Data sheet
5755_en_07 © PHOENIX CONTACT 2018-04-05
1 Description
The terminal is designed for use within an Inline station.
It is used to acquire signals from resistive temperature
sensors.
The terminal supports all common platinum and nickel
sensors according to DIN EN 60751 and SAMA.
Cu10, Cu50, and Cu53 sensors as well as KTY81 and
KTY84 sensors are also supported.
The measuring temperature is represented by 16-bit values
in two process data words (one word per channel).
Features
– Two inputs for resistive temperature sensors
– Pt, Ni, Cu, KTY sensor types according to DIN and
SAMA
– Connection of sensors in 2, 3, and 4-wire technology
– The channels are parameterized independently of one
another via the bus system
– Measured values can be represented in three different
formats
– Measured value acquisition with 16-bit resolution
This data sheet is only valid in association with the IL SYS INST UM E user manual.
2 Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 3
5 Tolerance and temperature response...................................................................................... 6
5.1 Typical measuring tolerances at 25 °C ...................................................................................... 6
5.2 Maximum measuring tolerances at 25 °C ................................................................................... 7
5.3 Temperature response at -25 °C ... +55 °C ................................................................................. 7
5.4 Additional tolerances influenced by electromagnetic interference .................................................... 7
16 Measuring ranges.................................................................................................................. 21
16.1 Measuring ranges depending on the resolution (IB IL format) ........................................................ 21
16.2 Input measuring ranges ....................................................................................................... 21
3 Ordering data
4 Technical data
136,8
119,8
71,5
Width 12.2 mm
Height 136.8 mm
Depth 71.5 mm
General data
Color green
Weight 67 g (with connector)
Operating mode Process data operation with 2 words
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
80 kPa ... 106 kPa (up to 3000 m above sea level, in ATEX
Zone 2)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Communications power UL
Supply voltage 7.5 V DC (via voltage jumper)
Current draw typ. 43 mA
max. 60 mA
Power consumption
Power consumption typ. 587 mW
max. 882 mW
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
UL+
UANA
UL- 7 Electrical isolation
24 V
±5V
Key:
Protocol chip
OPC
Optocoupler
Input amplifier
Installation notes
Tamb = -25 °C ... +55 °C
The category 3 device is designed for installation in zone 2
potentially explosive areas.
The device meets the requirements of EN 60079-0 and
EN 60079-15.
• Observe the specified conditions for use in potentially
explosive areas! Also observe the requirements of
EN 60079-14.
• Install the device in a suitable approved housing (with at
least IP54 protection) that meets the requirements of
EN 60079-15.
• Only assemble, disassemble as well as connect and
disconnect cables when the power is disconnected.
• Only devices that are designed for operation in Ex Zone
2 and the conditions at the installation location may be
connected to the circuits in Zone 2.
• For safe operation, lockable plug connections must
have a functional interlock (e. g. locking clip, screw
connection etc.). Insert the interlock. Repair any
damaged connectors immediately.
• Only connect one cable per terminal point.
• Use transient protection so that short-term surge
voltages do not exceed 119 V.
• The air pressure during operation must not exceed
106 kPa.
• Perform a dielectric test after installing the device in the
housing.
• For all supply and signal lines connected to the station,
make sure that there is a connection to ground potential.
• Make sure that the maximum permissible current of 4 A
flowing through potential jumpers UM and US (total
current) is not exceeded.
• When using the device in potentially explosive areas,
observe the specifications in the application note
AH DE IL EX ZONE 2 (German) / AH EN IL EX ZONE 2
(English).
configuration.
1.2 2.2
1.2 2.2
• If required, provide signals with safe
isolation (e.g., for thermistor detection).
1.3 2.3
1.3 2.3
1.4 2.4
10 Installation instructions
High current flowing through potential jumpers UM and US
leads to a temperature rise in the potential jumpers and
inside the terminal. To keep the current flowing through the
potential jumpers of the analog terminals as low as possible,
Figure 3 Terminal point assignment always place the analog terminals after all the other
terminals at the end of the main circuit (for the sequence of
9.1 2- and 3-wire termination the Inline terminals: see also IL SYS INST UM E user
manual).
Terminal Signal Meaning
point 11 Connection notes
1.1 I1+ Constant current RTD sensor 1
1.2 I1- supply Connecting the resistance temperature detectors
1.3 U1- Measuring input
2.1 I2+ Constant current RTD sensor 2 Only connect a sensor in 4-wire technology to
2.2 I2- supply channel 1.
2.3 U2- Measuring input In this case, only connect a sensor in 2-wire
1.4, 2.4 Shield Shield connection Channel 1 and 2 technology to channel 2.
2
illustrate the connection (without overall
3 1.3 2.3
shielding braid). I 1-
1.4 2.4
A I 1+
1.1 2.1
I 2+
B Figure 6 Connection of a potentiometer in 2-wire
1.2 2.2
technology with shield connection
I 1- I 2-
1.3 2.3
U2-
1.4 2.4
1 I 1+ 1.1 2.1
1.2 2.2
2
3 1.3 2.3
A I 1+
1.1 2.1
I 2+
B
1.2 2.2
I 1- I 2-
1.3 2.3
U1-
U1+ 1.4 2.4
Parameter configuration using the output process data when connecting a potentiometer
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Meaning Parameteri- Reserved Connection R0 Resolution Format Sensor type
zation
2-wire technology
Assignment 1 0 0 1 1 1 1 0 0 1 0 0 1 1 0 1
Setting Parameteri- 0 2-wire 2 kΩ 0.1 % IB IL Potentiometer
zation (Dhex/13dec)
3-wire technology
Assignment 1 0 0 0 1 1 1 0 0 1 0 0 1 1 0 1
Setting Parameteri- 0 3-wire 2 kΩ 0.1 % IB IL Potentiometer
zation (Dhex/13dec)
No. Position of the potentiometer Potentiometer resistance at Value in input Percent value
slider tap tap process data
1 Open 2000 Ω 1000 100 %
2 Middle 1000 Ω 500 50 %
3 Almost closed 22 Ω 11 1.1 %
4 Closed 0Ω 0 0%
Figure 8 Local diagnostic and status indicators 14.1 OUT process data
You can parameterize each channel independently of the
Designation Color Meaning other channels. Parameterize the first channel via the first
D Green Diagnostics (bus and logic output word (OUT0), and the second channel via the second
voltage) output word (OUT1).
The following parameterization options are available:
For detailed information on diagnostics, – Type of sensor connection
please refer to the IL SYS INST UM E user – Value of the reference resistor R0
manual.
– Selecting the formats for representing measured values
– Sensor type selection
Function identification
Green The two channels are dependent on each
other for the connection method.
The 4-wire termination method is only
available for channel 1.
Only connect a sensor in 4-wire technology to
channel 1.
In this case, only connect a sensor in 2-wire
technology to channel 2.
OUT0 OUT1
Channel 1 Channel 2
Assignment of the parameter words (OUT0 and OUT1)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Paramete- Reserved Connection R0 Resolution Format Sensor type
rization
Bit 7 ... 6
Bit 5 ... 4
Code Format
dec bin
0 00 IB IL
1 01 IB ST (12 bits)
2 10 IB RT (15 Bit)
3 11 Reserved
Bit 3 ... 0
IN0 IN1
Channel 1 Channel 2
Word x Channel
IN0 1
IN1 2
15.1 IB IL format
The measured value is represented in bits 14 to 0. An
additional bit (bit 15) is available as a sign bit.
This format supports extended diagnostics. Values >
8000hex indicate an error.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
V Analog value
V Sign bit
15.2 IB ST format
The measured value is represented in bits 14 to 3.
An additional bit (bit 15) is available as a sign bit.
IB ST format corresponds to the data format used on INTERBUS ST modules.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
V Analog value 0 OC BÜ
V Sign bit
0 Reserved
OC Open circuit
BÜ Overrange
AV Analog value
x Can have the value 0 or 1
15.3 IB RT format
The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit.
IB RT format corresponds to the data format used on INTERBUS RT modules.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
V Analog value
V Sign bit
Sensor type (bits 3 ... 0) RTD sensor (0 ... 10) Linear resistance (15)
Resolution (bits 7 ... 6) 00bin or 10bin 00bin
Process data item (= analog value) 0.1°C or 0.1°F 1Ω
hex dec °C or °F Ω
7FFF 32767 - > 2048
Upper limit value + 1 LSB Measuring range exceeded -
(overrange)
7D00 32000 - 2000
2710 10000 1000.0 625
000A 10 1 0.625
0001 1 0.1 0.0625
0000 0 0 0
FFFF -1 -0.1 -
FC18 -1000 -100.0 -
Lower limit value - 1 LSB Below measuring range -
(underrange)
Lower limit value - 2 LSB Open circuit/short circuit -
Sensor type (bits 3 ... 0) RTD sensor (0 ... 10) Linear resistance (15)
Resolution (bits 7 ... 6) 01bin or 11bin 01bin
Process data item (= analog value) 0.01°C or 0.01°F 0.1 Ω
hex dec °C or °F Ω
7FFF 32767 - > 4096
Upper limit value + 1 LSB Measuring range exceeded -
(overrange)
7D00 32000 320.00 4000
2710 10000 100.0 1250
0001 1 0.1 0.125
0000 0 0 0
FFFF -1 -0.1 -
D8F0 -10000 -100.0 -
Lower limit value - 1 LSB Below measuring range -
(underrange)
Lower limit value - 2 LSB Open circuit/short circuit -
16 Measuring ranges
16.1 Measuring ranges depending on the resolution (IB IL format)
Where:
T [°F] Temperature in °F
T [°C] Temperature in °C
I-
thermometers, systematic measuring errors are often the RL UM 1.3 2.3
There are three main ways to connect the sensors: 2-, 3, and
4-wire technology.
through the sensor via wires I+ and I-. With the other two I-
wires U+ and U-, the temperature-related voltage is tapped RL 1.3 2.3
and measured at the sensor. The cable resistances have 1.4 2.4
1
RL = RL20 x ( 1 + 0,0039 x (T - 20°C ))
K
l 1
RL = x ( 1 + 0,0039 x (T - 20°C ))
cxA K
Where:
RL Cable resistance in Ω
RL20 Cable resistance at 20°C in Ω
l Cable length in m
χ Specific electrical resistance of copper in
m/Ωmm²
A Cable cross section in mm²
0.0039 1/K Temperature coefficient for copper
(percentage purity of 99.9%)
T Ambient temperature (cable temperature)
in °C