AIR CIRCUIT BREAKER

LS ACB production specification

[目 次]

1. Major specification table

2. Outline drawing

3. Wiring diagram
LS ACB production specification
1. Major specification table
NO Item Rating of ACB Remarks

1 Type AH-E

2 Description AH-20E AH-25E AH-32E AH-40E

3 Ampere Frame 2000AF 2500AF 3200AF 4000AF

4 Rated current (In max) 2000A 2500A 3200A 4000A at 40℃

5 Rated current of neutral pole 2000A 2500A 3200A 4000A

6 Number of poles 3P/ 4P

7 setting current (0.4~1.0) X In max

8 Rated insulation voltage 1000V

9 Rated operation voltage 690V

10 Rated impulse withstand voltage 12kV

11 Rated frequency 50/ 60Hz


Rated breaking capacity
12 100kA at 220~415V
(AC 50/60Hz)
Rated making capacity
13 220kA at 220~415V
(AC 50/60Hz)
1S 85kA

14 Rated short-time withstand current 2S 75kA

3S 65kA

15 Maxium total breaking time 40ms

16 Maxium closing time 80ms

Mechanical 15000times
17 Life cycle
Electrical 5000times

18 standards IEC60947-2

3P : 412 x 430 x 423


2000~3200A
4P : 527 x 430 x 423
Draw-out type
3P : 412 x 430 x 473
4000A
External dimension (mm) 4P : 527 x 430 x 473
19
WxHxD 3P : 378 x 300 x 327
2000~3200A
4P : 493 x 300 x 327
Fixed type
3P : 432 x 320 x 360
4000A
4P : 547 x 320 x 360

Motor chaging type 87/103


Main Body
Draw-out type Manual chaging type 85/101

20 weight (3/4P) Cradle only 44/55

Motor chaging type 44/55


Fixed type
Manual chaging type 42/53
LS ACB production specification
1. Major specification table
AH 40 E 3 40 J

M2 D2 D2 BX SC1 U0 T Hyx CN
LS ACB production specification
2. Outline drawing
1) Fixed type (ACB, AH-32E3-32A M2D2D2BX SC1U0T Hyx CN )
LS ACB production specification
2. Outline drawing
2) Draw-out type (ACB, AH-32E3-32A M2D2D2BX SC1U0T Hyx CN )
LS ACB production specification
2. Outline drawing
3) Fixed type (ACB, AH-40E3-40A M2D2D2BX SC1U0T Hyx CN )
LS ACB production specification
2. Outline drawing
4) Draw-out type (ACB, AH-40E3-40A M2D2D2BX SC1U0T Hyx CN )
This diagram is based on "CONNECTED" position of a circuit breaker and Opening, Motor charging, Releasing of locking plate should be normal condition.

Voltage Module Power supply Temperature


Module

Common

ZSI Input

ZSI Output
ZCT

OFF
OFF
ON

Reset
183
V1 V2 V3 VN E1 Z3 Z1 485+ R11 R22 513 R2 R1 251 83 /RES(+)
D1 C11 C1 A1 U1 413 423 51 41 31 21 11 53 43 33 23 13 T1 TC1 T2 TC2 341 331 321 311

Temperature Temperature

Axb
Sensor-1 Sensor-2

Axb
Axb
Axb
Axb
Axb
Axa
Axa
Axa
Axa
Axa
CL4
CL3
CL2
CL1

Trip relay UVT SHT2 SHT1 CC

or
3. Wiring diagram

184
E2 Z4 Z2 485- 544 534 524 252 84 /RES(-)
D2 C12 C2 A2 U2 414 424 52 42 32 22 12 54 44 34 24 14 342 344 332 334 322 324 312 314

OFF
ON

LTD

GTD
STD/Inst
Charged
Charged
Main circuit Digital trip relay Electric opertaion Charge Auxiliary switch Thermal module Cell switch
Fault trip Circuit Completion contact

UVT
Secondary
Ready to close trip coil

Terminal code description Accessory code description


Auxiliary switch"a" Voltage input thermal of UVT ZSI input Axa , Axb Auxiliary swtich Internal/External wiring(by customer)

Auxiliary switch"b" ALARM1 "a" ZSI output LTD Long time delay trip indicator Connector of the control
circuit terminal of drawout type
Charge signal ALARM2 "a" ZCT STD/Inst Short time delay/instantaneous

Charge signal communication Ready to close swtich Voltage Module GTD Ground fault trip indicator <Connector terminal configuration>

Motor charge Control power Thermal Module CL1~CL4 Cell switch


OCR
Closing coil Alarm contact Position switch Motor

Shunt coil Alarm reset Closing Coil


(Trip cause LED, Alarm contact)

2nd shunt trip RS - 485 communication Shunt tripping device1

Shunt tripping device2


OPERATING
Note)
1) The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position UVT coil
2) Relay is normal condition and charging type is "OFF charging".
3) The standard of auxiliary contact is 3a3b. The auxiliary switch in above diagram is composed of 5a5b. 7) UVT and SHT2 can not work together at the same time.
LS ACB production specification

4) Option 8) Temperature Sensor and Auxiliary switch(6a6b) can not work together at the same time.
- Ready to close contact, Trip alarm contact, UVT coil, Fully charged contact, secondary trip coil. 9) AL2 and RES can not work together at the same time.
- Cell switch, Thermal Module,Voltage Module,Remote close-open Module, ZCT, ZSI. AUX S/W
10) Ready to close switch and Charge completion contact can not work together at the same time.
5) Please consult us for the use of ZSI (Zone selective Interlocking).
6) Refer to the catalogue for the connection of Trip relay and UVT.