Professional Documents
Culture Documents
Protection and measuring devices require The role of a phase-current sensor is to provide its secondary winding with a current
data on the electrical rating of the equipment proportional to the measured primary current. They are used for both measurements
and protection.
to be protected. There are two types of sensors:
For technical, economic and safety reasons, b current transformers (CT),
this data cannot be obtained directly b current transformers with a voltage output (LPCT).
from the high-voltage power supply
of the equipment. The following intermediary General characteristics (fig. 1)
devices are needed: The current transformer is made up of two circuits, the primary and the secondary,
coupled by a magnetic circuit.
b phase-current sensors, When there are a number of turns in the primary circuit, the transformer is of the wound-
b core balance CTs to measure earth fault primary type.
currents, When the primary is a single conductor running through a sensor, the transformer
b voltage transformers (VT). may be of the bar-primary type (integrated primary made up of a copper bar), support
type (primary formed by an uninsulated conductor of the installation) or the toroidal
These devices fulfill the following functions: type (primary formed by an insulated cable of the installation).
b reduction of the value to be measured
(e.g. 1500/5 A), The CTs are characterized by the following values (according to standard IEC 60044)(1).
b galvanic isolation, CT rated insulation level
b provision of the power required for data This is the highest voltage applied to the CT primary.
Note that the primary is at the HV voltage level and that one of the secondary
processing and for the protection function terminals is generally earthed.
itself. Similar to other equipment, the following values are defined:
b maximum1 min. withstand voltage at power frequency,
b maximum impulse withstand voltage.
Example. For a 24 kV rated voltage, the CT must withstand 50 kV for 1 minute at 50 Hz
and an impulse voltage of 125 kV.
Rated transformation ratio
It is usually given as the transformation ratio between primary and secondary current
Ip/Is.
The rated secondary current is generally 5 A or 1 A.
Accuracy
It is defined by the composite error for the accuracy-limit current.
The accuracy-limit factor is the ratio between the accuracy-limit current and the
rated current.
b For class P:
P1 Ip 5P10 means 5% error for 10 In and 10P15 means 10% error for 15 In,
5P and 10P are the standard accuracy classes for protection CTs,
DE57330
(1) Also to be taken into account are elements related to the type of assembly,
characteristics of the site (e.g. temperature, etc.), power frequency, etc.
19
Sensors Phase-current sensors (CT) 0
R Vk 10%
C
T
+
Is R
w
RCT Rwire ire
+
Im R
S1 lo 50%
ad
E Lm Vs Rload
S2
Isecondary Imagnetizing
Isat Isn Im at Vk 1.5 Im
P2
Fig. 1. Equivalent diagram of a CT secondary current... and CT magnetization curve.
x 1.5 x 1.5
I I
Isetting Isaturation Iscmax Isaturation
Fig. 2. Fig. 3.
Differential protection
Fig. 4.
20
Sensors Phase-current sensors (LPCT) 0
S1
LPCTs are used for measurement and protection functions.
They are defined by:
Vs
b the rated primary current,
S2 b the rated extended primary current,
P2 b the rated accuracy-limit primary current.
They have a linear output over a wide current range and begin to saturate at levels
Fig. 1. LPCT-type current sensors. above the currents to be interrupted.
Example of measurement characteristics as per IEC 60044-8
b Rated primary current Ipn = 100 A
b Rated extended primary current Ipe = 1250 A
b Secondary voltage Vsn = 22.5 mV
b Class 0.5:
v accuracy 0.5% from 100 A to 1250 A,
v accuracy 0.75% at 20 A,
v accuracy 1.5% at 5 A.
Example of protection characteristics as per IEC 60044-8
b Primary current Ipn = 100 A
b Secondary voltage Vsn = 22.5 mV
b Class 5P from 1.25 kA to 40 kA (fig. 2).
Module
(%)
DE55337EN
5%
1.5%
0.75%
Module
0.5%
Ip
Phase
(min)
90'
60'
45'
Phase
30'
Ip
5A 20 A 100 A 1 kA 1.25 10 40
kA kA kA
Fig. 2. LPCT accuracy characteristics.
21
Sensors Residual-current sensors 0
Fig. 1. Definition of
I2 residual current. Detection of the fault current
Earth-fault current can be detected in a number of ways.
Measurement Accuracy Recommended Assembly
sensors minimum threshold
for earth-fault
protection
51G Neutral 51G
Special core +++ A few amperes
DE57339
DE57340EN
Irsd Irsd
balance CT
Irsd Irsd
51N
3 phase CTs + No H2 restraint I1
DE57344
22
Sensors Voltage transformers (VT) 0
In isolated neutral systems, all phase-neutral VTs sufficiently loaded to avoid the risk
of ferromagnetic resonance.
(1) Elements related to the type of assembly, characteristics of the site (e.g. temperature), etc.
must also be taken into account.
The residual voltage is equal to three times the zero-sequence voltage V0:
Vrsd = 3 • V0 = V1 + V2 + V3 (fig. 3)
Vrsd
V1 The occurrence of this voltage signals the existence of an earth fault.
It can be measured or calculated:
b measurement using three voltage transformers whose primaries are star connected
V2 and the secondaries, in an open delta arrangement, supply the residual voltage (fig. 4),
Fig. 3. Definition of residual voltage. b calculation by the relay, using three voltage transformers whose primaries and
secondaries are star connected (fig. 5).
DE57348
DE57349
59N V1 59N
V2
Vrsd
V3
23