Professional Documents
Culture Documents
Instrument Transformers :
CT and PT
The both of transformer have low VA rating
Current transformers
• To reduce the heavy current
• To isolate the relay circuit from the primary circuit
Specifications
1. Rated primary and secondary current
2. Rated short time current
3. Rated burden
4. Accuracy class
5. Ratio error
1
6. Insulation level (for only primary)
The secondary current rating is usually 5 or 1 ampere.
C.T used for instrumentations is required to be accurate
over the normal working range of currents.
C.T. used for protection is required to give a correct
ratio up to several times the rated primary current.
The rated primer current
2.5 A; 5; 7.5; 10; 15; 20; 25 30 up to10,000 Ampere.
Rated short time currents and duration for example
750 A for 0.5 sec; 525 A for 1 sec; 300 A for 3 sec.
5
Saturation with symmetrical Fault Current (with DC Component)
8
FiGURE . Typical exciter curve of a Class C or Class K multiratio CT
9
CT EXCITATION CURVE
10
Example
Current transformer is designated as 600/5 A, 2 5VA, 5P20,
RCT = 0.2 ohm. Détermine knee point voltage.
11
C.Ts. Construction
Current transformers can be classified into
a). Window type CT
which includes bushing type ; bar type C.T split-core type CT
The window type CT is the simplest form of instruments transformer
b). Wound type C.T. the latter having both a primary and secondary winding.
The most common type is that wound on a torroidal core
12
Current Transformer
13
14
Figure Polarity convection for current transformer
20
KV S V P
Percentage ratio error = x 100
VP
21
The standard accuracy classes at the rated burden are 0.3, 0.6, and
1.2. For medium and high-voltage systems, VT is selected with an
accuracy class of 0.3 at the rated burden. The standard burden
designations are W, X, M, Y, Z, and ZZ.
22
23
69 kV Single bushing Dual bushing out-door PT 242 kV single bushing
PT Construction 24