You are on page 1of 14

IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 4, NO.

3, JULY 2013 563

Analysis and Active-Impedance-Based Stabilization


of Voltage-Source-Rectifier Loads in Grid-Connected
and Isolated Microgrid Applications
Amr Ahmed A. Radwan, Student Member, IEEE, and Yasser Abdel-Rady I. Mohamed, Senior Member, IEEE

Abstract—This paper addresses the stability analysis and individual converters is not sufficient to guarantee stable perfor-
active-impedance-based stabilization of pulsewidth modulated mance if these entities (VSIs and VSRs) are connected together
voltage-source rectifier (VSR) loads in grid-connected and isolated [3]. Similar instabilities might be yielded in grid-connected
voltage-source inverter (VSI)-based microgrid systems. Using
small-signal analysis, detailed and coupled admittance-based VSRs. Therefore, the term “interaction dynamics” is used in
models of the VSR-interfaced load and the source side are this paper to refer to the destabilizing effect in these systems
obtained in the rotating reference frame by considering all not due to their inherent parameters or controllers but due to
control loops and phase-locked loop dynamics. Therefore, a their combination in one network. The degraded performance
multi-input–multi-output (MIMO) impedance-admittance net- in such systems is mainly attributed to: 1) The violation of
work is yielded. Using the generalized Nyquist stability criterion,
it is shown that a VSR-interfaced load can negatively interact with the admittance ratio or “Nyquist” criterion [2], [4], [5]. For
the source-side dynamics resulting in unstable voltage response voltage source power electronic systems, with equivalent load
at the point of interconnection. To suppress these instabilities, and source admittance around a common
proposed active-impedance-based compensators are implemented point of investigation, the system stability is guaranteed if
in the control structure of the VSR-interfaced load to satisfy the the ratio is less than unity. This ratio must not
generalized Nyquist stability criterion and provide seamless inte-
gration of VSRs into both grid-connected and isolated VSI-based encircle the ( 1, 0) point on Nyquist contours. However, this
ac systems. A theoretical analysis, time-domain simulations, and criterion is only valid for single-input–single-output (SISO)
experimental results are presented to evaluate the effectiveness of systems. For multi-input–multi-output (MIMO) systems, the
the proposed techniques. generalized Nyquist criterion should be used. 2) The real part
Index Terms—Impedance matching, Nyquist stability criterion, of input/output impedance of a voltage source converter (VSC)
voltage-source rectifier (VSR). might appear as negative resistance in the low frequency range
due to the controllers parameters [2], [5], [6]. The equivalent
negative resistive behavior of VSCs reduces the damping of
I. INTRODUCTION the overall system.
In spite of the importance of the VSR as an interfacing device
in ac systems, most ac microgrid stability and dynamic interac-

T HE energy sector is moving toward extensive use of


power electronic converters to interface distributed gen-
eration (DG) units and loads. It is expected that the penetration
tion studies are conducted for static loads only. For instance, a
generalized computational method is proposed in [7] to deter-
mine the overall system stability for an ac microgrid composed
level of converter-fed loads (high-efficiency motor drives, of three VSIs. Linear resistive-inductive loads are considered in
lighting, heating, etc.) will increase to 80% in 2015 [1]. With [8] where a complete analysis and testing of an ac microgrid is
this progressive trend, voltage-source rectifiers (VSRs) are provided based on small-signal analysis and state space mod-
gaining wide adoption as the main power electronic dc load-in- eling. The impact of dynamic line-start induction motors on the
terface to existing ac systems such as voltage-source inverter ac microgrid stability is presented in [9]. In [10], the overall
(VSI)-based microgrids or conventional ac distribution system system stability is investigated for two parallel-connected in-
[2]. verters supplying a common tightly-regulated converter-inter-
In a cascaded power electronic system consisting of a faced load in islanded mode. The load is generically modeled by
VSR-interfaced load and VSI-based ac microgrid, the system a negative resistance assuming constant power operation which
stability at the interconnection point might be an issue. In power ignores the load dynamics and its interactions with the micro-
electronic systems, the inherent stability and functionality of grid VSIs. A passive damping solution is used to enhance the
system stability [11]. However, this solution is not appreciated
Manuscript received April 27, 2012; revised September 10, 2012; accepted due to the associated power losses. The work in [12] addresses
October 29, 2012. Date of publication January 18, 2013; date of current version
the interaction dynamics analysis and stabilization of an ac mi-
June 17, 2013.
The authors are with the Department of Electrical and Computer Engi- crogrid supplying multiple power electronic-interfaced loads.
neering, University of Alberta, Edmonton, AB T6G 2V4, Canada (e-mail: Active stabilization techniques are implemented to enhance the
aradwan@ieee.org; yasser_rady@ieee.org).
system stability from the VSI side (source). However, a neg-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. ative resistance augmented model of the overall load-side is
Digital Object Identifier 10.1109/TSTE.2012.2227981 considered.

1949-3029/$31.00 © 2013 IEEE


564 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 4, NO. 3, JULY 2013

Fig. 1. VSR-interfaced load connected to VSI-based microgrid or the utility grid.

In this paper, the interaction dynamics of the VSR-interfaced sufficient stability conditions and hence seamless integra-
loads are investigated in both grid-connected and isolated VSI- tion characteristics in both grid-connected and isolated mi-
based ac microgrid systems. Admittance-based models of the crogrid applications.
source-load entities are obtained in the rotating reference frame The remainder of this paper is organized as follows. The
by considering all control loops and phase-locked loop (PLL) detailed admittance-based models of the VSR, VSI-based
dynamics. Therefore, a MIMO system is yielded. To investi- microgrid, and the utility grid are derived in Section II. The
gate the stability of the admittance-modeled MIMO systems, input admittance of the VSR-interfaced load is then inves-
two approaches can be followed. 1) Approximate approach in tigated in Section III. The generalized Nyquist criterion is
which the diagonal or anti-diagonal elements of the ac source applied in Section IV in order to address possible interaction
or load admittance should be zero. Following this approach, the dynamics between the VSR-interfaced load and the source side.
MIMO system can be decomposed into four independent SISO The proposed active stabilization techniques are presented in
systems. Conventional Nyquist criterion can be applied to the Section V so that the generalized Nyquist stability criterion
resultant SISO systems to check the system stability. Several is actively satisfied. The influence of the proposed compen-
studies have applied the Nyquist stability criterion on SISO sys- sators on the operation of the VSR is thoroughly addressed in
tems [2], [4], [13]–[15] for dc systems. For ac systems, a SISO Section VI. Simulation and experimental results are provided
system has been assumed in [12] by ignoring the coupling terms in Sections VII and VIII, respectively. Finally, the conclusion
yielded from the direct-quadrature transformation. In is drawn in Section IX.
[16] and [17], space vectors are used to model the ac system
under study so that a SISO system is also yielded. 2) Exact ap- II. IMPEDANCE-BASED MODELING OF VSR-INTERFACED
proach in which the complete coupled 2 2 input–output ma- LOAD IN ISLANDED AC MICROGRID AND
trix impedances are obtained in the reference frame and GRID-CONNECTED SYSTEMS
the resultant MIMO system is treated without simplifications. Fig. 1 shows the system under study where the VSR-inter-
In this case, the generalized Nyquist stability criterion has to be faced load can be connected to the VSI-based micorgrid through
used [18], [19]. Both approached are considered in this work. the circuit breaker-2 (Br-2). The utility grid can individually
The contributions of this paper are as follows: supply the VSR load by closing Br-1 and opening Br-2. A resis-
1) Development of the complete coupled ac impedance tive load can be connected in parallel with the VSR-interfaced
matrices of a VSR-interfaced load and VSI with power load through the Br-3. As shown, VSIs in the ac microgrid are
sharing control functions in islanded microgrids in the terminated by an ac LC filter and are connected together via a
reference frame. distribution feeder with an equivalent resistance and induc-
2) Investigation of possible interaction dynamics and insta- tance . System parameters are given in Appendix A.
bilities in a VSR-interfaced load in both grid-connected In this paper, the analysis is based on small-signal lineariza-
and isolated VSI-based microgrids using the generalized tion in a synchronous coordination system to equiva-
Nyquist stability criterion. lently obtain the overall source-load admittances including the
3) Based on the generalized Nyquist stability criterion, pro- physical parameters and controller dynamics [20]. This method
posed active-impedance reshaping loops are implemented yields a computationally efficient and modular modeling ap-
in the control structure of the VSR-interface to guarantee proach that is suitable for analyzing large networks at the cost of
RADWAN AND MOHAMED: ANALYSIS AND ACTIVE-IMPEDANCE-BASED STABILIZATION OF VSR LOADS 565

assuming balanced operation, which is a reasonable assumption The inner PI current controller synthesizes the
due to the small unbalance factor in typical distribution systems duty ratios in the frame which are used to generate the
[21]. controlled signals of the IGBT switches

A. Admittance Model of VSR-Interfaced Load (11)


As shown in Fig. 1, for vector-oriented control, a (12)
phase-locked-loop (PLL) is used to project the three-phase
space-phasor variables on the rotating frame. The relation The input ac impedance matrix of the VSR-interfaced load
between the capacitor voltage space-phasor and its can be obtained as follow. Apply small-signal perturbations on
components is described by (3) and (4) considering (2) to replace the perturbed angular fre-
quency by the PLL dynamics, yields
(1)

In (1), the angular speed of the frame is equal to the


angular speed of the space vector . The PLL lo- (13)
cally synchronizes the VSR with respect to its input ac voltage.
Therefore, the -component of the ac voltages is zero in
steady-state conditions which is achieved by the PLL propor- where all system matrices in (13) and forthcoming equations are
tional-and-integral (PI) controller as described in the defined in Appendix B.
following: Similarly, (9) is rearranged as in (14) whereas (15) is yielded
from (10)–(12):
(2)
(14)
Using the PLL to decompose all space-phasors into the two-
phase synchronous reference frame, the large-signal
model of VSR can be given by [22]
(15)
(3)
(4) In a similar manner, the small-signal model of (5), (6) and (7),
(8) gives
(5)
(6) (16)
(7)
(8) (17)

(9) Substitute (14) in both (13) and (15) to remove , and


solve the resultant two equations together
where and are the per phase equivalent resistance
and inductance of the distribution line and the input ac filter of (18)
the VSR whereas and are the ac side and the dc-link ca-
pacitor, respectively; is the terminated load at the dc side of
Using (18) in (17) to remove and solve the
the VSR and is assumed resistive with a dc-link voltage
resultant equation with (16) to remove , the ac
and input dc current ; are the components of
admittance matrix of the VSR-interfaced that relates
the rectifier input ac current ; are the compo-
to is given by
nents of ; while and are the compo-
nents of the ac voltages and , respectively; and are
the rectifier duty ratios in frame and are determined by the
control topology.
An outer PI dc voltage controller is used for dc
voltage tracking and regulation. The mathematical model for
the dc voltage controller is given by (10), where it generates (19)
the -axis component of the VSR reference current . The
quadrature component of the input ac current is set to zero
for unity power factor operation. Therefore, the
B. Source Impedance Model of Islanded AC Microgrid
steady-state value of the -component of the input ac current
Interface (VSI) and Utility-Grid System
is zero
As shown in Fig. 1, the current and voltage dynamics of the
(10) power circuits are modeled by (20)–(23) in the frame that
566 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 4, NO. 3, JULY 2013

rotates synchronously with the inverter output voltage angular (27). The resultant two equations are arranged in a matrix form
speed [23] as follows:

(20) (34)
(21)
(22) Applying small perturbations on (24) and (25) yields
(23)

where , , , and are the inverter output voltages


and currents ; , , , and are the ac bus (35)
voltages and injected currents ; , , and are Similarly, (22) and (23) yield
the per-phase resistance, inductance, and capacitance of the
filter, respectively; and is the Laplace operator. The dynamics
of the voltage and current controllers can be described by
(36)
Applying small perturbation on the power sharing dynamics in
(24)
(28)–(33) yields
(25)
(26)
(37)
(27)

where is a feed-forward gain; and are the Solving (34) and (36) to remove yields an equa-
voltage and current PI controller functions with and tion in which (35) is used to substitute . Using
as proportional gains and and as integral gains, re- (37), the resultant equation that relates the output ac voltages
spectively; and and are the - and -components of to the injected ac currents is given
the generated control signal. The superscript “ ” denotes the ref- by
erence value. is usually set to zero.
The instantaneous active and reactive power delivered
to the ac common bus are given by

(38)
(28)
(29)

The average active and reactive powers that corre- where is the output impedance of the VSI in is-
spond to the fundamental components are obtained by a low- landed microgrid mode of operation.
pass filter (LPF) with a cutoff frequency to achieve high Similar to the preceding analysis, an approximated source
power quality injection; therefore, impedance of the VSI in isolated microgrid mode can be ob-
tained but with the following assumptions:
1) Ignoring the effect of the outer power sharing loop by set-
(30) ting both droop coefficients to zero. Therefore, and
in (37) are zero ( and ).
(31) 2) Ignoring the small-signal ac capacitor current as com-
pared to the injected ac current to the load .
Virtual droop characteristics are emulated in paralleled in- By considering these two assumptions, the approximated
verter systems to share the active and reactive power of the source impedance of the VSI can be obtained
common load. The following droop functions are adopted [23]: in the form of (38) but with zero anti-diagonal elements
and equal diagonal elements
. The approximated source
(32)
admittance is defined in Appendix B.
(33) It is shown in Fig. 1 that the VSR-interfaced load can be sup-
plied from the utility grid by closing the Br-1 and opening Br-2.
where and are the static droop gains of the active and reac- The source impedance of the utility-grid in the reference
tive powers, respectively. frame is given as
The source impedance of the VSI can be obtained by applying
small-signal linearization on (20) and (26) and solve together to
(39)
remove the coupling terms. A similar step is applied to (21) and
RADWAN AND MOHAMED: ANALYSIS AND ACTIVE-IMPEDANCE-BASED STABILIZATION OF VSR LOADS 567

Fig. 3. Input admittance of VSR—Effect of drawn active power. (a) Frequency


response. (b) Real part.

Fig. 4. Input admittance of VSR—Effect of the PLL.

Fig. 2. Input admittance of VSR—Effect of the dc voltage controller. (a) Fre-


quency response. (b) Real part. Fig. 4 shows the influence of the PI controller of the PLL
on the real part of . The consideration of the
PLL dynamics in the model of is not significant. On the
III. ANALYSIS OF THE INPUT ADMITTANCE OF contrary, the magnitude of the real part of remarkably in-
VSR-INTERFACED LOAD creases when the PLL dynamics is considered as compared to
the case when the PLL is ignored. For , the magnitude of
The frequency response of the four channels of in (19) the real part with PLL is slightly higher than that without PLL
is shown in Fig. 2. A resonant peak appears in the high fre- in frequencies up to 200 Hz. Beyond this frequency, the real part
quency region due to the combination of the ac LC filter and of drifts to more negative value without the PLL whereas it
distribution feeder of the VSR as shown in Fig. 2(a). The tight drifts to be more positive when the PLL dynamics is considered.
regulation of the output dc voltage of the VSR has a significant Fig. 4 implies that the PLL dynamics is preferred to be included
influence on . As the proportional gain of the dc in the dynamics of the VSR model as it affects the electrical
voltage controller increases, goes further to higher negative damping of the VSR.
value as the phase angle approaches 180 . The same effect is no- The influence of parameter variations; mainly LCL combina-
tion values, is also investigated. As shown in Fig. 5(a) for ,
ticed on the frequency response of . Note that is slightly
, with higher values of , the resonant peak magnitude
influenced by the dc voltage controller as the voltage controller
increases whereas the resonant frequency decreases. Fig. 5(b)
is employed in the -channel only. For further investigation, the
shows the influence of the variation of VSR capacitor on
real part component of the four-channel input admittance of the
. It is shown that as increases from 0.8 to 1.2 p.u.,
VSR is shown in Fig. 2(b). The negative value of the real part the magnitude of the resonant peak of increases implying
increases with the increase of the dc voltage controller gain for less damping around the resonant frequency. Similar influence
both and . is yielded for and but on the whole frequency range of
The effect of the injected active power to the VSR is shown the input admittance. In Fig. 5, the response of is similar
in Fig. 3. With lower power level, the resonant peak magni- to . The influence of the value of on the input admit-
tude of decreases. is more negative as the in- tances of the VSR only appears around the resonant frequency
jected active power increases to 1.2 p.u. as shown in Fig. 3(b). of the equivalent LCL filter (not shown here). As increases,
Both anti-diagonal elements are not sensitive to the drawn ac- the magnitude of the resonant peak decreases. This effect is the
tive power. same for , , and whereas is not affected by .
568 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 4, NO. 3, JULY 2013

Fig. 6. Input–output admittance mismatching using the approximated ap-


proach— : passive damping resistor in series with the ac capacitor .

filter capacitor of the VSR to be damped as shown for the


first subsystem in Fig. 6. However, the passive resistor locally
reshapes the input admittance of the VSR without any signifi-
cant improvement in the mid-frequency region. Moreover, the
incremental negative resistance characteristics at the low- and
Fig. 5. Input admittance of VSR—Effect of LCL parameters variations. (a) . mid-frequency regions cannot be mitigated by this technique
(b) .
(the phase angle of VSR-admittance ). More impor-
IV. INTERACTION DYNAMICS BETWEEN EQUIVALENT tantly, this passive solution is not preferred in DG applications
SOURCE AND LOAD SIDES due to the associated power losses. It is also shown in Fig. 6
In this section, the interaction dynamics between the VSR- that the remaining subsystems in (40) do not contribute to the
interfaced load and the source sides are investigated. violation of the Nyquist stability criterion (no magnitude inter-
sections).
A. Using Approximated Modeling Approach for the Source For further investigation, Nyquist plots are utilized to eval-
Side uate the overall interaction dynamics between the equivalent
load and approximated source admittances. Fig. 7 shows the
Considering the approximated source impedance of the VSI-
Nyquist contours for the first subsystem in (40) as other sub-
microgrid and the obtained load admittance of the
systems are not significant to the system stability (as shown in
VSR-interfaced load in (19), the source-load impedance-admit-
Fig. 6). Fig. 7(a) shows that the stability margin of the uncom-
tance matrix is given as follows:
pensated system is very low. In the same figure, the effect of
adding passive load in parallel with the VSR-interfaced load
is shown (close Br-3 in Fig. 1). The parallel combination of
(40) the VSR and passive loads positively contributes to the overall
system stability. However, it might not be feasible to put restric-
By considering the approximate source impedance of the tions on the amount or type of front-end loads that are supplied
VSI, the impedance matrix ratio can from microgrids. This contradicts the visionary policy of fu-
be easily decomposed into four independent transfer functions. ture grids that can accommodate different loads especially con-
Therefore, the MIMO stability problem has been transformed verter-fed types which will be highly penetrated to future distri-
into an SISO problem on which the conventional Nyquist bution system at the expense of conventional passive loads [24].
stability criterion is applied. The influence of cascading more than one VSR is shown in
The frequency response of the four subsystems in (40) is Fig. 7(b) for the first subsystem in (40). As shown, the reduced
shown in Fig. 6. For the first subsystem , the stability margin with one VSR unit is dramatically degraded
resonant peak interacts with the output admittance of the VSI vi- with two or three VSR units.
olating the Nyquist stability criterion. Moreover, in the mid-fre- To study the interaction dynamics between the VSR-inter-
quency region, the stability margin is limited and subjects the faced load and utility grid impedance, the approximate approach
overall system to instabilities. For the high-frequency resonant can be adopted by neglecting the anti-diagonal coupling terms in
peak, a physical resistor can be added in series with the ac (39). However, the generalized Nyquist stability criterion can be
RADWAN AND MOHAMED: ANALYSIS AND ACTIVE-IMPEDANCE-BASED STABILIZATION OF VSR LOADS 569

Fig. 9. Proposed MFC and HFC for VSR-interfaced load. Similar structure is
applied for the -channel.

successfully mitigates the intersections and provides a consider-


able stability margin as compared to the unstable case, is shown.
Fig. 8 also shows the singular values of the VSR and utility grid
Fig. 7. Nyquist admittance ratio criterion— . (a) Activating
Br-3 in Fig. 1 with different level of passive load (0.1, 0.2 p.u.). (b) Parallelism
impedances. The uncompensated VSR system negatively inter-
of multiple VSR supplied from the common ac bus. acts with the grid impedance . As the grid impedance in-
creases, the frequency range of intersection increases implying
a remarkable reduction in the system damping with weak grids.
However, the passive damping resistance can im-
prove the system damping.

V. ACTIVE-IMPEDANCE-BASED STABILIZATION OF
VSR-INTERFACED LOADS
In this section, active-impedance-based compensators are
proposed for the VSR load to mitigate destabilizing effects
associated with impedance interactions between VSR loads and
source dynamics (e.g., VSI-based microgrid or utility grid).

A. Modified Control Structure of the VSR-Interfaced Load


Fig. 9 shows a schematic diagram of the modified control
Fig. 8. Maximum and minimum singular values of the source and load sides loops of the VSR. As shown, two proposed compensators are
with the passive damping effect ( in series with C)—interactions dynamics employed: a mid-frequency compensator (MFC) to actively re-
with the VSI-microgrid and the utility grid.
shape the input admittance of the VSR to avoid possible inter-
actions with the source-side at this region, and a high-frequency
applied on the exact source impedance to investigate the system compensator (HFC) to damp the resonant peak due to the LCL
stability. ac filter of the VSR. The HFC is employed by feeding the -axis
component of the ac capacitor current through a con-
B. Using Exact Modeling Approach for the Source Side stant gain to mimic a virtual voltage drop that is sub-
tracted from the generated control signal [ in (44)]. A
The preceding analysis in Section IV-A is restricted to the
similar modified structure is applied to the -channel of the con-
condition of zero anti-diagonal (or diagonal) elements in the
trol structure. For the mid-frequency compensation, is ap-
source (or load) impedance matrices. Otherwise, the general-
plied through a compensator function to generate the
ized Nyquist stability criterion should be used. According to
active compensation signal that is added to the dc-link voltage
(41), for MIMO systems with 2 2 source-load impedance/ad-
reference. As shown in (42), the selection of is based
mittance matrices, the system stability is guaranteed around the
on band-pass (BP) filter characteristics to allow admittance re-
point of connection if the maximum singular value of the source
shaping around the required frequency band
impedance is less than the minimum singular value
of the load impedance [18], [19] (42)
(41)
where is the damping factor, is the operating frequency,
Fig. 8 shows the maximum and minimum singular values and is the compensator gain.
of the complete load and source impedances. As previously The modified system dynamics due to proposed MFC and
shown with the approximated analysis, the uncompensated load HFC are described in (43) and (44), respectively,
impedance of the VSR intersects with the source impedance of
(43)
the VSI in the region 250–1000 Hz which clearly reflects the vi-
olation of the generalized Nyquist stability criterion. In the same
figure, the influence of the passive damping technique, which (44)
570 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 4, NO. 3, JULY 2013

Fig. 10. Influence of the MFC parameters on the input admittance of the VSR
( channel). (a) Effect of . (b) Effect of . (c) Effect of .

Following similar mathematical procedures, the compensated


small-signal input admittance ( of the VSR) is obtained
in the form of (45) and is detailed in Appendix B:

(45)
Fig. 11. Frequency response of the compensated input admittance of VSR
using the approximated approach— , rad/s,
To show the sole influence of the BP compensator , .
on the input admittance of the VSR, passive damping is con-
sidered with to neutralize the interactions due to
LCL resonance at high frequencies. The effect of the proposed
MFC on the first channel of is shown in
Fig. 10. The compensated input admittance of the VSR can be
actively reshaped to avoid possible interactions with the source
side. The compensated input admittance follows the dynamic
response of the BP filter. In Fig. 10(a), the operating frequency
of the proposed compensator is 50 rad/s with a unity Fig. 12. Influence of the proposed compensator on the real part of the admit-
tance of the VSR-interfaced load.
damping factor . With the increase of the compensator
gain , the magnitude of the input admittance decreases ac-
cordingly around the designed frequency. Fig. 10(b) shows the admittance of VSR, the objective of the high frequency com-
effect of changing the operating frequency of . The width pensator is to dampen the resonant peak of the VSR LCL filter.
of the resultant peak increases with the increase of the damping The objective of the medium frequency compensator is to: 1) de-
factor , as shown in Fig. 10(c). crease the magnitude of the input admittance of the VSR in the
medium frequency range, just before the ac filter resonant fre-
B. Active Compensation Effect Using Approximated Modeling quency; and 2) reshape the VSR phase response in the medium
Approach of the Source Side frequency range to mitigate the equivalent negative resistive be-
havior (shift the phase from 180 in mid-frequencies).
Fig. 11 shows the input–output admittance matching by con-
Both objectives can be achieved without accurate knowledge
sidering the compensated input admittance of VSR and the ap-
of the VSI (source) parameters. Similar to Fig. 11, any VSR can
proximated output admittance of the VSI [similar to (40)]. For
be compensated and to maximize the stable operation region.
the first subsystem , the HFC successfully
Fig. 13(a) shows the Nyquist contours of the first compen-
mitigates the resonant peak whereas the MFC results in higher
sated subsystem . The effect of the pro-
stability margin. Moreover, the 180 phase angle of the uncom-
posed active compensator is clearly reflected to the system sta-
pensated input admittance at low- and mid-frequency regions is
bility. As the MFC gain varies from 0.1 to 0.8, the stability
shifted to be more positive which increases the overall system
margin is significantly improved as compared to the uncompen-
damping.
sated case . The effect of multicascaded VSR with the
The effect of the proposed compensator on the real part of
proposed active compensator is investigated in Fig. 13(b). As
the VSR admittance can be clearly shown in Fig. 12. As com-
compared to Fig. 7(b), the stability is maintained with two and
pared to the uncompensated system in Fig. 2, the real part of the
three identical VSR units.
four-channel admittance becomes positive in the low- to mid-
frequency range implying more damping added to the system.
C. Active Compensation Effect Using Exact Modeling
Note that the previously shown passive damped system in Fig. 6
Approach of the Source Side
is not able to reshape the admittance to be more positive.
As shown in Fig. 11, the user may not need the VSI parame- Using the generalized Nyquist stability criterion, the in-
ters to design the load-side compensators. Regarding the input fluence of the proposed MFC and the HFC is shown in
RADWAN AND MOHAMED: ANALYSIS AND ACTIVE-IMPEDANCE-BASED STABILIZATION OF VSR LOADS 571

Fig. 13. Nyquist admittance ratio criterion— —


rad/s, , . (a) Different values of . (b) Parallelism of
multiple VSR supplied from the common ac bus with .

Fig. 15. Output dc voltage tracking of VSR— .

A. Effect on the DC Voltage Tracking


The transfer function is obtained in (46) using block
diagram reductions before and after employing the active com-
pensator to evaluate its effect on the dc voltage tracking of the
VSR. for the uncompensated system

(46)

Fig. 15 shows the frequency response of (46). As in-


creases from 0 to 0.8, the dc voltage controller bandwidth be-
comes 224, 212, 200, and 176 Hz, respectively. The uncom-
pensated dc voltage controller is designed with high bandwidth
for advanced power electronic rectifiers and tight regulated dc
voltage performance. The employed active compensator does
not deform the dc voltage controller significantly.

B. Sensitivity Against DC Voltage Controller Bandwidth


Using the approximated approach, the Nyquist admittance
Fig. 14. Maximum and minimum singular values of the source and load sides ratio criterion for the first subsystem is in-
with the proposed MFC and HFC. (a) Influence of the MFC. (b) Influence of
the HFC. (c) Combined effect of both MFC and HFC on the VSR impedance vestigated under variation of dc voltage controller bandwidth of
( , , ). the VSR. As shown in Fig. 16(a), the encirclements with the real
axis at is ( 0.6382, 0) whereas it is ( 0.5563, 0) with
with a variation in damping by 0.0819 on the real
Fig. 14(a) and (b), respectively. It is clear that each compen-
axis. On the other hand, the compensated system in Fig. 16(b)
sator has an independent objective; MFC is responsible for
encirclements the real axis at ( 0.222, 0) with and
reshaping the input impedance in the mid-frequency range
( 0.19, 0) with with a difference of 0.025. The
whereas the HFC’s responsibility is to mitigate the resonant
compensated system is more robust against dc voltage controller
peak at the relatively high frequency region. Both objectives
variations as compared to the uncompensated system.
are successfully met to achieve better stability margin when the
VSR is plugged into the source side, as shown in Fig. 14(c). As VII. SIMULATION RESULTS: VSR-INTERFACED LOAD IN A
concluded earlier from the approximated analysis, the proposed VSI-BASED MICROGRID
compensators provide sufficient stability margin on the overall
frequency range between the VSR and VSI-based microgrid. To verify the preceding analytical results, a complete
In the same figure, the interaction dynamics between the VSR 44-kW 208-V ac-microgrid system is implemented under
and the utility grid is completely mitigated. the Matlab/Simulink environment. As shown in Fig. 17, the
implemented system consists of two DG units interfaced by
two 22-kVA VSIs operating in the isolated microgrid mode
VI. INFLUENCE OF THE PROPOSED COMPENSATOR ON
of operation. The ac microgrid system is highly penetrated
VSR-DYNAMICS
by three converter-fed loads: VSR-1 is feeding a permanent
This section investigates the associated possible negative ef- magnet synchronous motor (PMSM) drive rated at 10 hp and
fects of the proposed compensators on the operation of the VSR. resistive load at the dc-link side with power rating of 6.25 kW
572 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 4, NO. 3, JULY 2013

Fig. 16. Nyquist criterion with different values of voltage controller propor-
tional gain . (a) Uncompensated. (b) Compensated case.

Fig. 19. Uncompensated response for the simulated ac microgrid excluding


VSR-3. (a) Common ac-voltage. (b) Total injected active power.

A. Test 1: Inherent Stability of VSR-Interfaced Loads


The ac microgrid in Fig. 17 is tested without active compen-
sation; the VSR-3 is disconnected in this test while the same
load disturbances in VSR-1 and -2 are applied. A damped dy-
namic response is obtained as shown in Fig. 19. It is clear that
both VSR-1 and -2 are inherently stable even with similar load
side disturbances at 0.3, 0.4, and 0.5 s. Moreover, VSR-3 is in-
herently stable as well when individually supplied (not shown
here). However, when these units are connected together, desta-
bilizing dynamics are yielded due to the violation of the admit-
tance ratio criterion as shown in test 2.

B. Test 2: Uncompensated System


Applying the loading/unloading scenario in Fig. 18, the un-
compensated system response is shown in Fig. 20. It is clear
Fig. 17. Simulated ac microgrid. that the response is unstable at the loading instant of VSR-1 at
s whereas a decayed response is yielded due to removing
the excessive loading at s. The system response builds
up again at s due to the increased load power of VSR-2.
The unstable response is reflected to the total injected active
power to the augmented converter-fed loads as shown in
Fig. 20(b). Although the loading/unloading disturbances are ap-
plied to VSR-1 and -2, the dc-link voltage of VSR-3
is completely degraded with unstable response, as shown in
Fig. 20(c). It is clear that the lightly damped modes of the un-
compensated system results in unstable response that interacts
with the whole entities of the ac microgrid system. As shown in
Fig. 20(d), the PMSM speed is also affected with a similar
trend.
Fig. 18. Load curve of the simulated ac microgrid.
C. Test 3: Actively Compensated VSR-Interfaced Load
that increases to 9.4 kW at time s then returns back to The active compensation technique is investigated in this sub-
6.25 kW at s; VSR-2 interfaces a resistive load rated section under the same loading/unloading scenario shown in
at 4.7 kW and instantly increases to 8.3 kW at s; and Fig. 18. The design procedures of the proposed compensators
VSR-3 is feeding a constant resistive load with power demand are similar to that presented in this paper. However, a large
of 15.6 kW. A load curve that describes the loading conditions system model is simulated to investigate the effectiveness of the
of the ac microgrid is shown in Fig. 18. The ac microgrid is provided technique. Note that all entities in the simulated system
characterized by severe loading/unloading conditions to subject can be transferred to impedance-admittance-based models in-
the proposed compensators to the worst loading conditions. cluding the PMSM drive [15]. However, the design process of
RADWAN AND MOHAMED: ANALYSIS AND ACTIVE-IMPEDANCE-BASED STABILIZATION OF VSR LOADS 573

Fig. 20. Uncompensated response for the simulated ac microgrid. (a) Common
ac-voltage. (b) Total injected active power. (c) DC-side voltage of VSR-3. Fig. 21. Actively compensated response for the simulated ac microgrid.
(d) PMSM speed. (a) Common ac-voltage. (b) Total injected active power. (c) DC-side voltage
of VSR-3. (d) PMSM speed.

the HFC mainly depends on damping the LCL filter resonant of


the VSR whereas the MFC can be designed to increase the sta-
VSR system, the laboratory setup shown in Fig. 22 is im-
bility margin just before the resonant frequency. Therefore, the
plemented. The system in Fig. 22 consists of a weak utility
knowledge of the complete system models is not necessary.
grid interfaced by an inductive ac filter, and a VSR with
Fig. 21(a) shows the common ac voltage response whereas
LC ac filter interfacing variable resistive load (eight resistors
the injected active power is shown in Fig. 21(b); all responses
connected in parallel). The experimental system parameters
are damped and remarkably improved as compared to Fig. 20.
are given in Appendix A.
This clearly implies that input–output admittance ratio criterion
A Semistack intelligent power module, which includes gate
is satisfied from the VSR-side by employing the proposed com-
drives, six insulated gate bipolar transistors (IGBTs), and
pensators which validates the analytical results that obtained in
protection circuit is used as a VSR. The switching frequency
Figs. 11 and 14.
is 10 kHz, which indicates that the proposed compensator can
The obtained response in Fig. 21 is close to that in Fig. 19
be effectively implemented under high sampling frequency.
when VSR-3 is excluded. The proposed compensators reshape
The VSR-side inductor currents are measured by HASS-50-S
the input admittance of VSRs so that the ac microgrid can
current sensors (CS) whereas the voltage signals are mea-
accommodate a higher number of converter-interfaced loads
sured by LEM-V-25-400 voltage sensors (VS). The VSR
by introducing a higher stability margin to the system. The
control scheme, orientation and the PWM generation
converter-fed load performance is improved, as shown in
are implemented on the dSPACE1104 control card supported
Fig. 21(c), for of VSR-3 and the motor drive performance
with a TMS320F240-DSP coprocessor structure for PWM
as in Fig. 21(d).
generation. The dSPACE1104 interfacing board is equipped
with eight digital-to-analogue channels (DAC) and eight ana-
VIII. EXPERIMENTAL RESULTS: VSR-INTERFACED LOAD logue-to-digital channels (ADC) to interface the measured
CONNECTED TO A WEAK GRID signals to/from the control system. The software code is gener-
To validate the effectiveness of the proposed active ated by the Real-Time-WorkShop under the Matlab/Simulink
damping technique in reshaping the input admittance of a environment.
574 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 4, NO. 3, JULY 2013

Fig. 24. Compensated startup response of VSR at for: (a) -component of


the grid voltage and (b) dc link voltage. Compensated system response when dc
load increases at for: (c) -component of the grid voltage, (d) -component
of the injected ac current, and (e) phase “a” modulation signal.

Fig. 3, the increased injected power to the VSR increases the


magnitude of the load admittance and hence reduces the stability
margin. Therefore, the system becomes unstable in the loading
Fig. 22. Experimental verification. (a) Schematic diagram. (b) Laboratory
setup. period as shown in Fig. 23(c)–(e). Even in the grid-con-
nected operation mode, is unstable due to the impedance
mismatching. This behavior is reflected to the injected ac cur-
rent and converter’s duty ratio as shown in Fig. 23(d) and (e),
respectively.

B. Compensated Response
The same experimental setup is used to verify the effective-
ness of the proposed active impedance compensator. Similar to
the frequency response analysis in Figs. 11 and 14, the compen-
sator parameters are selected so that the load/source admittance
intersections are avoided (or minimized). The VSR is switched
on at . The -component of the PCC voltage and the resul-
tant dc-link voltage are shown in Fig. 24(a) and (b), respectively.
As compared to the uncompensated case in Fig. 23(a) and (b),
the proposed compensator shows excellent damped response
due to the stability margin added to the system.
Fig. 23. Uncompensated startup response of VSR at for: (a) -component of
the grid voltage and (b) dc link voltage. Uncompensated system response when
Similar to the uncompensated scenario, the dc load is in-
dc load increases at , decreases at for: (c) -component of the grid voltage, creased at . However, the maximum dc load is kept to
(d) -component of the injected ac current, and (e) phase “a” modulation signal. challenge the compensated system and the system response is
shown in Fig. 24(c)–(e). Unlike the uncompensated case, the
system stability is maintained under maximum dc loading con-
A. Uncompensated Response ditions. Experimental results show that proposed admittance
The VSR is initially connected to the minimum dc load. reshaping technique has a robust performance, where destabi-
Fig. 23(a) and (b) show the system response when the VSR lizing interaction dynamics can be mitigated at different loading
is switched on at s. As shown, -component of the conditions of the VSR.
PCC voltage suffers from relatively high oscillations for
more than 15 cycles. These oscillations are reflected to the dc IX. CONCLUSION
side with disturbed dc link voltage, as shown in Fig. 23(b). Analysis and active-impedance-based stabilization of VSR-
However, the dc link voltage response is more damped due to interfaced loads in grid-connected and isolated VSI-based mi-
the relatively high dc-link capacitor of the VSR (2040 F). crogrids have been presented in this paper. Using small-signal
The VSR is then kept working until a steady-state operating analysis, coupled ac impedance-admittance-based models of the
point is reached. Under steady-state conditions, at , the VSR, VSI-based microgrid, and utility grid are obtained by con-
dc load is increased to eight times by successive addition of the sidering all control loops and PLL dynamics. Therefore, the
remaining seven resistors in the load box. At , the dc overall system stability can be investigated using the general-
load is reset back to the minimum load. As indicated earlier in ized Nyquist stability criterion. It has been found that Nyquist
RADWAN AND MOHAMED: ANALYSIS AND ACTIVE-IMPEDANCE-BASED STABILIZATION OF VSR LOADS 575

stability criterion may be violated due to the interactions be- APPENDIX B


tween the VSR-interfaced load and the source side. Proposed
active impedance-based compensators from the VSR-side are A. Compensated Load Admittance of the VSR-Interfaced Load
presented to satisfy the generalized Nyquist stability criterion See the equation at the bottom of the page. (In , and
and to provide seamless integration of VSRs into power net- are zero for the uncompensated VSR.)
works under wide range of source characteristics. The proposed
compensators are easily implemented, and designed using linear B. Exact Source Impedance of VSI
tools, and do not require additional sensors or hardware. The
compensators have minimal influence on the dc voltage tracking
of the VSR and increase the robust stability margin against dc
voltage controller bandwidth variation. Several simulations and
experimental results are presented to validate the theoretical
analysis and the effectiveness of the proposed active-impedance
stabilization techniques.

APPENDIX A
Simulation Model:
VSR: H, , F,
F, 20 kW.
DC voltage controller s.
AC current controller s.
VSIs: mH, , F,
V, V, 60 Hz, 22 kVA.
AC voltage controller s.
AC current controller s.
PMSM: . mH, Flux linkage
V.s, inertia kg.m , pole pairs .
Speed controller s. Current controller
s.
Experimental Setup:
VSR: mH, , F,
F.
DC voltage controller s. C. Approximated Source Impedance of VSI
AC current controller s. Similar to the exact source impedance in (38) but with:
Source side: mH, . , , .
576 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 4, NO. 3, JULY 2013

REFERENCES [18] O. Gasparyan, Linear and Nonlinear Multivariable Feedback Con-


[1] ECPE European Center for Power Electronic, Strategic Research trol—A Classical Approach. Hoboken, NJ: Wiley, 2008.
Agenda on Intelligent Power Electronics for Energy Efficiency, Jan. [19] J. Maciejowski, Multivariable Feedback Design. Reading, MA: Ad-
2008. dision-Wesley, 1989.
[2] A. Radwan and Y. Mohamed, “Linear active stabilization of converter- [20] J. Sun, “Small-signal methods for ac distribution power systems—A
dominated dc microgrids,” IEEE Trans. Smart Grid, vol. 3, no. 1, pp. review,” IEEE Trans. Power Electron., vol. 24, no. 11, pp. 2545–2554,
203–216, Mar. 2012. Nov. 2009.
[3] IEEE Recommended Practice for Electronic Power Subsystems, IEEE [21] Electric Power Systems and Equipment—Voltage Ratings (60 Hertz),
Standard 1573-2003, 2004. ANSI Standard Publication no. ANSI C84.1-1995.
[4] X. Feng, J. Liu, and F. C. Lee, “Impedance specifications for stable dc [22] V. Blasko and V. Kaura, “A new mathematical model and control of
distribution power systems,” IEEE Trans. Power Electron., vol. 17, no. a three-phase AC-DC voltage source converter,” IEEE Trans. Power
2, pp. 157–162, Mar. 2002. Electron., vol. 12, no. 1, pp. 116–123, Jan. 1997.
[5] J. Sun, “Impedance-based stability criterion for grid-connected in- [23] Y. Mohamed and E. El-Saadany, “Adaptive decentralized droop con-
verters,” IEEE Trans. Power Electron., vol. 26, no. 11, pp. 3075–3078, troller to preserve power sharing stability of paralleled inverters in dis-
Nov. 2011. tributed generation microgrids,” IEEE Trans. Power Electron., vol. 23,
[6] L. Harnefors, M. Bongiorno, and S. Lundberg, “Input-admittance cal- no. 6, pp. 2806–2816, Nov. 2008.
culation and shaping for controlled voltage-source converters,” IEEE [24] D. Boroyevich, I. Cvetkovic, D. Dong, R. Burgos, F. Wang, and F.
Trans. Ind. Electron., vol. 54, no. 6, pp. 3323–3334, Dec. 2007. Lee, “Future electronic power distribution systems—A contemplative
[7] S. V. Iyer, M. N. Belur, and M. C. Chandorkar, “A generalized com- view,” in Proc. 2010 12th OPTIM Int. Conf., pp. 1369–1380.
putational method to determine stability of a multi-inverter microgrid,”
IEEE Trans. Power Electron., vol. 25, no. 9, pp. 2420–2432, Sep. 2010.
[8] N. Pogaku, M. Prodanovic’, and T. C. Green, “Modeling, analysis and
testing of autonomous operation of an inverter-based microgrid,” IEEE
Trans. Power Electron., vol. 22, no. 2, pp. 613–625, Mar. 2007. Amr Ahmed A. Radwan (S’11) was born in Cairo,
[9] G. Diaz, C. Gonzalez, J. G.-Aleixandre, and A. Diez, “Composite loads Egypt, on December 27, 1984. He received the B.Sc.
in stand-alone inverter-based micro-grids—Modeling procedure and degree (with honors) in electrical engineering from
effects on load margin,” IEEE Trans. Power Syst., vol. 25, no. 2, pp. Ain Shams University, Cairo, Egypt, in 2007, and the
894–905, May 2010. M.Sc. degree in electrical and computer engineering
[10] D. P. Ariyasinghe and D. M. Vilathgamuwa, “Stability analysis of mi- from University of Alberta, Edmonton, AB, Canada,
crogrids with constant power loads,” in Proc. 2008 IEEE ICEST Conf., in 2012, where he is currently working toward the
pp. 279–284. Ph.D. degree.
[11] M. Cespedes, L. Xing, and J. Sun, “Constant-power load system sta- His research interests are in the areas of smart
bilization by passive damping,” IEEE Trans. Power Electron., vol. 26, distribution systems and control of power electronic
no. 7, pp. 1832–1836, Jul. 2011. converters.
[12] A. Radwan and Y. Mohamed, “Modeling, analysis, and stabilization
of converter-fed ac microgrids with high penetration of converter-in-
terfaced loads,” IEEE Trans. Smart Grids, vol. 3, no. 3, pp. 1213–1225,
Sep. 2012. Yasser Abdel-Rady I. Mohamed (M’06–SM’011)
[13] A. Radwan and Y. Mohamed, “Assessment and mitigation of interac- was born in Cairo, Egypt, on November 25, 1977. He
tion dynamics in hybrid ac/dc distribution generation systems,” IEEE received the B.Sc. (with honors) and M.Sc. degrees
Trans. Smart Grid, vol. 3, no. 3, pp. 1382–1393, Sep. 2012. in electrical engineering from Ain Shams University,
[14] P. Liutanakul, A.-B. Awan, S. Pierfederici, B. N.-Mobarakeh, and F. Cairo, in 2000 and 2004, respectively, and the Ph.D.
M.-Tabar, “Linear stabilization of a dc bus supplying a constant power degree in electrical engineering from the University
load: A general design approach,” IEEE Trans. Power Electron., vol. of Waterloo, Waterloo, ON, Canada, in 2008.
25, no. 2, pp. 475–488, Feb. 2010. He is currently with the Department of Electrical
[15] Y. Mohamed, A. Radwan, and T. Lee, “Decoupled reference-voltage- and Computer Engineering, University of Alberta,
based active dc-link stabilization for PMSM drives with tight-speed AB, Canada, as an Assistant Professor. His research
regulation,” IEEE Trans. Ind. Electron., vol. 59, no. 12, pp. 4523–4536, interests include dynamics and controls of power
Dec. 2012. converters; distributed and renewable generation; modeling, analysis, and
[16] L. Fan and Z. Miao, “Nyquist-stability-criterion-based SSR explana- control of smart grids; and electric machines and motor drives.
tion for type-3 wind generators,” IEEE Trans. Energy Conv., vol. 27, Dr. Mohamed is an Associate Editor of the IEEE TRANSACTIONS
no. 3, pp. 807–809, Sep. 2012. ON INDUSTRIAL ELECTRONICS. He is also a Guest Editor of the IEEE
[17] Z. Miao, “Impedance-model-based SSR analysis for type 3 wind gen- TRANSACTIONS ON INDUSTRIAL ELECTRONICS SPECIAL SECTION ON
erator and series-compensated network,” IEEE Trans. Energy Conv., DISTRIBUTED GENERATION AND MICROGRIDS. His biography is listed in
vol. 27, no. 4, pp. 984–991, Dec. 2012. Marquis Who’s Who in the World.

You might also like