NOTES:
ALL DRAWINGS (ARCHITECTURAL, STRUCTURAL and SERVICES )
SHALL BE READ TOGETHER AND ANY DISCREPANCIES FOUND
SHALL BE REFFERED BACK TO THE MINISTRY OF HEALTH
SEE "DETAIL A" FOR DESIGN OFFICE PRIOR TO CONSTRUCTION.

VENTILATION ONLY WRITTEN DIMENSION TO BE FOLLOWED, NO SCALING.


40200 ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED.
1600 PREFERENCE TO BE GIVEN TO DETAILS OVER SMALLER
SCALED DRAWINGS

CONTRACTOR TO VERIFY EXISTING FINISH FLOOR LEVEL.

PROPOSED FINISH FLOOR LINE TO BE SAME LEVEL AS EXISTING


BUILDING FLOOR TO SLAB FOR PROPOSED TO BE SAME HEIGHT
1900

AS EXISTING.
2300
EXISTING
LOUVER
LEGEND:
EXISTING TO BE RELOCATED
EXTRACT FAN TO OTHER AREA
FLOOR TF TS SKIRTING

150x150
EXISTING DISK
WALL EP EX CEILING

VCD TF 300x300 TERRAZZO FLOOR TILES


3450

300x250
ADDITIONAL VCD
TS 300x100 HIGH TERRAZZO TILES FOR SKIRTING
400x300
VT 200x200 VITRIFIED NON-SKID FLOOR TILES
VCD VF SEAMLESS ANTI-STATIC VINYL FLOOR
OVER SELF-LEVELLING EPOXY
200 250x250
7500

VS READY-MADE COVED VINYL FLOOR SKIRTING


EXISTING DUCT RELOCATED EXISTING VCD
400x300 CT 300x300 CERAMIC WALL TILES
150x150 WALL MOUNTED A/C
UNIT TYP. TO ALL
SCD 450x450 @ CF 300x300 NON-SKID CERAMIC FLOOR TILE
250x250 560CFM TYP. TO 2

300x250
CS 300x100 HIGH NON-SKID CERAMIC SKIRTING
EXISTING DISK
WP APPROVED WALL PAINT
3450

MC 600x600 METAL FALSE CEILING

SCD 450x450 @
600CFM TYP. TO 2 DOORS AND WINDOWS LEGEND:
ND2
ED EXISTING DOOR
ED3
ND NEW DOOR
NW NEW WINDOW

EXISTING DOORS AND WINDOWS DESCRIPTION:


2300

ED-1 1400x1900 DOUBLE LEAF WOODEN DOOR


ED-2 1400x1900 DOUBLE LEAF ALUMINUM DOOR
ED-3 1200x2100 SINGLE LEAF WOODEN DOOR

PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT


ED-4 1100x2100 SINGLE LEAF WOODEN DOOR
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT

ED-5 1000x2100 SINGLE LEAF WOODEN DOOR


ED-6 900x2100 SINGLE LEAF WOODEN DOOR
1900

NOTE:
ALL PROPOSED NEW WALLS TO BE GYPSUM BOARD,
REFER TO DETAILS.

1600 MECHANICAL GENERAL NOTES THIS SITE


1. GENERAL CONTRACTOR TO PROVIDE FOR FRAMED ROOF OPENING FOR DUCT 10. SUB CONTRACT LANDLORD APPROVED ROOFING CONTRACTOR FOR ALL ROOFING WORK TO
PENETRATION. MAINTAIN ROOFING WARRANTY.

2. ELECTRICAL CONTRACTOR TO MAKE POWER CONNECTION TO EQUIPMENT INSTALLED BY 11. VERIFY ALL ROOFTOP UNIT AND EXHAUST FAN OPENINGS AND WEIGHTS WITH THE
MECHANICAL CONTRACTOR. FURNISH, INSTALL AND CONNECT ALL RELAYS, SWITCHES, STRUCTURAL ENGINEER AND LANDLORD WITH DIMENSIONS AND WEIGHTS OF THE ACTUAL RTU'S &
FUSES, DISCONNECT, CONDUITS AND TRANSFORMERS AS REQUIRED, ALL IN ACCORDANCE FANS USED.
WITH WIRING DIAGRAMS, MANUFACTURER'S RECOMMENDATIONS, AND LOCAL CODE LIMIT OF
CORRIDOR
IN PHASE
ONE

REQUIREMENTS. 12. COORDINATE WITH THE WORK OF OTHER SECTIONS, EQUIPMENT FURNISHED BY OTHERS,
1900

REQUIREMENTS OF THE OWNER, AND WITH THE CONSTRAINTS OF THE EXISTING CONDITIONS OF EXISTING PEDIATRIC WARD

EXISTING FEMALE WARD

3. MECHANICAL CONTRACTOR TO FURNISH AND INSTALL THE HVAC UNITS, CONTROL WIRING THE PROJECT SITE. PROVIDE DUCT RISES AND DROPS AS REQUIRED FOR FIELD INSTALLATION AND
2300 AND CONDUITS; DUCT WORK, REGISTER, START-UP AND BALANCE THE COMPLETE SYSTEM. TRADE COORDINATION. NOTIFY ARCHITECT OF ANY DISCREPANCIES BEFORE STARTING WORK. EXISTING MALE WARD

EXISTING PHYSIOTHERAPY
BUILDING

4. PROVIDE BACKDRAFT DAMPERS ON ALL EXHAUST FANS IF NOT A STANDARD ITEM. 13. DRAWINGS FOR HVAC WORK ARE DIAGRAMMATIC, SHOWING THE GENERAL LOCATION, TYPE, EXISTING STORES

EXISTING
OPERATION THEATRE BUILDING

LAYOUT, AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT EXISTING KITCHEN, LAUNDRY, PHARMACY

5. ALL DUCT WORK SHALL BE CONSTRUCTED, ERECTED, AND TESTED IN ACCORDANCE WITH MEASUREMENT. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS. REFER TO
450x450

THE MOST RESTRICTIVE OF LOCAL REGULATIONS, ASHRAE, SMACNA, OR THE APPLICABLE MANUFACTURER'S STANDARD INSTALLATION DRAWINGS FOR EQUIPMENT CONNECTIONS AND EXISTING ADMIN.
BUILDING

STANDARDS ADOPTED BY LOCAL AGENCIES. INSTALLATION REQUIREMENTS. PROVIDE DUCTWORK, CONNECTIONS, ACCESSORIES, OFFSETS, EXISTING C.S.S.D.
ACCOUNTING EXISTING O.P.D.

AND MATERIALS NECESSARY FOR A COMPLETE SYSTEM.


6. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF EQUIPMENT EXISTING
REGISTRATION
AND RECORDS

BEING PROVIDED AND INSTALLED BY HIM TO FIT DIMENSIONALLY AND CLEAR OTHER 14. ALL WORK SHALL COMPLY WITH STATE AND LOCAL CODE REQUIREMENTS AS APPROVED AND
EQUIPMENT/COMPONENT IN LOCATION SHOW ON THE DRAWINGS. MECHANICAL AMENDED BY THE GOVERNING CITY. PURCHASE ALL PERMITS ASSOCIATED WITH THE WORK.
CONTRACTOR SHALL VERIFY DUCT SIZES AND DUCT ROUTES SHOWN ON THE DRAWINGS TO OBTAIN ALL INSPECTIONS REQUIRED BY CODE.
CLEAR OTHER EQUIPMENT AND COMPONENTS OF THE BUILDING BEFORE COMMENCING
3450

WORK. ANY DISCREPANCY SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION 15. CONTRACTOR SHALL COORDINATE INSTALLATION OF ALL UTILITIES ABOVE THE CEILING TO
IMMEDIATELY. PROVIDE THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION AND FUTURE CHANGES IN
N
MECHANICAL EQUIPMENT. CONDUIT AND PIPE TO BE RUN UP IN JOISTS SPACE. COORDINATE
7. CONTRACTORS AND SUBCONTRACTORS SHALL CAREFULLY REVIEW THE CONSTRUCTION SERVICE AND ACCESS POINTS ABOVE CEILING TO MINIMIZE REQUIRED.
450x450 DOCUMENTS. INFORMATION REGARDING THE COMPLETE WORK IS DISPERSED KEY PLAN
THROUGHOUT THE DOCUMENT SET AND CANNOT BE ACCURATELY DETERMINED WITHOUT
VCD
REFERENCE TO THE COMPLETE DOCUMENT SET.
200
7500

VCD FAN SIDE MOTOR SIDE


AREA ELECTRICAL
DESIGNATION QUANTITY AIR FLOW TOTAL STATIC RATING REMARKS
SERVED TYPE CHARACTERISTICS
RATE (CFM) PRESSURE (Pa) (HP)
3450

VOLTS PHASE Hz
REV. DATE DESCRIPTION BY CKD.
UNIT MUST BE DAIKIN, MITSUBISHI
1 SEE PLAN 800 100 CEILING CONCEALED - 220-240 1 50
OR APPROVED EQUIVALENT

SCD 375x375 @ ECD 375x375 @


400CFM TYP. TO 2 400CFM TYP. TO 2
MINISTRY OF HEALTH
OPERATING
DIRECTORATE GENERAL
NOMINAL POWER SOURCE CONTROL REFRIGERANT PIPING SERVING
DESIGNATION QUANTITY
(TR)
CURRRENT
(AMPS)
SYSTEM
REFRIGERANT SIZE (MM) LIQ./GAS FAN COIL
REMARKS OF PROJECTS &
VOLTS PHASE Hz
EACH UNIT SHALL BE FACTORY ASSEMBLED TO MEET THE DESIGN
ENGINEERING AFFAIRS
AS PER MANUFACTURER
1 3.0 415-380 3 50 5.2 STANDARD R-410A REQUIREMENT AND SHALL BE COMPLETE WITH VIBRATION ISOLATORS,
RECOMMENDATION
DRAINS, AIR FILTERS AND DYNAMICALLY BALANCED BLOWER.
2300

P.O.BOX 393
POSTAL CODE 100
SULTANATE OF OMAN
NOMINAL ELECTRICAL SOURCE OPERATING
AIR FLOW
DESIGNATION QUANTITY AREA SERVED COOLING CURRRENT TYPE REMARKS
CAPACITY(TR) VOLTS PHASE HERTS
(CFM)
(AMPS) PROJECT

GENERAL, DAIKIN MITSUBISHI PROPOSED MAINTENANCE WORKS AT MALE WARD


1900

1 SEE PLAN 3.0 220-240 1 50 1200 1.39 CEILING CONCEALED


OR EQUAL MODEL
& COVERING OF MAIN CORRIDOR AT SUMAIL OLD HOSPITAL

TITLE

PROPOSED AC & VENTILATION LAYOUT,


GENERAL NOTES AND SCHEDULE
ISSUE TENDER
DATE 14-02-2019 SCALE 1:75

DESIGNED d.e.d.
PROJECT NO. MOH/2018/4999
CAD/DRAWN IAN REV.

CHECKED NASSER DRAWING NO. M-01 0