN / (RN+RH)*Ures.OSC )
Voltage measurement: u
Ohmic divider: RH = 3994Ω (calibration valid until 08/2014)
RN = 61.0Ω (calibration valid until 03/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC
Current measurement: i
Shunt RSH = 40.38mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC
13.3 Discharge withstand current rating test, high current impulse test
Inductance µH 1
L
Uc TG
TS RH
Cs
RSH RN
i u
Voltage measurement: u
Ohmic divider: RH = 4394Ω (calibration valid until 04/2014)
RN = 61.0Ω (calibration valid until 03/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC
Current measurement: i
Shunt RSH = 10.54mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC
TO
GT
CH1 CH2 CH3
T
AP RD
kV
CS
A
CL1 CL2 CL3
M1 Rsh
kV
M2
T Transformer
AP Protective arrester
L Induction coil (48 mH)
GA Auxiliary gap (rod – rod; 900 mm)
CS Surge capacitance
R F, R F* Front resistance
RD Discharge resistance
GT Trigger gap
Measuring device:
2 Index
Sheet-no.
1 Test Report ................................................................................................................................................. 1
2 Index ........................................................................................................................................................... 2
3 Technical data of the test object ................................................................................................................. 3
4 Drawings of test object ............................................................................................................................... 4
5 Radio interference voltage (RIV) and visible corona test on arrester set ................................................... 6
5.1 Participants of test............................................................................................................................... 6
5.2 Test conditions .................................................................................................................................... 6
5.3 Test results .......................................................................................................................................... 8
5.4 Photos of test object and test circuit .................................................................................................10
5.5 Circuit diagram (Radio interference voltage test) .............................................................................11
6 Power frequency withstand voltage test on arrester set ........................................................................... 12
6.1 Participants of test.............................................................................................................................12
6.2 Test conditions ..................................................................................................................................13
6.3 Test results ........................................................................................................................................14
6.4 Photos of test object and test circuit .................................................................................................15
6.5 Circuit diagram (Power frequency withstand voltage test)................................................................16
7 Switching overvoltage test on arrester set ................................................................................................ 17
7.1 Participants of test.............................................................................................................................17
7.2 Test conditions ..................................................................................................................................17
7.3 Test results ........................................................................................................................................19
7.4 Photos of test object and test circuit .................................................................................................21
7.5 Circuit diagram (Switching overvoltage test).....................................................................................22
8 Lightning impulse insulation coordination test on arrester set .................................................................. 23
8.1 Participants of test.............................................................................................................................23
8.2 Test conditions ..................................................................................................................................23
8.3 Test Results ......................................................................................................................................24
8.4 Circuit diagram (Lightning impulse insulation coordination test).......................................................27
9 Lightning impulse withstand voltage test on body .................................................................................... 28
9.1 Participants of test.............................................................................................................................28
9.2 Test conditions ..................................................................................................................................28
9.3 Test results ........................................................................................................................................29
9.4 Photos of test object..........................................................................................................................29
9.5 Circuit diagram ..................................................................................................................................29
10 Power frequency withstand voltage test on body ..................................................................................... 30
10.1 Participants of test.............................................................................................................................30
10.2 Test conditions ..................................................................................................................................30
10.3 Test results ........................................................................................................................................31
10.4 Photos of test object..........................................................................................................................31
10.5 Circuit diagram ..................................................................................................................................31
Report No.: HBA 11505 P Sheet: 3
Rated frequency 60 Hz
5 Radio interference voltage (RIV) and visible corona test on arrester set
Date and place of test March 6, 2014 Technical University Darmstadt,
High Voltage Test Laboratory
Observers:
Test engineer:
All components were in a factory new condition and completely assembeled as in service. All gap
distances were adjusted to the specified values (630 mm and 1120 mm).
Ambient conditions:
Table 1: Ambient conditions for RIV and corona test
Wet conditions:
Conductivity of sprayed water: 102 μS/cm
Precipitation rate horiz.: 3.2 mm / min
Precipitation rate vert.: 3.6 mm / min
Spray angle: 45°
Under dry conditions, 1.2 times the phase-to-ground voltage (1.2 x 170/√3 = 117.8 kV) was applied to the
test sample. Under wet conditions, the phase-to-ground voltage of 170/√3 = 98.1 kV was applied.
While the voltage was applied, the testing hall was completely dimmed. All participants of the test were
not more than approx. 10 m away from the test object.
The test voltage was at first increased to 1.2 times the phase-to-ground voltage (1.2 x 170/√3 = 117.8
kV). After that, the voltage was lowered to 1.1 x 170/√3, where it was maintained for 5 min.
Based on the method in IEC 60099-4, the voltage was then changed in steps of 9.8 kV (0.1 times the
phase-to-ground voltage). First it was decreased to 0.5 times 170/√3, raised again to 1.05 times 170/√3
for 5 min and finally decreased to 0.5 times 170/√3. At each step, a radio interference measurement was
performed.
Report No.: HBA 11505 P Sheet: 8
Pass criteria was fulfilled: Under both dry and wet conditions, there was no corona visible. The test
object passed the visible corona test without any objection.
Pass criteria was fulfilled: Under dry conditions, the corona noises at test voltage of 118 kV were below
1000 µV (60 dBµV).
Report No.: HBA 11505 P Sheet: 9
Pass criteria was fulfilled: Under wet conditions, the corona noises at test voltage of 118 kV were below
31600 µV (90 dBµV).
Report No.: HBA 11505 P Sheet: 10
Power Generation:
AEG transformer cascade (1200 kV; 16-60 Hz, 1.2 MVA, 4 stages)
Series resistance RS = 10 kΩ
Measurement:
U is measured with
a 1200 kV-Divider (Haefely CW 3000) (C1 = 380 pF; ü = 8000)
and a AC peak voltmeter Haefely 51 with a 75 Ω-coaxial-cable with a length of 20 m
The complete AC voltage measuring system is approved according to IEC 60060-2. The calibration
certificate by the national german calibration laboratory for High-Voltage Measuring Equipments has the
calibration mark 360 DKD-K- 15901, 2012-02. (calibration is valid until 2017-02)
Report No.: HBA 11505 P Sheet: 12
Observers:
Test engineer:
Observers:
Test engineer:
All components were in a factory new condition and completely assembeled as in service. All gap
distances were adjusted to the specified values (630 mm and 1120 mm).
Ambient conditions:
Table 4: Ambient conditions for the AC withstand test
Wet conditions:
Conductivity of sprayed water: 102 μS/cm
Precipitation rate horiz.: 3.2 mm / min
Precipitation rate vert.: 3.6 mm / min
Spray angle: 45°
Test method:
Under dry condition, the rated voltage of 144 kV was applied to the test sample for one minute (60s). The
test was conducted a second time after shortening the arresters by a wire.
Under wet conditions, the rated voltage of 144 kV was applied to the test sample for 10 seconds. The test
was conducted a second time after shortening the arresters by a wire.
Report No.: HBA 11505 P Sheet: 14
Pass criteria was fulfilled: The test object passed the power frequency withstand test without any
objection.
Report No.: HBA 11505 P Sheet: 15
Power Generation:
Measurement:
U is measured with
a 1200 kV-Divider (Haefely CW 3000) (C1 = 380 pF; ü = 8000)
and a AC peak voltmeter Haefely 51 with a 75 Ω-coaxial-cable with a length of 20 m
The complete AC voltage measuring system is approved according to IEC 60060-2. The calibration
certificate by the national german calibration laboratory for High-Voltage Measuring Equipments has the
calibration mark 360 DKD-K- 15901, 2012-02. (calibration is valid until 2017-02)
Report No.: HBA 11505 P Sheet: 17
Observers:
Test engineer:
The same test sample as for the preceding power frequency withstand test has been used. All gap
distances were adjusted to the specified values (630 and 1120 mm).
Ambient conditions:
Wet conditions:
Prior to the tests, the precipitation rate of rain was measured. The rain water has been collected for
60 seconds and the precipitation rates have been calculated from the collected volumes.
Test method:
The 50 % flashover voltage Ud50 has been determined by the up-and-down method. The standard
deviation ( δ ) is set to be 6 % for 250 / 2500 µs impulses. To calculate the values, the following approach
(after Dixon and Mood) has been used:
1. choice of a starting voltage U00, where no sparkover will occur for sure
2. increasing of the test voltage by a fixed value Δu (7 kV / 12 kV) until the first sparkover occurs.
This first occasion is counted as test no. 1.
3. after the first sparkover, the test voltage is decreased by Δu. If another sparkover occurs, the
voltage is decreased again. If there is no sparkover, the test voltage is increased by Δu. This is
repeated until the total test number of 20 is reached.
4. determination of the occasion (sparkover or withstand) that happened less frequently. The
number of this occasion is k, the number of the complementary occasion q = 20 - k.
5. for the statistical analysis, the voltage levels are assigned to indices i : the level with the first
sparkover is U0, the following U1, U2, U3 etc.
6. the estimates for the 50% flashover voltage Ud50 calculated with the following formulas:
r
A = ∑ iki
i =1
r
B = ∑ i 2 ki (with ki as the number of occasions in the voltage step i)
i =1
U d 50 = u0 + ∆u ( kA ± 12 )
In the formula for Ud50, the prefix + is choosen if the considered occasions are withstands, – if the
occasions are sparkovers.
The lightning impulse withstand voltage UWS is than calculated with the following formula
Test results for the test with positive voltage and normal arresters
Test results for the test with negative voltage and normal arresters
Pass criteria was fulfilled: The withstand voltages UWS of the arrester in normal condition were above
the required values of ± 458 kV. UWS = V WS [=V 50x(1-3σ )]
Report No.: HBA 11505 P Sheet: 20
Test results for the test with positive voltage and shorted arresters
Test results for the test with negative voltage and shorted arresters
Pass criteria was fulfilled: The withstand voltages UWS of the arrester in shorted condition were above
the required values of ± 347 kV. UWS = V WS [=V 50x(1-3σ )]
Report No.: HBA 11505 P Sheet: 21
Measurement SI:
U is measured with
a 2 MV-Divider (Haefely CR 3000) (C1 = 1 nF; R1 = 114 Ω; ü = 2712.2)
a 75 Ω-coaxial cable with a length of 30 m
and a Highvolt Digital-Recorder MIA 200-12/2B with an input divider of 200:1
The complete switching impulse voltage measuring system is approved according to IEC 60060-2. The
calibration certificate by the national german calibration laboratory for High-Voltage Measuring
Equipments has the calibration mark 358 DKD-K- 15901, 2012-02. (calibration is valid until 2017-02)
Report No.: HBA 11505 P Sheet: 23
Observers:
Test engineer:
The same test sample as for the preceding switching overvoltage test has been used. All gap distances
were adjusted to the specified values (630 and 1120 mm).
Ambient conditions:
Table 7: Ambient conditions for the lightning impulse insulation coordination test
Tests under wet condition
Wet conditions:
Conductivity of sprayed water: 102 μS/cm
Precipitation rate horiz.: 3.2 mm / min
Precipitation rate vert.: 3.6 mm / min
Spray angle: 45°
Test method:
Lightning voltage impulses with a rate of rise greater than 1.500 kV/µs have been applied five times for
both positive and negative polarity. All fashovers shall only occur in the series gap of the arrester.
Pass criteria was fulfilled: Flashover occurred only in the series gap. The tested sample was set to the
minimum arcing horn interval and insulation gap interval supposed in actual use.
Report No.: HBA 11505 P Sheet: 25
8.3.1 Oscillograms
Report No.: HBA 11505 P Sheet: 26
Report No.: HBA 11505 P Sheet: 27
Measurement LI:
U is measured with
a 3 MV-Divider (Haefely CZ 3000) (C1 = 250 pF; R1 = 900 Ω; ü = 2370.4)
a 75 Ω-coaxial cable with a length of 30 m
and a Highvolt Digital-Recorder MIA 200-12/2B with an input divider of 200:1.
The complete lightning impulse voltage measuring system is approved according to IEC 60060-2. The
calibration certificate by the national german calibration laboratory for High-Voltage Measuring
Equipments has the calibration mark 359 DKD-K-15901, 2012-02. (calibration is valid until 2017-02)
Report No.: HBA 11505 P Sheet: 28
Observers:
Test engineer:
The lightning impulse withstand test was performed on a single arrester body without MOV blocks.
The arrester body was installed at the complete arrester set, replacing one active part. The remaining
second active part and the spark gap were short circuited.
Ambient conditions:
Table 10: Test results for the Lightning impulse withstand test
Test result
Test voltage /
Test condition number of impulses /
[kV]
disruptive discharges
Negative voltage -310 5/0
Positive voltage +310 5/0
Pass criteria was fulfilled: No flashovers occured per polarity. The required lightning voltage impulse of
488 kV (1.2×50µs) for two bodys or 244 kV for one body was fulfilled. The specified lightning impulse
withstand voltage of ± 310 kV (for one unit) was verified.
Photo 7: Test object (lower active part and spark gap short circuited)
The same test setup as for the lightning impulse insulation coordination test was used (see 8.4)
Report No.: HBA 11505 P Sheet: 30
Observers:
Test engineer:
The power frequency withstand test was performed on a single arrester body without MOV blocks.
The arrester body was installed at the complete arrester set, replacing one active part. The remaining
second active part and the spark gap were short circuited.
Ambient conditions:
Table 91: Ambient conditions for power frequency withstand test
Wet conditions:
Conductivity of sprayed water: 99 μS/cm
Precipitation rate horiz.: 3.2 mm / min
Precipitation rate vert.: 3.6 mm / min
Spray angle: 45°
Test method:
Under dry condition, the test voltage of 100 kV was applied to the test sample for one minute (60 s).
Under wet conditions, the test voltage of 144 kV was applied to the test sample for 10 seconds.
Pass criteria was fulfilled: The required power frequency withstand voltage of 100 kV (for one unit) was
verified.
Photo 8: Test object (lower active part and spark gap short circuited)
The same test setup as for the power frequency withstand test (on complete arrester) was used (see 6.5)
Report No.: HBA 11506 P Sheet: 2
2 Index
Sheet-no.
1 Test Report ............................................................................................................................................... 1
2 Index ......................................................................................................................................................... 2
3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9 .................................................................... 3
4 Dimensional drawings arrester of accessories (arrester set) ................................................................... 4
4.1 Mounting angle, drawing no. 802-62518 ............................................................................................. 4
4.2 Electrode angle (short) L=58”, drawing no. 802-62519 ...................................................................... 5
4.3 Electrode angle (long) L=204”, drawing no. 802-62520 ...................................................................... 6
4.4 Electrode (short) L= 120”, drawing no. 802-62521 ............................................................................. 7
4.5 Electrode (long) L=193”, drawing no. 802-62522................................................................................ 8
5 Visual and structure inspection ................................................................................................................ 9
5.1 Test result ............................................................................................................................................ 9
6 Galvanizing test ...................................................................................................................................... 12
6.1 Test liquid was preparation ...............................................................................................................12
6.2 Parts before test ................................................................................................................................13
6.3 Operation ...........................................................................................................................................13
6.4 Parts in the test solution ....................................................................................................................14
6.5 Parts in after test ...............................................................................................................................14
6.6 Test result copper sulfate test ...........................................................................................................15
6.7 Test result hot dip galvanized coatings adhesion quantity test ........................................................15
6.8 Test result summary ..........................................................................................................................15
Report No.: HBA 11506 P Sheet: 3
Appearance and structure of the arrester accessory have been inspected and the dimensions have been
checked. The results of the inspection can be seen in the tables below. For the dimension indications
please see the attached drawings on sheet no. 4 to 8.
Pass criteria was fulfilled: The results of the inspection was satisfactory.
6 Galvanizing test
The Galvanizing test was performed as coating mass test with direct method according to Item 4.1, KS
D0201:2011 as well as copper sulfate test according to KS D0201:2011.
For the copper sulfate test first the test liquid was prepared according to requirement of D0201 Item 5.2
Two times copper sulfate of 360g was mixed with two times distilled water of 1 liter:
After heating and dissolving it, 2g cupric hydroxide was mixed for the 2 Liters test liquid. Then, after
leaving it for 24 hours, it was filtered to get the test solution.
Report No.: HBA 11506 P Sheet: 13
6.3 Operation
The washed test pieces were immersed in the test solution for 1 min. Immediately after their were taking
out, washed in water and copper on the plating were removed with a brush.
This procedure was repeated five times.
Report No.: HBA 11506 P Sheet: 14
For the parts drawing nos. 802-62521 and 802-62522 the surface was still in good condition and shinning.
For the parts drawing nos. 802-62518, 802-62519 and 802-62520 the surface was black, but no copper
on the surface was visible and the measured thickness of zinc was still more than 70µm.
6.7 Test result hot dip galvanized coatings adhesion quantity test
Total Surface
Drawing No. Sample No. Before Coating After Coating Coating Weight Coating Mass
Area
/g /g /g mm2 g/m2
1 69.68 72.34 2.66 5250 506.7
802-62521 2 68.76 71.44 2.68 5250 510.5
3 69.25 71.92 2.67 5250 508.6
1 238.32 243.26 4.94 9750 506.7
802-62522 2 239.19 244.38 5.19 9750 532.3
3 235.42 240.71 5.29 9750 542.6
1 96.1 99.95 3.85 7170 537.0
802-62519 2 95.56 99.21 3.65 7170 509.1
3 96.04 99.68 3.64 7170 507.7
1 222.38 229.85 7.47 14760 506.1
802-62520 2 225.84 234.26 8.42 14760 570.5
3 226.94 235.55 8.61 14760 583.3
1 322.36 329.09 6.73 13020 516.9
802-62518 2 321.58 328.47 6.89 13020 529.2
3 321.77 328.68 6.91 13020 530.7
Pass criteria were fulfilled: No termination point was reached have 5 times application of test solution.
2
The required coating mass of minimum 505 g/m was fulfilled.
Test Report No. 313d E Page 1 of 7
Fachgebiet
Hochspannungstechnik
(1000-h-salt-fog-test)
Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 2 of 7
1 Tests performed
A Weather Aging Test, Series A according to standard IEC 60099-4, Ed. 2.2, Clause 10.8.14
and standard IEEE C62.11-2005, Clause 8.7 was performed on the following metal-oxide
surge arrester:
For identification of the test sample see figure 2.1 (dimension drawing, Section 2).
The test consists of a 1000 h salt fog application while the arrester is energized at a test
voltage of U = 48 kV. The test was performed with a salt mass concentration of 10 kg/m³ at
the beginning. Because of flashovers on other arresters inside the test chamber, the salt
mass concentration was first reduced to 5 kg/m³ after 170 hours and then to 2,5 kg/m³ after
415 hours.
This test shall confirm that there is no tracking or erosion on the surface of the SVU housing
that may impair the EGLA's operating performance.
During the test, the peak values of the surface current (maximum values within 15-minute-
intervals) were recorded by a computer aided data acquisition system.
Before and after the test, following arrester characteristics were measured for the purpose of
test evaluation:
Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 3 of 7
2 Drawing of the test sample 3EV5 (identical with arrester 3EK7 600-4CK4)
Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 4 of 7
Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 5 of 7
Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 6 of 7
4 Test results
Diagram Figure 4.2 shows the recorded surface current peak values within 15-minute-
intervals each.
Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 7 of 7
Before and after the test, the reference voltage (rms) at 1,5 mA peak current and the partial
discharge level were measured for purpose of test evaluation.
22
îref 1,5 mA
Uref 61,5 kV
PD level at U = 50,4 kV < 10pC
22
îref 1,5 mA
Uref 61,6 kV
PD level at U = 50,4 kV < 10pC
The partial discharge level measured at U = 50,4 kV before and after the test is < 10 pC and
thus fulfils the requirements.
The pass criteria of IEC 60099-4, Ed. 2.2, Clause 10.8.14 and IEEE C62.11-2005, 8.7 are
fulfilled.
4.5 Conclusion
Fachgebiet
Hochspannungstechnik
Test Report No. 351 E Page 1 of 4
Fachgebiet
Hochspannungstechnik
Fachgebiet
Hochspannungstechnik
Test Report No. 351 E Page 2 of 4
1 Test objective
The test objective was the artificial weathering of silicone rubber sheds according to
ASTM G154 – 12a, as proposed in IEEE C62 11-2012, clause 8.6.1.2 c).
For evaluation of the degradation behavior of the material a visual evaluation was performed
at the beginning and the end of the test, as proposed in ASTM D750, clause 7.1.1. For
passing the test according to IEEE C62 11-2012, clause 8.6.1.3 there shall be no cracking of
any sample’s surface to depths greater than 0.1 mm.
Six semi-circular silicone rubber sheds of the surge arrester 3EV5 were tested.
2 Performed Tests
The tests were performed in a weathering tester of type Q-Lab QUV/se. Irradiation is
achieved by means of fluorescent UVA-340-lamps. Wetting of the specimens is achieved by
condensation.
The artificial weathering test was run for 1000 hours.
The test specimens were examined according to ASTM G154 – 12a, Cycle 1, Table X2.1.
The test parameters are shown in Table 1.
Fachgebiet
Hochspannungstechnik
Test Report No. 351 E Page 3 of 4
3 Test Results
Photographs of the test specimen were taken before and after the test. The state before the
test is documented in Figures 1 to 3, the state after the test is shown in Figures 4 to 6. Visual
evaluation of the specimen’s surfaces did not show any abnormalities in the form of surface
or colour changes or cracks.
Figure 1: Specimen 1 (top) and Figure 2: Specimen 3 (top) and Figure 3: Specimen 5 (top) and
2 (bottom) before testing 4 (bottom) before testing 6 (bottom) before testing
Fachgebiet
Hochspannungstechnik
Test Report No. 351 E Page 4 of 4
Figure 4: Specimen 1 (top) and Figure 5: Specimen 3 (top) and Figure 6: Specimen 5 (top) and
2 (bottom) after testing 4 (bottom) after testing 6 (bottom) after testing
4 Summary
The weathering test of the silicone rubber sheds of the surge arrester 3EV5 according to
ASTM G154 – 12a, as proposed in IEEE C62 11-2012, clause 8.6.1.2 c) is passed.
Fachgebiet
Hochspannungstechnik
Report No.: 14-021-HS Sheet: 2
Notes
1. The testing station of the Siemens switchgear factory (Prüffeld der Schaltwerke), Siemens AG, Berlin, has been
approved by the DAkkS (German accreditation body) for rendering the following testing services:
mechanical tests,
temperature rise tests,
environment tests,
dielectric tests and
power tests (e.g. switching capacity, load switching, short-time current tests, etc.)
on high-voltage switchgear and controlgear and on power engineering equipment.
The approval was given under registration no. D-PL-11055-10. Testing services beyond the scope certified
cannot be regarded as testing services of an approved testing station. No test documents will be made out for
them.
2. In the Prüffeld der Schaltwerke, Siemens AG, Berlin, all tests will be carried out according to EN ISO/IEC 17025
and the pertinent international and national test specifications. Moreover, all criteria specified by the accreditation
authority will be taken into account in the tests.
3. The Prüffeld der Schaltwerke, Siemens AG, Berlin, points out that its accreditation or its test documents do not
imply that the accreditation authority or another authority have acknowledged the product tested.
4. Test documents or parts thereof may not be used or released by the purchaser for advertising purposes if the
accreditation authority considers their use as misleading. Reproduction in extracts of the test documents is
acceptable only on condition of the prior consent of the Prüffeld der Schaltwerke, Siemens AG, Berlin. Copying
the cover sheet and sheet 2 is an exception.
If test documents or extracts thereof are to be used for advertising purpose or publication, the agreement of the
Prüffeld der Schaltwerke, Siemens AG, Berlin, must be obtained in due time before utilization. If necessary, the
Prüffeld der Schaltwerke, Siemens AG, Berlin, will obtain the accreditation authority’s consent.
5. If reference is to be made in one way or other to the utilization of the Prüffeld der Schaltwerke, Siemens AG,
Berlin, as approved testing laboratory, this shall be worded as follows:
"Testing by the Testing Station of Siemens Schaltwerke Berlin, which is accredited by the DAkkS (German
accreditation body) for tests on high-voltage switchgear and controlgear and power engineering equipment under
registration No. D-PL-11055-10."
6. The Prüffeld der Schaltwerke applies the internal procedure PSW-IA 020 for determining the uncertainties of
measurement. As long as no explicit statements are made, the uncertainties required by the relevant standards
have been complied with.
Addresses
Client: Siemens AG
E T HP AR R&D 2
Nonnendammallee 104
13629 Berlin
Germany
201SE1108
Report No.: 14-021-HS Sheet: 3
Table of Contents
14PE0402
Report No.: 14-021-HS Sheet: 4
Representatives of Client:
Further Participants:
51SE01008
Report No.: 14-021-HS Sheet: 5
Test object: Metal-oxide surge arrester without pressure relief device and with directly
moulded polymeric housing
Designation: 3EV5 144-0LK12
Manufacturer: Siemens Surge Arresters Limited
Serial No.: Type test samples 1 -13
Year of manufacture: 2014
Drawing No.: PTD H51 / 802 61398
Further data: -
Remarks: The test sample was the largest unit of the 3EV5 series
320SE1110
Report No.: 14-021-HS Sheet: 6
317SE0407
Report No.: 14-021-HS Sheet: 7
Remarks: -
12dSE0407
Report No.: 14-021-HS Sheet: 8
Circuit Diagram
Single-phase Direct Test
AD
G UTO TO
AD
ITO
T Transformer
44-17bSE1008
Report No.: 14-021-HS Sheet: 9
Test Results
Power Arc Tests
Test No. 2) 6 3) 7 8 9
Test object No. - 1 2 3
Applied voltage kV 31.9 31.9 31.9 31.9
Peak short-circuit current kA 132 129 129 130
Short-circuit current First cycle kA 52.4 52.1 51.9 52.1
Last cycle kA 52.3 51.7 51.8 52.0
Duration ms 205 206 206 206
4)
Equivalent short-circuit current Current kA 53.0 52.1 52.1 52.3
Duration ms 200 200 200 200
X/R 31 - - -
Time to arc ignition ms - 1.0 1.1 1.2
5)
Time to vent ms - 1.0 1.1 1.2
Duration of open flames s - - - -
Internal parts outside the circular enclosure - no no no
Test result (P/N) - P P P
Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed outside the arrester housing
2)
Tests 1 - 5: Equipment tests, oscillograms are not included in this document
3)
Prospective test for the following test
4)
Calculated using Simpson’s Rule
5)
Arc detected with outside placed optical arcing detector (see sketch on sheet 8)
322SE0902
Report No.: 14-021-HS Sheet: 10
Test Results
Pressure Relief Tests
Test No. 10 11 12 -
Test object No. 4 5 6 -
Applied voltage kV 31.9 31.9 31.9 -
Peak short-circuit current kA 129 128 129 -
Short-circuit current First cycle kA 52.0 51.9 52.0 -
Last cycle kA 51.9 52.0 51.9 -
Duration ms 206 206 206 -
3)
Equivalent short-circuit current Current kA 52.3 52.2 52.3 -
Duration ms 200 200 200 -
X/R - - - -
Time to arc ignition ms 0.9 0.8 0.7 -
4)
Time to vent ms 0.9 0.8 0.7 -
Duration of open flames s - - - -
Internal parts outside the circular enclosure no no no -
Test result (P/N) P P P -
Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed along the surface of the active part inside the arrester housing
2)
Prospective test for the following test
3)
Calculated using Simpson’s Rule
4)
Arc detected with outside placed optical arcing detector (see sketch on sheet 8)
322SE0902
Report No.: 14-021-HS Sheet: 11
Test Results
Power Arc Tests
Test No. 2) 15 16 17 -
Test object No. 7 8 9 -
Applied voltage kV 80.4 80.5 81.5 -
Peak short-circuit current A 845 851 850 -
Short-circuit current First cycle A 419 419 419 -
Last cycle A 424 426 425 -
Duration s 2.11 2.11 2.11 -
3)
Equivalent short-circuit current Current A 427 428 429 -
Duration ms 2.00 2.00 2.11 -
X/R - - - -
Time to arc ignition ms 1.3 40.4 25.0 -
4)
Time to vent ms 1.3 40.4 25.0 -
Duration of open flames s - - - -
Internal parts outside the circular enclosure no no no -
Test result (P/N) P P P -
Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed outside the arrester housing
2)
Tests 13 - 14: Equipment tests, oscillograms are not included in this document
3)
Calculated using Simpson’s Rule
4)
Arc detected with outside placed optical arcing detector (see sketch on sheet 8)
322SE0902
Report No.: 14-021-HS Sheet: 12
Test Results
Pressure Relief Tests
Test No. 18 19 20 21
Test object No. 10 11 12 13
Applied voltage kV 81.0 80.8 82.6 80.4
Peak short-circuit current A 846 847 1094 846
Short-circuit current First cycle A 402 404 457 411
Last cycle A 420 421 446 419
5)
Duration s 2.11 2.11 1.00 2.11
3)
Equivalent short-circuit current Current A 424 426 - 422
Duration s 2.11 2.00 - 2.00
X/R - - - -
Time to arc ignition ms 12.9 15.4 12.9 17.1
4)
Time to vent ms 23.9 24.6 1125.0 24.0
Duration of open flames s - 5 - -
Internal parts outside the circular enclosure no no no no
Test result (P/N) P P - 5) P
Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed along the surface of the active part inside the arrester housing
2)
Prospective test for the following test
3)
Calculated using Simpson’s Rule
4)
Arc detected with outside placed optical arcing detector (see sketch on sheet 8)
5)
Test not valid, current cleared after 0.26 s and started new after 1.09 s for a duration
of 1.00 s.
322SE0902
Report No.: 14-021-HS Sheet: 13
311SE0407
Report No.: 14-021-HS Sheet: 14
315SE0407
Report No.: 14-021-HS Sheet: 15
315SE0407
Report No.: 14-021-HS Sheet: 16
311SE0407
Report No.: 14-021-HS Sheet: 17
315SE0407
Report No.: 14-021-HS Sheet: 18
315SE0407
Report No.: 14-021-HS Sheet: 19
311SE0407
Report No.: 14-021-HS Sheet: 20
315SE0407
Report No.: 14-021-HS Sheet: 21
315SE0407
Report No.: 14-021-HS Sheet: 22
311SE0407
Report No.: 14-021-HS Sheet: 23
315SE0407
Report No.: 14-021-HS Sheet: 24
315SE0407
Report No.: 14-021-HS Sheet: 25
315SE0407
Report No.: 14-021-HS Sheet: 26
311SE0407
Report No.: 14-021-HS Sheet: 27
315SE0407
Report No.: 14-021-HS Sheet: 28
315SE0407
Report No.: 14-021-HS Sheet: 29
315SE0407
Report No.: 14-021-HS Sheet: 30
311SE0407
Report No.: 14-021-HS Sheet: 31
315SE0407
Report No.: 14-021-HS Sheet: 32
315SE0407
Report No.: 14-021-HS Sheet: 33
315SE0407
Report No.: 14-021-HS Sheet: 34
311SE0407
Report No.: 14-021-HS Sheet: 35
315SE0407
Report No.: 14-021-HS Sheet: 36
315SE0407
Report No.: 14-021-HS Sheet: 37
311SE0407
Report No.: 14-021-HS Sheet: 38
315SE0407
Report No.: 14-021-HS Sheet: 39
315SE0407
Report No.: 14-021-HS Sheet: 40
311SE0407
Report No.: 14-021-HS Sheet: 41
315SE0407
Report No.: 14-021-HS Sheet: 42
315SE0407
Report No.: 14-021-HS Sheet: 43
311SE0407
Report No.: 14-021-HS Sheet: 44
315SE0407
Report No.: 14-021-HS Sheet: 45
315SE0407
Report No.: 14-021-HS Sheet: 46
315SE0407
Report No.: 14-021-HS Sheet: 47
311SE0407
Report No.: 14-021-HS Sheet: 48
315SE0407
Report No.: 14-021-HS Sheet: 49
315SE0407
Report No.: 14-021-HS Sheet: 50
315SE0407
Report No.: 14-021-HS Sheet: 51
311SE0407
Report No.: 14-021-HS Sheet: 52
315SE0407
Report No.: 14-021-HS Sheet: 53
315SE0407
Report No.: 14-021-HS Sheet: 54
315SE0407
Report No.: 14-021-HS Sheet: 55
311SE0407
Report No.: 14-021-HS Sheet: 56
315SE0407
Report No.: 14-021-HS Sheet: 57
315SE0407
Report No.: 14-021-HS Sheet: 58
315SE0407
Report No.: 14-021-HS Sheet: 59
Oscillogram No.: 6 - 21
Abbreviation in Description
oscillograms
Remarks: The amplitude scaling of the individual signals is apparent at the labels on the right
side of the oscillograms, as a value taken from the upper to the lower borderline of the
inner graphic area.
All measurements and all measurement systems are calibrated. The measuring
uncertainties are determined and stated in the calibration certificates.
61SE0707
Report No.: 14-021-HS Sheet: 60
Oscillograms
Oscillogram No.: 6
316SE1103
Report No.: 14-021-HS Sheet: 61
Oscillogram No.: 7
316SE1103
Report No.: 14-021-HS Sheet: 62
Oscillogram No.: 8
316SE1103
Report No.: 14-021-HS Sheet: 63
Oscillogram No.: 9
316SE1103
Report No.: 14-021-HS Sheet: 64
Oscillogram No.: 10
316SE1103
Report No.: 14-021-HS Sheet: 65
Oscillogram No.: 11
316SE1103
Report No.: 14-021-HS Sheet: 66
Oscillogram No.: 12
316SE1103
Report No.: 14-021-HS Sheet: 67
Oscillogram No.: 15
316SE1103
Report No.: 14-021-HS Sheet: 68
Oscillogram No.: 16
316SE1103
Report No.: 14-021-HS Sheet: 69
Oscillogram No.: 17
316SE1103
Report No.: 14-021-HS Sheet: 70
Oscillogram No.: 18
316SE1103
Report No.: 14-021-HS Sheet: 71
Oscillogram No.: 19
316SE1103
Report No.: 14-021-HS Sheet: 72
Oscillogram No.: 20
316SE1103
Report No.: 14-021-HS Sheet: 73
Oscillogram No.: 21
316SE1103