PROPOSAL

JOB MIX FORMULA

Zulu Jetty Construction (Cargill)

Kontraktor
PT Mutiara Indah Construction

CV Arum Abadi

PLANT TARAHAN
DATA, PENGUJIAN DAN REFERENSI
MATERIAL UNTUK BETON
I MATERIAL DAN PENGUJIAN UNTUK BETON

A. MATERIAL

1. Semen

a. Jenis Semen : Ordinary Portland Cement dari PT Semen Padang

b. Tipe : OPC (Type 1)


Type V

c. Spesifikasi : ASTM. C 150. Specification for Portland Cement

d. Periode Test : Intern Pabrik 1 Bulan


Laboratorium Independen 6 Bulan

2. Slag Powder

a. Jenis Slag : Ground Granulated Blast Furnace Slag dari PT Krakatau Strell

b Spesifikasi : ASTM. C 989 (Standard Specification for Ground Granulated


Blast Furnace Slag for Use in Concrete and Mortar)

c Periode Test : Intern Pabrik 1 Bulan


Laboratorium Independen 6 Bulan

3. Air

a. Sumber : Air Tanah

b. Spesifikasi : DIN ( Methods of test for Water for Making Concrete )


4. Aggregate

a. Asal Aggregate Halus : Pasir dari Gunung Sugih, Bandar Lampung

b. Asal Aggregate Kasar : Ex Tanjungan, Bandar Lampung

c. Spesifikasi : ASTM. C 33

d. Pengujian Meliputi : 1 Test method for Organic Impurities in Fine Aggregate for
Concrete (ASTM.C 40)

2 Test Method for Soundness of Aggregates by Use of Sodium


Sulfate or Magnesium Sulfate (ASTM.C 88)

3 Test Method for Materials Finer than 75 micrometer (No.200)


sieve in Mineral Aggregates by Washing. (ASTM C.177)

4 Test Method for Specific Gravity and Absorption of Coarse


Aggregate (ASTM C. 127)

5 Test Method for Specific Gravity and Absorption of Fine


Aggregate (ASTM C. 128)

6 Test Method for Resistance to Degradation of small- size


Coarse Aggregate by Abrasion and Impact in the Los Angeles
Machine (ASTM. C131)

7 Test Method for Sieve Analisys of Fine and Coarse Aggregate


(ASTM. C 136)

8 Test Method for Clay Lumps and Friabl Particles in Aggregate


(ASTM. C 142)
5. Admixture

a. Jenis Admixture : Liquid Admixture

b. Nama Admixture : Plastiment V105


(Type G : Water Reducing & Retarding)
Sikament LN
(Type F : High Range Water Reducing & Retarding)

c. Spesifikasi : ASTM. C 494 (Standard Specification for Chemical Admixtures


for Concrete)

d. Produksi : PT. Sika Indonesia

e. Periode test : Sertifikat Pabrik 1 Bulan


MIX DESIGN DATA
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Zulu Jetty Construction (Cargill)

CONTRACTOR PT Mutiara Indah Construction

SPECIFICATION CLASS OF CONCRETE : C 40 / 50


Minimum Caracteristic Compression strength 40 Mpa when tested at age of 28 days
using 15x30 cm Cylinder sample
Slump on site : 12 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2,60

COARSE AGGREGATE Crushed Stone 10/25 ex Tanjungan


SSD 2,65
Portland Cement Type I.
CEMENT PT Semen Padang (OPC) Conform to ASTM C.150. 3,15
SLAG POWDER Ex Krakatau Stell 2,1

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0,35 % 1,18


Sikament LN 0 % 1,2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0,35

Free water required 182 kg/m³ 182 dm³

Cement 338 kg/m³ 107,3 dm³


Slag Powder 182 kg/m³ 86,7 dm³
Admixtures V105 1,82 kg/m³ 1,54 dm³
LN 0,00 kg/m³ 0,00 dm³

PASTE VOLUME 378 dm³

AGGREGATE VOLUME 622 dm³

Fine aggregate (SSD) 0,38 x 622 x 2,604 616 kg

Coarse aggregate (SSD) 0,62 x 622 x 2,649 1022 kg

Tarahan, 15 Juli 2021


Prepared by,

Teguh Aji P.
Quality Control Dept.
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

CONCRETE MIX DESIGN DATA

PROJECT Zulu Jetty Construction (Cargill)

CONTRACTOR PT Mutiara Indah Construction

SPECIFICATION CLASS OF CONCRETE : C 40/50


Minimum Caracteristic Compression strength 40 MPa when tested at age of 28 days
using 15x30 cm Cylinder sample
Slump on site : 12 ± 2.0 cm.
Maximum size of coarse aggregate : 25 mm.

MATERIAL

FINE AGGREGATE Natural sand ex Gunung Sugih SP.GRAVITY


SSD 2,60

COARSE AGGREGATE Crushed Stone 10/25 ex Tanjungan


SSD 2,65
Portland Cement Type V
CEMENT PT Semen Padang (Type V) Conform to ASTM C.150. 3,15
2,8

WATER Pottable and not contain more than 0.1 % of chloride ions. 1

ADMIXTURES Plastiment V105 0,35 % 1,18


Sikament LN 0,6 % 1,2

DESIGN CALCULATION Based on : MD01 - S02

Water cement ratio 0,30

Free water required 160 kg/m³ 160 dm³

Cement 540 kg/m³ 171,4 dm³


Silica fume 0 kg/m³ 0,0 dm³
Admixtures V105 1,89 kg/m³ 1,60 dm³
LN 3,24 kg/m³ 2,70 dm³

PASTE VOLUME 336 dm³

AGGREGATE VOLUME 664 dm³

Fine aggregate (SSD) 0,37 x 664 x 2,604 640 kg

Coarse aggregate (SSD) 0,63 x 664 x 2,649 1109 kg

Tarahan, 15 Juli 2021


Prepared by,

Teguh Aji P.
Quality Control Dept.
KONTROL PROSES PRODUKSI
II. Kontrol Proses Produksi

Pengetesan campuran beton segar dilaksanakan :

Slump test di Plant : ASTM. C 143 (Test Methods for Slump of Hydraulic Cement Concrete)

Test Yield : ASTM. C 138 (Test Method for Unit Weight Yield, and Air Content
(Gravimetric) of Concrete.

Slump Test di Proyek : ASTM. C 143 (Test Methods for Slump of Hydraulic Cement Concrete)
MATERIAL QUALITY CONTROL FLOWCHART

START

FINE AGGREGATE LABORATORY

- QUARRY VOLUME
- GRADATION MIX TRIAL MIX JOB MIX
ASTM C136-93
- SPECIFIC GRAVITY/ ASTM C 128-93 DESIGN FORMULA
ABSORPTION
- SILT CONTENT ASTM C 177-90 ACI 211.1-89 - MOIST CONTENT ASTM C566-89 ACI 211.1-89
- ORGANIC IMPURITY ASTM C 40-92 ACI 211.-89 - SLUMP TEST ASTM C143-90a ACI 211.1-81
- SOUNDNESS TEST ASTM C 88-90 DOE - UNIT WEIGHT ASTM C138-92 DOE
- SETTING TIME ASTM C403-92
- VISUAL CONDITION ACI 311.4R-88
- STRENGTH ASTM C39-93a

COARSE AGGREGATE

- QUARRY VOLUME
- GRADATION ASTM C136-93
- SPECIFIC GRAVITY/ ASTM C 127-88
ABSORPTION
- SILT CONTENT
BATCHING PLANT PRODUCTION
ASTM C 177-90
- ABRASION TEST ASTM C 131-89
- SOUNDNESS TEST ASTM C 88-90 - AGGREGATE & CEMENT SCALE CONTROL ASTM C94-94
- WATER & ADDITIVE FLOW CONTROL ASTM C94-94
- AGGREGATE MOISTURE CONTENT ASTM C566-89
- CONRETE UNIT WEIGHT UNIT WEIGHT ASTM C138-92
- CONCRETE VISUAL CHECK ASTM 311.4R-88

CEMENT
- GRAIN FINENESS ASTM C024
- SETTING TIME ASTM C191-77
- SPECIFIC GRAVITY/ ASTM C188-78
TRANSPORTATION
TRANSPORTATION ASTM C94-94

FLY ASH

- FINEST TEST ASTM C311-94a PROJECT LOCATION


- LOSS OF IGNITION TEST ASTM C311-94a
- SLUMP TEST ASTM C143-90a
- CONCRETE SAMPLING ASTM C31-91

ADDITIVE
LABORATORY

- INITIAL TIME ASTM C191-77 - CONCRETE SAMPLING CURING ASTM C192-90a


- VISCOSITY TEST ASTM C494-92 - CONCRETE STRENGTH TEST 7 & 28 DAYS ASTM C39-93a
- TEST RESULT EVALUATION ASTM 437.1R
- REPORTING ASTM C94-94

WATER AREA MANAGER

- pH - TEST REPORT CONFIRMATION


- CHLORIDE CONTENT ASTM C1218-92

MAIN
CONTRACTOR

END
PENGENDALIAN MUTU PRODUKSI
III. Pengendalian Mutu Produksi

1. Frekwensi Pengambilan Benda Uji


Pengambilan sample sesuai dengan ACI 318-83

a. Minimal diambil satu kali pengambilan benda uji untuk setiap mutu dalam satu hari pengecoran atau,

b. Minimal diambil satu kali pengambilan untuk setiap volume, 114 - m3 ( 150 cu yd ) untuk setiap mutu dalam
satu hari pengecoran atau,

c. Minimal satu kali pengambilan untuk pengecoran konstruksi plat atau dinding dengan luas (5000 sq ft)
464.5 m2.

Sesuai hal tersebut diatas maka pengambilan benda uji diatur sebagai berikut :

TM ke 1 : adalah 1 kali pengambilan, 3 buah sample


TM ke 2 - 5 : adalah 2 kali pengambilan, 3 buah sample
TM ke 6 - 10 : adalah 3 kali pengambilan, 3 buah sample
Setiap tambahan 10 TM ditambah 1X. 3 sample.

Tiap-tiap pengambilan dibuat 3 Benda Uji. Untuk dilaksanakan test :

1 Buah umur 7 hari


2 Buah umur 28 hari

Untuk Pengecoran precast maka jumlah sample diambil 4 sample dengan rincian
pengetesan adalah :
1 Buah umur 5 hari
1 Buah umur 7 hari
2 Buah umur 28 hari
Pengambilan sample sesuai dengan ASTM C.172
(Practice for sampling Freshly Mixed Concrete)

Pembuatan dan Perawatan benda uji sesuai dengan ASTM C.31


(Practice for Making and Curing Concrete Test Specimens in Field)

Pengetesan benda uji sesuai dengan ASTM. C 39 (Test Method for Compresive Strength of Cylindrical
Concrete Specimens)

Pengetesan benda uji dilakukan di Laboratorium CV Arum Abadi, Plant Tarahan.


CONCRETE PRODUCTION FLOWCHART

START

AGGREGATE
FLY ASH CEMENT WATER ADMIXTURE
QUARRY
SELECTION

NO
QUANTITY
TEST

OK

NO
QUALITY
TEST

OK

TRIAL
START
PRODUCTION

BATCHING PLANT
MIX DESIGN
ERECTION

TRIAL MIX SCALE


CALIBRATION

SCALE
NO REPAIRING
YIELD & YES NO
VISUAL CALIBRATION
DEVIATION CHECK
TREND RESULT
MONITOR
OK
FOR
THE
NEXT PRODUCTION
PRODUCT
CONTROL

DELIVERY

CONCRETE POURING ON SITE

SAMPLING

SAMPLE TESTING &


EVALUATION

END
EVALUASI PENERIMAAN BETON
IV. Evaluasi Penerimaan Beton

Kriteria Penerimaan Mutu Beton Mengacu pada ACI. 318-83

Ketentuan Umum
a. Satu hasil test adalah dari 2 benda uji dalam sample yang sama.

b. Evaluasi berdasarkan 30 atau lebih hasil test (Umur 28 hari) yang dihitung dengan rumus :
f'c = fcr - 1.34 S

c. Untuk hasil test, 15 s/d 29 untuk Deviasi Standar dikalikan Faktor koreksi :

No Test Modifikasi Faktor Untuk


Standar Deviasi
15 1,16
20 1,08
25 1,03
30 1,0

d. Secara khusus kekuatan dari masing2 mutu sesuai dengan yang disyaratkan :

1. Rata-rata dari semua pasangan tiga hasil test berurutan sama atau lebih dari f'c.

2. Tidak ada satupun hasil test (Rata2 dua Cylinder) dibawah f'c.
HASIL TEST SEMEN
SLAG POWDER
HASIL TEST AGREGAT KASAR
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

SIEVE ANALYSIS

DESCRIPTION AND : RECEIVED


SOURCE OF SAMPLE Crushed stone ex Tanjung (G 20) ON : 2-Mar-21

TO BE USED FOR : All Concrete TOTAL WEIGHT 5424


OF SAMPLE : GRAM

SIEVE RETAINED ON SIEVE CUMULATIV CUMULATIVE GRADING SPECIFICATION


SIZE RETAINED PASSING JISS-5 CLASS II
MM GRAM % % %

40 0 0,00 0,0 100,0 100 - 100


25 0 0,00 0,0 100,0 100 - 100
20 0 0,00 0,0 100,0 90 - 100
15 1783 32,87 32,9 67,1 55 - 80
10 2025 37,33 70,2 29,8 20 - 55
5 1343 24,76 95,0 5,0 0 - 10
2,5 245 4,52 99,5 0,5 0 - 5
1,2 28 0,52 100,0 0,0 0 0
0,6 0 0,00 100,0 0,0 0 0
0,3 0 0,00 100,0 0,0 0 0
0,15 0 0,00 100,0 0,0 0 0
FM = 6,98

100

90

80
PASSING PERCENTAGE

70

60

50

40

30

20

10

0
0,1 1 10 100

SIEVE SIZE (MM)

Low Limit Up Limit Aggregate Grading

TESTED AND CALCULATED BY : Jamhari DATE : 2-Mar-21

CHECKED BY : Teguh AP DATE : 3-Mar-21


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

MATERIAL LABORATORIUM ASTM C 127 /84

SPECIFIC GRAVITY OF COARSE AGGREGATE

TO BE USED FOR All Concrete

SAMPLE NO RECEIVED ON 3-Mar-21

DESCRIPTION & Crushed stone ex Tanjung


SOURCE OF SAMPLE I.( G.20 ) II.( G.25 )

RUN NO : I II
NO. OF FLASK

A WEIGHT OF SSD SAMPLE ON AIR (gram) 8757 8657

B WEIGHT OF SSD SAMPLE IN WATER (gram) 5420 5330

C WEIGHT OF OVEN DRY SAMPLE (gram) 8650 8540

1 SPECIFIC GRAVITY A 2,624 2,602


SSD BASIS --------------------------
A - B 2,613

2 SPECIFIC GRAVITY C 2,592 2,567


OVEN DRY BASIS --------------------------
A - B 2,580

3 SPECIFIC GRAVITY C 2,678 2,660


APPARENT --------------------------
C - B 2,669

A - C 1,237 1,370
4 WATER ABSORPTION -------------------------- x 100 %
C 1,304

REMARKS :

TESTED & CALCULATED BY Jamhari DATE 3-Mar-21

CHECKED BY Teguh AP DATE 4-Mar-21


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

MATERIAL LABORATORIUM ASTM C 177 - 90

AMOUNT OF MATERIAL FINNER THAN 0.075 MM ( NO. 200 )


SIEVE IN AGGREGATE

TO BE USED FOR All Concrete

SAMPLE NO RECEIVED ON 3-Mar-21

DESCRIPTION &
SOURCE OF SAMPLE Crushed Stone ex Tanjung

RUN NO : I II

B WEIGHT OF DRY OVEN SAMPLE 795 789


( gram )

C WEIGHT OF WASHED & DRY OVEN SAMPLE AND 790 785


RETAINED ON 0.075 MM ( No. 200 ) SIEVE

A OF MATERIAL FINER THAN (B)-(C)


------------- * 100% 0,63% 0,51%
0.075 MM ( NO. 200 ) SIEVE (B)

REMARKS 0,57%

TESTED & CALCULATED BY Jamhari DATE 3-Mar-21

CHECKED BY Teguh AP DATE 4-Mar-21


HASIL TEST AGREGAT HALUS
CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

SIEVE ANALYSIS

DESCRIPTION AND : RECEIVED


SOURCE OF SAMPLE Natural Sand Ex Gunung Sugih ON : 2-Mar-21

TO BE USED FOR : All Concrete TOTAL WEIGHT 3150


OF SAMPLE : GRAM

SIEVE RETAINED ON SIEVE CUMULATIV CUMULATIVE GRADING SPECIFICATION


SIZE RETAINED PASSING JISS-5 CLASS II
MM GRAM % % %

40 0 0,00 0,0 100,0 100 - 100


25 0 0,00 0,0 100,0 100 - 100
20 0 0,00 0,0 100,0 100 - 100
15 0 0,00 0,0 100,0 100 - 100
10 25 0,79 0,8 99,2 100 - 100
5 115 3,65 4,4 95,6 90 - 100
2,5 228 7,24 11,7 88,3 80 - 100
1,2 592 18,79 30,5 69,5 50 - 90
0,6 1185 37,62 68,1 31,9 25 - 65
0,3 495 15,71 83,8 16,2 10 - 35
0,15 400 12,70 96,5 3,5 2 - 10
PAN 110 3,49 100,0 0,0
FM = 2,96

100

90

80
PASSING PERCENTAGE

70

60

50

40

30

20

10

0
0,1 1 10 100

SIEVE SIZE (MM)

Low Limit Up Limit Aggregate Grading

TESTED AND CALCULATED BY : Jamhari DATE : 2-Mar-21

CHECKED BY : Teguh AP DATE : 3-Mar-21


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

MATERIAL LABORATORIUM ASTM C 128 /84

SPECIFIC GRAVITY OF FINE AGGREGATE

TO BE USED FOR All Concrete

SAMPLE NO RECEIVED ON 3-Mar-21

DESCRIPTION & Natural sand ex Gunung Sugih


SOURCE OF SAMPLE

RUN NO : I II
NO. OF FLASK

A WEIGHT OF SSD SAMPLE ON AIR (gram) 507 511

B WEIGHT OF SSD SAMPLE IN WATER (gram) 142 142

C WEIGHT OF FLASK + SSD MATERIAL + (gram) 638 638


WATER UP TO CALIBRATION MARK

D WEIGHT OF FLASK + SSD MATERIAL + (gram) 950 953


WATER UP TO CALIBRATION MARK

E WEIGHT OF OVEN DRY SAMPLE (gram) 503 506

1 SPECIFIC GRAVITY A 2,600 2,607


SSD BASIS --------------------------
A+C-D 2,604

2 SPECIFIC GRAVITY E 2,600 2,607


OVEN DRY BASIS --------------------------
A+C-D 2,604

3 SPECIFIC GRAVITY E 2,634 2,649


APPARENT --------------------------
E+C-D 2,641

A-E 0,795 0,988


4 WATER ABSORPTION -------------------------- x 100 %
E 0,892

REMARKS :

TESTED & CALCULATED BY Jamhari DATE 3-Mar-21

CHECKED BY Teguh AP DATE 4-Mar-21


CV ARUM ABADI
Plant Tarahan
Jl Bakauheni Raya KM 15

MATERIAL LABORATORIUM ASTM C 177 - 90

AMOUNT OF MATERIAL FINNER THAN 0.075 MM ( NO. 200 )


SIEVE IN AGGREGATE

TO BE USED FOR All Concrete

SAMPLE NO RECEIVED ON 3-Mar-21

DESCRIPTION & Natural Sand ex Gunung Sugih


SOURCE OF SAMPLE

RUN NO : I II

B WEIGHT OF DRY OVEN SAMPLE 1765 1770


( gram )

C WEIGHT OF WASHED & DRY OVEN SAMPLE AND 1725 1715


RETAINED ON 0.075 MM ( No. 200 ) SIEVE

A OF MATERIAL FINER THAN (B)-(C)


------------- * 100% 2,27% 3,11%
0.075 MM ( NO. 200 ) SIEVE (B)

REMARKS 2,69%

TESTED & CALCULATED BY Jamhari DATE 3-Mar-21

CHECKED BY Teguh AP DATE 4-Mar-21


BROSUR ADMIXTURE
Technical Data Sheet
Edition 1, 2008
Identification no. xxx
Version no. 0010
Plastiment® -V105

®
Plastiment -V105
Mid-Range Water-Reducing Admixture

Product Plastiment® -V105 is a highly effective liquid Mid Range Water Reducing
Description admixture for the production of medium to high workability concrete

Plastiment® -V105 is chloride free admixture and is compatible with all types
of Portland Cement including Sulphate Resistant Cement (SRC).
Construction

Uses Plastiment® -V105 is suitable for the production of site mixed as well as ready
mixed concrete
Used for concrete with extended transport or placing times
Used for concrete in hot climates where long slump retention is required
Used for concrete using high absorbent sand
Used for concrete using high percentage of quarry dust

Characteristics / As a Mid Range Water Reducer


Advantages Workability and slump retention is greatly improved
Increased placeability in slender components with packed reinforcements
Suitable for use in conjunction with standard super plasticizers (synergized
mixes)
Significantly reduces the risk of segregation
Water reduction 4% -12% depending on dosage*
*(this will depend on dosage and mix design)

Back

Table of Contents

1 Plastiment® -V105 1/2


Product Data
Type Modified Polysaccaride
Appearance / Colour Dark Brown
Density 1.17 ± 0.20 kg/ ltr (at +25°C)
Packaging 200 litre drums
1,000 litre tanks & bulk delivery
Storage Condition / 12 months from the date of production if stored in undamaged and unopened,
Shelf Life original sealed containers, protected from direct sunlight and frost, at
temperatures between +5°C and +30°C.
System Information
Application Details
Dosage Plastiment® -V105 can be used at the dose rate 0.20% -1.00% per total
weight of cementitious material depending on requirements concerning
workability and strength. It is recommended that trial mixes be conducted to
determine the exact dosage rate required.
Construction

Note:
Typical dose rate is 0.30% -0.50% by weight of cementitious material for
normal absorbent sand e.g. silica sand
For use in high absorbent sand e.g. volcanic sand or in the case of use of
more than 30% of quarry dust (manufactured sand) the typical dose rate is in
the range of 0.45 – 0.90%
For more specific requirements, advice is available from our Technical Service
Department to determine the usage rate for optimum results.
Application Instructions

Dispensing Plastiment® -V105 shall be dispensed with the mixing water into the truck mixer
Do not dilute Plastiment® -V105
Application Method / The standard rules of good concreting practice, concerning production and
Tools placing, are to be followed.
Laboratory trials before concreting on site are strongly recommended when
using a new mix design or producing new concrete components.
Fresh concrete must be cured properly and as early as possible.
Cleaning of Tools Clean all tools and application equipment with water immediately after use.
Hardened / cured material can only be removed mechanically.
Notes of Application / When accidental overdosing occurs, Plastiment® -V105 does not entrain
Limitations excessive amounts of air, however the set retarding effect increases. During
this period the concrete must be kept moist in order to prevent premature
drying out.
Value Base All technical data stated in this Product Data Sheet are based on laboratory
tests.
Actual measured data may vary due to circumstances beyond our control.
Health and Safety For information and advice on the safe handling, storage and disposal of
Information chemical products, users should refer to the most recent Material Safety Data
Sheet (available on request) containing physical, ecological, toxicological and
other safety-related data.
Legal Notes The information, and, in particular, the recommendations relating to the application and end-use of
Sika products, are given in good faith based on Sika’s current knowledge and experience of the
product when properly stored, handled and applied under normal conditions in accordances with
Sika’s recommendations. In practice, the differences in materials, substrates and actual site
conditions are such that no warranty in respect of merchantability or of fitness for a particular
purpose, nor any liability arising out of any legal relationship whatsoever, can be inferred either from
this information, or from any written recommendations, or from any other advice offered. The user of
the product must test the product’s suitability for the intended application and purpose. Sika reserves
the right to change the properties of its products. The proprietary rights of third parties must be
observed. All orders are accepted subject to our current terms of sale and delivery. Users must
always refer to the most recent issue of the local Product Data Sheet for the product concerned,
copies of which will be supplied on request.

Branches
PT. Sika Indonesia Surabaya :
Jl. Raya Cibinong- Bekasi km. 20 Puri Niaga Blok G No. 29, Jl. Raya Rungkut Menanggal 11, Surabaya
Tel : 031-8690202 ; Fax : 031-8682123
Limusnunggal- Cileungsi Medan :
BOGOR 16820 - Indonesia Kawasan Industrial " Medan Star ", Tanjung Morawa Km.19,2
Jl. Pelita Raya Blok R No.32, Deli Serdang 20362
Tel. +62 21 8230025 Tel : 061-7941200 ; Fax : 061-7940822
Fax +62 21 8230025 Batam :
Website : www.sika.co. id Jl. Laksamana Bintan,Komp. Bumi Riau Makmur Blok E No.3,
Sungai Panas, Batam
e-mail: sikacare@id.sika.com Tel : 0778-424928 ; Fax : 0778-450189

2 Plastiment® -V105 2/2


Technical Data Sheet
Edition 3, 2007
Identification no.
02 01 01 01 100 0 000125
Version no. 0010
Sikament LN

Sikament LN
®

High Range Water Reducing

Description A highly effective water reducing agent and superplasticizer for promoting
accelerated hardening with high workability.
Complies with A.S.T.M. C 494-92 Type F
Construction

Use Sikament LN is a high range water reducing concrete admixture specially


formulated for the precast concrete element industry; to meet the demand of
early removal of formwork due to the early strength gain. Enables concrete
placing equipment to be used to its full capacity. Effective throughout dosage
range.

Advantages Sikament LN provides the following properties :


up to 20% reduction of water will produce 40% increase in 28 days
compressive strength
Increased watertightness.

Dosage 0.6% -1.5% by weight of cement


It is advisable to carry out trial mixes to establish the exact dosage rate required.
Sikament LN compatible with all types of Portland cement including SRC

Dispensing Sikament LN can be added to the gauging water prior to its addition to the dry
aggregates or separately to the freshly mixed concrete (on the batching plant or
on site into the truck mixer) where added to truck mixer on site, further mixing for
three to five minutes should be carried out.

Combinations Sikament LN may be combined with the following products:


Plastocrete series
Plastiment series
SikaFume
Sika AER
Sika Pump

Pre-trials are recommended if combinations with the above products are required.
Please consult our Technical Service Department.

Technical Data
Type Modified Naphthalene Formaldehyde Sulfonate
Colour Dark brown
Specific Gravity 1.18 – 1.20 kg/ ltr
Shelf life 1 year in unopened original container
Storage Dry, cool, shaded place
Packaging 240 kg drum
Bulk delivery

Back

Table of Contents

1 Sikament® LN 1/2
Handling
Precautions: Avoid contact with skin and eyes
Wear protective gloves and eye protection during work
If skin contact occurs, wash skin thoroughly.
If in eyes, hold eyes open, flood with warm water and seek medical attention
without delay.

Legal Notes The information, and, in particular, the recommendations relating to the application and end-use of Sika
products, are given in good faith based on Sika’s current knowledge and experience of the product when
properly stored, handled and applied under normal conditions in accordances with Sika’s
recommendations. In practice, the differences in materials, substrates and actual site conditions are such
that no warranty in respect of merchantability or of fitness for a particular purpose, nor any liability arising
out of any legal relationship whatsoever, can be inferred either from this information, or from any written
recommendations, or from any other advice offered. The user of the product must test the product’s
suitability for the intended application and purpose. Sika reserves the right to change the properties of its
products. The proprietary rights of third parties must be observed. All orders are accepted subject to our
current terms of sale and delivery. Users must always refer to the most recent issue of the local Product
Data Sheet for the product concerned, copies of which will be supplied on request.
Construction

Branches
PT. Sika Indonesia Surabaya :
Jl. Raya Cibinong- Bekasi km. 20 Puri Niaga Blok G No. 29, Jl. Raya Rungkut Menanggal 11, Surabaya
Tel : 031-8690202 ; Fax : 031-8682123
Limusnunggal- Cileungsi Medan :
BOGOR 16820 - Indonesia Kawasan Industrial " Medan Star ", Tanjung Morawa Km.19,2
Jl. Pelita Raya Blok R No.32, Deli Serdang 20362
Tel. +62 21 8230025 Tel : 061-7941200 ; Fax : 061-7940822
Fax +62 21 8230025 Batam :
Website : www.sika.co. id Jl. Laksamana Bintan,Komp. Bumi Riau Makmur Blok E No.3,
Sungai Panas, Batam
e-mail: sikacare@id.sika.com Tel : 0778-424928 ; Fax : 0778-450189

2 Sikament® LN 2/2
HASIL TEST AIR
LAMPIRAN
DAFTAR REFERENSI

1 ASTM ( American Society For Testing And Materials )


Vol. 04.02 ( Concrete and Aggregate )

1 ACI ( American Concrete Institute ) ACI.318-83 / Reaproved


1993 ( Building Code Requirements for Reinforced Concrete )