You are on page 1of 250

Report No.

: HBA 11483 P Sheet: 2

2 Index

Sheet-no.
1 Test Report ............................................................................................................................................... 1
2 Index ......................................................................................................................................................... 2
3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9 .................................................................... 3
4 Drawing of surge arrester body ................................................................................................................ 4
5 Residual voltage tests .............................................................................................................................. 5
5.1 Lightning current impulse residual voltage test (waveform 2/4µs) on single metal-oxide resistors ....5
5.2 Lightning current impulse residual voltage test (waveform 8/20µs) on single metal-oxide
resistors ............................................................................................................................................... 8
5.3 Lightning current impulse residual voltage test (waveform 8/20µs) on SVU ....................................10
5.4 High current impulse residual voltage test ........................................................................................12
5.5 Photographs of test samples (single metal-oxide resistors) .............................................................14
6 Lightning surge operating duty test ........................................................................................................ 15
6.1 Calculation of rated voltage ...............................................................................................................15
6.2 5 impulses +10kA, 8/20µs and simultaneously Ur.............................................................................15
6.3 5 impulses -10kA, 8/20µs and simultaneously Ur .............................................................................20
6.4 Lightning impulse residual voltage measurement at 10kA, 8/20µs ...................................................26
6.5 Oscillograms of the lightning impulse residual voltage .....................................................................26
6.6 Photographs of test samples (single metal-oxide resistors) .............................................................27
7 Technical data of test circuits ................................................................................................................. 28
7.1 Steep current impulse residual voltage test ......................................................................................28
7.2 Lightning impulse residual voltage test on single metal-oxide resistors ...........................................29
7.3 Lightning impulse residual voltage test on complete arrester ...........................................................30
7.4 High current impulse test...................................................................................................................31
7.5 Lightning surge operating duty test ...................................................................................................32
Report No.: HBA 11483 P Sheet: 3

3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9

Rated voltage 144kV

Rated frequency 60Hz

Nominal discharge current 10kA, 2/20µs

Maximum discharge current 30kA, 4/10µs

Maximum residual voltage at rated discharge current (10kA, 2/20µs) 420kV

Maximum residual voltage at discharge current (30kA, 4/10µs) 470kV

Maximum permissible service load, dynamic (MPSL) 882N

Maximum continuous cantilever load, static 617N

Tensile strength 882N


Report No.: HBA 11483 P Sheet: 4

4 Drawing of surge arrester body


Report No.: HBA 11483 P Sheet: 5

5 Residual voltage tests


Date of test: 17.02.2014
Test facilities: E T HP AR R&D Ü4 (metal-oxide resistors)
E T HP AR R&D Ü7 (metal-oxide resistors)
E T HP AR R&D Ü1/2 (complete arresters)

The residual voltage tests (lightning current impulse and high current impulse) were performed on three
typical arrester sections (1 metal-oxide resistor). Additionally the lightning current impulse residual voltage
test with 10kA, 8/20µs has also been carried out on three units (bodys) of SVU 3EV5 144-0LK12-4ZZ9.
According to the KEPCO technical specification, clause 8.1.7 all measured residual voltage values shall
be below the maximum values for one complete SVU (consisting of two units):

• 420kV at rated discharge current (10kA, 2/20µs)


• 470kV at maximum discharge current (30kA, 4/10µs)

5.1 Lightning current impulse residual voltage test (waveform 2/4µs) on single metal-oxide
resistors

The lightning current impulse residual voltage test (waveform 2/4µs) was performed with a current peak
value of 10kA (test circuit see sheet-no. 28).

5.1.1 Test results

I Ures Waveform

Sample no. / kA / kV T1 / T2

Metal block 10.00 0.09 2.1/4.3


1 10.03 15.50 2.0/4.5

2 10.11 15.39 2.0/4.5

3 10.01 15.36 2.0/4.6

The tolerances of the specified values for exponential impulse currents are listed in the following table
(according to IEC 62475 (2010):
Report No.: HBA 11483 P Sheet: 6

To determine inductive effects of the voltage measuring circuit a current impulse equal to the discharge
current was applied to a metal block having the same dimensions as the samples. Because the peak
voltage on the metal block was less than 2 % of the peak voltage of the resistor samples, no inductive
correction to the resistor measurements was required.

The maximum lightning current impulse residual voltage for the given complete SVU is calculated from
the lightning current impulse residual voltage of the single metal-oxide resistor multiplied by the scale
factor plus a calculated inductive voltage drop across the complete SVU according IEC 60099-8, clause
8.3.2, procedure b).

Ures, complete SVU = 2 • Ures, SVU


= 2 • (fscale • Ures, sample + UL)
= 2 • (fscale • Ures, sample + L’ • h • Id / Tf)

fscale = 12 / 1
Ures, sample, max = 15.50kV
L’ = 1µH / m
H = 0.51m
Id = 10kA
Tf = 2µs

Ures, complete SVU = 2 • (12 / 1 • 15.50kV + 1µH / m • 0.51m • 10kA / 2µs)


= 377.1kV

The test is passed: The measured residual voltage value of 377kV was lower than the corresponding
maximum specified values for the complete arrester set of 420kV at rated discharge current (10kA,
2/20µs).

5.1.2 Oscillograms of lightning current impulse residual voltage test


Report No.: HBA 11483 P Sheet: 7

5.1.3 Photograph of test setup


Report No.: HBA 11483 P Sheet: 8

5.2 Lightning current impulse residual voltage test (waveform 8/20µs) on single metal-oxide
resistors

The lightning current impulse residual voltage test (waveform 8/20µs) was performed with a current peak
value of 10kA (test circuit see sheet-no. 29).

5.2.1 Test results

)
I Ures 1 Waveform Ratio between

Sample no. / kA / kV T1 / T2 U10kA, 2µs / U10kA, 8µs

1 10.20 14.82 8.3/18.3 1.046


2 10.14 14.74 8.2/18.2 1.044

3 9.886 14.69 8.5/18.5 1.046

The tolerances of the specified values for exponential impulse currents are listed in the table on sheet-no.
5.

5.2.2 Oscillograms of lightning current impulse residual voltage test

1) Ures = Ures, oscilloscope - Ushunt


Report No.: HBA 11483 P Sheet: 9

5.2.3 Photograph of test setup


Report No.: HBA 11483 P Sheet: 10

5.3 Lightning current impulse residual voltage test (waveform 8/20µs) on SVU

The lightning current impulse residual voltage test (waveform 8/20µs) was performed with a current peak
value of 10kA (test circuit see sheet-no. 30).

5.3.1 Test results

)
I Ures 1 Waveform Calculated for

Sample no. / kA / kV T1 / T2 U10kA, 2/20µs

1 10.09 175.5 7.4/18.1 183.6


2 10.05 175.1 7.5/18.1 182.8

3 10.09 174.8 7.5/18.0 182.8

For calculation of the residual voltage at U10kA, 2/20µs the evaluated ratio of f2µs/8µs = 1.046 was used (see
sheet-no. 8). The tolerances of the specified values for exponential impulse currents are listed in the table
on sheet-no. 5.

The test is passed: The maximum residual voltage value of 183.6kV was lower than the corresponding
maximum specified value for the unit of SVU 3EV5 0144-0LK12-4ZZ9 of 420kV/2 = 210kV at rated
discharge current (10kA, 2/20µs).

5.3.2 Oscillograms of lightning current impulse residual voltage test

1) Ures = Ures, oscilloscope - Ushunt


Report No.: HBA 11483 P Sheet: 11

5.3.3 Photograph of test setup


Report No.: HBA 11483 P Sheet: 12

5.4 High current impulse residual voltage test

The high current impulse residual voltage test (waveform 4/10µs) was performed with a current peak
value of 30kA (test circuit see sheet-no. 31).

5.4.1 Test results

)
I Ures 1 Waveform

Sample no. / kA / kV T1 / T2

1 30.82 18.15 4.0/9.6


2 29.62 17.83 4.1/9.6

3 30.40 17.94 4.0/9.6

The tolerances of the specified values for exponential impulse currents are listed in the table on sheet-no.
5.

The maximum high current impulse residual voltage for the given complete SVU is calculated from the
lightning current impulse residual voltage of the single metal-oxide resistor multiplied by the scale factor
plus a calculated inductive voltage drop across the complete SVU according IEC 60099-8, clause 8.3.2,
procedure b).

Ures, complete SVU = 2 • Ures, SVU


= 2 • (fscale • Ures, sample + UL)
= 2 • (fscale • Ures, sample + L’ • h • Id / Tf)

fscale = 12 / 1
Ures, sample, max = 18.15kV
L’ = 1µH / m
H = 0.51m
Id = 30kA
Tf = 4µs

Ures, complete SVU = 2 • (12 / 1 • 18.15kV + 1µH / m • 0.51m • 30kA / 4µs)


= 443.3kV

The test is passed: The measured residual voltage value of 443.3kV was lower than the corresponding
maximum specified values for the complete arrester set of 470kV at maximum discharge current (30kA,
4/10µs).

1) Ures = Ures, oscilloscope - Ushunt


Report No.: HBA 11483 P Sheet: 13

5.4.2 Oscillograms of high current impulse residual voltage test

5.4.3 Test result summary

Pass criteria were fulfilled: All measured residual voltage values were lower than the corresponding
maximum specified values for the complete arrester set (consisting of 2 units):

• 420 kV at rated discharge current (10 kA)


• 470 kV at maximum discharge current (30 kA)
Report No.: HBA 11483 P Sheet: 14

5.4.4 Photograph of test setup

5.5 Photographs of test samples (single metal-oxide resistors)

before the tests after the tests


Report No.: HBA 11483 P Sheet: 15

6 Lightning surge operating duty test


Date of test: 18.02.2014
Test facility: E T HP AR R&D Ü4

The lightning surge operating duty test was carried out on single metal-oxide resistors (test circuits see
sheet-nos. 29 and 32). While the test samples were energized at rated voltage five nominal discharge
current impulses with waveform 8/20µs were applied 15 ± 15 electrical degrees before the positive peak
of the voltage. Within 10 minutes after the last positive nominal discharge current five more nominal
discharge current impulses with negative peak value were applied 15 ± 15 electrical degrees before the
negative peak of the voltage. The interval between the impulses was 1 minute.

Before and after the test the residual voltage at nominal discharge current 10kA, 8/20µs was measured.

6.1 Calculation of rated voltage

Prorating factor of 3EV5 144-0LK12-4ZZ9: n = 1 / 24

Ur, sample = n • Ur, complete arrester


= (1 / 24) • 144kV
= 6.00kV

6.2 5 impulses +10kA, 8/20µs and simultaneously Ur


Report No.: HBA 11483 P Sheet: 16
Report No.: HBA 11483 P Sheet: 17
Report No.: HBA 11483 P Sheet: 18
Report No.: HBA 11483 P Sheet: 19
Report No.: HBA 11483 P Sheet: 20

6.3 5 impulses -10kA, 8/20µs and simultaneously Ur


Report No.: HBA 11483 P Sheet: 21
Report No.: HBA 11483 P Sheet: 22
Report No.: HBA 11483 P Sheet: 23
Report No.: HBA 11483 P Sheet: 24
Report No.: HBA 11483 P Sheet: 25

6.3.1 Photograph of test setup


Report No.: HBA 11483 P Sheet: 26

6.4 Lightning impulse residual voltage measurement at 10kA, 8/20µs

Before the test After the test

Waveform Waveform ∆U / %


Sample no. U / kV I / kA T1 / T2 U / kV I / kA T1 / T2 ∆U / % required

1 14.76 9.9 8.4/18.6 14.85 9.9 8.3/18.9 + 0.6 ≤5


2 14.75 10.1 8.6/18.3 14.79 10.1 8.4/18.8 + 0.3 ≤5
3 14.73 10.0 8.3/18.5 14.81 10.1 8.5/18.4 + 0.5 ≤5

The tolerances of the specified values for exponential impulse currents are listed in the table on sheet-no.
5.

The test is passed: After the test visual inspection of the metal-oxide resistors revealed no evidence of
puncture, flashover or cracking. Change of the residual voltages of all three test samples was far below
the allowed 5%.

6.5 Oscillograms of the lightning impulse residual voltage


Report No.: HBA 11483 P Sheet: 27

6.5.1 Test result summary

Pass criteria were fulfilled: Before and after the test, the residual voltage at nominal discharge current
was measured. The changes between these two measurements was below 5 %.

6.6 Photographs of test samples (single metal-oxide resistors)

before the tests after the tests


Report No.: HBA 11483 P Sheet: 28

7 Technical data of test circuits


7.1 Steep current impulse residual voltage test

Test circuit: Discharge current kA 10


Surge capacitance µF 1.6

Inductance µH 1.6

Wave shape µs 2/4

H
CS
I

L Rd TS U1
RSH
TG
RL Re

U2
Uc

TG ... Trigger spark gap Rd ... Front resistor


TS ... Test sample Re ... Discharge resistor
Cs ... Surge capacitor RL ... Charge resistor
L ... Inductance H ... Shielded housing
Uc ... Charge voltage

Voltage measurement: u1, u2


High voltage probe HVP 1000:1, Tektronix P 6015A (calibration valid until 11/2014)
Oscilloscope Tektronix type TDS 3034C (calibration valid until 11/2014) / PC

Current measurement: i
Shunt RSH = 2.00mΩ (calibration valid until 11/2014)
Oscilloscope Tektronix type TDS 3034C (calibration valid until 11/2014) / PC

Test sample: 1 metal-oxide resistor


Report No.: HBA 11483 P Sheet: 29

7.2 Lightning impulse residual voltage test on single metal-oxide resistors

Test circuit: Discharge current kA 10


Surge capacitance µF 3.7

Inductance µH 12

Wave shape µs 8/20

L
Uc TG
TS RH

Cs

RSH RN

( Ushunt ) ( RN / (RN+RH)*Ures.OSC )

TG ... Trigger spark gap


TS ... Test sample
Cs ... Surge capacitor
L ... Inductance
Uc ... Charge voltage

Voltage measurement: u
Ohmic divider: RH = 3994Ω (calibration valid until 08/2014)
RN = 61.0Ω (calibration valid until 03/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Current measurement: i
Shunt RSH = 40.38mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Test sample: 1 metal-oxide resistor


Report No.: HBA 11483 P Sheet: 30

7.3 Lightning impulse residual voltage test on complete arrester

Test circuit: Discharge current kA 10


Surge capacitance µF 0.25

Inductance µH 150

Wave shape µs 8/20

L
Uc TG
TS

CH
Cs

CN
RSH

i u

TG ... Trigger spark gap


TS ... Test sample
CS ... Surge capacitor
L ... Inductance
Uc ... Charge voltage

Voltage measurement: u
Capacitive divider: CH = 1.537nF, CN = 1.849µF (calibration valid until 07/2018)
Probe 10:1, Oscilloscope Tektronix TDS 3034 (calibration valid until 01/2015) / PC

Current measurement: i
Shunt RSH = 40.14mΩ (calibration valid until 09/2014)
Probe 10:1, Oscilloscope Tektronix TDS 3034 (calibration valid until 01/2015) / PC

Test sample: arrester unit type 3EV5 144-0LK12-4ZZ9


Report No.: HBA 11483 P Sheet: 31

7.4 High current impulse test

Test circuit: Discharge current kA 30


Surge capacitance µF 11.2

Inductance µH 1

Wave shape µs 4/10

L
Uc TG
TS RH

Cs

RSH RN

i u

TG ... Trigger spark gap


TS ... Test sample
Cs ... Surge capacitor
L ... Inductance
Uc ... Charge voltage

Voltage measurement: u
Ohmic divider: RH = 4394Ω (calibration valid until 04/2014)
RN = 61.0Ω (calibration valid until 03/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Current measurement: i
Shunt RSH = 10.54mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Test sample: 1 metal-oxide resistor


Report No.: HBA 11483 P Sheet: 32

7.5 Lightning surge operating duty test

Test circuit: Discharge current kA 10


Surge capacitance µF 3.7

Inductance µH 12

Wave shape µs 8/20

L
Uc BG
TG

SG CH

Cs
RT Tr
TS
CN

RSH2
RSH1

i1 u i2
TG ... Trigger spark gap Tr ... Transformer: 20kV, 12kVA
TS ... Test sample RT ... Trigger resistor
Cs ... Surge capacitor BG ... Blocking gap
L ... Inductance SG ... Spark gap
Uc ... Charge voltage

Voltage measurement: u
Capacitive divider: CH = 256pF, CN = 256nF (calibration valid until 06/2014)
Oscilloscope Tektronix type TDS 3034 (calibration valid until 09/2014) / PC

Leakage current measurement: i2


Shunt RSH2 = 48.96Ω (calibration valid until 04/2014)
Probe 10:1, Oscilloscope Tektronix type TDS 3034 (calibration valid until 09/2014) / PC

Impulse current measurement: i1


Shunt RSH1 = 40.38mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Test sample: 1 metal-oxide resistor


Report No.: HBA 11496 P Sheet: 3

3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9

Rated voltage 144 kV

Rated frequency 60 Hz

Nominal discharge current 10 kA

Maximum discharge current 30 kA

Maximum permissible service load, dynamic (MPSL) 882 N

Maximum continuous cantilever load, static 617 N

Tensile strength 882 N

Maximum residual voltage at rated discharge current (10kA, 2/20µs) 420kV

Maximum residual voltage at discharge current (30kA, 4/10µs) 470kV


Report No.: HBA 11496 P Sheet: 4

4 Drawing of surge arrester body


Report No.: HBA 11496 P Sheet: 5

5 Vibration test
Date of test: 24.02.2014
Test facility: E T HP AR R&D Ü6b (reference voltage test)
E T HP BSS LAB ME (vibration test)

The vibration test was performed on three complete arrester units (test sample # 26, # 29 and # 31). After
the initial measurements - insulation resistance test (1000V) and reference voltage test (test circuit see
sheet no. 44) - the test samples were exposed to an acceleration of 0.1 g for 500,000 times at its natural
frequency.

Prior to the test itself, the frequency response was determined by a frequency scan. The natural
frequency of the test samples was determined:

natural
Sample-no.
frequency

# 26 40 Hz
# 29 39 Hz
# 31 35 Hz

Depending on this natural frequency, the testing time was calculated: t = 500,000 / (natural frequency)

Sample-no. testing time

# 26 12500s
# 29 12821s
# 31 14286s

After that, the insulation resistance (1000V) and reference voltage was measured again.

5.1 Setup for the vibration test

The arrester unit was fixed with the bottom flange to the vibration table. An acceleration sensor was
installed on both sides of the arrester. The one on the free end of the arrester was removed before the
vibration test; it was only installed to determine the natural frequency.
Report No.: HBA 11496 P Sheet: 6

5.2 Test result

5.2.1 Vibration test sample #26

Calculation of natural frequency

The calculated natural frequency is 40 Hz


Report No.: HBA 11496 P Sheet: 7

5.2.2 Vibration test sample #29

Calculation of natural frequency

The calculated natural frequency is 39 Hz


Report No.: HBA 11496 P Sheet: 8

5.2.3 Vibration test sample #31

Calculation of natural frequency

The calculated natural frequency is 35 Hz


Report No.: HBA 11496 P Sheet: 9

5.2.4 Reference voltage measurement at 1.0 mA

Reference Reference Reference Reference


deviation
Sample-no. voltage before current before voltage after current after
/%
test / kVrms test / mA test / kVrms test / mA
# 26 68.0 1.0 68.1 1.0 + 0.2
# 29 68.2 1.0 68.4 1.0 + 0.3
# 31 68.1 1.1 68.0 1.0 - 0.2

5.2.5 Oscillograms of reference voltage test


Report No.: HBA 11496 P Sheet: 10

5.2.6 Insulation resistance test (1000V)

Insulation resistance Insulation resistance


Sample-no. deviation
Before test / Ohm After test / Ohm /%

1 2.25T 2.33T +3.6


2 2.27T 2.34T +3.1
3 2.33T 2.38T +2.1

Test result: Passed.


There was no physical damage and the reference voltage deviation was below 5 %.

5.2.7 Test result summary

Pass criteria were fulfilled: There were no change in the appearance and structure of the arrester,
dielectric resistance and the change of action start voltage was within 5% before and after test.
Report No.: HBA 11496 P Sheet: 11

5.3 Photographs of test sample and test setup

5.3.1 Test sample at reference voltage measurement

5.3.2 Test sample at Insulation resistance test


Report No.: HBA 11496 P Sheet: 12

5.3.3 Test sample at vibration test setup


Report No.: HBA 11496 P Sheet: 13

6 Tensile test
Date of test: 24.02.2014 -25.02.2014
Test facility: E T HP AR R&D Ü1/1

The tensile test was performed on three complete arrester units (test samples # 8, #12, #23). The test
sample was mechanically loaded with a tensile force greater than 882 N for more than 60 s.

6.1 Setup for the tensile test

The arrester unit was fixed horizontally with the bottom flange to the test assembly. The load was applied
by a hydraulic cylinder and measured with a force sensor. Additionally, the elongation was measured by a
distance sensor.

6.2 Test result

6.2.1 Application of tensile load, test sample # 8


Report No.: HBA 11496 P Sheet: 14

6.2.2 Application of tensile load, test sample # 12


Report No.: HBA 11496 P Sheet: 15

6.2.3 Application of tensile load, test sample # 23


Report No.: HBA 11496 P Sheet: 16

Test result: Passed. There was no physical damage.

6.2.4 Test result summary

Pass criteria were fulfilled: There was no damage.

6.3 Photograph of test sample and test setup


Report No.: HBA 11496 P Sheet: 17

7 Bending moment test


Date of test: 21.02.2014 -28.02.2014
Test facility: E T HP AR R&D Ü1/2, E T HP AR R&D Ü6b, E T HP BSS SM ML

The bending moment test was performed on three complete arrester units and according to paragraph
10.8.9 of IEC 60099-4 with one terminal of the arrester fixed and the other terminal apply to a bending
load of 882N for a duration of 60 s. Thereafter all three test samples were immersed in a vessel, in boiling
3
deionized water with 1 kg/m of NaCl, for 42 h. At the end of the boiling, the arrester was kept in the
vessel until the water had cooled down to 50°C first and then to ambient temperature. For test evaluation
the internal partial discharge test, the measurement of watt losses and the residual voltage measurement
at 10 kA, 8/20µs were performed before and after test.

7.1 Setup for the bending moment test

The samples (# 2, #9, #10) were subjected to a bending moment test with a bending load of 882N within
30 to 60 s. When the test load was reached, it was maintained for 60 s to 90 s. The force was applied by
a hydraulic cylinder and measured by a force transducer. The deflection was measured by a string
potentiometer. After releasing the bending moment the residual deflection was measured over 600 s. The
arrester unit was fixed horizontally with the bottom flange to the test assembly. The load was applied by a
hydraulic cylinder and measured with a force sensor. Additionally, the elongation was measured by a
distance sensor.
Report No.: HBA 11496 P Sheet: 18

7.2 Test result

7.2.1 Application of bending load, test sample # 2


Report No.: HBA 11496 P Sheet: 19

7.2.2 Application of bending load, test sample # 9


Report No.: HBA 11496 P Sheet: 20
Report No.: HBA 11496 P Sheet: 21

7.2.3 Application of bending load, test sample # 10


Report No.: HBA 11496 P Sheet: 22

7.2.4 Water immersion test on 3 samples


3
After the previous tests all 3 samples were immersed in a vessel, in boiling deionized water with 1 kg/m
of NaCl, for 42 h.
Report No.: HBA 11496 P Sheet: 23

7.2.5 Watt losses measurement

The watt losses were measured at continuous operating voltage (test circuit see sheet-no. 44).

Before the test After the test ∆P / %


Unit-no. (sample) U / kV P/W U / kV P/W ∆P / % required

#2 50.0 0.82 50.0 0.87 +6.1 ≤ 20


#9 50.0 0.86 50.0 0.88 +2.3 ≤ 20
#10 50.0 0.88 50.0 0.84 -4.8 ≤ 20

Test result: Passed. The change in watt losses was below the required value.

7.2.6 Oscillograms of watt losses measurement


Report No.: HBA 11496 P Sheet: 24

7.2.7 Internal partial discharge test

The partial discharge level was measured at 1.05 times the continuous operating voltage before and after
the test (test circuit see sheet-no. 44). The noise level was 0.1 pC.

Before the test After the test PD / pC


Unit-no. (sample) U / kV PD / pC U / kV PD / pC required

#2 52.5 0.1 52.5 0.1 < 10


#9 52.5 0.1 52.5 0.1 < 10
#10 52.5 0.1 52.5 0.1 < 10

Test result: Passed. The partial discharge level was below the required level.
Report No.: HBA 11496 P Sheet: 25

7.2.8 Residual voltage test

The residual voltage was measured at a discharge current of 10 kA, 8/20 µs (test circuit see sheet-no.45).
After the test two successive impulses (50 ... 60 s) at nominal discharge current 10kA were applied.

∆U / %
st
Before the test After test (1 impulse)
Unit-no.
(sample) Waveform Waveform
U / kV I / kA U / kV I / kA ∆U / % required
T1/T2 T1/T2
#2 174.9 10.1 7.4/18.1 174.5 10.0 7.4/18.1 -0.23 ≤5
#9 175.4 10.1 7.4/18.2 173.8 10.1 7.8/18.2 -0.91 ≤5
#10 174.9 10.0 7.4/18.1 175.1 10.0 7.4/18.1 0.11 ≤5

∆U / %
nd
After test (2 impulse)
Unit-no.
(sample) Waveform
U / kV I / kA ∆U / % required
T1/T2
#2 175.2 10.0 7.4/18.2 0.40 ≤5
#9 175.7 10.0 7.4/18.2 1.09 ≤5
#10 176.3 10.1 7.4/18.2 0.69 ≤5

Tolerances of exponential impulse currents according to IEC 62475 (2010):

Test result: Passed. The change in residual voltage was below the required value.
Report No.: HBA 11496 P Sheet: 26

7.2.9 Oscillograms of residual voltage tests


Report No.: HBA 11496 P Sheet: 27

7.3 Reference voltage measurement

Before and after the residual voltage test with two successive impulses the reference voltage was
measured (test circuit see sheet-no. 44).

∆U / %
st nd
Before the 1 impulse After the 2 impulse
Unit-no. (sample) Uref / kV Iref / mA Uref / kV Iref / mA ∆U / % required
#2 67.6 1.0 68.0 1.0 +0.6 ≤2
#9 67.8 1.0 67.9 1.0 +0.1 ≤2
#10 68.1 1.0 68.4 1.1 +0.4 ≤2

Test result: Passed.


Report No.: HBA 11496 P Sheet: 28

7.3.1 Oscillograms of reference voltage measurement


Report No.: HBA 11496 P Sheet: 29

7.3.2 Test result summary

Pass criteria were fulfilled: There was no damage.

7.4 Photograph of test sample and test setup

7.4.1 Application of bending load

7.4.2 Water immersion test


Report No.: HBA 11496 P Sheet: 30

7.4.3 Internal partial discharge test, watt losses measurement, reference voltage
measurement
Report No.: HBA 11496 P Sheet: 31

7.4.4 Residual voltage test


Report No.: HBA 11496 P Sheet: 32

8 Moisture ingress test


Date of test: 21.02.2014 -28.02.2014
Test facility: E T HP AR R&D Ü1/2, E T HP AR R&D Ü6b, E T HP BSS SM ML

The moisture ingress test was performed on three complete arrester units (test sample # 14, #15, #30).
After initial measurements - consisting of a measurement of the watt losses, a partial discharge test and a
residual voltage test at 10 kA 8/20µs - the test samples were first mechanically preconditioned with the
specified terminal torque for a duration of 30 s and then thermo mechanically preconditioned with the
specified continuous cantilever load. The thermo-mechanical preconditioning was performed by
submitting the test samples to a permanent specified long term load (SLL) in four directions and thermal
variations according to the following sequence and temperature values:

After the thermo mechanical preconditioning all three test samples were immersed in a vessel, in boiling
deionized water with 1 kg/m3 of NaCl, for 42 h. At the end of the boiling, the arresters were kept in the
vessel until the water had cooled down to 50°C first and then to ambient temperature. For verification, all
initial measurements were repeated.
Report No.: HBA 11496 P Sheet: 33

8.1 Terminal torque preconditioning on the samples

Terminal torque preconditioning was carried with torque moment of 50Nm on all test samples # 14, #15,
#30.

8.1.1 Exemplary photograph of test sample # 14 and test setup

8.2 Thermomechanical preconditioning (- 40 °C … + 60 °C) on the samples

Test samples # 14, #15 and #30 were submitted to the specified long-term load (SLL) of 617 N in four
directions and in thermal variations of + 60 °C, - 25 °C, + 45 °C and - 40 °C.
Report No.: HBA 11496 P Sheet: 34

8.2.1 Thermomechanical preconditioning test samples # 14

8.2.2 Photograph of test sample # 14 in the climate chamber


Report No.: HBA 11496 P Sheet: 35

8.2.3 Thermomechanical preconditioning test samples #15, #30

8.2.4 Photograph of test sample #15, #30 in the climate chamber


Report No.: HBA 11496 P Sheet: 36

8.2.5 Water immersion test on 3 samples


3
After the previous tests all 3 samples were immersed in a vessel, in boiling deionized water with 1 kg/m
of NaCl, for 42 h.

8.2.6 Photograph of test samples Water immersion test


Report No.: HBA 11496 P Sheet: 37

8.3 Test result

8.3.1 Watt losses measurement

The watt losses were measured at continuous operating voltage (test circuit see sheet-no. 44).

Before the test After the test ∆P / %


Unit-no. (sample) U / kV P/W U / kV P/W ∆P / % required

#14 50.0 0.80 50.0 0.88 +10.0 ≤ 20


#15 50.0 0.86 50.0 0.92 +7.0 ≤ 20
#30 50.0 0.75 50.0 0.81 +8.0 ≤ 20

Test result: Passed. The change in watt losses was below the required value.

8.3.2 Oscillograms of watt losses measurement


Report No.: HBA 11496 P Sheet: 38

8.3.3 Internal partial discharge test

The partial discharge level was measured at 1.05 times the continuous operating voltage before and after
the test (test circuit see sheet-no. 44). The noise level was 0.1 pC.

Before the test After the test PD / pC


Unit-no. (sample) U / kV PD / pC U / kV PD / pC required

# 14 52.5 0.1 52.5 0.1 < 10


#15 52.5 0.1 52.5 0.1 < 10
#30 52.5 0.1 52.5 0.1 < 10

Test result: Passed. The partial discharge level was below the required level.
Report No.: HBA 11496 P Sheet: 39

8.3.4 Residual voltage test

The residual voltage was measured at discharge current of 10 kA, 8/20 µs (test circuit see sheet-no.45).
After the test two successive impulses (50 ... 60 s) at nominal discharge current 10kA were applied.

∆U / %
st
Before the test After test (1 impulse)
Unit-no.
(sample) Waveform Waveform
U / kV I / kA U / kV I / kA ∆U / % required
T1/T2 T1/T2
# 14 173.7 10.1 7.4/18.1 173.3 10.1 7.9/18.1 -0.23 ≤5
#15 175.0 10.1 7.4/18.2 174.4 10.1 7.7/18.2 -0.34 ≤5
#30 174.4 10.1 7.4/18.1 174.3 10.1 7.6/18.1 -0.06 ≤5

∆U / %
nd
After test (2 impulse)
Unit-no.
(sample) Waveform
U / kV I / kA ∆U / % required
T1/T2
# 14 175.9 10.1 7.6/18.2 1.50 ≤5
#15 176.3 10.0 7.5/18.2 1.09 ≤5
#30 175.8 10.0 7.6/18.2 0.86 ≤5

Tolerances of exponential impulse currents according to IEC 62475 (2010):

Test result: Passed. The change in residual voltage was below the required value.
Report No.: HBA 11496 P Sheet: 40

8.3.5 Oscillograms of residual voltage tests


Report No.: HBA 11496 P Sheet: 41

8.4 Reference voltage measurement

Before and after the residual voltage test with two successive impulses the reference voltage was
measured (test circuit see sheet-no. 44).

∆U / %
st nd
Before the 1 impulse After the 2 impulse
Unit-no. (sample) Uref / kV Iref / mA Uref / kV Iref / mA ∆U / % required
# 14 67.2 1.0 67.7 1.0 +0.7 ≤2
#15 68.1 1.0 68.0 1.0 -0.1 ≤2
#30 67.5 1.0 67.8 1.0 +0.4 ≤2

Test result: Passed.


Report No.: HBA 11496 P Sheet: 42

8.4.1 Oscillograms of reference voltage measurement


Report No.: HBA 11496 P Sheet: 43

8.4.2 Photograph of Internal partial discharge test, watt losses measurement, reference
voltage measurement

Please see Item 7.4.3

8.4.3 Test result summary

All Pass criteria were fulfilled:

- The internal partial discharge measured at 1.05 times Uc did not exceed 10 pC
- The increase in watt losses, measured at Uc and at ambient temperature was not more than 20%
- Change of residual voltage measured was not more than 5 % different from the initial
- The difference in voltage between two successive impulses at nominal discharge current did not
exceed 2 %, and the oscillograms of voltage and current did not reveal any partial or full
breakdown of the test sample.
Report No.: HBA 11496 P Sheet: 44

9 Technical data of test circuits

9.1 Internal partial discharge test, watt losses measurement, reference voltage
measurement

Transformer: Rated voltage kV 300


Rated power kVA 60

TS
C
CM

Tr

ZM

AC PD
RSH

u PDLevel i

Tr ... Transformer
TS ... Test sample

CK ... Coupling capacitor CK = 0.62nF


Zm ... Measuring impedance
M ... Measuring instrument Omicron mtronix, MPD 600
(calibration valid until 03/2014)

C ... Calibration pulse generator Omicron mtronix, CAL 542


(calibration valid until 08/2014)

Voltage measurement: u
Capacitive divider: CH = 0.62nF, CN = 29µF (calibration valid until 04/2014)
GLP3

Reference current measurement: i


Shunt RSH = 450Ω (calibration valid until 07/2015.)
GLP3

Test sample: arrester units of type 3EV5 144-0LK12-4ZZ9


Report No.: HBA 11496 P Sheet: 45

9.2 Lightning impulse residual voltage test

Test circuit: Discharge current kA 10


Surge capacitance µF 0.25

Inductance µH 150

Wave shape µs 8/20

L
Uc TG
TS

CH
Cs

CN
RSH

i u

TG ... Trigger spark gap


TS ... Test sample
CS ... Surge capacitor
L ... Inductance
Uc ... Charge voltage

Voltage measurement: u
Capacitive divider: CH = 1.537nF, CN = 1.849µF (calibration valid until 07/2018)
Probe 10:1, Oscilloscope Tektronix TDS 3034 (calibration valid until 01/2015) / PC

Current measurement: i
Shunt RSH = 40.14mΩ (calibration valid until 09/2014)
Probe 10:1, Oscilloscope Tektronix TDS 3034 (calibration valid until 01/2015) / PC

Test sample: arrester units of type 3EV5 144-0LK12-4ZZ9


Report No.: HBA 11501 P Sheet: 2

2 Index

Sheet-no.
1 Test Report ............................................................................................................................................... 1
2 Index ......................................................................................................................................................... 2
3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9 .................................................................... 3
4 Participants of Tests ................................................................................................................................. 4
4.1 Observer: ............................................................................................................................................. 4
4.2 Test engineer: ..................................................................................................................................... 4
5 Dimensional drawings .............................................................................................................................. 5
5.1 Arrester body ....................................................................................................................................... 5
5.2 Arrester accessories (arrester set) ...................................................................................................... 6
6 Visual and structure inspection .............................................................................................................. 10
6.1 Test result Body (based on 8.1.1 KEPCO Specification ITT) ...........................................................10
6.2 Test result Arrester Set (based on 8.2.1 KEPCO Specification ITT) ................................................10
6.3 Photograph of test samples (accessory parts) ..................................................................................11
7 Insulation resistance test ........................................................................................................................ 12
7.1 Test result ..........................................................................................................................................12
7.2 Photographs of test setup .................................................................................................................12
8 Leakage current test............................................................................................................................... 13
8.1 Test result ..........................................................................................................................................13
9 Reference voltage test ........................................................................................................................... 14
9.1 Test result ..........................................................................................................................................14
10 Internal partial discharge test ................................................................................................................. 16
10.1 Internal partial discharge test ............................................................................................................16
11 Discharge withstand current rating test .................................................................................................. 16
11.1 Test results ........................................................................................................................................16
11.2 Photographs of test samples .............................................................................................................21
12 Follow Current Interruption test .............................................................................................................. 22
12.1 Test conditions ..................................................................................................................................22
12.2 Test procedure ..................................................................................................................................23
12.3 Test results ........................................................................................................................................24
13 Technical data of test circuits ................................................................................................................. 35
13.1 Internal partial discharge test, leakage current test, reference voltage measurement .....................35
13.2 Discharge withstand current rating test, Lightning impulse residual voltage test .............................36
13.3 Discharge withstand current rating test, high current impulse test ...................................................37
13.4 Follow current interruption test ..........................................................................................................38
Report No.: HBA 11501 P Sheet: 3

3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9

Rated voltage 144kV

Rated frequency 60Hz

Nominal discharge current 10kA, 2/20µs

Maximum discharge current 30kA, 4/10µs

Maximum residual voltage at rated discharge current (10kA, 2/20µs) 420kV

Maximum residual voltage at discharge current (30kA, 4/10µs) 470kV

Maximum permissible service load, dynamic (MPSL) 882N

Maximum continuous cantilever load, static 617N

Tensile strength 882N


Report No.: HBA 11501 P Sheet: 4

4 Participants of Tests

4.1 Observer:

Mr. Kim Sang-soo Korea Electric Power Corporation

Mr. Choi Hwi Sung Korea Electric Power Corporation

Mr. Yoo KiSung Siemens Ltd. Seoul

4.2 Test engineer:

Mr. Schubert Matthias Siemens AG, E T HP AR R&D 2


Mr. Matthes Raif Siemens AG, E T HP BSS LAB HV
Report No.: HBA 11501 P Sheet: 5

5 Dimensional drawings

5.1 Arrester body


Report No.: HBA 11501 P Sheet: 6

5.2 Arrester accessories (arrester set)

5.2.1 Electrode Angle


Report No.: HBA 11501 P Sheet: 7

5.2.2 Electrode
Report No.: HBA 11501 P Sheet: 8

5.2.3 Mounting angle

MA_D
Report No.: HBA 11501 P Sheet: 9

5.2.4 Setup follow current interruption test


Report No.: HBA 11501 P Sheet: 10

6 Visual and structure inspection

Date of test: 04.03.2014


Test facility: E T HP AR R&D

Appearance and structure of each part of the arrester accessory and bodies have been inspected and the
dimensions have been checked with a slide gauge (500-123UCD15B, calibration valid until 11/14). The
results of the inspection can be seen in the table below. For the dimension indications (EA_A etc.) please
see the attached drawings on sheet no. 5 to 8.

6.1 Test result Body (based on 8.1.1 KEPCO Specification ITT)

Three bodies were measured

Measured Measured
Body part Required Value Tolerance Measured value
value value
(Drawing No.) / mm / mm / mm
/ mm / mm
(802-61398) #17 #32 #33
-5.3
EA_A 510 510 510 510
+0.7

Pass criteria was fulfilled: The results of the inspection was satisfactory.

6.2 Test result Arrester Set (based on 8.2.1 KEPCO Specification ITT)

Body part Required Value Tolerance Measured value Measured value


(Drawing No / mm / mm / mm / mm
(802-61398) #3 #21
-5.3
EA_A 510 510 510
+0.7
Accessory part Required Value Tolerance Measured value Measured value
(Drawing No.) / mm / mm / mm / mm
Electrode Angle
#1 #2
(802-61403)
EA_A 58 ±3 58.52 58.55
EA_B 6 ± 0.5 6.20 6.36
EA_C 60 ±3 60.91 61.47
EA_D 11 ± 0.5 11.26 11.12
Report No.: HBA 11501 P Sheet: 11

Accessory part Required Value Tolerance Measured value Measured value


(Drawing No.) / mm / mm / mm / mm
Electrode
# #
(802-61404)
EL_A 96 ±3 94.81 95.08
EL_B 120 ±3 118.66 119.48
EL_C 20 ±1 19.93 19.87
EL_D 11 ±1 11.00 10.72
EL_E 6 ± 0.5 6.17 6.09
EL_F 9.5 ±1 9.82 9.80
Mounting Angle
# #
(802-61402)
MA_A 10 ±1 10.01 10.08
MA_B 67 ±3 66.38 66.80
MA_C 9 ± 0.5 8.73 8.88
MA_D 15 ±1 14.90 14.92
MA_E 30 ±3 29.93 29.67
MA_F 13 ±1 13.53 13.68
MA_G 40 ±3 40.01 39.90
MA_H 83 ±3 83.06 82.89

Pass criteria was fulfilled: The results of the inspection was satisfactory.

6.3 Photograph of test samples (accessory parts)


Report No.: HBA 11501 P Sheet: 12

7 Insulation resistance test

Date of test: 04.03.2014


Test facility: E T HP AR R&D2

The insulation resistance between both terminals of the arrester body was measured with a 1000V
Megger.

Pass criteria: The results shall be 2000 MΩ or higher.

7.1 Test result

Insulation resistance
Sample
/ Ohm
#17 1.8T
#32 1.7T
#33 1.6T

Pass criteria was fulfilled: The results were higher than 2000 MΩ .

7.2 Photographs of test setup


Report No.: HBA 11501 P Sheet: 13

8 Leakage current test

Date of test: 04.03.2014


Test facility: E T HP AR R&D2

The voltage of peak operation voltage (170kv/√3 / 2) was applied between the arrester body terminals
and the leakage current in a stable condition measured (test circuit see sheet-no. 35).

Pass criteria: Total leakage current Itotal shall be 0.5 mA or less and the resistant leakage current
Iresistive shall be 100 µA or less.

8.1 Test result

Test voltage Itotal Iresistive

Sample / kVrms / mA / µA

#17 49.8 0.30 15


#32 49.6 0.30 15
#33 49.1 0.30 15

Pass criteria were fulfilled: Total leakage current Itotal was less than 0.5 mA and the resistant leakage
current Iresistive was less than 100 µA.

8.1.1 Oscillograms of leakage current test


Report No.: HBA 11501 P Sheet: 14

9 Reference voltage test

Date of test: 04.03.2014


Test facility: E T HP AR R&D2

The reference voltage test was carried out according to paragraph 7.2 of IEC 60099-4. An AC voltage
was applied to the test samples and was increased until the reference current of 1.0 mA was flowing. The
reference voltage Uref,1.0mA was calculated by dividing the voltage peak value by √2. The corresponding
reference voltage at 1 A peak current was calculated from the reference voltage Uref,1.0mA and the voltage-
current characteristic of the arrester according to the following formula (the factor between the reference
voltage at 1.0 mA and 1 A is 1.15): û1A = Uref,1.0mA *√2*nunits*1.15 (test circuit see sheet-no. 35).

Pass criteria: ûref1A ≥ 204kVp (two units in series) equal Uref,1.0mA unit ≥ 62.7 kV

9.1 Test result

Uref1mA Iref Uref1A (two units in series)

Unit-no. (sample) / kVrms / mA / kVpeak

#17 68.6 1.07 223.1


#32 68.1 1.01 221.5
#33 68.8 1.00 223.8

Pass criteria was fulfilled: ûref1A ≥ 204kVp (two units in series)


Report No.: HBA 11501 P Sheet: 15

9.1.1 Oscillograms of reference voltage test


Report No.: HBA 11501 P Sheet: 16

10 Internal partial discharge test

Date of test: 04.03.2014


Test facility: E T HP AR R&D2

The test was performed on three complete arrester units based on paragraph 8.8 of IEC 60099-4 (Internal
partial discharge test). The partial discharge test was performed at a test voltage of 52.5 kV (= 1.05*Uc*)
on complete arrester units. First the power frequency voltage was increased up to the complete arrester
unit equivalent rated voltage (Ur*) of 62.5 kV. Thereafter the voltage was decrease within 10s to the test
voltage of 52.5 kV and the partial discharge level was measured.

10.1 Internal partial discharge test

The partial discharge level was measured at 1.05 times the continuous operating voltage before and after
the test (test circuit see sheet-no. 35). The noise level was 0.06 pC.

Unit-no. (sample) U / kV PD / pC PD / pC required


#17 52.5 0.06 < 10
#32 52.5 0.06 < 10
#33 52.5 0.06 < 10

Pass criteria was fulfilled: The internal partial discharge level did not exceed 10 pC

11 Discharge withstand current rating test


Date of test: 04.03.2014
Test facility: E T HP AR R&D Ü4

The discharge withstand current rating test was carried out on three single metal-oxide resistors (test
circuits see sheet-nos. 22 to 37). The test was performed at a maximum discharge current at 30kA,
4/10µs with one positive and one negative impulse. The time between both impulses was 5 minutes.

Before and after the test the residual voltage at nominal discharge current 10kA, 8/20µs was measured.

11.1 Test results

11.1.1 1 impulse +30kA, 4/10µs

)
I Ures 1 Waveform

Sample no. / kA / kV T1 / T2

1 30.87 17.97 4.0/9.7


2 30.61 18.06 4.0/9.5

3 30.33 17.97 4.1/9.5

1) Ures = Ures, oscilloscope - Ushunt


Report No.: HBA 11501 P Sheet: 17

11.1.2 Oscillograms of impulse +30kA, 4/10µs


Report No.: HBA 11501 P Sheet: 18

11.1.3 1 impulse -30kA, 4/10µs

)
I Ures 1 Waveform

Sample no. / kA / kV T1 / T2

1 -30.73 -18.06 4.1/9.6


2 -30.34 -18.13 4.1/9.5

3 -30.45 -18.10 4.1/9.6

11.1.4 Oscillograms of impulse -30kA, 4/10µs

1) Ures = Ures, oscilloscope - Ushunt


Report No.: HBA 11501 P Sheet: 19

11.1.5 Photograph of test setup current impulse 30kA, 4/10µ


Report No.: HBA 11501 P Sheet: 20

11.1.6 Lightning impulse residual voltage measurement at 10kA, 8/20µs

Before the test After the test


Waveform Waveform ∆U / %
Sample no. I / kA U / kV T1 / T2 I / kA U / kV T1 / T2 ∆U / % required

1 10.19 14.72 8.3/18.3 10.01 14.71 8.6/18.4 - 0.1 ≤5


2 10.10 14.71 8.5/18.2 10.03 14.79 8.5/18.3 + 0.5 ≤5
3 10.14 14.76 8.3/18.4 9.91 14.80 8.4/18.3 + 0.3 ≤5

Tolerances of the specified values for exponential impulse currents are listed in the following table
(according to IEC 62475 (2010):

11.1.7 Test result summary

All Pass criteria were fulfilled: After the test visual inspection of the metal-oxide resistors revealed no
evidence of puncture, flashover or cracking. Change of the residual voltages of all three test samples was
far below the allowed 5%.

11.1.8 Oscillograms of the lightning impulse residual voltage


Report No.: HBA 11501 P Sheet: 21

11.2 Photographs of test samples

before the tests after the tests


Report No.: HBA 11501 P Sheet: 22

12 Follow Current Interruption test


Date of test: 03.03.2014
Test facility: E T HP BSS LAB HV

Background: During the follow current interruption test, the externally gapped line arrester (EGLA) has to
show that it has the capability to cut off the follow current after a sparkover due to lightning.

According to the technical specification of KEPCO, the sample has to be under contaminated condition.
Five impulses of lightning voltage have to be applied for each positive and negative polarity and the cutoff
time has to be lower than 1/2 cycle of power frequency. The required AC voltage is 170/√3 = 98.1 kVeff.
Drawing see sheet no. 9

12.1 Test conditions

Ambient conditions:

Air temperature / °C 21.5


Air pressure / hPa 993
Air humidity / % 23
Density correction factor k1
Humidity correction factor k2
Overall correction factor Kt
Applied correction factor Kt –

Prior to the test, the silicone surface of the arrester bodies (samples #3 and #21) have been abraded to
roughen their surface. To remove the hydrophobicity of the silicone, kaolin powder has been applied
thoroughly on the whole arrester surface, see photo 12.1.1. This treatment leads to a complete wetting of
the arrester surface when applying the contaminant solution.

12.1.1 Photograph of test sample kaolin powder has been applied


Report No.: HBA 11501 P Sheet: 23

The contaminant solution has been prepared according to IEC 60507, clause 13.2 with a salt deposit
density (SDD) of 0.5 mg/cm2, corresponding to a volume conductivity of the contaminant solution of
200 mS/cm. The solution prepared for the test had a volume conductivity of 206 mS/cm

12.1.2 Photograph of test sample contaminant solution

12.2 Test procedure

Prior to the test itself, the arresters with the applied kaolin have been mounted to the insulator device and
the gap distances have been adjusted to the specified values (630 mm). Besides the surface treatment,
all components were in a factory new condition and completely assembled as in service.
After installation, the arresters have been sprayed with the contaminant solution, wetting the whole
silicone surface.

After that, the AC voltage has been raised up to the specified value of 98.1 kVeff and the lightning
impulses were applied. For each test, the voltage and current of the test sample have been measured.

12.2.1 Photograph of test setup


Report No.: HBA 11501 P Sheet: 24

12.3 Test results

All Pass criteria were fulfilled: The test object has passed the follow current interrupting test without
any objection. For each test, including five tests with positive and five with negative polarity, the follow
current cutoff time was far below the required value of 1/2 cycle of the power frequency. The results are
displayed in the following table and the oscillograms on sheets no. 25 to 30.

Applied Applied
polarity
AC lightning cutoff time
Test no. of AC
voltage voltage / ms
voltage
/ kVeff / kVp
POS 1 100 + 900 positive < 1 ms
POS 2 100 + 900 positive < 1 ms
POS 3 100 + 900 positive < 1 ms
POS 4 100 + 900 positive < 1 ms
POS 5 100 + 900 positive < 1 ms

NEG 1 100 - 900 negative < 1 ms


NEG 2 100 - 900 negative < 1 ms
NEG 3 100 - 900 negative < 1 ms
NEG 4 100 - 900 negative < 1 ms
NEG 5 100 - 900 negative < 1 ms
Report No.: HBA 11501 P Sheet: 25

12.3.1 Oscillograms five tests with positive polarity


Report No.: HBA 11501 P Sheet: 26
Report No.: HBA 11501 P Sheet: 27
Report No.: HBA 11501 P Sheet: 28
Report No.: HBA 11501 P Sheet: 29
Report No.: HBA 11501 P Sheet: 30

12.3.2 Oscillograms five tests with negative polarity


Report No.: HBA 11501 P Sheet: 31
Report No.: HBA 11501 P Sheet: 32
Report No.: HBA 11501 P Sheet: 33
Report No.: HBA 11501 P Sheet: 34
Report No.: HBA 11501 P Sheet: 35

13 Technical data of test circuits


13.1 Internal partial discharge test, leakage current test, reference voltage measurement

Transformer: Rated voltage kV 300


Rated power kVA 60

TS
C
CM

Tr

ZM

AC PD
RSH

u PDLevel i

Tr ... Transformer
TS ... Test sample

CK ... Coupling capacitor CK = 0.62nF


Zm ... Measuring impedance
M ... Measuring instrument Omicron mtronix, MPD 600
(calibration valid until 03/2014)

C ... Calibration pulse generator Omicron mtronix, CAL 542


(calibration valid until 08/2014)

Voltage measurement: u
Capacitive divider: CH = 0.62nF, CN = 29µF (calibration valid until 04/2014)
GLP3

Reference current measurement: i


Shunt RSH = 450Ω (calibration valid until 07/2015.)
GLP3

Test sample: arrester units of type 3EV5 144-0LK12-4ZZ9


Report No.: HBA 11501 P Sheet: 36

13.2 Discharge withstand current rating test, Lightning impulse residual voltage test

Test circuit: Discharge current kA 10


Surge capacitance µF 3.7

Inductance µH 12

Wave shape µs 8/20

L
Uc TG
TS RH

Cs

RSH RN

( Ushunt ) ( RN / (RN+RH)*Ures.OSC )

TG ... Trigger spark gap


TS ... Test sample
Cs ... Surge capacitor
L ... Inductance
Uc ... Charge voltage

Voltage measurement: u
Ohmic divider: RH = 3994Ω (calibration valid until 08/2014)
RN = 61.0Ω (calibration valid until 03/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Current measurement: i
Shunt RSH = 40.38mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Test sample: 1 metal-oxide resistor


Report No.: HBA 11501 P Sheet: 37

13.3 Discharge withstand current rating test, high current impulse test

Test circuit: Discharge current kA 30


Surge capacitance µF 11.2

Inductance µH 1

Wave shape µs 4/10

L
Uc TG
TS RH

Cs

RSH RN

i u

TG ... Trigger spark gap


TS ... Test sample
Cs ... Surge capacitor
L ... Inductance
Uc ... Charge voltage

Voltage measurement: u
Ohmic divider: RH = 4394Ω (calibration valid until 04/2014)
RN = 61.0Ω (calibration valid until 03/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Current measurement: i
Shunt RSH = 10.54mΩ (calibration valid until 11/2014)
Probe 10:1, Oscilloscope Tektronix type DPO 4032 (calibration valid until 07/2014) / PC

Test sample: 1 metal-oxide resistor


Report No.: HBA 11501 P Sheet: 38

13.4 Follow current interruption test

Transformer Test Impulse generator


L object GA
RF* RF

TO
GT
CH1 CH2 CH3
T
AP RD

kV
CS
A
CL1 CL2 CL3
M1 Rsh

kV
M2

Essential elements of the test circuit:

T Transformer

AP Protective arrester
L Induction coil (48 mH)
GA Auxiliary gap (rod – rod; 900 mm)

TO Test object (3EV5 144)

CS Surge capacitance
R F, R F* Front resistance
RD Discharge resistance
GT Trigger gap

CH1,CL1 Voltage divider 1, ratio 8012 (calibration valid until 12/2014)


CH2,CL2 Voltage divider 2, ratio 29000 (calibration valid until 12/2015)
CH3,CL3 Voltage divider 3, ratio 679.9 (calibration valid until 12/2014)
Rsh Shunt (51 Ω) (calibration valid until 05/2015)

Measuring device:

M1 Measuring system – test object


M2 Measuring system – test setup
Report No.: HBA 11505 P Sheet: 2

2 Index
Sheet-no.
1 Test Report ................................................................................................................................................. 1
2 Index ........................................................................................................................................................... 2
3 Technical data of the test object ................................................................................................................. 3
4 Drawings of test object ............................................................................................................................... 4
5 Radio interference voltage (RIV) and visible corona test on arrester set ................................................... 6
5.1 Participants of test............................................................................................................................... 6
5.2 Test conditions .................................................................................................................................... 6
5.3 Test results .......................................................................................................................................... 8
5.4 Photos of test object and test circuit .................................................................................................10
5.5 Circuit diagram (Radio interference voltage test) .............................................................................11
6 Power frequency withstand voltage test on arrester set ........................................................................... 12
6.1 Participants of test.............................................................................................................................12
6.2 Test conditions ..................................................................................................................................13
6.3 Test results ........................................................................................................................................14
6.4 Photos of test object and test circuit .................................................................................................15
6.5 Circuit diagram (Power frequency withstand voltage test)................................................................16
7 Switching overvoltage test on arrester set ................................................................................................ 17
7.1 Participants of test.............................................................................................................................17
7.2 Test conditions ..................................................................................................................................17
7.3 Test results ........................................................................................................................................19
7.4 Photos of test object and test circuit .................................................................................................21
7.5 Circuit diagram (Switching overvoltage test).....................................................................................22
8 Lightning impulse insulation coordination test on arrester set .................................................................. 23
8.1 Participants of test.............................................................................................................................23
8.2 Test conditions ..................................................................................................................................23
8.3 Test Results ......................................................................................................................................24
8.4 Circuit diagram (Lightning impulse insulation coordination test).......................................................27
9 Lightning impulse withstand voltage test on body .................................................................................... 28
9.1 Participants of test.............................................................................................................................28
9.2 Test conditions ..................................................................................................................................28
9.3 Test results ........................................................................................................................................29
9.4 Photos of test object..........................................................................................................................29
9.5 Circuit diagram ..................................................................................................................................29
10 Power frequency withstand voltage test on body ..................................................................................... 30
10.1 Participants of test.............................................................................................................................30
10.2 Test conditions ..................................................................................................................................30
10.3 Test results ........................................................................................................................................31
10.4 Photos of test object..........................................................................................................................31
10.5 Circuit diagram ..................................................................................................................................31
Report No.: HBA 11505 P Sheet: 3

3 Technical data of the test object

Rated voltage 144 kV

Rated frequency 60 Hz

Nominal discharge current 10 kA, 2/20 µs

Maximum discharge current 30 kA, 4/10 µs

Maximum residual voltage at rated discharge current (10kA, 2/20µs) 420 kV

Maximum residual voltage at discharge current (30kA, 4/10µs) 470 kV

Maximum permissible service load, dynamic (MPSL) 882 N

Maximum continuous cantilever load, static 617 N

Tensile strength 882 N


Report No.: HBA 11505 P Sheet: 4

4 Drawings of test object


Report No.: HBA 11505 P Sheet: 5
Report No.: HBA 11505 P Sheet: 6

5 Radio interference voltage (RIV) and visible corona test on arrester set
Date and place of test March 6, 2014 Technical University Darmstadt,
High Voltage Test Laboratory

5.1 Participants of test

Observers:

Mr. Kim Sang-Soo Korea Electric Power Corporation

Mr. Choi Hwi Sung Korea Electric Power Corporation

Mr. Yoo KiSung Siemens Ltd. Seoul

Mr. Jin Hong Siemens AG, E T HP AR S 1

Mr. Schubert Matthias Siemens AG, E T HP AR R&D 2

Mr. Soerries Wolfgang Siemens AG, E T HP AR R&D 2

Test engineer:

Dr. Wietoska Thomas Technical University Darmstadt,


High Voltage Test Laboratory

5.2 Test conditions

All components were in a factory new condition and completely assembeled as in service. All gap
distances were adjusted to the specified values (630 mm and 1120 mm).

Ambient conditions:
Table 1: Ambient conditions for RIV and corona test

Tests under dry condition Tests under wet condition


(06.03.2014) (06.03.2014)

Air temperature / °C 18.1 18.1

Air pressure / hPa 1011 1011

Air humidity / g/m³ 5.5 5.5

Density correction factor k1 1.003 1.003

Humidity correction factor k2 0.962 –

Overall correction factor Kt 0.967 1.003

Applied correction factor Kt 1.000 1.003


Report No.: HBA 11505 P Sheet: 7

Wet conditions:
Conductivity of sprayed water: 102 μS/cm
Precipitation rate horiz.: 3.2 mm / min
Precipitation rate vert.: 3.6 mm / min
Spray angle: 45°

5.2.1 Visible corona test

Under dry conditions, 1.2 times the phase-to-ground voltage (1.2 x 170/√3 = 117.8 kV) was applied to the
test sample. Under wet conditions, the phase-to-ground voltage of 170/√3 = 98.1 kV was applied.

While the voltage was applied, the testing hall was completely dimmed. All participants of the test were
not more than approx. 10 m away from the test object.

5.2.2 Radio interference voltage test

The test voltage was at first increased to 1.2 times the phase-to-ground voltage (1.2 x 170/√3 = 117.8
kV). After that, the voltage was lowered to 1.1 x 170/√3, where it was maintained for 5 min.

Based on the method in IEC 60099-4, the voltage was then changed in steps of 9.8 kV (0.1 times the
phase-to-ground voltage). First it was decreased to 0.5 times 170/√3, raised again to 1.05 times 170/√3
for 5 min and finally decreased to 0.5 times 170/√3. At each step, a radio interference measurement was
performed.
Report No.: HBA 11505 P Sheet: 8

5.3 Test results

5.3.1 Visible corona test

Pass criteria was fulfilled: Under both dry and wet conditions, there was no corona visible. The test
object passed the visible corona test without any objection.

5.3.2 Radio interference voltage (RIV) test

Table 2: Measured values for the dry RIV test


Applied voltage Applied
duration Measured
in p.u. of voltage
/ min value / μV
170/√3 / kV
ambient noise – 5.1
1.2 118.0 1 130
1.1 108.0 5 68
1.0 98.1 0.1 17
0.9 88.5 0.1 5.9
0.8 79.0 0.1 5.4
0.7 69.0 0.1 5.3
0.6 59.0 0.1 5.3
0.5 49.1 0.1 5.2
0.6 59.0 0.1 5.3
0.7 69.0 0.1 5.4
0.8 79.0 0.1 5.5
0.9 88.5 0.1 5.8
1.0 98.1 0.1 8.5
1.1 108.0 5 28
1.0 98.1 0.1 8.2
0.9 88.5 0.1 5.7
0.8 79.0 0.1 5.5
0.7 69.0 0.1 5.4
0.6 59.0 0.1 5.3
0.5 49.1 0.1 5.2

Pass criteria was fulfilled: Under dry conditions, the corona noises at test voltage of 118 kV were below
1000 µV (60 dBµV).
Report No.: HBA 11505 P Sheet: 9

Table 3: Measured values for the wet RIV test


Applied Applied
duration Measured
voltage in p.u. voltage
/ min value / μV
of 170/√3 / kV
ambient noise – 5.1
1.2 118.0 1 650
1.1 108.0 5 300
1.0 98.1 1 230
0.9 88.5 0.1 90
0.8 79.0 0.1 46
0.7 69.0 0.1 29
0.6 59.0 0.1 15
0.5 49.1 0.1 9.5
0.6 59.0 0.1 14.5
0.7 69.0 0.1 27
0.8 79.0 0.1 50
0.9 88.5 0.1 75
1.0 98.1 0.1 180
0.9 88.5 0.1 85
0.8 79.0 0.1 45
0.7 69.0 0.1 33
0.6 59.0 0.1 16
0.5 49.1 0.1 9

Pass criteria was fulfilled: Under wet conditions, the corona noises at test voltage of 118 kV were below
31600 µV (90 dBµV).
Report No.: HBA 11505 P Sheet: 10

5.4 Photos of test object and test circuit

Photo 1: Test object (wet condition)

Photo 2: Test circuit


Report No.: HBA 11505 P Sheet: 11

5.5 Circuit diagram (Radio interference voltage test)

Power Generation:

AEG transformer cascade (1200 kV; 16-60 Hz, 1.2 MVA, 4 stages)
Series resistance RS = 10 kΩ

Measurement:

U is measured with
a 1200 kV-Divider (Haefely CW 3000) (C1 = 380 pF; ü = 8000)
and a AC peak voltmeter Haefely 51 with a 75 Ω-coaxial-cable with a length of 20 m

Radio interference voltage (RIV) is measured with


a RIV and PD measurement system Omicron MPD600

The complete AC voltage measuring system is approved according to IEC 60060-2. The calibration
certificate by the national german calibration laboratory for High-Voltage Measuring Equipments has the
calibration mark 360 DKD-K- 15901, 2012-02. (calibration is valid until 2017-02)
Report No.: HBA 11505 P Sheet: 12

6 Power frequency withstand voltage test on arrester set


Date and place of test March 5-6, 2014 Technical University Darmstadt,
High Voltage Test Laboratory

6.1 Participants of test

6.1.1 Power frequency withstand voltage test (dry)

Observers:

Mr. Soerries Wolfgang Siemens AG, E T HP AR R&D 2

Test engineer:

Mr. Psotta Thorsten Technical University Darmstadt,


High Voltage Test Lab

6.1.2 Power frequency withstand voltage test (wet)

Observers:

Mr. Kim Sang-Soo Korea Electric Power Corporation

Mr. Choi Hwi Sung Korea Electric Power Corporation

Mr. Yoo KiSung Siemens Ltd. Seoul

Mr. Jin Hong Siemens AG, E T HP AR S 1

Mr. Schubert Matthias Siemens AG, E T HP AR R&D 2

Mr. Soerries Wolfgang Siemens AG, E T HP AR R&D 2

Test engineer:

Dr. Wietoska Thomas Technical University Darmstadt,


High Voltage Test Laboratory
Report No.: HBA 11505 P Sheet: 13

6.2 Test conditions

All components were in a factory new condition and completely assembeled as in service. All gap
distances were adjusted to the specified values (630 mm and 1120 mm).

Ambient conditions:
Table 4: Ambient conditions for the AC withstand test

Tests under dry condition Tests under wet condition


(05.03.2014) (06.03.2014)

Air temperature / °C 19.4 18.1

Air pressure / hPa 997 1011

Air humidity / g/m³ 5.5 5.5

Density correction factor k1 0.994 1.003

Humidity correction factor k2 0.966 –

Overall correction factor Kt 0.960 1.003

Applied correction factor Kt 1.000 1.003

Wet conditions:
Conductivity of sprayed water: 102 μS/cm
Precipitation rate horiz.: 3.2 mm / min
Precipitation rate vert.: 3.6 mm / min
Spray angle: 45°

Test method:

Under dry condition, the rated voltage of 144 kV was applied to the test sample for one minute (60s). The
test was conducted a second time after shortening the arresters by a wire.

Under wet conditions, the rated voltage of 144 kV was applied to the test sample for 10 seconds. The test
was conducted a second time after shortening the arresters by a wire.
Report No.: HBA 11505 P Sheet: 14

6.3 Test results

Table 4: Test results for the AC withstand test


Test sample condition Test condition Test result
Arrester normal dry, 144 kV, 1 min no flashover
Arrester shorted dry, 144 kV, 1 min no flashover
Arrester normal wet, 144 kV, 10 s no flashover
Arrester shorted wet, 144 kV, 10 s no flashover

Pass criteria was fulfilled: The test object passed the power frequency withstand test without any
objection.
Report No.: HBA 11505 P Sheet: 15

6.4 Photos of test object and test circuit

Photo 3: Test object (with shorted arrester, dry condition)

Photo 4: Test circuit


Report No.: HBA 11505 P Sheet: 16

6.5 Circuit diagram (Power frequency withstand voltage test)

Power Generation:

AEG transformer cascade (1200 kV; 16-60 Hz, 1.2MVA, 4 stages)


Series resistance RS = 10 kΩ

Measurement:

U is measured with
a 1200 kV-Divider (Haefely CW 3000) (C1 = 380 pF; ü = 8000)
and a AC peak voltmeter Haefely 51 with a 75 Ω-coaxial-cable with a length of 20 m

The complete AC voltage measuring system is approved according to IEC 60060-2. The calibration
certificate by the national german calibration laboratory for High-Voltage Measuring Equipments has the
calibration mark 360 DKD-K- 15901, 2012-02. (calibration is valid until 2017-02)
Report No.: HBA 11505 P Sheet: 17

7 Switching overvoltage test on arrester set


Date and place of test March 4, 2014 Technical University Darmstadt,
High Voltage Test Laboratory

7.1 Participants of test

Observers:

Mr. Soerries Wolfgang Siemens AG, E T HP AR R&D 2

Test engineer:

Dr. Wietoska Thomas Technical University Darmstadt,


High Voltage Test Laboratory

7.2 Test conditions

The same test sample as for the preceding power frequency withstand test has been used. All gap
distances were adjusted to the specified values (630 and 1120 mm).

Ambient conditions:

Table 5: Ambient conditions for the switching overvoltage test


Tests under wet condition

Air temperature / °C 18.5


Air pressure / hPa 983
Air humidity / g/m³ 5.8
Density correction factor k1 0.971
Humidity correction factor k2 –
Overall correction factor Kt 0.971
Applied correction factor Kt –

Wet conditions:

Prior to the tests, the precipitation rate of rain was measured. The rain water has been collected for
60 seconds and the precipitation rates have been calculated from the collected volumes.

Conductivity of sprayed water: 96 μS/cm


Precipitation rate horiz.: 3.3 mm / min
Precipitation rate vert.: 3.5 mm / min
Spray angle: 45°
Report No.: HBA 11505 P Sheet: 18

Test method:

The 50 % flashover voltage Ud50 has been determined by the up-and-down method. The standard
deviation ( δ ) is set to be 6 % for 250 / 2500 µs impulses. To calculate the values, the following approach
(after Dixon and Mood) has been used:

1. choice of a starting voltage U00, where no sparkover will occur for sure
2. increasing of the test voltage by a fixed value Δu (7 kV / 12 kV) until the first sparkover occurs.
This first occasion is counted as test no. 1.
3. after the first sparkover, the test voltage is decreased by Δu. If another sparkover occurs, the
voltage is decreased again. If there is no sparkover, the test voltage is increased by Δu. This is
repeated until the total test number of 20 is reached.
4. determination of the occasion (sparkover or withstand) that happened less frequently. The
number of this occasion is k, the number of the complementary occasion q = 20 - k.
5. for the statistical analysis, the voltage levels are assigned to indices i : the level with the first
sparkover is U0, the following U1, U2, U3 etc.
6. the estimates for the 50% flashover voltage Ud50 calculated with the following formulas:

r
A = ∑ iki
i =1

r
B = ∑ i 2 ki (with ki as the number of occasions in the voltage step i)
i =1

U d 50 = u0 + ∆u ( kA ± 12 )

In the formula for Ud50, the prefix + is choosen if the considered occasions are withstands, – if the
occasions are sparkovers.
The lightning impulse withstand voltage UWS is than calculated with the following formula

U10% = U d 50% ⋅ (1 − 2.5 ⋅ δ )


Report No.: HBA 11505 P Sheet: 19

7.3 Test results

Table 6: Test result overview for the switching overvoltage test

Ud50 * Ud10 * tested tested value, required


Test condition value corrected value
/ kV / kV UWS /kV UWS /kV UWS /kV
Arrester normal, positive voltage +558 +474 +470 +485 +458
Arrester normal, negative voltage -538 -457 -466 -480 -458

Arrester shorted, positive voltage +354 +301 +347 +358 +347


Arrester shorted, negative voltage -368 -313 -340 -351 -347
* calculated values

Test results for the test with positive voltage and normal arresters

Test results for the test with negative voltage and normal arresters

Pass criteria was fulfilled: The withstand voltages UWS of the arrester in normal condition were above
the required values of ± 458 kV. UWS = V WS [=V 50x(1-3σ )]
Report No.: HBA 11505 P Sheet: 20

Test results for the test with positive voltage and shorted arresters

Test results for the test with negative voltage and shorted arresters

Pass criteria was fulfilled: The withstand voltages UWS of the arrester in shorted condition were above
the required values of ± 347 kV. UWS = V WS [=V 50x(1-3σ )]
Report No.: HBA 11505 P Sheet: 21

7.4 Photos of test object and test circuit

Photo 5: Test object (with shorted arrester)

Photo 6: Test circuit


Report No.: HBA 11505 P Sheet: 22

7.5 Circuit diagram (Switching overvoltage test)

Power Generation SI:

Haefely-Generator (3200 kV; 80 kWs; 16 stages)


Surge capacitance CS = 15.6 nF
Discharge resistance RE = 320 kΩ
Internal damping resistance Ri = 220 Ω
Front resistance Rd = 43 kΩ (l = 8 m)

Measurement SI:

U is measured with
a 2 MV-Divider (Haefely CR 3000) (C1 = 1 nF; R1 = 114 Ω; ü = 2712.2)
a 75 Ω-coaxial cable with a length of 30 m
and a Highvolt Digital-Recorder MIA 200-12/2B with an input divider of 200:1

The complete switching impulse voltage measuring system is approved according to IEC 60060-2. The
calibration certificate by the national german calibration laboratory for High-Voltage Measuring
Equipments has the calibration mark 358 DKD-K- 15901, 2012-02. (calibration is valid until 2017-02)
Report No.: HBA 11505 P Sheet: 23

8 Lightning impulse insulation coordination test on arrester set


Date and place of test March 6, 2014 Technical University Darmstadt,
High Voltage Test Laboratory

8.1 Participants of test

Observers:

Mr. Kim Sang-Soo Korea Electric Power Corporation

Mr. Choi Hwi Sung Korea Electric Power Corporation

Mr. Yoo KiSung Siemens Ltd. Seoul

Mr. Jin Hong Siemens AG, E T HP AR S 1

Mr. Schubert Matthias Siemens AG, E T HP AR R&D 2

Mr. Soerries Wolfgang Siemens AG, E T HP AR R&D 2

Test engineer:

Dr. Wietoska Thomas Technical University Darmstadt,


High Voltage Test Laboratory

8.2 Test conditions

The same test sample as for the preceding switching overvoltage test has been used. All gap distances
were adjusted to the specified values (630 and 1120 mm).

Ambient conditions:

Table 7: Ambient conditions for the lightning impulse insulation coordination test
Tests under wet condition

Air temperature / °C 18.1

Air pressure / hPa 1011

Air humidity / g/m³ 5.5

Density correction factor k1 1.003

Humidity correction factor k2 –

Overall correction factor Kt 1.003

Applied correction factor Kt –


Report No.: HBA 11505 P Sheet: 24

Wet conditions:
Conductivity of sprayed water: 102 μS/cm
Precipitation rate horiz.: 3.2 mm / min
Precipitation rate vert.: 3.6 mm / min
Spray angle: 45°

Test method:

Lightning voltage impulses with a rate of rise greater than 1.500 kV/µs have been applied five times for
both positive and negative polarity. All fashovers shall only occur in the series gap of the arrester.

8.3 Test Results

Table 8: Test results for the lightning impulse coordination test


û rise time t1 rate of rise flashover
Test condition Osc. no.
/ kV / μs / kV/μs location

Arrester normal, at EGLA series


- 1372 0.83 1653 1
negative voltage gap
Arrester normal, at EGLA series
- 1375 0.83 1656 2
negative voltage gap
Arrester normal, at EGLA series
- 1386 0.84 1650 3
negative voltage gap
Arrester normal, at EGLA series
- 1386 0.85 1630 4
negative voltage gap
Arrester normal, at EGLA series
- 1360 0.82 1658 5
negative voltage gap
Arrester normal, at EGLA series
+ 1347 0.82 1643 1
positive voltage gap
Arrester normal, at EGLA series
+ 1353 0.82 1650 2
positive voltage gap
Arrester normal, at EGLA series
+ 1342 0.81 1656 3
positive voltage gap
Arrester normal, at EGLA series
+ 1341 0.81 1655 4
positive voltage gap
Arrester normal, at EGLA series
+ 1371 0.85 1612 5
positive voltage gap

Pass criteria was fulfilled: Flashover occurred only in the series gap. The tested sample was set to the
minimum arcing horn interval and insulation gap interval supposed in actual use.
Report No.: HBA 11505 P Sheet: 25

8.3.1 Oscillograms
Report No.: HBA 11505 P Sheet: 26
Report No.: HBA 11505 P Sheet: 27

8.4 Circuit diagram (Lightning impulse insulation coordination test)

Power Generation LI:

Haefely-Generator (3200 kV; 80 kWs; 16 stages)


Surge capacitance CS = 15.6 nF
Discharge resistance RE = 4.8 kΩ
Internal damping resistance Ri = 220 Ω

Measurement LI:

U is measured with
a 3 MV-Divider (Haefely CZ 3000) (C1 = 250 pF; R1 = 900 Ω; ü = 2370.4)
a 75 Ω-coaxial cable with a length of 30 m
and a Highvolt Digital-Recorder MIA 200-12/2B with an input divider of 200:1.

The complete lightning impulse voltage measuring system is approved according to IEC 60060-2. The
calibration certificate by the national german calibration laboratory for High-Voltage Measuring
Equipments has the calibration mark 359 DKD-K-15901, 2012-02. (calibration is valid until 2017-02)
Report No.: HBA 11505 P Sheet: 28

9 Lightning impulse withstand voltage test on body

Date and place of test March 7, 2014 Technical University Darmstadt,


High Voltage Test Laboratory

9.1 Participants of test

Observers:

Mr. Kim Sang-Soo Korea Electric Power Corporation

Mr. Choi Hwi Sung Korea Electric Power Corporation

Mr. Yoo KiSung Siemens Ltd. Seoul

Mr. Jin Hong Siemens AG, E T HP AR S 1

Mr. Schubert Matthias Siemens AG, E T HP AR R&D 2

Mr. Soerries Wolfgang Siemens AG, E T HP AR R&D 2

Test engineer:

Dr. Wietoska Thomas Technical University Darmstadt,


High Voltage Test Laboratory

9.2 Test conditions

The lightning impulse withstand test was performed on a single arrester body without MOV blocks.

The arrester body was installed at the complete arrester set, replacing one active part. The remaining
second active part and the spark gap were short circuited.

Five impulses of both positive and negative polarity were applied.

Ambient conditions:

Table 9: Ambient conditions for the lightning impulse withstand test


Tests under dry condition

Air temperature / °C 18.5

Air pressure / hPa 1008

Air humidity / g/m³ 5.4

Density correction factor k1 1.002

Humidity correction factor k2 0.963

Overall correction factor Kt 0.965

Applied correction factor Kt 1.000


Report No.: HBA 11505 P Sheet: 29

9.3 Test results

Table 10: Test results for the Lightning impulse withstand test
Test result
Test voltage /
Test condition number of impulses /
[kV]
disruptive discharges
Negative voltage -310 5/0
Positive voltage +310 5/0

Pass criteria was fulfilled: No flashovers occured per polarity. The required lightning voltage impulse of
488 kV (1.2×50µs) for two bodys or 244 kV for one body was fulfilled. The specified lightning impulse
withstand voltage of ± 310 kV (for one unit) was verified.

9.4 Photos of test object

Photo 7: Test object (lower active part and spark gap short circuited)

9.5 Circuit diagram

The same test setup as for the lightning impulse insulation coordination test was used (see 8.4)
Report No.: HBA 11505 P Sheet: 30

10 Power frequency withstand voltage test on body

Date and place of test March 7, 2014 Technical University Darmstadt,


High Voltage Test Laboratory

10.1 Participants of test

Observers:

Mr. Kim Sang-Soo Korea Electric Power Corporation

Mr. Choi Hwi Sung Korea Electric Power Corporation

Mr. Yoo KiSung Siemens Ltd. Seoul

Mr. Jin Hong Siemens AG, E T HP AR S 1

Mr. Schubert Matthias Siemens AG, E T HP AR R&D 2

Mr. Soerries Wolfgang Siemens AG, E T HP AR R&D 2

Test engineer:

Dr. Wietoska Thomas Technical University Darmstadt,


High Voltage Test Laboratory

10.2 Test conditions

The power frequency withstand test was performed on a single arrester body without MOV blocks.

The arrester body was installed at the complete arrester set, replacing one active part. The remaining
second active part and the spark gap were short circuited.

Ambient conditions:
Table 91: Ambient conditions for power frequency withstand test

Tests under dry condition Tests under wet condition

Air temperature / °C 18.5 18.5

Air pressure / hPa 1008 1008

Air humidity / g/m³ 5.4 5.4

Density correction factor k1 1.002 1.002

Humidity correction factor k2 0.963 –

Overall correction factor Kt 0.965 1.002

Applied correction factor Kt 1.000 1.002


Report No.: HBA 11505 P Sheet: 31

Wet conditions:
Conductivity of sprayed water: 99 μS/cm
Precipitation rate horiz.: 3.2 mm / min
Precipitation rate vert.: 3.6 mm / min
Spray angle: 45°

Test method:

Under dry condition, the test voltage of 100 kV was applied to the test sample for one minute (60 s).

Under wet conditions, the test voltage of 144 kV was applied to the test sample for 10 seconds.

10.3 Test results

Table 12: Test results for the AC withstand test (body)


Test condition Test voltage Test result
Power frequency (dry) 100 kV, 1 min no flashover
Power frequency (wet) 100 kV, 10 s no flashover

Pass criteria was fulfilled: The required power frequency withstand voltage of 100 kV (for one unit) was
verified.

10.4 Photos of test object

Photo 8: Test object (lower active part and spark gap short circuited)

10.5 Circuit diagram

The same test setup as for the power frequency withstand test (on complete arrester) was used (see 6.5)
Report No.: HBA 11506 P Sheet: 2

2 Index

Sheet-no.
1 Test Report ............................................................................................................................................... 1
2 Index ......................................................................................................................................................... 2
3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9 .................................................................... 3
4 Dimensional drawings arrester of accessories (arrester set) ................................................................... 4
4.1 Mounting angle, drawing no. 802-62518 ............................................................................................. 4
4.2 Electrode angle (short) L=58”, drawing no. 802-62519 ...................................................................... 5
4.3 Electrode angle (long) L=204”, drawing no. 802-62520 ...................................................................... 6
4.4 Electrode (short) L= 120”, drawing no. 802-62521 ............................................................................. 7
4.5 Electrode (long) L=193”, drawing no. 802-62522................................................................................ 8
5 Visual and structure inspection ................................................................................................................ 9
5.1 Test result ............................................................................................................................................ 9
6 Galvanizing test ...................................................................................................................................... 12
6.1 Test liquid was preparation ...............................................................................................................12
6.2 Parts before test ................................................................................................................................13
6.3 Operation ...........................................................................................................................................13
6.4 Parts in the test solution ....................................................................................................................14
6.5 Parts in after test ...............................................................................................................................14
6.6 Test result copper sulfate test ...........................................................................................................15
6.7 Test result hot dip galvanized coatings adhesion quantity test ........................................................15
6.8 Test result summary ..........................................................................................................................15
Report No.: HBA 11506 P Sheet: 3

3 Technical data of the arrester type 3EV5 144-0LK12-4ZZ9

Rated voltage 144kV

Rated frequency 60Hz

Nominal discharge current 10kA, 2/20µs

Maximum discharge current 30kA, 4/10µs

Maximum residual voltage at rated discharge current (10kA, 2/20µs) 420kV

Maximum residual voltage at discharge current (30kA, 4/10µs) 470kV

Maximum permissible service load, dynamic (MPSL) 882N

Maximum continuous cantilever load, static 617N

Tensile strength 882N


Report No.: HBA 11506 P Sheet: 4

4 Dimensional drawings arrester of accessories (arrester set)

4.1 Mounting angle, drawing no. 802-62518


Report No.: HBA 11506 P Sheet: 5

4.2 Electrode angle (short) L=58”, drawing no. 802-62519


Report No.: HBA 11506 P Sheet: 6

4.3 Electrode angle (long) L=204”, drawing no. 802-62520


Report No.: HBA 11506 P Sheet: 7

4.4 Electrode (short) L= 120”, drawing no. 802-62521


Report No.: HBA 11506 P Sheet: 8

4.5 Electrode (long) L=193”, drawing no. 802-62522


Report No.: HBA 11506 P Sheet: 9

5 Visual and structure inspection

Date of test: 05.03.2014


Test facility: Siemens Surge Arresters Limited, Test Laboratory

Appearance and structure of the arrester accessory have been inspected and the dimensions have been
checked. The results of the inspection can be seen in the tables below. For the dimension indications
please see the attached drawings on sheet no. 4 to 8.

5.1 Test result

Pass criteria was fulfilled: The results of the inspection was satisfactory.

Dimensional Check 802-62518


"3EV5 Mounting Angle"
Dimension / mm
A B C D E
#
83 ± 1 mm 10 ± 0.5 mm 30 ± 0.5 mm 40 ± 1 mm Ø13.5 +1, -0
Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2
1 82.3 83.1 10.3 10.0 29.8 30.0 39.9 40.0 13.7 13.9
2 82.9 82.3 10.1 10.2 30.2 30.0 39.9 39.9 13.7 13.7
3 82.8 82.6 10.2 10.2 30.1 30.0 40.1 39.8 13.9 13.8
4 82.7 83.0 10.1 10.3 30.1 30.0 39.9 40.1 14.0 13.8
5 82.6 83.2 10.2 10.3 30.0 29.9 39.8 39.9 13.8 13.9
6 82.4 83.0 10.4 10.3 30.1 30.0 40.0 40.2 13.8 13.8
7 83.1 83.2 10.2 10.2 29.8 29.8 40.0 40.0 13.8 13.7
8 83.0 82.7 10.3 10.2 30.0 29.9 40.0 39.8 13.9 13.7
9 82.3 82.6 10.2 10.1 30.0 29.8 39.9 39.8 13.9 13.7
10 82.8 83.1 10.5 10.4 30.0 30.0 40.0 40.0 13.8 13.7
11 82.9 82.3 10.2 10.2 30.0 30.0 40.0 39.9 14.0 13.7
12 83.0 82.8 10.1 10.4 30.2 30.0 40.0 40.1 14.0 13.7
13 82.8 83.7 10.4 10.3 29.9 30.1 40.2 40.0 13.7 13.8
14 82.6 82.8 10.4 10.2 30.1 29.9 39.9 39.9 13.7 13.8
15 82.8 83.6 10.3 10.3 30.1 30.2 40.0 40.2 13.9 13.6
16 82.7 82.6 10.1 10.2 29.9 29.9 39.9 39.9 13.9 13.8
17 82.9 82.5 10.2 10.2 29.9 30.0 39.9 40.0 13.8 13.7
18 83.4 82.5 10.2 10.1 30.2 30.0 40.1 39.8 13.9 13.8
19 82.7 82.4 10.2 10.1 29.9 29.9 40.1 39.9 13.8 13.8
20 82.5 82.5 10.3 10.2 29.9 30.0 39.9 39.7 13.8 13.8
Report No.: HBA 11506 P Sheet: 10

Dimensional Check 802-62519


"3EV5 Electrode Angle, L = 58 mm"
Dimension / mm
A B C
#
58 ± 1 mm 6 ± 0.5 mm 60 ± 1 mm
Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2
1 58.3 58.6 6.3 6.1 60.4 59.6
2 58.4 58.1 6.3 6.1 60.3 60.1
3 58.1 58.6 6.3 6.1 60.5 60.5
4 58.4 58.4 6.4 6.2 60.7 60.7
5 58.5 58.3 6.3 6.2 60.8 60.7
6 58.4 58.4 6.2 6.2 60.4 60.5
7 58.3 58.3 6.2 6.1 60.4 60.6
8 58.3 58.3 6.3 6.2 60.6 60.0
9 58.5 58.3 6.2 6.2 60.3 60.5
10 59.0 58.7 6.2 6.2 60.2 60.4
11 58.6 58.5 6.2 6.2 60.4 60.6
12 58.2 58.5 6.1 6.2 60.1 60.1
13 58.2 58.2 6.1 6.3 61.0 60.1
14 58.7 58.2 6.2 6.1 60.3 59.9
15 58.6 58.7 6.3 6.4 60.6 60.4
16 58.1 58.3 6.2 6.1 60.3 60.3
17 58.5 58.4 6.2 6.1 60.3 59.3

Dimensional Check 802-62520


"3EV5 Electrode Angle, L = 204 mm"
Dimension / mm
A B C
#
204 ± 2 mm 6 ± 0.5 mm 60 ± 1 mm
Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2
1 202.3 203.1 6.1 6.1 60.7 60.6
2 203.6 202.5 6.3 6.2 60.3 61.0
3 203.8 203.0 6.2 6.2 61.0 60.5
Report No.: HBA 11506 P Sheet: 11

Dimensional Check 802-62521 "3EV5 Electrode


120 mm"
Dimension / mm
L A B C
#
120 ± 1.2 mm 20 ± 0.5 mm 6 ± 0.5 mm 95.5 ± 1 mm
Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2
1 119.8 119.7 19.6 19.8 6.1 6.0 95.1 94.8
2 119.6 120.0 19.7 19.9 6.1 6.1 94.9 95.3
3 119.4 119.8 19.6 19.6 6.0 6.0 95.0 95.0
4 119.6 119.7 20.1 19.6 6.0 6.1 94.8 95.1
5 119.7 119.7 19.7 19.5 6.1 6.1 94.9 95.0
6 119.4 119.8 19.5 19.9 6.0 6.1 95.0 94.9
7 120.1 119.8 19.5 19.7 6.1 6.1 95.2 94.8
8 119.8 119.8 19.5 19.7 6.0 6.2 95.1 95.0
9 119.4 119.8 19.6 19.6 6.0 6.1 94.9 95.1
10 119.8 119.5 19.5 19.6 6.2 6.1 95.1 94.7
11 120.1 120.0 19.5 19.5 6.1 6.2 95.4 95.2
12 119.6 119.9 20.3 19.5 6.2 6.1 94.8 94.9

Dimensional Check 802-62522 "3EV5 Electrode


193 mm"
Dimension / mm
L A B C
#
193 ± 1,2 mm 20 ± 0.5 mm 6 ± 0.5 mm 95.5 ± 1 mm
Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2 Unit 1 Unit 2
1 192.3 192.2 19.7 19.5 6.1 6.1 95.1 95.2
2 192.0 192.5 19.9 19.7 6.1 6.1 95.3 95.5
3 192.1 192.4 19.8 19.7 6.2 6.1 95.1 95.2
4 192.2 192.1 19.9 19.5 6.0 6.1 95.3 95.4
5 192.2 192.7 19.7 20.0 6.1 6.2 95.1 95.4
6 192.6 191.9 19.7 19.8 6.2 6.2 95.2 95.0
7 192.5 192.1 19.8 20.0 6.1 6.2 95.5 95.1
8 192.1 192.1 19.6 19.7 6.2 6.1 95.1 95.2
Report No.: HBA 11506 P Sheet: 12

6 Galvanizing test

Date of test: 04.03.2014


Test facility: Siemens Surge Arresters Limited, Test Laboratory

The Galvanizing test was performed as coating mass test with direct method according to Item 4.1, KS
D0201:2011 as well as copper sulfate test according to KS D0201:2011.

6.1 Test liquid was preparation

For the copper sulfate test first the test liquid was prepared according to requirement of D0201 Item 5.2
Two times copper sulfate of 360g was mixed with two times distilled water of 1 liter:

After heating and dissolving it, 2g cupric hydroxide was mixed for the 2 Liters test liquid. Then, after
leaving it for 24 hours, it was filtered to get the test solution.
Report No.: HBA 11506 P Sheet: 13

6.2 Parts before test

6.3 Operation

The washed test pieces were immersed in the test solution for 1 min. Immediately after their were taking
out, washed in water and copper on the plating were removed with a brush.
This procedure was repeated five times.
Report No.: HBA 11506 P Sheet: 14

6.4 Parts in the test solution

6.5 Parts in after test


Report No.: HBA 11506 P Sheet: 15

6.6 Test result copper sulfate test

For the parts drawing nos. 802-62521 and 802-62522 the surface was still in good condition and shinning.
For the parts drawing nos. 802-62518, 802-62519 and 802-62520 the surface was black, but no copper
on the surface was visible and the measured thickness of zinc was still more than 70µm.

6.7 Test result hot dip galvanized coatings adhesion quantity test

Total Surface
Drawing No. Sample No. Before Coating After Coating Coating Weight Coating Mass
Area
/g /g /g mm2 g/m2
1 69.68 72.34 2.66 5250 506.7
802-62521 2 68.76 71.44 2.68 5250 510.5
3 69.25 71.92 2.67 5250 508.6
1 238.32 243.26 4.94 9750 506.7
802-62522 2 239.19 244.38 5.19 9750 532.3
3 235.42 240.71 5.29 9750 542.6
1 96.1 99.95 3.85 7170 537.0
802-62519 2 95.56 99.21 3.65 7170 509.1
3 96.04 99.68 3.64 7170 507.7
1 222.38 229.85 7.47 14760 506.1
802-62520 2 225.84 234.26 8.42 14760 570.5
3 226.94 235.55 8.61 14760 583.3
1 322.36 329.09 6.73 13020 516.9
802-62518 2 321.58 328.47 6.89 13020 529.2
3 321.77 328.68 6.91 13020 530.7

6.8 Test result summary

Pass criteria were fulfilled: No termination point was reached have 5 times application of test solution.
2
The required coating mass of minimum 505 g/m was fulfilled.
Test Report No. 313d E Page 1 of 7

Fachgebiet
Hochspannungstechnik

TEST REPORT No. 313d E

Weather Aging Test, Series A according to standard IEC 60099-4, Ed.


2.2, Clause 10.8.14

Accelerated aging test with exposure to salt fog, according to standard


IEEE C62.11-2005, Clause 8.7

(1000-h-salt-fog-test)

Device under test:


Series Varistor Unit (SVU) of Externally Gapped Line Arrester
(EGLA) Type 3EV5
manufactured by

Siemens Surge Arresters Limited


Test result: The SVU of EGLA Type 3EV5
has passed the test.
Customer: Siemens AG, E T HP AR R&D, Berlin / Germany
Test period: November to December, 2011
Test Engineer: Dipl.-Ing. Torsten Psotta (TU Darmstadt)

Darmstadt, February 22nd, 2012

Dipl.-Ing. Torsten Psotta Prof. Dr.-Ing. Volker Hinrichsen

Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 2 of 7

1 Tests performed

A Weather Aging Test, Series A according to standard IEC 60099-4, Ed. 2.2, Clause 10.8.14
and standard IEEE C62.11-2005, Clause 8.7 was performed on the following metal-oxide
surge arrester:

Manufacturer: Siemens Surge Arresters Limited


Type: 3EV5 (identical in construction with arrester 3EK7 600-4CK4)
Date of manufacture: 10/2011
MCOV(Uc): 48 kV
Creepage distance: 1595 mm
Number of test samples: 1, serial number: 22

For identification of the test sample see figure 2.1 (dimension drawing, Section 2).

The test consists of a 1000 h salt fog application while the arrester is energized at a test
voltage of U = 48 kV. The test was performed with a salt mass concentration of 10 kg/m³ at
the beginning. Because of flashovers on other arresters inside the test chamber, the salt
mass concentration was first reduced to 5 kg/m³ after 170 hours and then to 2,5 kg/m³ after
415 hours.

This test shall confirm that there is no tracking or erosion on the surface of the SVU housing
that may impair the EGLA's operating performance.

During the test, the peak values of the surface current (maximum values within 15-minute-
intervals) were recorded by a computer aided data acquisition system.

Before and after the test, following arrester characteristics were measured for the purpose of
test evaluation:

 reference voltage at 1,5 mA peak current (a.c.),


 partial discharge level.

Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 3 of 7

2 Drawing of the test sample 3EV5 (identical with arrester 3EK7 600-4CK4)

Fig.2.1: Drawing 3EK7

Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 4 of 7

3 Test setup with test samples

Fig. 3.1: Top view of the test chamber

Technical data of the test chamber:


 Volume: 14.8 m3
 Total water flow rate of salt fog: 1,83 ml/h per 8000 mm² measuring area, generated by
one air humidifiers of a water flow rate of 3.0 l/h

Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 5 of 7

Fig. 3.2: Electrical test circuit

Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 6 of 7

4 Test results

4.1 Photograph of the test sample after test

Fig. 4.1: Arrester 22 after the 1000 h test

4.2 Visual inspection


No tracking or erosion or any other damage of the housing could be found.

4.3 Evaluation of surface currents

Diagram Figure 4.2 shows the recorded surface current peak values within 15-minute-
intervals each.

Fig. 4.46: Surface current peak values of arrester 22 (15-minute-intervals)

Fachgebiet
Hochspannungstechnik
Test Report No. 313d E Page 7 of 7

4.4 Electrical characterization before and after test

Before and after the test, the reference voltage (rms) at 1,5 mA peak current and the partial
discharge level were measured for purpose of test evaluation.

Results are shown in the tables below:

Characterization before test:

22
îref 1,5 mA
Uref 61,5 kV
PD level at U = 50,4 kV < 10pC

Characterization after test:

22
îref 1,5 mA
Uref 61,6 kV
PD level at U = 50,4 kV < 10pC

The reference voltage has increased by 0,2 %.

The partial discharge level measured at U = 50,4 kV before and after the test is < 10 pC and
thus fulfils the requirements.

The pass criteria of IEC 60099-4, Ed. 2.2, Clause 10.8.14 and IEEE C62.11-2005, 8.7 are
fulfilled.

4.5 Conclusion

The SVU type Siemens 3EV5 has passed the test.

Fachgebiet
Hochspannungstechnik
Test Report No. 351 E Page 1 of 4

Fachgebiet
Hochspannungstechnik

TEST REPORT No. 351 E

Accelerated aging by exposure to light according to standards


ASTM G154 – 12a (Cycle 1, Table X2.1),
ASTM D750, IEEE C62 11-2012

Device under test:


Series Varistor Unit (SVU) of Externally Gapped Line Arrester
(EGLA) Type 3EV5

manufactured by Siemens Surge Arresters Limited

Test result: The SVU of EGLA Type 3EV5


has passed the test.

Customer: Siemens AG, Energy Sector


Test period: January 2014 until March 2014
Test Engineer: Dipl.-Ing. Maximilian Secklehner (TU Darmstadt)

Darmstadt, March 06, 2014

Dipl.-Ing. Maximilian Secklehner Prof. Dr.-Ing. Volker Hinrichsen

Fachgebiet
Hochspannungstechnik
Test Report No. 351 E Page 2 of 4

1 Test objective

The test objective was the artificial weathering of silicone rubber sheds according to
ASTM G154 – 12a, as proposed in IEEE C62 11-2012, clause 8.6.1.2 c).
For evaluation of the degradation behavior of the material a visual evaluation was performed
at the beginning and the end of the test, as proposed in ASTM D750, clause 7.1.1. For
passing the test according to IEEE C62 11-2012, clause 8.6.1.3 there shall be no cracking of
any sample’s surface to depths greater than 0.1 mm.
Six semi-circular silicone rubber sheds of the surge arrester 3EV5 were tested.

2 Performed Tests

The tests were performed in a weathering tester of type Q-Lab QUV/se. Irradiation is
achieved by means of fluorescent UVA-340-lamps. Wetting of the specimens is achieved by
condensation.
The artificial weathering test was run for 1000 hours.
The test specimens were examined according to ASTM G154 – 12a, Cycle 1, Table X2.1.
The test parameters are shown in Table 1.

Table 1: Test Parameters

duration per cycle: 8 h,


UV Light exposure
temperature: 60 (±3) °C (black panel temperature)
duration per cycle: 4 h,
Condensation phase
temperature: 50 (±3) °C (black panel temperature)

Typical irradiance 0.89 W/m²/nm

Approximate wavelength 340 nm

test duration 1000 h

Fachgebiet
Hochspannungstechnik
Test Report No. 351 E Page 3 of 4

3 Test Results

Photographs of the test specimen were taken before and after the test. The state before the
test is documented in Figures 1 to 3, the state after the test is shown in Figures 4 to 6. Visual
evaluation of the specimen’s surfaces did not show any abnormalities in the form of surface
or colour changes or cracks.

Figure 1: Specimen 1 (top) and Figure 2: Specimen 3 (top) and Figure 3: Specimen 5 (top) and
2 (bottom) before testing 4 (bottom) before testing 6 (bottom) before testing

Fachgebiet
Hochspannungstechnik
Test Report No. 351 E Page 4 of 4

Figure 4: Specimen 1 (top) and Figure 5: Specimen 3 (top) and Figure 6: Specimen 5 (top) and
2 (bottom) after testing 4 (bottom) after testing 6 (bottom) after testing

4 Summary

The weathering test of the silicone rubber sheds of the surge arrester 3EV5 according to
ASTM G154 – 12a, as proposed in IEEE C62 11-2012, clause 8.6.1.2 c) is passed.

Fachgebiet
Hochspannungstechnik
Report No.: 14-021-HS Sheet: 2

Notes

1. The testing station of the Siemens switchgear factory (Prüffeld der Schaltwerke), Siemens AG, Berlin, has been
approved by the DAkkS (German accreditation body) for rendering the following testing services:
mechanical tests,
temperature rise tests,
environment tests,
dielectric tests and
power tests (e.g. switching capacity, load switching, short-time current tests, etc.)
on high-voltage switchgear and controlgear and on power engineering equipment.
The approval was given under registration no. D-PL-11055-10. Testing services beyond the scope certified
cannot be regarded as testing services of an approved testing station. No test documents will be made out for
them.
2. In the Prüffeld der Schaltwerke, Siemens AG, Berlin, all tests will be carried out according to EN ISO/IEC 17025
and the pertinent international and national test specifications. Moreover, all criteria specified by the accreditation
authority will be taken into account in the tests.
3. The Prüffeld der Schaltwerke, Siemens AG, Berlin, points out that its accreditation or its test documents do not
imply that the accreditation authority or another authority have acknowledged the product tested.
4. Test documents or parts thereof may not be used or released by the purchaser for advertising purposes if the
accreditation authority considers their use as misleading. Reproduction in extracts of the test documents is
acceptable only on condition of the prior consent of the Prüffeld der Schaltwerke, Siemens AG, Berlin. Copying
the cover sheet and sheet 2 is an exception.
If test documents or extracts thereof are to be used for advertising purpose or publication, the agreement of the
Prüffeld der Schaltwerke, Siemens AG, Berlin, must be obtained in due time before utilization. If necessary, the
Prüffeld der Schaltwerke, Siemens AG, Berlin, will obtain the accreditation authority’s consent.
5. If reference is to be made in one way or other to the utilization of the Prüffeld der Schaltwerke, Siemens AG,
Berlin, as approved testing laboratory, this shall be worded as follows:
"Testing by the Testing Station of Siemens Schaltwerke Berlin, which is accredited by the DAkkS (German
accreditation body) for tests on high-voltage switchgear and controlgear and power engineering equipment under
registration No. D-PL-11055-10."
6. The Prüffeld der Schaltwerke applies the internal procedure PSW-IA 020 for determining the uncertainties of
measurement. As long as no explicit statements are made, the uncertainties required by the relevant standards
have been complied with.

Addresses

Testing Station: Prüffeld der Schaltwerke


Siemens AG
E T HP BSS LAB HP
Nonnendammallee 104
13629 Berlin
Germany

Manufacturer: Siemens Surge Arrester Limited


B-2 Building, No.43 Ximei Road, B22-A Plot,
Wuxi National Hi-Tech Industry Development Zone
214028 Jiangsu, PRC

Client: Siemens AG
E T HP AR R&D 2
Nonnendammallee 104
13629 Berlin
Germany

201SE1108
Report No.: 14-021-HS Sheet: 3

Table of Contents

Cover Sheet ............................................................................................................................................ 1


Notes ...................................................................................................................................................... 2
Table of Contents.................................................................................................................................... 3
List of Test Participants ........................................................................................................................... 4
Technical Data of Test Object ................................................................................................................. 5
Drawing of Test Object............................................................................................................................ 6
Technical Data of Test Circuit ................................................................................................................. 7
Circuit Diagram ....................................................................................................................................... 8
Test Results - High-current Power Arc Tests ........................................................................................... 9
Test Results - High-current Pressure Relief Tests ..................................................................................10
Test Results - Low-current Power Arc Tests ...........................................................................................11
Test Results - Low-current Pressure Relief Tests ...................................................................................12
Photos of Test Object.............................................................................................................................13
List of Symbols and Abbreviations Used in Oscillograms ........................................................................59
Oscillograms ..........................................................................................................................................60

14PE0402
Report No.: 14-021-HS Sheet: 4

List of Test Participants

Test Engineer / Test Operator:

Mr. Wurster Prüffeld der Schaltwerke, Siemens AG, Berlin


Mr. Löbel Prüffeld der Schaltwerke, Siemens AG, Berlin

Representatives of Client:

Mr. Schubert Siemens AG, E T AR R&D 2


Mr. Kruska Siemens AG, E T AR R&D 1

Further Participants:

Mr. Nguyen Prüffeld der Schaltwerke, Siemens AG, Berlin


Mr. Brünjes Prüffeld der Schaltwerke, Siemens AG, Berlin

51SE01008
Report No.: 14-021-HS Sheet: 5

Technical Data of Test Object


Arrester

Test object: Metal-oxide surge arrester without pressure relief device and with directly
moulded polymeric housing
Designation: 3EV5 144-0LK12
Manufacturer: Siemens Surge Arresters Limited
Serial No.: Type test samples 1 -13
Year of manufacture: 2014
Drawing No.: PTD H51 / 802 61398

Ratings assigned by the manufacturer:


Rated voltage 144 kV
Nominal discharge current (8/20 µs) 10 kA
Max. discharge voltage at 10 kA (8/20 µs) 30 kV
Rated short-circuit withstand current 50 kA
Low short-circuit current (2 s) 400 A
No. of resistor columns 1

Further data: -

Essential characteristics and installed devices: -

Remarks: The test sample was the largest unit of the 3EV5 series

320SE1110
Report No.: 14-021-HS Sheet: 6

Drawing of Test Object

317SE0407
Report No.: 14-021-HS Sheet: 7

Technical Data of Test Circuit


Power Arc and Pressure Relief Direct Test

Test performed High-current Low-current


power arc and power arc and
pressure relief tests pressure relief tests
Test No. 1 - 12 13 - 21
Test object
Rated voltage kV 144 144
Rated frequency Hz 60 60
Short-circuit current kA 50 0.4
Number of units under test 1 1
Test circuit
Circuit diagram see sheet 8 8
Number of phases 1 1
Power factor X/R > 15 > 15
Test voltage kV 32 81
Frequency Hz 50 50
Earthing conditions see circuit diagram see circuit diagram
Diameter of circular enclosure m 1.80 1.80

Remarks: -

12dSE0407
Report No.: 14-021-HS Sheet: 8

Circuit Diagram
Single-phase Direct Test

QMB QMS LCL T QAB

AD

G UTO TO

AD

ITO

Essential elements of the test circuit: Recorded quantities:

G Generator UTO Voltage across the test object


(resistive-damped capacitive divider)
QMB Master breaker
ITO Current through the test object (shunt)
QMS Making switch
AD Light intensity emitted by the arc
LCL Current-limiting reactor (optical arcing detector)

T Transformer

QAB Auxiliary breaker

TO Test object: Arrester

44-17bSE1008
Report No.: 14-021-HS Sheet: 9

Test Results
Power Arc Tests

Test performed: High-current power arc tests


Date of test: February 13, 2014
Condition of test object before test: New
Test arrangement: Test sample with fuse wire 1)
Connection to test object: According to IEC 60099-4, sub-clause 8.7, figure 14b. The top
terminal connected over air insulated gap, bypassed with fuse
wire.
Number of units per arrester: 1
Number of units tested: 1

Test No. 2) 6 3) 7 8 9
Test object No. - 1 2 3
Applied voltage kV 31.9 31.9 31.9 31.9
Peak short-circuit current kA 132 129 129 130
Short-circuit current First cycle kA 52.4 52.1 51.9 52.1
Last cycle kA 52.3 51.7 51.8 52.0
Duration ms 205 206 206 206
4)
Equivalent short-circuit current Current kA 53.0 52.1 52.1 52.3
Duration ms 200 200 200 200
X/R 31 - - -
Time to arc ignition ms - 1.0 1.1 1.2
5)
Time to vent ms - 1.0 1.1 1.2
Duration of open flames s - - - -
Internal parts outside the circular enclosure - no no no
Test result (P/N) - P P P

Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed outside the arrester housing
2)
Tests 1 - 5: Equipment tests, oscillograms are not included in this document
3)
Prospective test for the following test
4)
Calculated using Simpson’s Rule
5)
Arc detected with outside placed optical arcing detector (see sketch on sheet 8)

Condition of test object after test:


1) No violent shattering (Structural failure of the samples are permitted as long as criteria 2 and 3 are
met). The arrester housings were completely intact (see photos on sheet 13 - 21).
2) No parts of the test samples were found outside the enclosure, except fragments, less than 60 g each,
of ceramic material such as MOV or porcelain; pressure relief vent covers and diaphragms; soft parts of
polymeric materials.
3) The arresters were able to self-extinguish open flames within 2 min after the end of the test (no open
flames were detected).

322SE0902
Report No.: 14-021-HS Sheet: 10

Test Results
Pressure Relief Tests

Test performed: High-current pressure relief tests


Date of test: February 13, 2014
Condition of test object before test: New
Test arrangement: Test sample with fuse wire 1)
Connection to test object: According to IEC 60099-4, sub-clause 8.7, figure 14b. The top
terminal connected over air insulated gap, bypassed with fuse
wire.
Number of units per arrester: 1
Number of units tested: 1

Test No. 10 11 12 -
Test object No. 4 5 6 -
Applied voltage kV 31.9 31.9 31.9 -
Peak short-circuit current kA 129 128 129 -
Short-circuit current First cycle kA 52.0 51.9 52.0 -
Last cycle kA 51.9 52.0 51.9 -
Duration ms 206 206 206 -
3)
Equivalent short-circuit current Current kA 52.3 52.2 52.3 -
Duration ms 200 200 200 -
X/R - - - -
Time to arc ignition ms 0.9 0.8 0.7 -
4)
Time to vent ms 0.9 0.8 0.7 -
Duration of open flames s - - - -
Internal parts outside the circular enclosure no no no -
Test result (P/N) P P P -

Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed along the surface of the active part inside the arrester housing
2)
Prospective test for the following test
3)
Calculated using Simpson’s Rule
4)
Arc detected with outside placed optical arcing detector (see sketch on sheet 8)

Condition of test object after test:


1) No violent shattering (Structural failure of the samples are permitted as long as criteria 2 and 3 are
met). The arrester housings were completely intact (see photos on sheet 22 - 33).
2) No parts of the test samples were found outside the enclosure, except fragments, less than 60 g each,
of ceramic material such as MOV or porcelain; pressure relief vent covers and diaphragms; soft parts of
polymeric materials.
3) The arresters were able to self-extinguish open flames within 2 min after the end of the test (no open
flames were detected).

322SE0902
Report No.: 14-021-HS Sheet: 11

Test Results
Power Arc Tests

Test performed: Low-current power arc tests


Date of test: February 13, 2014
Condition of test object before test: New
Test arrangement: Test sample with fuse wire 1)
Connection to test object: According to IEC 60099-4, sub-clause 8.7, figure 14b. The top
terminal connected over air insulated gap, bypassed with fuse
wire.
Number of units per arrester: 1
Number of units tested: 1

Test No. 2) 15 16 17 -
Test object No. 7 8 9 -
Applied voltage kV 80.4 80.5 81.5 -
Peak short-circuit current A 845 851 850 -
Short-circuit current First cycle A 419 419 419 -
Last cycle A 424 426 425 -
Duration s 2.11 2.11 2.11 -
3)
Equivalent short-circuit current Current A 427 428 429 -
Duration ms 2.00 2.00 2.11 -
X/R - - - -
Time to arc ignition ms 1.3 40.4 25.0 -
4)
Time to vent ms 1.3 40.4 25.0 -
Duration of open flames s - - - -
Internal parts outside the circular enclosure no no no -
Test result (P/N) P P P -

Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed outside the arrester housing
2)
Tests 13 - 14: Equipment tests, oscillograms are not included in this document
3)
Calculated using Simpson’s Rule
4)
Arc detected with outside placed optical arcing detector (see sketch on sheet 8)

Condition of test object after test:


1) No violent shattering (Structural failure of the samples are permitted as long as criteria 2 and 3 are
met). The arrester housings were completely intact (see photos on sheet 34 - 42).
2) No parts of the test samples were found outside the enclosure, except fragments, less than 60 g each,
of ceramic material such as MOV or porcelain; pressure relief vent covers and diaphragms; soft parts of
polymeric materials.
3) The arresters were able to self-extinguish open flames within 2 min after the end of the test (no open
flames were detected).

322SE0902
Report No.: 14-021-HS Sheet: 12

Test Results
Pressure Relief Tests

Test performed: Low-current pressure relief tests


Date of test: February 13, 2014
Condition of test object before test: New
Test arrangement: Test sample with fuse wire 1)
Connection to test object: According to IEC 60099-4, sub-clause 8.7, figure 14b. The top
terminal connected over air insulated gap, bypassed with fuse
wire.
Number of units per arrester: 1
Number of units tested: 1

Test No. 18 19 20 21
Test object No. 10 11 12 13
Applied voltage kV 81.0 80.8 82.6 80.4
Peak short-circuit current A 846 847 1094 846
Short-circuit current First cycle A 402 404 457 411
Last cycle A 420 421 446 419
5)
Duration s 2.11 2.11 1.00 2.11
3)
Equivalent short-circuit current Current A 424 426 - 422
Duration s 2.11 2.00 - 2.00
X/R - - - -
Time to arc ignition ms 12.9 15.4 12.9 17.1
4)
Time to vent ms 23.9 24.6 1125.0 24.0
Duration of open flames s - 5 - -
Internal parts outside the circular enclosure no no no no
Test result (P/N) P P - 5) P

Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed along the surface of the active part inside the arrester housing
2)
Prospective test for the following test
3)
Calculated using Simpson’s Rule
4)
Arc detected with outside placed optical arcing detector (see sketch on sheet 8)
5)
Test not valid, current cleared after 0.26 s and started new after 1.09 s for a duration
of 1.00 s.

Condition of test object after test:


1) No violent shattering (Structural failure of the samples are permitted as long as criteria 2 and 3 are met).
The arrester housings were completely intact (see photos on sheet 43 - 58).
2) No parts of the test samples were found outside the enclosure, except fragments, less than 60 g each, of
ceramic material such as MOV or porcelain; pressure relief vent covers and diaphragms; soft parts of
polymeric materials.
3) The arresters were able to self-extinguish open flames within 2 min after the end of the test (no open
flames were detected).The open flames after the test with test sample 11 were self-extinguished after 5 s.

322SE0902
Report No.: 14-021-HS Sheet: 13

Photos of Test Object

Test sample no.1 before test

Test sample no. 1 after test

311SE0407
Report No.: 14-021-HS Sheet: 14

Test sample no. 1 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 15

Test sample no. 1 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 16

Test sample no. 2 before test

Test sample no. 2 after test

311SE0407
Report No.: 14-021-HS Sheet: 17

Test sample no. 2 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 18

Test sample no. 2 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 19

Test sample no. 3 before test

Test sample no. 3 after test

311SE0407
Report No.: 14-021-HS Sheet: 20

Test sample no. 3 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 21

Test sample no. 3 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 22

Test sample no. 4 before test

Test sample no. 4 after test

311SE0407
Report No.: 14-021-HS Sheet: 23

Test sample no. 4 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 24

Test sample no. 4 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 25

Detail of test sample no. 4 after test

315SE0407
Report No.: 14-021-HS Sheet: 26

Test sample no. 5 before test

Test sample no. 5 after test

311SE0407
Report No.: 14-021-HS Sheet: 27

Test sample no. 5 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 28

Test sample no. 5 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 29

Detail of test sample no. 5 after test

315SE0407
Report No.: 14-021-HS Sheet: 30

Test sample no. 6 before test

Test sample no. 6 after test

311SE0407
Report No.: 14-021-HS Sheet: 31

Test sample no. 6 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 32

Test sample no. 6 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 33

Detail of test sample no. 6 after test

315SE0407
Report No.: 14-021-HS Sheet: 34

Test sample no. 7 before test

Test sample no. 7 after test

311SE0407
Report No.: 14-021-HS Sheet: 35

Test sample no. 7 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 36

Test sample no. 7 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 37

Test sample no. 8 before test

Test sample no. 8 after test

311SE0407
Report No.: 14-021-HS Sheet: 38

Test sample no. 8 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 39

Test sample no. 8 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 40

Test sample no. 9 before test

Test sample no. 9 after test

311SE0407
Report No.: 14-021-HS Sheet: 41

Test sample no. 9 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 42

Test sample no. 9 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 43

Test sample no. 10 before test

Test sample no. 10 after test

311SE0407
Report No.: 14-021-HS Sheet: 44

Test sample no. 10 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 45

Test sample no. 10 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 46

Detail of test sample no. 10 after test

315SE0407
Report No.: 14-021-HS Sheet: 47

Test sample no. 11 before test

Test sample no. 11 after test

311SE0407
Report No.: 14-021-HS Sheet: 48

Test sample no. 11 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 49

Test sample no. 11 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 50

Detail of test sample no. 11 after test

315SE0407
Report No.: 14-021-HS Sheet: 51

Test sample no. 12 before test

Test sample no. 12 after test

311SE0407
Report No.: 14-021-HS Sheet: 52

Test sample no. 12 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 53

Test sample no. 12 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 54

Detail of test sample no. 12 after test

315SE0407
Report No.: 14-021-HS Sheet: 55

Test sample no. 13 before test

Test sample no. 13 after test

311SE0407
Report No.: 14-021-HS Sheet: 56

Test sample no. 13 (front view) after test

315SE0407
Report No.: 14-021-HS Sheet: 57

Test sample no. 13 (back view) after test

315SE0407
Report No.: 14-021-HS Sheet: 58

Detail of test sample no. 13 after test

315SE0407
Report No.: 14-021-HS Sheet: 59

List of Symbols and Abbreviations Used in Oscillograms

Oscillogram No.: 6 - 21

Abbreviation in Description
oscillograms

U_TO Voltage across the test object

I_TO Current through the test object

Light_Top Arcing detector top

Light_Bottom Arcing detector bottom

Remarks: The amplitude scaling of the individual signals is apparent at the labels on the right
side of the oscillograms, as a value taken from the upper to the lower borderline of the
inner graphic area.
All measurements and all measurement systems are calibrated. The measuring
uncertainties are determined and stated in the calibration certificates.

61SE0707
Report No.: 14-021-HS Sheet: 60

Oscillograms

Oscillogram No.: 6

316SE1103
Report No.: 14-021-HS Sheet: 61

Oscillogram No.: 7

316SE1103
Report No.: 14-021-HS Sheet: 62

Oscillogram No.: 8

316SE1103
Report No.: 14-021-HS Sheet: 63

Oscillogram No.: 9

316SE1103
Report No.: 14-021-HS Sheet: 64

Oscillogram No.: 10

316SE1103
Report No.: 14-021-HS Sheet: 65

Oscillogram No.: 11

316SE1103
Report No.: 14-021-HS Sheet: 66

Oscillogram No.: 12

316SE1103
Report No.: 14-021-HS Sheet: 67

Oscillogram No.: 15

316SE1103
Report No.: 14-021-HS Sheet: 68

Oscillogram No.: 16

316SE1103
Report No.: 14-021-HS Sheet: 69

Oscillogram No.: 17

316SE1103
Report No.: 14-021-HS Sheet: 70

Oscillogram No.: 18

316SE1103
Report No.: 14-021-HS Sheet: 71

Oscillogram No.: 19

316SE1103
Report No.: 14-021-HS Sheet: 72

Oscillogram No.: 20

316SE1103
Report No.: 14-021-HS Sheet: 73

Oscillogram No.: 21

316SE1103

You might also like