CV ARUM ABADI

Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : Fc 35


Minimum Caracteristic Compression strength 35 MPa when tested at age of 28 days
using 15x30cm cylinder sample
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Tiga Roda Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.4 % 1.18


Sikament LN 0.6 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.41

Free water required 184 kg/m³ 184 dm³

Cement 415 kg/m³ 131.7 dm³


Silica fume 35 kg/m³ 12.5 dm³
Admixtures V105 1.80 kg/m³ 1.53 dm³
LN 2.70 kg/m³ 2.25 dm³

PASTE VOLUME 332 dm³

AGGREGATE VOLUME 668 dm³

Fine aggregate (SSD) 0.39 x 668 x 2.642 688 kg

Coarse aggregate (SSD) 0.61 x 668 x 2.649 1079 kg

Tarahan, 5-Dec-17
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : C 40


Minimum Caracteristic Compression strength 500 kg/cm2 when tested at age of 28 days
using 15x15 cm cube sample
Slump on site : 12 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Tiga Roda Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0% 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.36

Free water required 182 kg/m³ 182 dm³

Cement 513 kg/m³ 162.8 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.79 lt/m³ 1.79 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 347 dm³

AGGREGATE VOLUME 653 dm³

Fine aggregate (SSD) 0.38 x 653 x 2.642 647 kg

Coarse aggregate (SSD) 0.63 x 653 x 2.649 1082 kg

Tarahan, 5-Dec-17
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : C 40 SF


Minimum Caracteristic Compression strength 500 kg/cm2 when tested at age of 28 days
using 15x15 cm cube sample
Slump on site : 12 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Tiga Roda Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0.6 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.36

Free water required 182 kg/m³ 182 dm³

Cement 500 kg/m³ 158.7 dm³


Silica fume 30 kg/m³ 10.7 dm³
Admixtures V105 1.86 lt/m³ 1.86 dm³
LN 3.18 lt/m³ 3.18 dm³

PASTE VOLUME 356 dm³

AGGREGATE VOLUME 644 dm³

Fine aggregate (SSD) 0.36 x 644 x 2.642 609 kg

Coarse aggregate (SSD) 0.64 x 644 x 2.649 1094 kg

Tarahan, 5-Dec-17
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : Fc 35 SF Slag Cement


Minimum Caracteristic Compression strength 35 MPa when tested at age of 28 days
using 15x30 cm cylinder sample
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.67
Slag Cement
CEMENT PT.Semen Tiga Roda Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Pozzolith 402R 0.15 % 1.18


Rheobuild 1100 0.65 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.30

Free water required 165 kg/m³ 165 dm³

Cement 539 kg/m³ 171.1 dm³


Silica fume 20 kg/m³ 7.1 dm³
Admixtures V105 0.84 lt/m³ 0.84 dm³
LN 3.63 lt/m³ 3.63 dm³

PASTE VOLUME 348 dm³

AGGREGATE VOLUME 652 dm³

Fine aggregate (SSD) 0.32 x 652 x 2.642 558 kg

Coarse aggregate (SSD) 0.68 x 652 x 2.670 1177 kg

Tarahan, 24-Apr-18
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : K 125


Minimum Caracteristic Compression strength 125 kg/cm2 when tested at age of 28 days
using 15x15cm cube sample
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Tiga Roda Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0% 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.84

Free water required 188 kg/m³ 188 dm³

Cement 225 kg/m³ 71.4 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 0.79 lt/m³ 0.79 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 260 dm³

AGGREGATE VOLUME 740 dm³

Fine aggregate (SSD) 0.43 x 740 x 2.642 840 kg

Coarse aggregate (SSD) 0.57 x 740 x 2.649 1117 kg

Tarahan, 24-Apr-18
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : Fs 45 (P)


Minimum Caracteristic Flexture strength 45 kg/cm2 when tested at age of 28 days
using 15x15x45 cm beam sample
Slump on site : < 5.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0% 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.38

Free water required 160 kg/m³ 160 dm³

Cement 425 kg/m³ 134.9 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.49 lt/m³ 1.49 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 296 dm³

AGGREGATE VOLUME 704 dm³

Fine aggregate (SSD) 0.40 x 704 x 2.642 744 kg

Coarse aggregate (SSD) 0.60 x 704 x 2.649 1118 kg

Tarahan, 24-Apr-18
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT PT Indocement

CONTRACTOR CLASS OF CONCRETE :

SPECIFICATION CLASS OF CONCRETE : K 350 (B-2)


Minimum Caracteristic Compression strength 350 kg/cm2 when tested at age of 28 days
using 15x15cm cube sample
Slump on site : 15 ± 2.5 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.60

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 1% 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.49

Free water required 195 kg/m³ 195 dm³

Cement 399 kg/m³ 126.7 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.40 lt/m³ 1.40 dm³
LN 3.99 lt/m³ 3.99 dm³

PASTE VOLUME 327 dm³

AGGREGATE VOLUME 673 dm³

Fine aggregate (SSD) 0.41 x 673 x 2.604 718 kg

Coarse aggregate (SSD) 0.59 x 673 x 2.649 1052 kg

Tarahan, 30-Dec-99
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : Fc 15 (D)


Minimum Caracteristic Compression strength 15 Mpa when tested at age of 28 days
using 15x30 cm cylinder samples.
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.60

COARSE AGGREGATE Crushed Stone 10/25 ex SBC


SSD 2.649
Portland Cement Type I.
CEMENT PT.Indocement (Tiga Roda) Type I. Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.4 % 1.18


Sikament LN 0% 1.2

DESIGN CALCULATION Based on : MD01 S01

Water cement ratio 0.67

Free water required 187 kg/m³ 187 dm³

Cement 280 kg/m³ 88.9 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.12 lt/m³ 1.12 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 277 dm³

AGGREGATE VOLUME 723 dm³

Fine aggregate (SSD) 0.43 x 723 x 2.604 809 kg

Coarse aggregate (SSD) 0.57 x 723 x 2.649 1092 kg

Tarahan, 13-Jan-16
Prepared by,

Teguh Aji P
Quality Control Dept.
12
TR C 430 NFA + V 107 CP
N/A K 450 Type I 10+/-2 0 184 440 415 0 2500%

0.108108

0.084337
24.09639

,
15 N/A K 525 Type I 10+/-2 0.36 182 513 513 0 0
12
TR C 470 NFA + V 107 CP
N/A K 500 Type I 10+/-2 0.34 182 530 500 0 30
11
TR C 415 NFA + V 107 CP
N/A K 425 / Fc 35 Type I 10+/-2 0.28 155 559 539 0 20
2TR C 250 NFA + V218.63149
105 K 200 Type I 10+/-2 0.74 186 250 250 0 0

18.07229
12
TR C 430 NFA + V 107 CP
N/A K 450 Type I 10+/-2 0.38 160 425 425 0 0

2447
8 MD 01 S02 K 350 N/A K 350 Type I 10+/-2 0.44 182 410 410 0 0
TR
4 C 280 NFA + V 105
248.81276
CP K 225 Type I 10+/-2 1 187 280 280 0 0%

18.07229
0 671 733 395 0.00 1.860 2.79
38% 642 722 389 0 2.05 0.000 2397.98 #DIV/0! #DIV/0!
36% 603 730 393 0 2.24 3.360 2397.98 ### ###
32% 559 885 295 0 1.74 3.632 2388.98 #DIV/0! #DIV/0!
44% #DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00 0.000 2389.98 #DIV/0! #DIV/0!
37% #DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00 0.000 2389.98 #DIV/0! #DIV/0!
41% #DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00 0.000 2393.98 #DIV/0! #DIV/0!
0.435 824 722.21 388.8825 0 1.12 0
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : Fc 35 TRIAL CODE / NUMBER : TR FC 35 SF

SLUMP DESIGN : 12 +/- 2

DATE : 7-Dec-17 START MIXING : 10.07 WIB

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 415.0 Kg 16.6 Kg 16.6 Kg 16.6 Kg 0.0 16.6 Kg 415 Kg

SILICAFUME 35.0 Kg 1.4 Kg 1.4 Kg 1.4 Kg 0.0 1.4 Kg 35 Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 688.3 Kg 27.5 Kg 28.5 Kg 28.5 Kg 0.0 28.5 Kg 712.6 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 701.6 Kg 28.1 Kg 28.6 Kg 28.6 Kg 0.0 28.6 Kg 715.8 Kg
Crushed Stone 20/30 ex SBB 35 1.8 377.8 Kg 15.1 Kg 15.4 Kg 15.4 Kg 0.0 15.4 Kg 385.4 Kg

WATER ADDED 184.0 Kg 7.4 Kg 6.7 Kg 5.6 Kg 1.1 7.8 Kg 194.5 Kg

ADDITIVES
Plastiment V105 1.5 Lt 0.06 Lt 0.06 Lt 0.06 Lt 0.0 0.06 Lt 1.5 Lt
Sikament LN 2.3 Lt 0.09 Lt 0.09 Lt 0.09 Lt 0.0 0.09 Lt 2.3 Lt

SLUMP Time : 10 s 2405.4 98.51 2462.07


Cm : 12.0 cm
6.3366

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = 23.5 Kg Air tempr. : 27 C

Weight of container = 10.5 Kg Conc.temp.: 30 C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = 13 Kg

Approved by Checked by Submitted Prepared


Volume of container = 5.301 Lt

Fresh concrete density = 2452.4 Kg/m³

Actual batch volume = 0.040 x 5 = 0,2 m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : C 40 TRIAL CODE / NUMBER : TR K 500

SLUMP DESIGN : 12 +/- 2

DATE : 12/07/17 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 513 Kg 20.5 Kg Kg 20.5 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 647 Kg 25.9 Kg Kg 27.1 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 703.2 Kg 28.1 Kg Kg 28.6 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 378.7 Kg 15.1 Kg 15.4 Kg

WATER ADDED 182.0 Kg 7.3 Kg Kg 5.3 Kg Kg Kg

ADDITIVES
Plastiment V105 1.79 Lt 0.07 Lt Lt 0.07 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : 2426 _____ _________


Cm : 12.0 cm _____

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : C 40 SF TRIAL CODE / NUMBER : K 500 SF

SLUMP DESIGN : 12 +/- 2

DATE : 4-Oct-17 START MIXING :

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(SSD) (A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 500.0 Kg 20.0 Kg 20 Kg 20.0 Kg 0.0 20.0 Kg 500 Kg

SILICAFUME 30.0 Kg 1.2 Kg 1.2 Kg 1.2 Kg 0.0 1.2 Kg 30 Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 608.7 Kg 24.3 Kg 24.3 Kg 25.5 Kg -1.2 23.1 Kg 577 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 711.4 Kg 28.5 Kg 28.5 Kg 29.0 Kg -0.5 28.0 Kg 701 Kg
Crushed Stone 20/30 ex SBB 35 1.8 383.0 Kg 15.3 Kg 15.3 Kg 15.6 Kg -0.3 15.0 Kg 375 Kg

WATER ADDED 182.0 Kg 7.3 Kg 7.6 Kg 5.3 Kg 2.3 9.9 Kg 247 Kg

ADDITIVES
Plastiment V105 1.86 Lt 0.07 Lt 0.07 Lt 0.07 Lt 0.0 0.07 Lt 1.6 Lt
Sikament LN 3.2 Lt 0.13 Lt 0.13 Lt 0.13 Lt 0.0 0.13 Lt 3.3 Lt

SLUMP : Time : s 2421 97.43 2434.89


Cm : cm

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : C

Weight of container = Kg Conc.temp.: C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Minimum Caracteristic Compression strength 35 MPa when tested at age of 28 days

CONTRACTOR : Slump on site : 10 ± 2.0 cm.

CLASS OF CONCRETE : Fc 35 SF Slag Cement TRIAL CODE / NUMBER : TR 01 FC 35 SF Slag Cement

SLUMP DESIGN : 10 +/- 2

DATE : 14-Dec-17 START MIXING : 13 : 30 WIB

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 539 Kg 21.6 Kg 21.6 Kg 21.6 Kg 0.0 21.6 Kg 541 Kg

SILICAFUME 20.0 Kg 0.8 Kg 0.8 Kg 0.8 Kg 0.0 0.8 Kg 20 Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 558.4 Kg 22.3 Kg 22.6 Kg 23.1 Kg -0.5 22.1 Kg 552.1 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 765.3 Kg 30.6 Kg 31 Kg 31.2 Kg -0.2 30.8 Kg 770.9 Kg
Crushed Stone 20/30 ex SBB 35 1.8 412.1 Kg 16.5 Kg 16.7 Kg 16.8 Kg -0.1 16.6 Kg 415.5 Kg

WATER ADDED 165.0 Kg 6.6 Kg 6.3 Kg 5.0 Kg 1.3 7.6 Kg 190.7 Kg

ADDITIVES
Plastiment V105 0.8 Lt 0.03 Lt 0.07 Lt 0.03 Lt 0.0 0.11 Lt 2.7 Lt
Sikament LN 3.6 Lt 0.15 Lt 0.15 Lt 0.15 Lt 0.0 0.15 Lt 3.9 Lt

SLUMP Time : 13:50 2464.1 99.92 2496.9


Cm : 16.0 cm
After 60 Menit 14:50 12.0 cm

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : 27 C

Weight of container = Kg Conc.temp.: 28 C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


0.432262995445

3.5000

1.8000
1.8000

6.3366
1.408133333333
4.8000

1.8000
1.8000
4.8000

1.8000
1.8000

0.465877861227
0.339888347675

3.5000

1.8000
1.8000

6.3366
1.129163522013
42.1686746988

#REF!

0.00530
#REF!
#REF!
42.1686746988

#REF!

0.00530
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : Fc 35 TRIAL CODE / NUMBER : TR FC 35 SF

SLUMP DESIGN : 12 +/- 2

DATE : 7-Dec-17 START MIXING : 10.07 WIB

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 415.0 Kg 16.6 Kg 16.6 Kg 16.6 Kg 0.0 16.6 Kg 415 Kg

SILICAFUME 35.0 Kg 1.4 Kg 1.4 Kg 1.4 Kg 0.0 1.4 Kg 35 Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 688.3 Kg 27.5 Kg 28.5 Kg 28.5 Kg 0.0 28.5 Kg 712.6 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 701.6 Kg 28.1 Kg 28.6 Kg 28.6 Kg 0.0 28.6 Kg 715.8 Kg
Crushed Stone 20/30 ex SBB 35 1.8 377.8 Kg 15.1 Kg 15.4 Kg 15.4 Kg 0.0 15.4 Kg 385.4 Kg

WATER ADDED 184.0 Kg 7.4 Kg 6.7 Kg 5.6 Kg 1.1 7.8 Kg 194.5 Kg

ADDITIVES
Plastiment V105 1.5 Lt 0.06 Lt 0.06 Lt 0.06 Lt 0.0 0.06 Lt 1.5 Lt
Sikament LN 2.3 Lt 0.09 Lt 0.09 Lt 0.09 Lt 0.0 0.09 Lt 2.3 Lt

SLUMP Time : 10 s 2405.4 98.51 2462.07


Cm : 12.0 cm
6.3366

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = 23.5 Kg Air tempr. : 27 C

Weight of container = 10.5 Kg Conc.temp.: 30 C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = 13 Kg

Approved by Checked by Submitted Prepared


Volume of container = 5.301 Lt

Fresh concrete density = 2452.4 Kg/m³

Actual batch volume = 0.040 x 5 = 0,2 m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : C 40 TRIAL CODE / NUMBER : TR K 500

SLUMP DESIGN : 12 +/- 2

DATE : 12/07/17 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 513 Kg 20.5 Kg Kg 20.5 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 647 Kg 25.9 Kg Kg 27.1 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 703.2 Kg 28.1 Kg Kg 28.6 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 378.7 Kg 15.1 Kg 15.4 Kg

WATER ADDED 182.0 Kg 7.3 Kg Kg 5.3 Kg Kg Kg

ADDITIVES
Plastiment V105 1.79 Lt 0.07 Lt Lt 0.07 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : 2426 _____ _________


Cm : 12.0 cm _____

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : C 40 SF TRIAL CODE / NUMBER : K 500 SF

SLUMP DESIGN : 12 +/- 2

DATE : 4-Oct-17 START MIXING :

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(SSD) (A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 500.0 Kg 20.0 Kg 20 Kg 20.0 Kg 0.0 20.0 Kg 500 Kg

SILICAFUME 30.0 Kg 1.2 Kg 1.2 Kg 1.2 Kg 0.0 1.2 Kg 30 Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 608.7 Kg 24.3 Kg 24.3 Kg 25.5 Kg -1.2 23.1 Kg 577 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 711.4 Kg 28.5 Kg 28.5 Kg 29.0 Kg -0.5 28.0 Kg 701 Kg
Crushed Stone 20/30 ex SBB 35 1.8 383.0 Kg 15.3 Kg 15.3 Kg 15.6 Kg -0.3 15.0 Kg 375 Kg

WATER ADDED 182.0 Kg 7.3 Kg 7.6 Kg 5.3 Kg 2.3 9.9 Kg 247 Kg

ADDITIVES
Plastiment V105 1.86 Lt 0.07 Lt 0.07 Lt 0.07 Lt 0.0 0.07 Lt 1.6 Lt
Sikament LN 3.2 Lt 0.13 Lt 0.13 Lt 0.13 Lt 0.0 0.13 Lt 3.3 Lt

SLUMP : Time : s 2421 97.43 2434.89


Cm : cm

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : C

Weight of container = Kg Conc.temp.: C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Minimum Caracteristic Compression strength 35 MPa when tested at age of 28 days

CONTRACTOR : Slump on site : 10 ± 2.0 cm.

CLASS OF CONCRETE : Fc 35 SF Slag Cement TRIAL CODE / NUMBER : TR 02 FC 35 SF Slag Cement

SLUMP DESIGN : 10 +/- 2

DATE : 14-Dec-17 START MIXING : 14 : 29 WIB

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 539 Kg 21.6 Kg 21.6 Kg 21.6 Kg 0.0 21.6 Kg 541.176 Kg

SILICAFUME 20.0 Kg 0.8 Kg 0.8 Kg 0.8 Kg 0.0 0.8 Kg 20 Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 558.4 Kg 22.3 Kg 23.5 Kg 23.1 Kg 0.4 23.9 Kg 597.1 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 765.3 Kg 30.6 Kg 31 Kg 31.2 Kg -0.2 30.8 Kg 770.9 Kg
Crushed Stone 20/30 ex SBB 35 1.8 412.1 Kg 16.5 Kg 16.7 Kg 16.8 Kg -0.1 16.6 Kg 415.5 Kg

WATER ADDED 165.0 Kg 6.6 Kg 6.5 Kg 5.0 Kg 1.5 8.0 Kg 200.7 Kg

ADDITIVES
Plastiment V105 0.8 Lt 0.03 Lt 0.07 Lt 0.03 Lt 0.0 0.11 Lt 2.7 Lt
Sikament LN 3.6 Lt 0.15 Lt 0.15 Lt 0.15 Lt 0.0 0.15 Lt 3.9 Lt

SLUMP Time : 14:41 2464.1 102 2551.9


Cm : 15.5 cm
After 60 Menit 15:41 12.0 cm

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : 27 C

Weight of container = Kg Conc.temp.: 28 C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


0.432262995445

3.5000

1.8000
1.8000

6.3366
1.408133333333
4.8000

1.8000
1.8000
4.8000

1.8000
1.8000

0.465877861227
0.357708054174

3.5000

1.8000
1.8000

6.3366
1.129163522013
42.1686746988

#REF!

0.00530
#REF!
#REF!
42.1686746988

#REF!

0.00530
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : Fc 35 TRIAL CODE / NUMBER : TR FC 35 SF

SLUMP DESIGN : 12 +/- 2

DATE : 7-Dec-17 START MIXING : 10.07 WIB

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 415.0 Kg 16.6 Kg 16.6 Kg 16.6 Kg 0.0 16.6 Kg 415 Kg

SILICAFUME 35.0 Kg 1.4 Kg 1.4 Kg 1.4 Kg 0.0 1.4 Kg 35 Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 688.3 Kg 27.5 Kg 28.5 Kg 28.5 Kg 0.0 28.5 Kg 712.6 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 701.6 Kg 28.1 Kg 28.6 Kg 28.6 Kg 0.0 28.6 Kg 715.8 Kg
Crushed Stone 20/30 ex SBB 35 1.8 377.8 Kg 15.1 Kg 15.4 Kg 15.4 Kg 0.0 15.4 Kg 385.4 Kg

WATER ADDED 184.0 Kg 7.4 Kg 6.7 Kg 5.6 Kg 1.1 7.8 Kg 194.5 Kg

ADDITIVES
Plastiment V105 1.5 Lt 0.06 Lt 0.06 Lt 0.06 Lt 0.0 0.06 Lt 1.5 Lt
Sikament LN 2.3 Lt 0.09 Lt 0.09 Lt 0.09 Lt 0.0 0.09 Lt 2.3 Lt

SLUMP Time : 10 s 2405.4 98.51 2462.07


Cm : 12.0 cm
6.3366

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = 23.5 Kg Air tempr. : 27 C

Weight of container = 10.5 Kg Conc.temp.: 30 C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = 13 Kg

Approved by Checked by Submitted Prepared


Volume of container = 5.301 Lt

Fresh concrete density = 2452.4 Kg/m³

Actual batch volume = 0.040 x 5 = 0,2 m³

CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15
TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : C 40 TRIAL CODE / NUMBER : TR K 500

SLUMP DESIGN : 12 +/- 2

DATE : 12/07/17 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 513 Kg 20.5 Kg Kg 20.5 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 647 Kg 25.9 Kg Kg 27.1 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 703.2 Kg 28.1 Kg Kg 28.6 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 378.7 Kg 15.1 Kg 15.4 Kg

WATER ADDED 182.0 Kg 7.3 Kg Kg 5.3 Kg Kg Kg

ADDITIVES
Plastiment V105 1.79 Lt 0.07 Lt Lt 0.07 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : 2426 _____ _________


Cm : 12.0 cm _____

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : C 40 SF TRIAL CODE / NUMBER : K 500 SF

SLUMP DESIGN : 12 +/- 2

DATE : 4-Oct-17 START MIXING :

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(SSD) (A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 500.0 Kg 20.0 Kg 20 Kg 20.0 Kg 0.0 20.0 Kg 500 Kg

SILICAFUME 30.0 Kg 1.2 Kg 1.2 Kg 1.2 Kg 0.0 1.2 Kg 30 Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 608.7 Kg 24.3 Kg 24.3 Kg 25.5 Kg -1.2 23.1 Kg 577 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 711.4 Kg 28.5 Kg 28.5 Kg 29.0 Kg -0.5 28.0 Kg 701 Kg
Crushed Stone 20/30 ex SBB 35 1.8 383.0 Kg 15.3 Kg 15.3 Kg 15.6 Kg -0.3 15.0 Kg 375 Kg

WATER ADDED 182.0 Kg 7.3 Kg 7.6 Kg 5.3 Kg 2.3 9.9 Kg 247 Kg

ADDITIVES
Plastiment V105 1.86 Lt 0.07 Lt 0.07 Lt 0.07 Lt 0.0 0.07 Lt 1.6 Lt
Sikament LN 3.2 Lt 0.13 Lt 0.13 Lt 0.13 Lt 0.0 0.13 Lt 3.3 Lt

SLUMP : Time : s 2421 97.43 2434.89


Cm : cm

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : C

Weight of container = Kg Conc.temp.: C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Minimum Caracteristic Compression strength 35 MPa when tested at age of 28 days

CONTRACTOR : Slump on site : 10 ± 2.0 cm.

CLASS OF CONCRETE : Fc 35 SF Slag Cement TRIAL CODE / NUMBER : TR 03 FC 35 SF Slag Cement

SLUMP DESIGN : 10 +/- 2

DATE : 14-Dec-17 START MIXING : 14 : 57 WIB

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 539 Kg 21.6 Kg 21.6 Kg 21.6 Kg 0.0 21.6 Kg 541 Kg

SILICAFUME 20.0 Kg 0.8 Kg 0.8 Kg 0.8 Kg 0.0 0.8 Kg 20 Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 558.4 Kg 22.3 Kg 22.6 Kg 23.1 Kg -0.5 22.1 Kg 552.1 Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 765.3 Kg 30.6 Kg 31 Kg 31.2 Kg -0.2 30.8 Kg 770.9 Kg
Crushed Stone 20/30 ex SBB 35 1.8 412.1 Kg 16.5 Kg 16.7 Kg 16.8 Kg -0.1 16.6 Kg 415.5 Kg

WATER ADDED 165.0 Kg 6.6 Kg 6.05 Kg 5.0 Kg 1.1 7.1 Kg 178.2 Kg

ADDITIVES
Plastiment V105 0.8 Lt 0.03 Lt 0.07 Lt 0.03 Lt 0.0 0.11 Lt 2.7 Lt
Sikament LN 3.6 Lt 0.15 Lt 0.15 Lt 0.15 Lt 0.0 0.15 Lt 3.9 Lt

SLUMP Time : 15:10 2464.1 99.42 2484.4


Cm : 9.0 cm
After 30 Menit 15:40 8.0 cm

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : 27 C

Weight of container = Kg Conc.temp.: 28 C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


0.432262995445

3.5000

1.8000
1.8000

6.3366
1.408133333333
4.8000

1.8000
1.8000
4.8000

1.8000
1.8000

0.465877861227
0.317613714551

3.5000

1.8000
1.8000

6.3366
1.129163522013
42.1686746988

#REF!

0.00530
#REF!
#REF!
42.1686746988

#REF!

0.00530
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : P Fs 45 TRIAL CODE / NUMBER : TR FS 45

SLUMP DESIGN : Max : 5 cm

DATE : 13-Jan-16 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 425.0 Kg 17.0 Kg Kg 17.0 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 743.6 Kg 29.7 Kg Kg 30.8 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 50 1.8 559.1 Kg 22.4 Kg Kg 22.8 Kg Kg Kg


Crushed Stone 20/30 ex SBB 50 1.8 559.1 Kg 22.4 Kg 22.8 Kg

WATER ADDED 160.0 Kg 6.4 Kg Kg 4.6 Kg Kg Kg

ADDITIVES
Plastiment V105 1.5 Lt 0.06 Lt Lt 0.06 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : _____ _________


Cm : cm _____
6.3366

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : B2 C 40 TRIAL CODE / NUMBER : TR K 350

SLUMP DESIGN : 16 +/- 2

DATE : 01/13/16 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 399.0 Kg 16.0 Kg Kg 16.0 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 718.3 Kg 28.7 Kg Kg 30.1 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 683.6 Kg 27.3 Kg Kg 27.8 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 368.1 Kg 14.7 Kg 15.0 Kg

WATER ADDED 195.0 Kg 7.8 Kg Kg 5.7 Kg Kg Kg

ADDITIVES
Plastiment V105 1.4 Lt 0.06 Lt Lt 0.06 Lt Lt
Sikament LN 4.0 Lt 0.16 Lt Lt 0.16 Lt Lt Lt

SLUMP : Time : 2370 _____ _________


Cm : cm _____

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³


Actual batch volume = m³

CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : D Fc 15 TRIAL CODE / NUMBER : TR Fc 15

SLUMP DESIGN : 5 +/- 2

DATE : 01/13/16 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 280.0 Kg 11.2 Kg Kg 11.2 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 809.4 Kg 32.4 Kg Kg 33.9 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 50 1.8 545.8 Kg 21.8 Kg Kg 22.2 Kg Kg Kg


Crushed Stone 20/30 ex SBB 50 1.8 545.8 Kg 21.8 Kg 22.2 Kg

WATER ADDED 187.0 Kg 7.5 Kg Kg 5.1 Kg Kg Kg

ADDITIVES
Plastiment V105 1.1 Lt 0.04 Lt Lt 0.04 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : 2369 _____ _________


Cm : cm _____

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Approved by Checked by Submitted Prepared
Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


#DIV/0!

3.5000

1.8000
1.8000

6.3366
#DIV/0!
4.8000

1.8000
1.8000
4.8000

1.8000
1.8000
#REF!
#REF!
18.07228916

#REF!
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : K 250 ( C )


Minimum Caracteristic Compression strength 250 kg/cm2 when tested at age of 28 days
using 15x15cm cube sample
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.59

Free water required 187 kg/m³ 187 dm³

Cement 318 kg/m³ 101.0 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.11 kg/m³ 0.94 dm³
LN 0.00 kg/m³ 0.00 dm³

PASTE VOLUME 289 dm³

AGGREGATE VOLUME 711 dm³

Fine aggregate (SSD) 0.43 x 711 x 2.642 798 kg

Coarse aggregate (SSD) 0.58 x 711 x 2.649 1083 kg

Tarahan, 28-Nov-15
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : K 350 ( B-1)


Minimum Caracteristic Compression strength 350 kg/cm2 when tested at age of 28 days
using 15x15cm cube sample
Slump on site : 7,5 ± 2.5 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.48

Free water required 182 kg/m³ 182 dm³

Cement 380 kg/m³ 120.6 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.33 lt/m³ 1.33 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 304 dm³

AGGREGATE VOLUME 696 dm³

Fine aggregate (SSD) 0.41 x 696 x 2.642 756 kg

Coarse aggregate (SSD) 0.59 x 696 x 2.649 1086 kg

Tarahan, 28-Nov-15
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : Fc 35


Minimum Caracteristic Compression strength 35 MPa when tested at age of 28 days
using 15x30cm cylinder sample
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.43

Free water required 184 kg/m³ 184 dm³

Cement 430 kg/m³ 136.5 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.51 lt/m³ 1.51 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 322 dm³

AGGREGATE VOLUME 678 dm³

Fine aggregate (SSD) 0.40 x 678 x 2.642 711 kg

Coarse aggregate (SSD) 0.60 x 678 x 2.649 1083 kg

Tarahan, 28-Nov-15
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : K 300


Minimum Caracteristic Compression strength 300 kg/cm2 when tested at age of 28 days
using 15x15cm cube sample
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.52

Free water required 182 kg/m³ 182 dm³

Cement 350 kg/m³ 111.1 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.23 lt/m³ 1.23 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 294 dm³

AGGREGATE VOLUME 706 dm³

Fine aggregate (SSD) 0.42 x 706 x 2.642 783 kg

Coarse aggregate (SSD) 0.58 x 706 x 2.649 1084 kg

Tarahan, 28-Nov-15
Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : K 125 (E)


Minimum Caracteristic Compression strength 125 kg/cm2 when tested at age of 28 days
using 15x15cm cube sample
Slump on site : 5 ± 2.5 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.84

Free water required 188 kg/m³ 188 dm³

Cement 225 kg/m³ 71.4 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 0.79 lt/m³ 0.79 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 260 dm³

AGGREGATE VOLUME 740 dm³

Fine aggregate (SSD) 0.43 x 740 x 2.642 840 kg

Coarse aggregate (SSD) 0.57 x 740 x 2.649 1117 kg

Tarahan, 28-Nov-15
Prepared by,

Teguh Aji P.
Quality Control Dept.

CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : Fs 45 (P)


Minimum Caracteristic Flexture strength 45 kg/cm2 when tested at age of 28 days
using 15x15x45 cm beam sample
Slump on site : < 5.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.64

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 0 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.38

Free water required 160 kg/m³ 160 dm³

Cement 425 kg/m³ 134.9 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.49 lt/m³ 1.49 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 296 dm³

AGGREGATE VOLUME 704 dm³

Fine aggregate (SSD) 0.40 x 704 x 2.642 744 kg

Coarse aggregate (SSD) 0.60 x 704 x 2.649 1118 kg

Tarahan, 28-Nov-15
Prepared by,
Teguh Aji P.
Quality Control Dept.

CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT PT Adhi Karya (Persero) Tbk

CONTRACTOR CLASS OF CONCRETE :

SPECIFICATION CLASS OF CONCRETE : K 350 (B-2)


Minimum Caracteristic Compression strength 350 kg/cm2 when tested at age of 28 days
using 15x15cm cube sample
Slump on site : 15 ± 2.5 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.60

COARSE AGGREGATE Crushed Stone 10/25 ex SBB


SSD 2.65
Portland Cement Type I.
CEMENT PT.Semen Holcim Readyflow Plus Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.35 % 1.18


Sikament LN 1 % 1.2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0.48

Free water required 182 kg/m³ 182 dm³

Cement 380 kg/m³ 120.6 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.33 lt/m³ 1.33 dm³
LN 3.80 lt/m³ 3.80 dm³

PASTE VOLUME 308 dm³

AGGREGATE VOLUME 692 dm³

Fine aggregate (SSD) 0.41 x 692 x 2.604 741 kg

Coarse aggregate (SSD) 0.59 x 692 x 2.649 1080 kg

Tarahan, 30-Dec-99
Prepared by,
Teguh Aji P.
Quality Control Dept.

CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Lampung Cement Terminal

CONTRACTOR PT Indocement

SPECIFICATION CLASS OF CONCRETE : Fc 15 (D)


Minimum Caracteristic Compression strength 15 Mpa when tested at age of 28 days
using 15x30 cm cylinder samples.
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.60

COARSE AGGREGATE Crushed Stone 10/25 ex SBC


SSD 2.649
Portland Cement Type I.
CEMENT PT.Indocement (Tiga Roda) Type I. Conform to ASTM C.150. 3.15
SILICAFUME PT.Sika Indonesia 2.8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0.4 % 1.18


Sikament LN 0 % 1.2

DESIGN CALCULATION Based on : MD01 S01

Water cement ratio 0.67

Free water required 187 kg/m³ 187 dm³

Cement 280 kg/m³ 88.9 dm³


Silica fume 0 kg/m³ 0.0 dm³
Admixtures V105 1.12 lt/m³ 1.12 dm³
LN 0.00 lt/m³ 0.00 dm³

PASTE VOLUME 277 dm³

AGGREGATE VOLUME 723 dm³

Fine aggregate (SSD) 0.44 x 723 x 2.604 819 kg

Coarse aggregate (SSD) 0.57 x 723 x 2.649 1082 kg


Tarahan, 13-Jan-16
Prepared by,

Teguh Aji P
Quality Control Dept.
TR
5 C 318 NFA + V 105 CP
N/A K 275 Type I 10+/-2 1 187 318 318 0 0% 0

0.108108

24.09639
8 MD 01 S02 K 350 N/A K 350 Type I 10+/-2 0.44 182 410 410 0 0 41%
12
TR C 430 NFA + V 107 CP
N/A K 450 Type I 10+/-2 0.43 184 430 430 0 0 40%
1 MD 01 S02 K 125 N/A K 125 Type I 10+/-2 0.70 182 260 260 0 0 43%
2TR C 250 NFA + V218.63149
105 K 200 Type I 10+/-2 0.74 186 250 250 0 0 44%

18.07229
12
TR C 430 NFA + V 107 CP
N/A K 450 Type I 10+/-2 0.38 160 425 425 0 0 37%

2447
8 MD 01 S02 K 350 N/A K 350 Type I 10+/-2 0.44 182 410 410 0 0 41%
TR
4 C 280 NFA + V 105
248.81276
CP K 225 Type I 10+/-2 1 187 280 280 0 0% 0.435

18.07229
791 723 389 0.00 1.272
#DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00 0.000 2393.98 #DIV/0! #DIV/0!
705 723 389 0 1.72 0.000 2397.98 ### ###
#DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00 0.000 2388.98 #DIV/0! #DIV/0!
#DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00 0.000 2389.98 #DIV/0! #DIV/0!
#DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00 0.000 2389.98 #DIV/0! #DIV/0!
#DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00 0.000 2393.98 #DIV/0! #DIV/0!
824 722.21 388.8825 0 1.12 0
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : Fs 45 TRIAL CODE / NUMBER : TR FS 45

SLUMP DESIGN : Max : 5 cm

DATE : 22-Oct-15 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 425.0 Kg 17.0 Kg Kg 17.0 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 743.6 Kg 29.7 Kg Kg 30.8 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 726.9 Kg 29.1 Kg Kg 29.6 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 391.4 Kg 15.7 Kg 15.9 Kg

WATER ADDED 160.0 Kg 6.4 Kg Kg 4.6 Kg Kg Kg

ADDITIVES
Plastiment V105 1.5 Lt 0.06 Lt Lt 0.06 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : _____ _________


Cm : cm _____
6.3366

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : Fc 35 SF Sl NFA TRIAL CODE / NUMBER : TR K 300

SLUMP DESIGN : 7 +/- 2

DATE : 10/22/15 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 538.8 Kg 21.6 Kg Kg 21.6 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 558.4 Kg 22.3 Kg Kg 22.3 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 765.3 Kg 30.6 Kg Kg 31.2 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 412.1 Kg 16.5 Kg 16.8 Kg

WATER ADDED 165.0 Kg 6.6 Kg Kg 5.8 Kg Kg Kg

ADDITIVES
Plastiment V105 0.8 Lt 0.03 Lt Lt 0.03 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : 2440 _____ _________


Cm : cm _____

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³


Actual batch volume = m³

CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : C 40 NFA TRIAL CODE / NUMBER : TR K 350

SLUMP DESIGN : 10 +/- 2

DATE : 10/22/15 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 512.7 Kg 20.5 Kg Kg 20.5 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 647.4 Kg 25.9 Kg Kg 25.9 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 703.2 Kg 28.1 Kg Kg 28.6 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 378.7 Kg 15.1 Kg 15.4 Kg

WATER ADDED 182.0 Kg 7.3 Kg Kg 6.5 Kg Kg Kg

ADDITIVES
Plastiment V105 1.8 Lt 0.07 Lt Lt 0.07 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : 2426 _____ _________


Cm : cm _____

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt
Fresh concrete density = Kg/m³

Actual batch volume = m³


#DIV/0!

3.5000

1.8000
1.8000

6.3366
#DIV/0!
1.8000
1.8000
1.8000
1.8000
#REF!
1177
1082
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : Fc 35 TRIAL CODE / NUMBER : TR Fc 35

SLUMP DESIGN : 10 +/- 2

DATE : 10-Sep-15 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 0.040 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 500.0 Kg 20.0 Kg Kg 20.0 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Pasir Gunung Sugih 3.5 608.7 Kg 24.3 Kg Kg 25.2 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 711.4 Kg 28.5 Kg Kg 29.0 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 383.0 Kg 15.3 Kg 15.6 Kg

WATER ADDED 182.0 Kg 7.3 Kg Kg 5.6 Kg Kg Kg

ADDITIVES
Plastiment V105 1.9 Lt 0.07 Lt Lt 0.07 Lt Lt
Sikament LN 3.2 Lt 0.13 Lt Lt 0.13 Lt Lt Lt

SLUMP : Time : _____ _________


Cm : cm _____
6.3366

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³

Actual batch volume = m³


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

TRIALMIX WORKSHEET

PROJECT : Lampung Cement Terminal

CONTRACTOR : PT Indocement

CLASS OF CONCRETE : C 40 NFA TRIAL CODE / NUMBER : TR K 175

SLUMP DESIGN : 4 +/- 2

DATE : 09/10/15 START MIXING : ________

BATCH FIGURES : QUANTITY


Design Design Real Berat Koreksi BERAT STL
(A) (B) Stl Koreksi air Vol 0.04 m3 KOREKSI
Teoritis Real VOLUME
SIZE OF BATCH 1.000 M3 1.000 M3 0.040 M3 (C) D=(B-C) E=(A+D) 1.000 M3

MATERIAL

CEMENT 265.0 Kg 265.0 Kg Kg 265.0 Kg Kg Kg

SILICAFUME 0.0 Kg 0.0 Kg Kg 0.0 Kg Kg Kg


Kadar air
FINE AGGREGATE

Natural sand ex Gunung Sugih 4.8 852.0 Kg 852.0 Kg Kg 860.0 Kg Kg Kg

COARSE AGGREGATE

Crushed Stone 10/20 ex SBB 65 1.8 729.0 Kg 729.0 Kg Kg 739.0 Kg Kg Kg


Crushed Stone 20/30 ex SBB 35 1.8 392.0 Kg 392.0 Kg 398.0 Kg

WATER ADDED 150.0 Kg 150.0 Kg Kg 160.0 Kg Kg Kg

ADDITIVES
Plastiment VZ 0.8 Lt 0.82 Lt Lt 0.82 Lt Lt
Sikament LN 0.0 Lt 0.00 Lt Lt 0.00 Lt Lt Lt

SLUMP : Time : 2389 _____ _________


Cm : cm _____

UNIT WEIGHT CHECK REMARKS :

Weight of container + concrete = Kg Air tempr. : _______ C

Weight of container = Kg Conc.temp.: _______ C


______ ______ __________ _ __ ______ _ _ ______ _
Air cont. : _______ %
Weight of fresh concrete = Kg

Approved by Checked by Submitted Prepared


Volume of container = 5,301 Lt

Fresh concrete density = Kg/m³


Actual batch volume = m³
#DIV/0!

3.5000

1.8000
1.8000

6.3366
#DIV/0!
1.8000
1.8000
#REF!
#REF!
TRIALMIX WORKSHEE

PROJECT TOL BENOA

CLASS OF CONCRETE : K 600 TRIAL CODE / NUMBER : TR PC 521 PLASTIMENT 163

DATE START MIXING : 15:0

BATCH FIGURES : QUANTITY


Design Real Berat Koreksi
Stl Koreksi air
SIZE OF BATCH 1.000 M3 1 M3 Teoritis

MATERIAL

CEMENT 521.0 Kg 521 Kg 521.0

FLYASH 114.0 Kg 112 Kg 114.0


Abs Kadar air
FINE AGGREGATE

Pasir Ex Butus 3.67 10 561.3 Kg 555 Kg 596.8

COARSE AGGREGATE

Split 10/20 Ex Muncan 2.80 0.5 934.9 Kg 905 Kg 913.4

WATER ADDED 190.0 Kg 196 Kg 175.9

ADDITIVES
Retarder 0.0 Lt 0 Lt
Sikament 163 6.2 Lt 5.30 Lt 5.3

SLUMP : Time : ### 2328


Cm : ### cm

UNIT WEIGHT CHE REMARKS :

Weight of container + concrete Kg Air tempr. :


Weight of container Kg Conc.temp.:
______ ______ _________ ___ __ ______ _ _ _____ _
Air cont. :
Weight of fresh concrete = Kg

Volume of container Lt CONCRETE TECHNICIAN :

Fresh concrete density = Kg/m³

Actual batch volume m³

Actual batch volume = #DIV/0! #DIV/0! m³


21 PLASTIMENT 163

Berat Koreksi BERAT STL K


VOLUME
1.000 M3

M3

521.0 Kg 528 Kg 0.3307943 528.0823977058

114.0 Kg 116 Kg Kg #DIV/0!

Kg

### 519 Kg 527 Kg 6.3285

Kg 0.0000

### 926 Kg 939 Kg -2.2961

Kg 0.0000
### 210 Kg 213 Kg

Kg
6
5.30 Lt 5.37 Lt

Lt
2297.25 2328.48
1.014 2328.48 6.3366
0.9845065
6.3366
#DIV/0!

C
C C

- % C

%
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

SIEVE ANALYSIS

DESCRIPTION AND : RECEIVED


SOURCE OF SAMPLE Natural Sand Ex Gunung Sugih ON : 19-Aug-17

TO BE USED FOR : All Concrete TOTAL WEIGHT 3150


OF SAMPLE : GRAM

SIEVE RETAINED ON SIEVE CUMULATIV CUMULATIVE GRADING SPECIFICATION


SIZE RETAINED PASSING JISS-5 CLASS II
MM GRAM % % %

40 0 0.00 0.0 100.0 100 - 100


25 0 0.00 0.0 100.0 100 - 100
20 0 0.00 0.0 100.0 100 - 100
15 0 0.00 0.0 100.0 100 - 100
10 25 0.79 0.8 99.2 100 - 100
5 115 3.65 4.4 95.6 90 - 100
2.5 228 7.24 11.7 88.3 80 - 100
1.2 592 18.79 30.5 69.5 50 - 90
0.6 1185 37.62 68.1 31.9 25 - 65
0.3 495 15.71 83.8 16.2 10 - 35
0.15 400 12.70 96.5 3.5 2 - 10
PAN 110 3.49 100.0 0.0
FM = 2.96
PASSIN G PERCENT AG E

100

90

80

70

60

50

40

30

20

10

0
0.1 1 10 100
SIEVE SIZE (MM)
Low Limit Up Limit Aggregate G rading

TESTED AND CALCULATED BY : Jamhari DATE : 19-Aug-17

CHECKED BY : Teguh AP DATE : 20-Aug-17


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

SIEVE ANALYSIS

DESCRIPTION AND : RECEIVED


SOURCE OF SAMPLE Crushed stone ex Tanjung (G 20) ON : 19-Aug-17

TO BE USED FOR : All Concrete TOTAL WEIGHT 5424


OF SAMPLE : GRAM

SIEVE RETAINED ON SIEVE CUMULATIV CUMULATIVE GRADING SPECIFICATION


SIZE RETAINED PASSING JISS-5 CLASS II
MM GRAM % % %

40 0 0.00 0.0 100.0 100 - 100


25 0 0.00 0.0 100.0 100 - 100
20 0 0.00 0.0 100.0 90 - 100
15 1783 32.87 32.9 67.1 55 - 80
10 2025 37.33 70.2 29.8 20 - 55
5 1343 24.76 95.0 5.0 0 - 10
2.5 245 4.52 99.5 0.5 0 - 5
1.2 28 0.52 100.0 0.0 0 0
0.6 0 0.00 100.0 0.0 0 0
0.3 0 0.00 100.0 0.0 0 0
0.15 0 0.00 100.0 0.0 0 0
FM = 6.98
PASSIN G PER CEN T AG E

100

90

80

70

60

50

40

30

20

10

0
0.1 1 10 100
SIEVE SIZE (MM)

Low Limit Up Limit Aggregate Grading

TESTED AND CALCULATED BY : Jamhari DATE : 19-Aug-17

CHECKED BY : Teguh AP DATE : 20-Aug-17


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

SIEVE ANALYSIS

DESCRIPTION AND : RECEIVED


SOURCE OF SAMPLE Crushed stone ex Tanjung (G25) ON : 19-Aug-17

TO BE USED FOR : All Concrete TOTAL WEIGHT 5426


OF SAMPLE : GRAM

SIEVE RETAINED ON SIEVE CUMULATIV CUMULATIVE GRADING SPECIFICATION


SIZE RETAINED PASSING JISS-5 CLASS II
MM GRAM % % %

40 0 0.00 0.0 100.0 100 - 100


25 0 0.00 0.0 100.0 90 - 100
20 483 8.90 8.9 91.1 60 - 90
15 1944 35.83 44.7 55.3 40 - 70
10 1804 33.25 78.0 22.0 20 - 50
5 957 17.64 95.6 4.4 0 - 10
2.5 218 4.02 99.6 0.4 0 - 5
1.2 20 0.37 100.0 0.0 0 0
0.6 0 0.00 100.0 0.0 0 0
0.3 0 0.00 100.0 0.0 0 0
0.15 0 0.00 100.0 0.0 0 0
FM = 7.27
PASSIN G PER CEN T AG E

100

90

80

70

60

50

40

30

20

10

0
0.1 1 10 100
SIEVE SIZE (MM)

Low Limit Up Limit Aggregate Grading

TESTED AND CALCULATED BY : Jamhari DATE : 19-Aug-17

CHECKED BY : Teguh AP DATE : 20-Aug-17


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

SIEVE ANALYSIS

DESCRIPTION AND : RECEIVED


SOURCE OF SAMPLE Crushed stone ex Tanjung (G25) ON : 28-Mar-13

TO BE USED FOR : All Concrete TOTAL WEIGHT 4823.2461


OF SAMPLE : GRAM

SIEVE RETAINED ON SIEVE CUMULATIV CUMULATIVE GRADING SPECIFICATION


SIZE RETAINED PASSING JISS-5 CLASS II
MM GRAM % % %

40 0 0.00 0.0 100.0 100 - 100


25 0 0.00 0.0 100.0 90 - 100
20 91.71 1.90 1.9 98.1 60 - 90
15 1617 33.53 35.4 64.6 40 - 70
10 1760 36.49 71.9 28.1 20 - 50
5 1122 23.26 95.2 4.8 0 - 10
2.5 212.9 4.41 99.6 0.4 0 - 5
1.2 19.6 0.41 100.0 0.0 0 0
0.6 0 0.00 100.0 0.0 0 0
0.3 0 0.00 100.0 0.0 0 0
0.15 0 0.00 100.0 0.0 0 0
FM = 7.04
PASSING PERCENTAG E

100

90

80

70

60

50

40

30

20

10

0
0.1 1 10 100
Low Limit Up Limit SIEVE SIZE (MM)
Aggregate Grading

TESTED AND CALCULATED BY : Jamhari DATE : 29-Mar-13

CHECKED BY : Teguh AP DATE : 29-Mar-13


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

SIEVE ANALYSIS

DESCRIPTION AND : RECEIVED


SOURCE OF SAMPLE Fine Aggregate and Coarse Aggregate ON :

TO BE USED FOR : All Concrete TOTAL WEIGHT


OF SAMPLE : GRAM

SIEVE RETAINED ON SIEVE CUMULATIV CUMULATIVE GRADING SPECIFICATION


SIZE RETAINED PASSING JISS-5 CLASS II
MM GRAM % % %

40 0.00 0.0 100.0 100 - 100


25 0.00 0.0 100.0 100 - 100
20 0.00 0.0 100.0 50 - 75
15 0.00 0.0 100.0 42 - 70
10 0.00 0.0 100.0 36 - 60
5 0.00 0.0 100.0 24 - 47
2.5 0.00 0.0 100.0 18 - 39
1.2 0.00 0.0 100.0 12 30
0.6 0.00 0.0 100.0 7 23
0.3 0.00 0.0 100.0 3 15
0.15 0.00 0.0 100.0 0 5
FM = 0.00
PASSING PERCENTAGE

100

90

80

70

60

50

40

30

20

10

0
0.1 1 10 100
SIEVE SIZE (MM)

Batas 1 Batas 2 Batas 3 Batas 4


Batas 1 Batas 2 Batas 3 Batas 4

TESTED AND CALCULATED BY : Jamhari DATE :

CHECKED BY : Teguh AP DATE :


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

MATERIAL LABORATORIUM ASTM C 177 - 90

AMOUNT OF MATERIAL FINNER THAN 0.075 MM ( NO. 200 )


SIEVE IN AGGREGATE

TO BE USED FOR All Concrete

SAMPLE NO RECEIVED ON 19-Aug-17

DESCRIPTION &
SOURCE OF SAMPLE Crushed Stone ex Tanjung

RUN NO : I II

B WEIGHT OF DRY OVEN SAMPLE 795 789


( gram )

C WEIGHT OF WASHED & DRY OVEN SAMPLE AND 790 785


RETAINED ON 0.075 MM ( No. 200 ) SIEVE

A OF MATERIAL FINER THAN (B)-(C)


------------- * 100% 0.63% 0.51%
0.075 MM ( NO. 200 ) SIEVE (B)

REMARKS 0.57%

TESTED & CALCULATED BY Jamhari DATE 19-Aug-17

CHECKED BY Teguh AP DATE 20-Aug-17


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

MATERIAL LABORATORIUM ASTM C 177 - 90

AMOUNT OF MATERIAL FINNER THAN 0.075 MM ( NO. 200 )


SIEVE IN AGGREGATE

TO BE USED FOR All Concrete

SAMPLE NO RECEIVED ON 19-Aug-17

DESCRIPTION & Natural Sand ex Gunung Sugih


SOURCE OF SAMPLE

RUN NO : I II

B WEIGHT OF DRY OVEN SAMPLE 1765 1770


( gram )

C WEIGHT OF WASHED & DRY OVEN SAMPLE AND 1737 1741


RETAINED ON 0.075 MM ( No. 200 ) SIEVE

A OF MATERIAL FINER THAN (B)-(C)


------------- * 100% 1.59% 1.64%
0.075 MM ( NO. 200 ) SIEVE (B)

REMARKS 1.61%

TESTED & CALCULATED BY Jamhari DATE 19-Aug-17

CHECKED BY Teguh AP DATE 20-Aug-17


195000
910000 1,105,000
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

MATERIAL LABORATORIUM ASTM C 127 /84

SPECIFIC GRAVITY OF COARSE AGGREGATE

TO BE USED FOR All Concrete

SAMPLE NO RECEIVED ON 20-Aug-17

DESCRIPTION & Crushed stone ex Tanjung


SOURCE OF SAMPLE I.( G.20 ) II.( G.25 )

RUN NO : I II
NO. OF FLASK

A WEIGHT OF SSD SAMPLE ON AIR (gram) 8757 8657

B WEIGHT OF SSD SAMPLE IN WATER (gram) 5420 5330

C WEIGHT OF OVEN DRY SAMPLE (gram) 8650 8540

1 SPECIFIC GRAVITY A 2.624 2.602


SSD BASIS --------------------------
A - B 2.670

2 SPECIFIC GRAVITY C 2.592 2.567


OVEN DRY BASIS --------------------------
A - B 2.580

3 SPECIFIC GRAVITY C 2.678 2.660


APPARENT --------------------------
C - B 2.669

A - C 1.237 1.370
4 WATER ABSORPTION -------------------------- x 100 %
C 1.304

REMARKS :

TESTED & CALCULATED BY Jamhari DATE 20-Aug-17

CHECKED BY Teguh AP DATE 21-Aug-17


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

MATERIAL LABORATORIUM ASTM C 128 /84

SPECIFIC GRAVITY OF FINE AGGREGATE

TO BE USED FOR All Concrete

SAMPLE NO RECEIVED ON 20-Aug-17

DESCRIPTION & Natural sand ex Gunung Sugih


SOURCE OF SAMPLE

RUN NO : I II
NO. OF FLASK

A WEIGHT OF SSD SAMPLE ON AIR (gram) 507 511

B WEIGHT OF SSD SAMPLE IN WATER (gram) 142 142

C WEIGHT OF FLASK + SSD MATERIAL + (gram) 638 638


WATER UP TO CALIBRATION MARK

D WEIGHT OF FLASK + SSD MATERIAL + (gram) 950 953


WATER UP TO CALIBRATION MARK

E WEIGHT OF OVEN DRY SAMPLE (gram) 501 505

1 SPECIFIC GRAVITY A 2.600 2.607


SSD BASIS --------------------------
A+C-D 2.642

2 SPECIFIC GRAVITY E 2.600 2.607


OVEN DRY BASIS --------------------------
A+C-D 2.604

3 SPECIFIC GRAVITY E 2.651 2.658


APPARENT --------------------------
E+C-D 2.654

A-E 1.198 1.188


4 WATER ABSORPTION -------------------------- x 100 %
E 1.193

REMARKS :

TESTED & CALCULATED BY Jamhari DATE 20-Aug-17

CHECKED BY Teguh AP DATE 21-Aug-17


2.670

2.566

2.682

1.304
2.642

1.193
#100 0.15 No mm 0 0 2
#50 0.33 3 7 11
#30 0.6 2" 50 7 13 17
#16 1.18 1.5" 38.1 12 16 24
#8 2.36 1" 25.4 18 25 31
#4 4.75 3/4" 19 24 32 40
3/8" 9.5 1/2" 12.5 36 43 52
3/4" 19 3/8" 9.5 50 60 67
1 1/2" 38.1 No 4 4.75 100 100 100
2" 50 No 8 2.36 100 100 100
No 10
No 12 1.7
No 16 1.18
No 30 0.6
No 50 0.33
No 70 0.212
No 100 0.15
No 200 0.075
No 270 0.053
5
15
23
30
39
47
60
75
100
100
No Ayakan

No mm Jml
G 25 (PLN)
2" 50 1.5"
1.5" 38.1 1"
1" 25.4 3/4"
3/4" 19 1/2"
1/2" 12.5 3/8"
3/8" 9.5 No 4
No 4 4.75 2 No 8
No 8 2.36
No 10
No 12 1.7 2
No 16 1.18 3
No 30 0.6 Keuntungan
No 50 0.33 Harga Bp
No 70 0.212 Harga silo tambahan
No 100 0.15 2 Bor air
No 200 0.075 Direksi kit & Lab
No 270 0.053 Upah
Kendaraan
Biaya operasional

2 tahun
60% harga jual
Penyusutan 20%/tahun
0.64
640 jt
640,000,000.00 10,847.46
Sand
3/8"
No 4
No 8
No 16
No 30
No 50
No 100

1,600,000,000.00 Sales
120,000,000.00 Biaya
70,000,000.00 Keuntungan - Biaya penyusutan
- Keuntungan
PT AD HI KARYA ( Pe rs e ro ), Tbk
Divisi Konstruksi II
Plant Tarahan

CONCRETE MIX DESIGN DATA

PROJECT Tarahan Coal Fired Steam Power Plant Project

CONTRACTOR PT. ADHI KARYA (Persero) Division II

SPECIFICATION CLASS OF CONCRETE : Class A K 270


Minimum Caracteristic Compression strength 270 kg/cm² when tested at age of 28 days
using 15 x 30 cm silinder samples.
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.6

COARSE AGGREGATE Crushed Stone 10/25 ex SBC


SSD 2.61
Portland Cement Type I.
CEMENT PT.Semen Baturaja Conform to ASTM C.150. 3.15
FLYASH PT Sinarfajar Cahaya Suryatama 2.1

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Pozzolith 100 Ri 0.25 % 1.12

DESIGN CALCULATION
Water cement ratio 0.44

Free water required 174 kg/m³ 174 dm³

Cement 316 kg/m³ 100.3 dm³


Fly Ash 79 kg/m³ 37.6 dm³
Admixtures 0.988 lt/m³ 0.988 dm³

PASTE VOLUME 313 dm³

AGGREGATE VOLUME 687 dm³

Fine aggregate (SSD) 0.38 x 687 x 2.6 679 kg

Coarse aggregate (SSD) 0.62 x 687 x 2.61 1112 kg

Jakarta , ###
Prepared by,

Quality Control Dept.


PT AD HI KARYA ( Pe rs e ro ), Tbk
Divisi Konstruksi II
Plant Tarahan

CONCRETE MIX DESIGN DATA

PROJECT Tarahan Coal Fired Steam Power Plant Project

CONTRACTOR PT. ADHI KARYA (Persero) Division II

SPECIFICATION CLASS OF CONCRETE : Class D K 150


Minimum Caracteristic Compression strength 150 kg/cm² when tested at age of 28 days
using 15 x 30 cm silinder samples.
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.6

COARSE AGGREGATE Crushed Stone 10/25 ex SBC


SSD 2.61
Portland Cement Type I.
CEMENT PT.Semen Baturaja Conform to ASTM C.150. 3.15
FLYASH PT Sinarfajar Cahaya Suryatama 2.1

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Pozzolith 100 Ri 0.25 % 1.12

DESIGN CALCULATION
Water cement ratio 0.62

Free water required 179 kg/m³ 179 dm³

Cement 232 kg/m³ 73.7 dm³


Fly Ash 58 kg/m³ 27.6 dm³
Admixtures 0.725 lt/m³ 0.725 dm³

PASTE VOLUME 281 dm³

AGGREGATE VOLUME 719 dm³

Fine aggregate (SSD) 0.38 x 719 x 2.6 710 kg

Coarse aggregate (SSD) 0.62 x 719 x 2.61 1163 kg

Jakarta , ###
Prepared by,

Quality Control Dept.


PT ADHI KARYA ( Pe rs e ro ), Tbk
Divisi Konstruksi II
Plant Tarahan

CONCRETE MIX DESIGN DATA

PROJECT Tarahan Coal Fired Steam Power Plant Project

CONTRACTOR PT. ADHI KARYA (Persero) Division II

SPECIFICATION CLASS OF CONCRETE : Class B K 210


Minimum Caracteristic Compression strength 210 kg/cm² when tested at age of 28 days
using 15 x 30 cm silinder samples.
Slump on site : 10 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2.6

COARSE AGGREGATE Crushed Stone 10/25 ex SBC


SSD 2.61
Portland Cement Type II.
CEMENT PT.Semen Padang Conform to ASTM C.150. 3.15
FLYASH PT Sinarfajar Cahaya Suryatama 2.1

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Pozzolith 100 Ri 0.25 % 1.12

DESIGN CALCULATION
Water cement ratio 0.5

Free water required 173 kg/m³ 173 dm³

Cement 276 kg/m³ 87.6 dm³


Fly Ash 69 kg/m³ 32.9 dm³
Admixtures 0.863 lt/m³ 0.863 dm³

PASTE VOLUME 294 dm³

AGGREGATE VOLUME 706 dm³

Fine aggregate (SSD) 0.38 x 706 x 2.6 697 kg

Coarse aggregate (SSD) 0.62 x 706 x 2.61 1142 kg

Jakarta , ###
Prepared by,

Quality Control Dept.


Hasil Pengujian Kuat Tekan Beton
PT AD HI KARYA ( Pe rs e ro ), Tbk
Divisi Konstruksi II Benda Uji : Silinder dia 15 x 30
Plant Tarahan Proyek : Tarahan Coal Fired Steam Power Plant Project
Umur : 7 hari
Semen : Type I

Concrete Mutu Tanggal Berat Volume Berat isi Luas Slump Beban Kuat Tekan 7 H Kuat Tekan 28 H
No fas (Estimasi)
Type kg/cm 2
Pembuatan Pengujian kg cm 3
cm 2
cm kg kg/cm 2
kg/cm 2
1 A 270 0.44 29-May-04 5-Jun-04 12.75 5301.44 2.405 176.71 10 33000 186.75 287.30
2 12.46 5301.44 2.350 176.71 10 29000 164.11 252.48
3 12.46 5301.44 2.351 176.71 10 35000 198.06 304.71
4 B 210 0.50 29-May-04 5-Jun-04 12.56 5301.44 2.370 176.71 10 26000 147.13 226.36
5 12.52 5301.44 2.362 176.71 10 28000 158.45 243.77
6 12.48 5307.44 2.352 176.71 10 28000 158.45 243.77
7 D 150 0.62 29-May-04 5-Jun-04 12.53 5307.44 2.361 176.71 10 21000 118.84 182.83
8 12.44 5306.44 2.344 176.71 10 19000 107.52 165.42
9 12.43 5307.44 2.341 176.71 10 21000 118.84 182.83
10

Checked by Tested by

Quality Control Laboratory


MATERIAL QUALITY CONTROL FLOWCHART

START

FINE AGGREGATE LABORATORY

- QUARRY VOLUME
- GRADATION MIX TRIAL MIX JOB MIX
ASTM C136-93
- SPECIFIC GRAVITY/ ASTM C 128-93 DESIGN FORMULA
ABSORPTION
- SILT CONTENT ASTM C 177-90 ACI 211.1-89 - MOIST CONTENT ASTM C566-89 ACI 211.1-89
- ORGANIC IMPURITY ASTM C 40-92 ACI 211.-89 - SLUMP TEST ASTM C143-90a ACI 211.1-81
- SOUNDNESS TEST ASTM C 88-90 DOE - UNIT WEIGHT ASTM C138-92 DOE
- SETTING TIME ASTM C403-92
- VISUAL CONDITION ACI 311.4R-88
- STRENGTH ASTM C39-93a

COARSE AGGREGATE

- QUARRY VOLUME
- GRADATION ASTM C136-93
- SPECIFIC GRAVITY/ ASTM C 127-88
ABSORPTION
- SILT CONTENT
BATCHING PLANT PRODUCTION
ASTM C 177-90
- ABRASION TEST ASTM C 131-89
- SOUNDNESS TEST ASTM C 88-90 - AGGREGATE & CEMENT SCALE CONTROL ASTM C94-94
- WATER & ADDITIVE FLOW CONTROL ASTM C94-94
- AGGREGATE MOISTURE CONTENT ASTM C566-89
- CONRETE UNIT WEIGHT UNIT WEIGHT ASTM C138-92
- CONCRETE VISUAL CHECK ASTM 311.4R-88

CEMENT
- GRAIN FINENESS ASTM C024
- SETTING TIME ASTM C191-77
- SPECIFIC GRAVITY/ ASTM C188-78
TRANSPORTATION
TRANSPORTATION ASTM C94-94

FLY ASH

- FINEST TEST ASTM C311-94a PROJECT LOCATION


- LOSS OF IGNITION TEST ASTM C311-94a
- SLUMP TEST ASTM C143-90a
- CONCRETE SAMPLING ASTM C31-91

ADDITIVE
LABORATORY

- INITIAL TIME ASTM C191-77 - CONCRETE SAMPLING CURING ASTM C192-90a


- VISCOSITY TEST ASTM C494-92 - CONCRETE STRENGTH TEST 7 & 28 DAYS ASTM C39-93a
- TEST RESULT EVALUATION ASTM 437.1R
- REPORTING ASTM C94-94

WATER AREA MANAGER

- pH - TEST REPORT CONFIRMATION


- CHLORIDE CONTENT ASTM C1218-92

MAIN
CONTRACTOR

END
CONCRETE PRODUCTION FLOWCHART

START

AGGREGATE
FLY ASH CEMENT WATER ADMIXTURE
QUARRY
SELECTION

NO
QUANTITY
TEST

OK

NO
QUALITY
TEST

OK

TRIAL
START
PRODUCTION

BATCHING PLANT
MIX DESIGN
ERECTION

TRIAL MIX SCALE


CALIBRATION

SCALE
NO REPAIRING
YIELD & YES NO
VISUAL CALIBRATION
DEVIATION CHECK
TREND RESULT
MONITOR
OK
FOR
THE
NEXT PRODUCTION
PRODUCT
CONTROL

DELIVERY

CONCRETE POURING ON SITE

SAMPLING

SAMPLE TESTING &


EVALUATION

END
PROPOSAL
JOB MIX FORMULA

Lampung Cement Terminal

Kontraktor
PT Indocement

CV Arum Abadi

PLANT TARAHAN
DATA, PENGUJIAN DAN REFERENSI
MATERIAL UNTUK BETON
MIX DESIGN DATA
KONTROL PROSES PRODUKSI
PENGENDALIAN MUTU PRODUKSI
EVALUASI PENERIMAAN BETON
HASIL TEST SEMEN
HASIL TEST AGREGAT KASAR
HASIL TEST AGREGAT HALUS
BROSUR ADMIXTURE
HASIL TEST AIR
LAMPIRAN
SCHEDULE ESTIMASI
Lampung Cement Terminal

PT Indocement
I MATERIAL DAN PENGUJIAN UNTUK BETON

A. MATERIAL

1. Semen

a. Jenis Semen : Ordinary Portland Cement dari PT Semen Tiga Roda

b. Tipe : Readyflow Plus (Type 1)

c. Spesifikasi : ASTM. C 150. Specification for Portland Cement

d. Periode Test : Intern Pabrik 1 Bulan


Laboratorium Independen 6 Bulan

2. Silicafume

a. Jenis Fly Ash : Silicafume dari PT Sika Indonesia

b Spesifikasi : ASTM. C 1240 (Standard Specification for Silica fume for Use
in Hydraulic Cement Concrete and Mortart.)

c Periode Test : Intern Pabrik 1 Bulan


Laboratorium Independen 6 Bulan

3. Air

a. Sumber : Air Tanah

b. Spesifikasi : DIN ( Methods of test for Water for Making Concrete )


4. Aggregate

a. Asal Aggregate Halus : Pasir dari Gunung Sugih, Bandar Lampung

b. Asal Aggregate Kasar : Ex SBB Tanjungan, Bandar Lampung

c. Spesifikasi : ASTM. C 33

d. Pengujian Meliputi : 1 Test method for Organic Impurities in Fine Aggregate for
Concrete (ASTM.C 40)

2 Test Method for Soundness of Aggregates by Use of Sodium


Sulfate or Magnesium Sulfate (ASTM.C 88)

3 Test Method for Materials Finer than 75 micrometer (No.200)


sieve in Mineral Aggregates by Washing. (ASTM C.177)

4 Test Method for Specific Gravity and Absorption of Coarse


Aggregate (ASTM C. 127)

5 Test Method for Specific Gravity and Absorption of Fine


Aggregate (ASTM C. 128)

6 Test Method for Resistance to Degradation of small- size


Coarse Aggregate by Abrasion and Impact in the Los Angeles
Machine (ASTM. C131)

7 Test Method for Sieve Analisys of Fine and Coarse Aggregate


(ASTM. C 136)

8 Test Method for Clay Lumps and Friabl Particles in Aggregate


(ASTM. C 142)
5. Admixture

a. Jenis Admixture : Liquid Admixture

b. Nama Admixture : Plastiment V105


(Type G : Water Reducing & Retarding)

c. Spesifikasi : ASTM. C 494 (Standard Specification for Chemical Admixtures


for Concrete)

d. Produksi : PT. Sika Indonesia

e. Periode test : Sertifikat Pabrik 1 Bulan


II. Kontrol Proses Produksi

Pengetesan campuran beton segar dilaksanakan :

Slump test di Plant : ASTM. C 143 (Test Methods for Slump of Hydraulic Cement Concrete)

Test Yield : ASTM. C 138 (Test Method for Unit Weight Yield, and Air Content
(Gravimetric) of Concrete.

Slump Test di Proyek : ASTM. C 143 (Test Methods for Slump of Hydraulic Cement Concrete)
III. Pengendalian Mutu Produksi

1. Frekwensi Pengambilan Benda Uji


Pengambilan sample sesuai dengan ACI 318-83

a. Minimal diambil satu kali pengambilan benda uji untuk setiap mutu dalam satu hari pengecoran atau,

b. Minimal diambil satu kali pengambilan untuk setiap volume, 114 - m3 ( 150 cu yd ) untuk setiap mutu dalam
satu hari pengecoran atau,

c. Minimal satu kali pengambilan untuk pengecoran konstruksi plat atau dinding dengan luas (5000 sq ft)
464.5 m2.

Sesuai hal tersebut diatas maka pengambilan benda uji diatur sebagai berikut :

TM ke 1 : adalah 1 kali pengambilan, 3 buah sample


TM ke 2 - 5 : adalah 2 kali pengambilan, 3 buah sample
TM ke 6 - 10 : adalah 3 kali pengambilan, 3 buah sample
Setiap tambahan 10 TM ditambah 1X. 3 sample.

Tiap-tiap pengambilan dibuat 3 Benda Uji. Untuk dilaksanakan test :

1 Buah umur 7 hari


2 Buah umur 28 hari

Untuk Pengecoran precast maka jumlah sample diambil 4 sample dengan rincian
pengetesan adalah :
1 Buah umur 5 hari
1 Buah umur 7 hari
2 Buah umur 28 hari
Pengambilan sample sesuai dengan ASTM C.172
(Practice for sampling Freshly Mixed Concrete)

Pembuatan dan Perawatan benda uji sesuai dengan ASTM C.31


(Practice for Making and Curing Concrete Test Specimens in Field)

Pengetesan benda uji sesuai dengan ASTM. C 39 (Test Method for Compresive Strength of Cylindrical
Concrete Specimens)

Pengetesan benda uji dilakukan di Laboratorium CV Arum Abadi, Plant Tarahan.


IV. Evaluasi Penerimaan Beton

Kriteria Penerimaan Mutu Beton Mengacu pada ACI. 318-83

Ketentuan Umum
a. Satu hasil test adalah dari 2 benda uji dalam sample yang sama.

b. Evaluasi berdasarkan 30 atau lebih hasil test (Umur 28 hari) yang dihitung dengan rumus :
f'c = fcr - 1.34 S

c. Untuk hasil test, 15 s/d 29 untuk Deviasi Standar dikalikan Faktor koreksi :

No Test Modifikasi Faktor Untuk


Standar Deviasi
15 1.16
20 1.08
25 1.03
30 1.0

d. Secara khusus kekuatan dari masing2 mutu sesuai dengan yang disyaratkan :

1. Rata-rata dari semua pasangan tiga hasil test berurutan sama atau lebih dari f'c.

2. Tidak ada satupun hasil test (Rata2 dua Cylinder) dibawah f'c.
DAFTAR REFERENSI

1 ASTM ( American Society For Testing And Materials )


Vol. 04.02 ( Concrete and Aggregate )

1 ACI ( American Concrete Institute ) ACI.318-83 / Reaproved


1993 ( Building Code Requirements for Reinforced Concrete )
mutu dalam