SYSTEM TEST REPORT

Powerline Carrier Equipment: Series ETL600R4

Project : …………………………..

ABB Order N° : …………………………..

Station : …………………………..

Link : …………………………..

Equipment N° : …………………………..

Frequency : Tx = …………kHz Rx = …………kHz

Direction : …………………………..

System Test Report contains

ETL600 System Test Report Pages B1 to B17

HMI600 Printout of Configuration Pages .............

HMI600 Printout of Status Pages .............

Test ETL600 List of used Test-instruments Pages .............

………………………….. ………………………………… Pages .............

The tuning of the equipment is in accordance with the following instructions:

Programming and Testing of ETL600R4 1KHW002609-EN


Compatibility Requirements for ETL600 1KHW001490-EN
Tuning of ETL600R4 Rx RF Filter P4RX 1KHW002584-EN
Tuning of ETL600R4 Tx RF Filter on E5TH and E5TC 1KHW002585-EN
APLC Channel Equalization for ETL600 1KHW001494-EN
Firmware Download for ETL600R4 1KHW002589-EN
Technical Data ETL600R4 1KHW002590-EN

Rev. ind:
Type des. Part no.
No. of p.
Prep. Hans Benninger / PSND 2012-04-11 Doc.kind

Appr. M. Israel / PSND2 2012-05-15 Title System Test Report ETL600R4 17+
Resp.dept. PSNEX
Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B1


FILE: 1KHW002568AE System Test Report ETL600R4; TEMPLATE: TECHN_DOC_STAND_P.dot R0; SKELETON: ; SAVEDATE: 5/15/2012 11:45:00 AM
SAFETY INSTRUCTIONS
Please refer to chapter 2 of ETL600R4 instruction manual 1KHW002582.

Designations and abbreviations used:


Refer to 1KHW002609-EN Programming and testing of ETL600R4

REVISION
Rev. Page (p.) Description Date
ind. Chapter (c.) Dept./Init.
A c. B.2 Measurement at MCB 2012-05-15 / Be

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B2


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.1 General

B.1.1 Visual checks


Correct wiring of protective earth P7LH, P7LF, P7LP, P7LQ PE wired [ ]
Correct wiring of power supply P7LH, P7LF, P7LP, P7LQ polarity ok [ ]
Equipment connected to adequate [ ]
voltage source

Left Right
B.2 Check power supply B5LD

B.2.1 Battery supply 48V DC MCB -46 to –56 V DC [ ] [ ]D

B.2.2 Ripple on 48V DC MCB <1 V rms [ ] [ ]D

B.2.3 Green LED B5LD front panel Lit [ ] [ ]D

B.3 Connect to the equipment, download


configuration and prepare for tuning &
testing
Connect to the equipment Check communication [ ]
between PC and P4LT/V/X
Download configuration Download successful [ ]
Activate the Tuning & testing dialog box Prepare Tuning & testing [ ]

B.4 Change configuration, if necessary [ ]

B.5 Transmitter

E5TC E5TH
B.5.1 Programming of Tx RF filter
Refer to 1KHW002585 Mark if not programmed
1 [ ] [ ]D
Tuning Instructions for ETL600R4
Tx RF Filter on E5TH/C
Bandwidth = 4 kHz E5TH/E5TC Refer [ ] [ ]D
Bandwidth = 8 kHz E5TH/E5TC to [ ] [ ]D
Bandwidth = 16 kHz E5TH/E5TC document [ ] [ ]D
Bandwidth = 32 kHz E5TH/E5TC 1KHW002585 [ ] [ ]D
Center frequency E5TH/E5TC fTx=________ kHz

B.5.2 Settings for RF hybrid on E5TH


Jumpers for operation mode set
according to dialog box View / Display
E5TH H1 … H13 [ ]
hardware settings only, under the
heading E5TH in rack P7L? at slot N??

1
As the channel frequencies were not known at test time, the system was tested with temporarily inserted factory-owned
filter(s), programmed and tuned to a standard frequency and bandwidth.

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B3


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

E5TC E5TH
B.5.3 Tune Tx RF filter Mark if not configured: [ ]
2
Mark if not tuned : [ ] [ ]D
Dialog box 'Tune Tx RF filter' E5TH, E5TC Refer to doc. [ ] [ ]D
1KHW002585

B.5.4 Adjust Tx RF level


Dialog box Adjust Tx RF level: [ ]
Click Select and then Start
Mark if the Tx level is not [ ]
measured
Measured Tx level is within tolerance RF LINE MONITOR or Permissible [ ]
RF LINE socket at E5TH range indicated
front panel in dialog box

B.5.5 Adjust Tx alarm level


Dialog box: Adjust Tx alarm level
Follow the instructions given in the dialog [ ]
box
Tx ALARM indication: E5TH and - in case of LED(s) to be ON [ ]
ETL600-100 – E5TC
State of HW alarm relay after Pins 2-3 of V9OT cable Closed [ ]
programmed delay.
Turn  potentiometer(s) TX-LVL-AL LED(s) to be [ ]
ADJUST on P1LP till TX-LVL-AL LED(s) OFF
go(es) off.
Tx alarm indication E5TH and - in case of LED(s) to be [ ]
ETL600-100 – E5TC OFF
State of HW alarm relay after Pins 2-3 of V9OT cable Open [ ]
programmed delay.
Click OK.

B.6 Receiver

B.6.1 Programming of Rx RF filter


Refer to 1KHW002584 Mark if not configured: [ ]
2
Tuning of ETL600R4 Rx RF Filter P4RX Mark if not programmed : [ ]

Bandwidth = 4 kHz P4RX Refer [ ]


Bandwidth = 8 kHz P4RX to [ ]
Bandwidth = 16 kHz P4RX document [ ]
Bandwidth = 32 kHz P4RX 1KHW002584 [ ]
Center frequency P4RX fRx=________ kHz

B.6.2 Tune Rx RF filter P4RX, if present Mark if not configured: [ ]


2
Mark if not tuned : [ ]
Dialog box 'Tune Rx RF filter' P4RX, P4LM Refer to doc. [ ]
1KHW002584

2
As the channel frequencies were not known at test time, the system was tested with temporarily inserted factory-owned
filter(s), programmed and tuned to a standard frequency and bandwidth.
Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B4


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.6.3 Adjust Rx RF level


Dialog box: Tuning & testing…
Dialog box: Adjust Rx RF level Dialog box Value dBu [ ]
indicated
in dialog box.
Follow the instructions in the dialog box

B.6.4 Tune RF hybrid on E5TH


Tuned Default
Dialog box: Tune RF hybrid Dialog box Tuned / default [ ] [ ]D
setting

B.6.5 Link alarm indication


Activate link alarm by interrupting RF Link alarm LED on P4LT LED to be ON [ ]
connection.
State of Link alarm relay after Terminals 5-6 at V9OT Closed [ ]
programmed delay. external cable
Deactivate link alarm by restoring the Link alarm LED on P4LT LED to be OFF [ ]
link.
State of link alarm relay after Terminals 5-6 at V9OT Open [ ]
programmed delay. external cable

B.7 Equalization

Ch 1 Ch 2 Ch 3
B.7.1 Measure frequency response Mark if not configured: [ ] [ ] [ ]

In menu Equipment / Commissioning and HMI600 Ch 1 Ch 2 Ch 3


maintenance / Frequency response / [ ] [ ] [ ]
APLC channel 1, APLC channel 2 or
APLC channel 3
Ch 1 Ch 2 Ch 3
B.7.2 Select Equalizer Mark if not configured: [ ] [ ] [ ]

In menu Equipment / Commissioning and HMI600 Ch 1 Ch 2 Ch 3


maintenance / Select equalizer / APLC [ ] [ ] [ ]
channel 1, APLC channel 2 or
APLC channel 3

B.8 Testing of R1BC, if present Mark if not configured: [ ]

Activate alarms as programmed on Corresponding N/C contacts Closed [ ]


R1BC. on R1BC.
Deactivate alarms as programmed on Corresponding N/C contacts Open [ ]
R1BC. on R1BC.

B.9 Configure Real Time Clock (RTC)

B.9.1 Setting real time clock


Menu: Equipment, Commissioning and
maintenance, Eventrecorder, Set clock
Download date / time to RTC Dialog box Actual time and [ ]
date

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B5


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.9.2 Testing external real time clock Mark if not configured: [ ]


synchronization (if available)
Menu: Equipment, Commissioning and
maintenance, Eventrecorder, Set clock
Download date/time to RTC Dialog box Wrong time
Upload date/time from RTC Dialog box Correct time [ ]

Test Permissible Test


No. Test procedure Test point value Units result

B.10 Testing of NSD600 / G4AI, if


present
N02 N08 N14 N20
B.10.1 Inputs Mark if not configured: N24 N30 N36 N42 N48 N54 N60
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
Input 1 IN1 Terminal, U1, see N02 N08 N14 N20
Activate Input 1 (T…/1) – (T.../2) System settings V DC N24 N30 N36 N42 N48 N54 N60
Check LED IN1 LED IN1 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Input 2 IN2 Terminal, U2, see N02 N08 N14 N20


Activate Input 2 (T…/3) – (T.../4) System settings V DC N24 N30 N36 N42 N48 N54 N60
Check LED IN2 LED IN2 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Input 3 IN3 Terminal, U3, see N02 N08 N14 N20


Activate Input 3 (T…/5) – (T.../6) System settings V DC N24 N30 N36 N42 N48 N54 N60
Check LED IN3 LED IN3 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Input 4 IN4 Terminal, U4, see N02 N08 N14 N20


Activate Input 4 (T…/7) – (T.../8) System settings V DC N24 N30 N36 N42 N48 N54 N60
Check LED IN4 LED IN4 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

B.10.2 Outputs

Enforce action for OUT1. Terminal, N02 N08 N14 N20


Check Output 1, OUT1: (T…/9) – (T.../10) Closed N24 N30 N36 N42 N48 N54 N60
Check LED OUT1 LED OUT1 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Enforce action for OUT2. Terminal, N02 N08 N14 N20


Check Output 2, OUT2: (T…/11) – (T.../12) Closed N24 N30 N36 N42 N48 N54 N60
Check LED OUT2 LED OUT2 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Enforce action for OUT3. Terminal, N02 N08 N14 N20


Check Output 3, OUT3: (T…/13) – (T.../14) Closed N24 N30 N36 N42 N48 N54 N60
Check LED OUT3 LED OUT3 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Enforce action for OUT4. Terminal, N02 N08 N14 N20


Check Output 4, OUT4: (T…/15) – (T.../16) Closed N24 N30 N36 N42 N48 N54 N60
Check LED OUT4 LED OUT4 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Enforce action for relay 1 Terminal, Refer G4AI N02 N08 N14 N20
REL1 close/open (T…/17) – (T.../18) programming N24 N30 N36 N42 N48 N54 N60
Check LED REL1 LED REL1 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Enforce action for relay 2 Terminal, Refer G4AI N02 N08 N14 N20
REL2 close/open (T…/19) – (T.../20) programming N24 N30 N36 N42 N48 N54 N60
Check LED REL2 LED REL2 ON [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B6


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result
TPE1 TPE2
B.10.3 NSD600 loop test Mark if not configured: [ ] [ ]
Check Actual transmission
time TLink HMI600 < 1.3*T0 ms _______ _______
Menu: Equipment,
Commissioning and
maintenance, NSD600 send
loop test

B.10.4 Command transmission


time

TPE1 TPE2
Command A Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command A (T71/1) – (T71/2) [ ] Mean value
(T…/...) – (T.../…) [ ]
 T0 ms ________ ________
Rx command A (T71/9) – (T71/10) [ ]
(T…/...) – (T.../…) [ ]
TPE1 TPE2
Command B Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command B (T71/3) – (T71/4) [ ] Mean value
(T…/...) – (T.../…) [ ] ms
 T0 ________ ________
Rx command B (T71/11) – (T71/12) [ ]
(T…/...) – (T.../…) [ ]
TPE1 TPE2
Command C Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command C (T71/5) – (T71/6) [ ] Mean value
(T…/...) – (T.../…) [ ] ms
 T0 ________ ________
Rx command C (T71/13) – (T71/14) [ ]
(T…/...) – (T.../…) [ ]
TPE1 TPE2
Command D Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command D (T71/7) – (T71/8) [ ] Mean value
(T…/...) – (T.../…) [ ] ms
 T0 ________ ________
Rx command D (T71/15) – (T71/16) [ ]
(T…/...) – (T.../…) [ ]

B.10.5 Reset counters Mark if not configured: [ ]


Menu: Equipment, HMI600 All counters = 0 [ ]
Commissioning and
maintenance, Eventrecorder,
Reset counter, OK:

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B7


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.11 Testing of O4LE

N02 N08 N14


B.11.1 Service Phone Mark if not configured: N24 N30 N48
[ ] [ ] [ ]
Pick up the phones and talk. Service phone, at front Remote service N02 N08 N14
panel phone rings, buzzer N24 N30 N48
drones, talk is [ ] [ ] [ ]
possible

N02 N08 N14


B.11.2 Hot line direct phone Mark if not configured: N24 N30 N48
[ ] [ ] [ ]
Pick up the phone, wait, pick Direct phone Remote direct N02 N08 N14
up remote phone phone rings until N24 N30 N48
phone is picked up. [ ] [ ] [ ]

Measure Output level. Feed into rem. equ. at Configured Output dBm N02 N08 N14
Feed 800 Hz with configured terminal telephony 0a-0b level ±1 dB (600 ) N24 N30 N48
input level of remote Measure at terminal (Def.: -7.0 dBm) [ ] [ ] [ ]
subscriber (Def.: 0.0 dBm). telephony 0a-0b

N02 N08 N14


B.11.3 Remote subscriber. At Mark if not configured: N24 N30 N48
remote equ. is Pax 2-Wire [ ] [ ] [ ]

Test Ringer: Feed ringing Feed into rem. equ. at Subscriber must N02 N08 N14
voltage (25 VAC, 25 Hz, R = terminal telephony 8a-8b ring N24 N30 N48
2.2 k) into remote PAX 2- [ ] [ ] [ ]
Wire

Measure Output level. Feed into rem. equ. at Configured Output dBm N02 N08 N14
Feed 800 Hz with configured terminal telephony 8a-8b level ±1 dB (600 ) N24 N30 N48
input level of remote Measure at terminal (Def.: -7.0 dBm) [ ] [ ] [ ]
PAX.(Def.: 0.0 dBm) telephony 0a-0b

N02 N08 N14


B.11.4 Remote subscriber. At Mark if not configured: N24 N30 N48
remote equ. is Pax 4-wire [ ] [ ] [ ]

Test Ringer: Activate at Remote equ. Subscriber must N02 N08 N14
Activate M-WIRE of remote at terminal telephony 4a- ring N24 N30 N48
Pax 4-wire. 4b [ ] [ ] [ ]

Measure Output level. Feed into rem. equ. at Configured Output dBm N02 N08 N14
Feed 800 Hz with configured terminal telephony 1a-1b level ±1 dB (600 ) N24 N30 N48
input level of remote Measure at terminal (Def.: -7.0 dBm) [ ] [ ] [ ]
PAX.(Def.: -3.5 dBm) telephony 0a-0b

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B8


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

N02 N08 N14


B.11.5 Pax 2-wire Mark if not configured: N24 N30 N48
[ ] [ ] [ ]
Measure Output level. Feed into rem. equ. at Configured Output dBm N02 N08 N14
Feed 800 Hz with configured terminal telephony 0a-0b level ±1 dB (600 ) N24 N30 N48
input level of remote Measure at terminal (Def.: -7.0 dBm) [ ] [ ] [ ]
subscriber.(Def.: 0.0 dBm) telephony 8a-8b
PAX-BLOCKING normal Measure at terminal 6a-6b is open, N02 N08 N14
telephony 6a-6b, 6b-7a 6b-7a is closed N24 N30 N48
[ ] [ ] [ ]
PAX-BLOCKING blocked Measure at terminal 6a-6b is closed, N02 N08 N14
Switch off remote equ., wait telephony 6a-6b, 6b-7a 6b-7a is open N24 N30 N48
about 30 sec. [ ] [ ] [ ]

N02 N08 N14


B.11.6 Pax 4-wire. At remote equ. is Mark if not configured: N24 N30 N48
Pax 4-wire [ ] [ ] [ ]
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N02 N08 N14
Close and open at Remote N24 N30 N48
equ. at terminal telephony [ ] [ ] [ ]
4a-4b
Measure Output level. Feed into rem. equ. at Configured Output dBm N02 N08 N14
Feed 800 Hz with configured terminal telephony 1a-1b level ±1 dB (600 ) N24 N30 N48
input level of remote PAX Measure at terminal (Def.: -3.5 dBm) [ ] [ ] [ ]
(Def.: -3.5 dBm). telephony 2a-2b
(Activate at terminal telephony
4a-4b on both equ.)

PAX-BLOCKING normal Measure at terminal 6a-6b is open, N02 N08 N14


telephony 6a-6b, 6b-7a 6b-7a is closed N24 N30 N48
[ ] [ ] [ ]

PAX-BLOCKING blocked Measure at terminal 6a-6b is closed, N02 N08 N14


telephony 6a-6b, 6b-7a 6b-7a is open N24 N30 N48
Switch off remote equ., wait [ ] [ ] [ ]
about 30 sec.

N02 N08 N14


B.11.7 Pax 4-wire. At remote equ. is Mark if not configured: N24 N30 N48
Remote subscriber [ ] [ ] [ ]

Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N02 N08 N14
Toggle hook of phone. N24 N30 N48
(Close and open at Remote [ ] [ ] [ ]
equ. at terminal telephony
0a-0b)

Measure Output level. Feed into rem. equ. at Configured Output dBm N02 N08 N14
Feed 800 Hz with configured terminal telephony 0a-0b level ±1 dB (600 ) N24 N30 N48
input level of remote Measure at terminal (Def.: -3.5 dBm) [ ] [ ] [ ]
subscriber.(Def.: 0.0 dBm) telephony 2a-2b
PAX-BLOCKING normal Measure at terminal 6a-6b is open N02 N08 N14
telephony 6a-6b, 6b-7a 6b-7a is closed N24 N30 N48
[ ] [ ] [ ]
PAX-BLOCKING blocked Measure at terminal 6a-6b is closed N02 N08 N14
telephony 6a-6b, 6b-7a 6b-7a is open N24 N30 N48
Switch off remote equ., wait
about 30 sec. [ ] [ ] [ ]

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B9


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

N02 N08 N14


B.11.8 Pax 4/2-wire Mark if not configured: N24 N30 N48
[ ] [ ] [ ]
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N02 N08 N14
Close and open at Remote N24 N30 N48
equ. at terminal telephony [ ] [ ] [ ]
4a-4b
Measure Output level of AF1. Feed into rem. equ. at Configured Output dBm N02 N08 N14
Feed 800 Hz with configured terminal telephony 1a-1b level ±1 dB (600 ) N24 N30 N48
input level of remote PAX Measure at terminal (Def.: -3.5 dBm) [ ] [ ] [ ]
(Def.: -3.5 dBm). telephony 2a-2b
Activate at terminal telephony
4a-4b on both equ..
Measure Output level of Feed into rem. equ. at Configured Output dBm N02 N08 N14
PAX2W. terminal telephony 1a-1b level ±1 dB (600 ) N24 N30 N48
Feed 800 Hz with configured Measure at terminal (Def.: -7.0 dBm) [ ] [ ] [ ]
input level of remote PAX telephony 8a-8b
(Def.: -3.5 dBm).
(Activate at terminal telephony
4a-4b on both equ.)
Test Local/Transit: Feed into rem. equ. at Configured Output dBm N02 N08 N14
Measure Output level at AF1. terminal telephony 8a-8b level ±1.5 dB (600 ) N24 N30 N48
Feed 800 Hz with configured Measure at terminal (Def.: -7.0 dBm) [ ] [ ] [ ]
input level of remote PAX2W telephony 8a-8b
(Def.: -0.0 dBm).
Activate at terminal telephony
5a-4b of remote equ..
(Activate at terminal telephony
4a-4b on both equ.)
PAX-BLOCKING normal Measure at terminal 6a-6b is open N02 N08 N14
telephony 6a-6b, 6b-7a 6b-7a is closed N24 N30 N48
[ ] [ ] [ ]
PAX-BLOCKING blocked Measure at terminal 6a-6b is closed N02 N08 N14
telephony 6a-6b, 6b-7a 6b-7a is open N24 N30 N48
Switch off remote equ., wait
about 30 sec. [ ] [ ] [ ]

N02 N08 N14


B.11.9 Transit mode for E&M wire Mark if not configured: N24 N30 N48
[ ] [ ] [ ]
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N02 N08 N14
Close and open at Remote N24 N30 N48
equ. at terminal telephony [ ] [ ] [ ]
4a-4b

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B10


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.11.10 Testing the teleoperation


ports

B.11.11 Teleoperation AF1, if not Mark if not configured: N02 N08 N14 N20
used for telephony N24 N30 N42 N48 N54
[ ] [ ] [ ] [ ] [ ]

Fed input level, [dBm], Expected Output Measured Output level at


@ 800 Hz at AF1-IN of remote. level at AF1-OUT AF1-OUT
N02/N24: ___________±1 Feed into rem. equ. at N02/N24: ______±1 dBm N02/N24: ___________
terminal telephony 1a-1b
N08/N30: ___________±1 N08/N30: ______±1 (600 ) N08/N30: ___________
Measure at terminal
N14/N42: ___________±1 telephony 2a-2b N14/N42: ______±1 N14/N42: ___________
N20/N48: ___________±1 ext. Boost not active. N20/N48: ______±1 N20/N48: ___________
N54: ___________±1 N54: ______±1 N54: ___________

N02 N08 N14 N20


B.11.12 Teleoperation AF2 Mark if not configured:
N24 N30 N42 N48 N54
[ ] [ ] [ ] [ ] [ ]

Fed input level, [dBm], Expected Output Measured Output level at


@ 800 Hz at AF2-IN of remote. level at AF2-OUT AF2-OUT
N02/N24: ___________±1 Feed into rem. equ. at N02/N24: ______±1 dBm N02/N24: ___________
terminal teleop. 3a-3b
N08/N30: ___________±1 N08/N30: ______±1 (600 ) N08/N30: ___________
Measure at terminal
N14/N42: ___________±1 teleop. 4a-4b N14/N42: ______±1 N14/N42: ___________
N20/N48: ___________±1 ext. Boost not active. N20/N48: ______±1 N20/N48: ___________
N54: ___________±1 N54: ______±1 N54: ___________

N02 N08 N14 N20


B.11.13 Teleoperation AF3 Mark if not configured:
N24 N30 N42 N48 N54
[ ] [ ] [ ] [ ] [ ]

Fed input level, [dBm], Expected Output Measured Output level at


@ 800 Hz at AF3-IN of remote. level at AF3-OUT AF3-OUT
N02/N24: ___________±1 Feed into rem. equ. at N02/N24: ______±1 dBm N02/N24: ___________
terminal teleop. 5a-5b
N08/N30: ___________±1 N08/N30: ______±1 (600 ) N08/N30: ___________
Measure at terminal
N14/N42: ___________±1 teleop. 6a-6b N14/N42: ______±1 N14/N42: ___________
N20/N48: ___________±1 ext. Boost not active. N20/N48: ______±1 N20/N48: ___________
N54: ___________±1 N54: ______±1 N54: ___________

B.11.14 Teleoperation AF4 Mark if not configured: N02 N08 N14 N20
N24 N30 N42 N48 N54
[ ] [ ] [ ] [ ] [ ]

Fed input level, [dBm], Expected Output Measured Output level at


@ 800 Hz at AF4-IN of remote. level at AF4-OUT AF4-OUT
N02/N24: ___________±1 Feed into rem. equ. at N02/N24: ______±1 dBm N02/N24: ___________
terminal teleop. 7a-7b
N08/N30: ___________±1 N08/N30: ______±1 (600 ) N08/N30: ___________
Measure at terminal
N14/N42: ___________±1 teleop. 8a-8b N14/N42: ______±1 N14/N42: ___________
N20/N48: ___________±1 ext. Boost not active. N20/N48: ______±1 N20/N48: ___________
N54: ___________±1 N54: ______±1 N54: ___________

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B11


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

N02 N08 N14


B.11.15 Teleoperation AF4 used for Mark if not configured: N24 N30 N48
ext. teleprotection [ ] [ ] [ ]
Test EXT-BOOST: Activate at remote equ. at
terminal teleop. 9a-9b

Fed input level, [dBm], Feed into rem. equ. at Expected Output Measured Output level at
@ 800 Hz at AF4-IN terminal teleop. 7a-7b level at AF4-OUT AF4-OUT
N02/N24: ___________±1 Measure at terminal N02/N24: ______±1 dBm N02/N24: ___________
teleop. 8a-8b
N08/N30: ___________±1 N08/N30: ______±1 (600 ) N08/N30: ___________

N14/N48: ___________±1 N14/N48: ______±1 N14/N48: ___________

B.12 Testing of V.11 ports

B.12.1 V.11 Port 1 Mark if not configured: [ ]


-6
BER test Front plate P4LT/V/X, BER ≤ 10 [ ]
V.11 PORT 1 during ____ sec

B.12.2 V.11 Port 2 Mark if not configured: [ ]


BER test Front plate P4LX, BER ≤ 10-6 [ ]
V.11 PORT 2 during ____ sec

B.13 Testing of V.24 ports

B.13.1 V.24 Port 1 Mark if not configured: [ ]


-6
BER test Front plate P4LT/V/X, BER ≤ 10 [ ]
V.24 PORT 1 during ____ sec

B.13.2 V.24 Port 2 Mark if not configured: [ ]


-6
BER test Front plate P4LT/V/X, BER ≤ 10 [ ]
V.24 PORT 2 during ____ sec

B.13.3 V.24 Port 3 Mark if not configured: [ ]


-6
BER test Front plate P4LX, BER ≤ 10 [ ]
V.24 PORT 3 during ____ sec

B.13.4 V.24 Port 4 Mark if not configured: [ ]


-6
BER test Front plate P4LX, BER ≤ 10 [ ]
V.24 PORT 4 during ____ sec

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B12


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.14 Testing of LAN ports

B.14.1 LAN Port 1 Mark if not configured: [ ]


Test of throughput Front plate P4LV/X, Throughput
LAN PORT 1 during ______ sec _____ __________________
% errored or missing frames of Front plate P4LV/X, ≤ 0.5% errored or
[ ]D 10’000 LAN PORT 1 missing 128-byte [ ]
frames during
[ ] ……………..
transmitted frames. ___________ sec

B.14.2 LAN Port 2 Mark if not configured: [ ]


Test of throughput Front plate P4LV/X, Throughput
LAN PORT 2 during ______ sec _____ __________________
% errored or missing frames of Front plate P4LV/X, ≤ 0.5% errored or
[ ]D 10’000 LAN PORT 2 missing 128-byte [ ]
frames during
[ ] ……………..
transmitted frames. ___________ sec

B.14.3 LAN Port 3 Mark if not configured: [ ]


Test of throughput Front plate P4LV/X, Throughput
LAN PORT 3 during ______ sec _____ __________________
% errored or missing frames of Front plate P4LV/X, ≤ 0.5% errored or
[ ]D 10’000 LAN PORT 3 missing 128-byte [ ]
frames during
[ ] ……………..
transmitted frames. ___________ sec

B.14.4 LAN Port 4 Mark if not configured: [ ]


Test of throughput Front plate P4LV/X, Throughput
LAN PORT 4 during ______ sec _____ __________________
% errored or missing frames of Front plate P4LV/X, ≤ 0.5% errored or
[ ]D 10’000 LAN PORT 4 missing 128-byte [ ]
frames during
[ ] ……………..
transmitted frames. ___________ sec

B.14.5 HMI over LAN


Test of connectivity Front plate P4LV/X, Connected [ ]
LAN PORT ___

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B13


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.15 Testing of O4CV

B.15.1 Slot positions of O4CV


boards
Record slot positions of O4CV Refer to HMI600
boards configuration view O4CV#1: N_____

O4CV#2: N_____

O4CV#3: N_____

O4CV#4: N_____

B.15.2 Service Phone Mark if not configured: [ ]


Pick up the phones and talk. Service phone, at front Remote service [ ]
panel of O4CV#1 phone rings, buzzer
drones, talk is
possible

B.15.3 Hot line direct phone Mark if not configured: [ ]


Pick up the phone, wait, pick Direct phone Remote direct O4CV#1: O4CV#2:
up remote phone phone rings until P1 P2 P3 P4 P1 P2 P3 P4
phone is picked up. [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
O4CV#3: O4CV#4:
P1 P2 P3 P4 P1 P2 P3 P4
[ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
Measure Output level. Feed into rem. equ. at Configured Output dBm O4CV#1: O4CV#2:
Feed 800 Hz with configured
terminals 7a-7b, 8a-8b, level ±5 dB (600 ) P1 P2 P3 P4 P1 P2 P3 P4
9a-9b, 0a-0b of term.bl.2 (Def.: -7.0 dBm) [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
input level of remote
for ports P1, P2, P3, P4 O4CV#3: O4CV#4:
subscriber (Def.: 0.0 dBm).
Measure at terminals P1 P2 P3 P4 P1 P2 P3 P4
7a-7b, 8a-8b, 9a-9b, [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
0a-0b of term.bl.2 for
ports P1, P2, P3, P4

B.15.4 Remote subscriber. At Mark if not configured: [ ]


remote equ. is Pax 2-Wire
Test Ringer: Feed ringing Feed into rem. equ. at Subscriber must O4CV#1: O4CV#2:
voltage (25 VAC, 25 Hz, R = terminals 7a-7b, 8a-8b, ring P1 P2 P3 P4 P1 P2 P3 P4
2.2 k) into remote PAX 2- 9a-9b, 0a-0b of term.bl.2 [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
Wire for ports P1, P2, P3, P4 O4CV#3: O4CV#4:
P1 P2 P3 P4 P1 P2 P3 P4
[ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
Measure output level. Feed into rem. equ. at Configured output dBm O4CV#1: O4CV#2:
Feed 800 Hz with configured
terminals 7a-7b, 8a-8b, level ±5 dB (600 ) P1 P2 P3 P4 P1 P2 P3 P4
9a-9b, 0a-0b of term.bl.2 (Def.: -7.0 dBm) [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
input level of remote
for ports P1, P2, P3, P4 O4CV#3: O4CV#4:
PAX.(Def.: 0.0 dBm)
Measure at terminals P1 P2 P3 P4 P1 P2 P3 P4
7a-7b, 8a-8b, 9a-9b, [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
0a-0b of term.bl.2 for
ports P1, P2, P3, P4

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B14


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.15.5 Remote subscriber. At Mark if not configured: [ ]


remote equ. is Pax 4-wire
Test Ringer: Activate at rem. equ. at Subscriber must O4CV#1: O4CV#2:
terminals 4a-4b, 8a-8b of ring P1 P2 P3 P4 P1 P2 P3 P4
Activate M-WIRE of remote
term.bl.1 for ports P1, P2 [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
Pax 4-wire.
or 2a-2b, 6a-6b of O4CV#3: O4CV#4:
term.bl.2 for ports P3, P4 P1 P2 P3 P4 P1 P2 P3 P4
[ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
Measure output level. Feed into rem. equ. at Configured output dBm O4CV#1: O4CV#2:
Feed 800 Hz with configured
terminals 1a-1b, 5a-5b, level ±5 dB (600 ) P1 P2 P3 P4 P1 P2 P3 P4
9a-9b of term.bl.1 for (Def.: -7.0 dBm) [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
input level of remote
ports P1, P2, P3 or 3a-3b O4CV#3: O4CV#4:
PAX.(Def.: -3.5 dBm)
of term.bl.2 for port P4
P1 P2 P3 P4 P1 P2 P3 P4
Measure at terminals [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
7a-7b, 8a-8b, 9a-9b,
0a-0b of term.bl.2 for
ports P1, P2, P3, P4

B.15.6 Pax 2-wire Mark if not configured: [ ]


Measure output level. Feed into rem. equ. at Configured output dBm O4CV#1: O4CV#2:
Feed 800 Hz with configured
terminals 7a-7b, 8a-8b, level ±5 dB (600 ) P1 P2 P3 P4 P1 P2 P3 P4
9a-9b, 0a-0b of term.bl.2 (Def.: -7.0 dBm) [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
input level of remote
for ports P1, P2, P3, P4 O4CV#3: O4CV#4:
subscriber.(Def.: 0.0 dBm)
Measure at terminals P1 P2 P3 P4 P1 P2 P3 P4
7a-7b, 8a-8b, 9a-9b, [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
0a-0b of term.bl.2 for
ports P1, P2, P3, P4

B.15.7 Pax 4-wire. At remote equ. is Mark if not configured: [ ]


Pax 4-wire
Test E-Wire: Terminals 3a-3b, 7a-7b E-Wire must toggle O4CV#1: O4CV#2:
of term.bl.1 for ports P1, P1 P2 P3 P4 P1 P2 P3 P4
Close and open M-Wire at
P2 or 1a-1b, 5a-5b of [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
rem. equ. at terminals 4a-4b,
term.bl.2 for ports P3, P4 O4CV#3: O4CV#4:
8a-8b of term.bl.1 for ports P1,
P2 or 2a-2b, 6a-6b of term.bl.2 P1 P2 P3 P4 P1 P2 P3 P4
for ports P3, P4 [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
Measure output level. Feed into rem. equ. at Configured output dBm O4CV#1: O4CV#2:
Feed 800 Hz with configured
terminals 1a-1b, 5a-5b, level ±5 dB (600 ) P1 P2 P3 P4 P1 P2 P3 P4
9a-9b of term.bl.1 for (Def.: -3.5 dBm) [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
input level of remote PAX
ports P1, P2, P3 or 3a-3b O4CV#3: O4CV#4:
(Def.: -3.5 dBm).
of term.bl.2 for port P4 P1 P2 P3 P4 P1 P2 P3 P4
(Activate at terminals 4a-4b, [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
Measure at terminals
8a-8b of term.bl.1 for ports P1,
2a-2b, 6a-6b, 0a-0b of
P2 or 2a-2b, 6a-6b of term.bl.2
term.bl.1 for ports P1, P2,
for ports P3, P4 on both equ.)
P3 or 4a-4b of term.bl.2
for port P4

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B15


Rev. ind.
System Test Report ETL600R4 Equipment HE

Test Permissible Test


No. Test procedure Test point value Units result

B.15.8 Pax 4-wire. At remote equ. is Mark if not configured: [ ]


Remote subscriber
Test E-Wire: Terminals 3a-3b, 7a-7b E-Wire must toggle O4CV#1: O4CV#2:
of term.bl.1 for ports P1, P1 P2 P3 P4 P1 P2 P3 P4
Toggle hook of phone.
P2 or 1a-1b, 5a-5b of [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
(Close and open at rem. equ.
term.bl.2 for ports P3, P4 O4CV#3: O4CV#4:
at terminals 7a-7b, 8a-8b,
9a-9b, 0a-0b of term.bl.2 for P1 P2 P3 P4 P1 P2 P3 P4
ports P1, P2, P3, P4) [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
Measure output level. Feed into rem. equ. at Configured output dBm O4CV#1: O4CV#2:
Feed 800 Hz with configured
terminals 7a-7b, 8a-8b, level ±5 dB (600 ) P1 P2 P3 P4 P1 P2 P3 P4
9a-9b, 0a-0b of term.bl.2 (Def.: -3.5 dBm) [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
input level of remote
for ports P1, P2, P3, P4 O4CV#3: O4CV#4:
subscriber.(Def.: 0.0 dBm)
Measure at terminals P1 P2 P3 P4 P1 P2 P3 P4
(Activate at terminals 4a-4b, [ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]
2a-2b, 6a-6b, 0a-0b of
8a-8b of term.bl.1 for ports P1,
term.bl.1 for ports P1, P2,
P2 or 2a-2b, 6a-6b of term.bl.2
P3 or 4a-4b of term.bl.2
for ports P3, P4 on local equ.)
for port P4

B.16 Documentation

Make a printout of equipment [ ]


configuration and status data.
Save the '*.et6' file on disk [ ]
with Serial No. of ETL coded
in the file name,
e.g. HE400327B0.ET6

B.17 Manual reset [ ]

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B16


Rev. ind.
System Test Report ETL600R4 Equipment HE

CUSTOMER ACCEPTANCE
The acceptance form is completed by ABB and the customer representative once all equipment tests
detailed in this document have been performed successfully. Customer acceptance form is part of the
test report.

Testfield ABB Switzerland Ltd


Department PSNEX

Date: ……………….……

Test Engineer: _____________________________

Supervisor: _____________________________

FAT Witnessed

Date: _____________________________

Engineer: _____________________________

…………………………………………………..... _____________________________

…………………..…… Date: ..………..….… _____________________________

…………………..…… Date: ..………..….… _____________________________

……………………..… Date: ..………..….… _____________________________

……………………..… Date: ..………..….… _____________________________

……………………..… Date: ..………..….… _____________________________

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHW002568 en A B17