CIS INTERPHASE LEVEL CONTROL – SINGLE AND CASCADE LOOP

STARTING CONDITION DCS SELECTION 43FIC-1052 MODE 11LIC-1035 MODE 43LCV-1035

Normal CIS level @ 65-70%

INPUT FROM
DCS selection 11-LIIT-1036
(LIC or FIC [CAS])

LIC Out % converted to


LIC MODE 43LCV-1035
NOTES FOR CASCADE MODE: Flow m3/hr (as a SP)
0% LIC Output = 0 m3/hr
100% LIC Output = 130 m3/hr
INPUT FROM
43FT-1052

FIC mode [CAS]

CIS level
<62%

LIC activated
*Level Override
FIC in IMAN
setting (<62% or
>75%)

CIS level
>62%
<75%

Emerson to
support to
automate this loop

Manual re-activate
to FICA
Phase