You are on page 1of 12

TX-C

SERIES COOLING TOWER


SINGLE-CELL UP TO 1500HRT COOLING CAPACITY
High Performance Crossflow Type

PROVEN PERFORMANCE • RELIABILITY • EASY INSTALLATION


TX-C Series is an induced draft cross-flow, film
filled, FRP multi-cell rectangular cooling
tower designed for the equipment cooling,
and industrial process cooling and air
conditioning applications.

The TX-C Series Cooling Tower is designed to


meet maximum performance, reliability and
minimum maintenance.

The thermal performance of TX-C Series is :: Mid Valley-The Garden, 15,600 HRT
backed by full written guarantee. Field
performance test to CTI standards can be
carried out and witnessed by the owners
appointed inspection engineer to ensure the
supplied cooling tower meets the thermal
performance.

TX-C Series Cooling Towers are designed and


provided with high quality v-belt & pulley
drive system or right-angle gear reducer
drive system for trouble free operation.

:: Chartered Semiconductor Singapore, 1800 HRT

Advantages

• Proven Reliability
TX-C Series Cooling Towers have been installed
in many applications. Customer satisfaction is
testified by its long list of proven installations.

• Energy Saving
The low speed, high efficiency fan and low :: Carsem Ipoh, 500 HRT
pressure drop fill design optimize the energy
consumption.

• High Efficiency Drift Eliminator


The efficient drift eliminators remove entrained
water droplets from the air stream to less than
0.005%.

• Proven Corrosion Protection


Tower components are made of anti-corrosive
material suitable for cooling water application.

:: SMI Bank Kuala Lumpur, 2100 HRT


1
Features

:: Bangkok International Airport, 8000 HRT

No Description Material / Specification

1 V-Belt and Pulley System FRP Pulley Cover

2 Fan Assembly Aluminium Alloy


:: Queens Bay Penang, 5300 HRT
3 Fan Stack FRP

4 Hot Water Basin FRP

5 Main Frame Structure HDG Steel

6 High Performance PVC


Film Fill Pack

7 Cold Water Basin Floor FRP

8 Suction Sump FRP

9 Motor Weather Proof TEFC type

10 Ladder HDG Steel

11 Casing FRP

:: Biopolis DCS Plant Singapore, 5200 HRT 12 Inspection Door FRP

13 Cold Water Basin Frame HDG Steel


14 Internal Piping Optional

15 Gear Reducer System Optional

:: SAAS Building, 3000 HRT


2
Outline And Foundation Drawings (Single Cell)

TXC 500-1B TXC 525-1B


TXC 550-1B TXC 600-1B
TXC 625-1B TXC 650-1B

SECTION Y-Y VIEW


TXC 700-1B TXC 750-1B
TXC 800-1B TXC 850-1B
TXC 900-1B TXC 950-1B
TXC 1000-1B

PLAN VIEW

SECTION X-X VIEW


RC FOUNDATION DETAIL

MAKE UP AUTO
& MANUAL

DRAIN OUTLET

SUMP DETAIL
SIDE VIEW FRONT VIEW

TX-C SERIES
Tower
OVERALL DIMENSION MOTOR AXIAL FLOW FAN
Model
Rated Rated
Output Current Power Diameter Fan No of Drive
TXC - 1 L W H h A kW (A 50Hz) Type Source (mm) Speed blades System
500-1B 5325 2710 3297 1000 2440 15.0 27.6 2440 340
TEFC, outdoor, 3 phase, induction motor, 4 pole

525-1B 5325 2710 3297 1000 2440 18.5 33.4 2440 364
3ph/380V/50Hz or 3ph/415V/50Hz

550-1B 5325 2710 3297 1000 2440 22.0 39.5 2440 386
600-1B 5325 3321 3297 1000 2440 18.5 33.4 2440 362
625-1B 5325 3321 3297 1000 2440 22.0 39.5 2440 383
V Belt and Pulley
Four (4) to Six (6)

650-1B 5325 3321 3297 1000 2440 30.0 52.7 2440 425
700-1B 5550 3626 3297 1025 2745 30.0 52.7 2745 365
750-1B 5550 3626 3297 1025 2745 37.0 64.0 2745 392
800-1B 6057 3626 3965 1025 2745 37.0 64.0 2745 390
850-1B 6057 3626 3965 1025 2745 45.0 77.5 2745 416
900-1B 6057 4075 4630 1025 3050 30.0 52.7 3050 351
950-1B 6057 4075 4630 1025 3050 37.0 64.0 3050 376
1000-1B 6057 4075 4630 1025 3050 45.0 77.5 3050 382
1250-1B 6830 4280 6010 1950 3350 45.0 77.5 3350 348
1500-1B 7430 4280 6010 1950 3350 55.0 94.3 3350 348

3
Outline And Foundation Drawings (Single Cell)

TXC 1250-1B

SECTION Y-Y VIEW


TXC 1500-1B

PLAN VIEW

SECTION X-X VIEW


RC FOUNDATION DETAIL

MAKE UP AUTO
& MANUAL

DRAIN OUTLET

SUMP DETAIL
SIDE VIEW FRONT VIEW

Tower
ANCHOR BOLTS DATA PIPING DATA PIPING SIZE WEIGHT (KG)
Model
Make Up
Auto & Dry Oper.
TXC - 1 B C D E1 E2 F G J Water Inlet Water Outlet Overflow Drain Manual Weight Weight
500-1B - 5275 2660 1000 2138 1930 1355 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 3230 7900
525-1B - 5275 2660 1000 2138 1930 1355 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 3300 7970
550-1B - 5275 2660 1000 2138 1930 1355 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 3350 8020
600-1B - 5275 3271 1000 2138 1930 1661 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 3750 9450
625-1B - 5275 3271 1000 2138 1930 1661 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 3800 9500
650-1B - 5275 3271 1000 2138 1930 1661 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 3850 9550
700-1B - 5500 3576 1330 2085 2043 1813 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 4100 10650
750-1B - 5500 3576 1330 2085 2043 1813 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 4150 10650
800-1B - 6007 3576 1525 2241 2296 1813 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 4600 11900
850-1B - 6007 3576 1525 2241 2296 1813 - 200 x 2 300 x 1 100 x 1 50 x 1 50 x 1 4680 11980
900-1B - 6007 4025 1525 2241 2296 2038 - 200 x 2 350 x 1 100 x 1 50 x 1 50 x 1 5000 13000
950-1B - 6007 4025 1525 2241 2296 2038 - 200 x 2 350 x 1 100 x 1 50 x 1 50 x 1 5050 13050
1000-1B - 6007 4025 1525 2241 2296 2038 - 200 x 2 350 x 1 100 x 1 50 x 1 50 x 1 5100 13100
1250-1B - 6780 4230 2239 2270 2682 2140 - 200 x 2 400 x 1 100 x 1 50 x 1 50 x 1 7275 16200
1500-1B - 7380 4230 2440 2470 2982 2140 - 200 x 2 400 x 1 100 x 1 50 x 1 50 x 1 8550 21000
* Note: 1.) For Internal Piping Detail, Please Contact Truwater's Engineer. 2.) Balancing Pipe Connection Is Available Upon Request.
3.) External Piping to Open End. Internal Piping & Water Outlet to JIS10K FF Flange. 4.) Overflow, Drain, Make Up Auto & Manual to BSP Male Thread. 4
5.) Power source other than the above, please contact Truwater’s Engineer.
Outline And Foundation Drawing (Two Cell)

TXC 1000-2B
TXC 1050-2B
TXC 1100-2B
TXC 1200-2B
TXC 1250-2B
TXC 1300-2B
TXC 1400-2B
TXC 1500-2B
TXC 1600-2B
TXC 1700-2B
TXC 1800-2B
TXC 1900-2B
TXC 2000-2B

TX-C SERIES
Tower
OVERALL DIMENSION MOTOR AXIAL FLOW FAN
Model
Rated Rated
Output Current Power Diameter Fan No of Drive
TXC-2 L W H h A kW (A 50Hz) Type Source (mm) Speed blades System
1000-2B 5325 5470 3297 1000 2440 15.0 27.6 2440 340
TEFC, outdoor, 3 phase, induction motor, 4 pole

1050-2B 5325 5470 3297 1000 2440 18.5 33.4 2440 364
1100-2B 5325 5470 3297 1000 2440 22.0 39.5 2440 386
3ph/380V/50Hz or 3ph/415V/50Hz

1200-2B 5325 6692 3297 1000 2440 18.5 33.4 2440 362
1250-2B 5325 6692 3297 1000 2440 22.0 39.5 2440 383
V Belt and Pulley
Four (4) to Six (6)

1300-2B 5325 6692 3297 1000 2440 30.0 52.7 2440 425
1400-2B 5550 7302 3297 1025 2745 30.0 52.7 2745 365
1500-2B 5550 7302 3297 1025 2745 37.0 64.0 2745 392
1600-2B 6057 7302 3965 1025 2745 37.0 64.0 2745 390
1700-2B 6057 7302 3965 1025 2745 45.0 77.5 2745 416
1800-2B 6057 8200 4630 1025 3050 30.0 52.7 3050 351
1900-2B 6057 8200 4630 1025 3050 37.0 64.0 3050 376
2000-2B 6057 8200 4630 1025 3050 45.0 77.5 3050 382
2500-2B 6830 8610 6010 1950 3350 45.0 77.5 3350 348
3000-2B 7430 8610 6010 1950 3350 55.0 94.3 3350 348

5
Outline And Foundation Drawing (Two Cell)

TXC 2500-2B
TXC 3000-2B

SECTION Y-Y VIEW


PLAN VIEW

SECTION X-X VIEW


RC FOUNDATION DETAIL

MAKE UP AUTO
& MANUAL

DRAIN OUTLET

SUMP DETAIL
SIDE VIEW FRONT VIEW

Tower
ANCHOR BOLTS DATA PIPING DATA PIPING SIZE WEIGHT (KG)
Model
Make Up
Auto & Dry Oper.
TXC - 1 B C D E1 E2 F G J Water Inlet Water Outlet Overflow Drain Manual Weight Weight
1000-2B 2660 5275 5420 1000 2138 1930 1355 2760 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 6460 15800
1050-2B 2660 5275 5420 1000 2138 1930 1355 2760 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 6600 15940
1100-2B 2660 5275 5420 1000 2138 1930 1355 2760 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 6700 16040
1200-2B 3271 5275 6642 1000 2138 1930 1661 3371 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 7500 18900
1250-2B 3271 5275 6642 1000 2138 1930 1661 3371 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 7600 19000
1300-2B 3271 5275 6642 1000 2138 1930 1661 3371 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 7700 19100
1400-2B 3576 5500 7252 1330 2085 2043 1813 3676 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 8200 21300
1500-2B 3576 5500 7252 1330 2085 2043 1813 3676 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 8300 21300
1600-2B 3576 6007 7252 1525 2241 2296 1813 3676 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 9200 23800
1700-2B 3576 6007 7252 1525 2241 2296 1813 3676 200 x 4 300 x 2 100 x 2 50 x 2 50 x 2 9360 23960
1800-2B 4025 6007 8150 1525 2241 2296 2038 4125 200 x 4 350 x 2 100 x 2 50 x 2 50 x 2 10000 26000
1900-2B 4025 6007 8150 1525 2241 2296 2038 4125 200 x 4 350 x 2 100 x 2 50 x 2 50 x 2 10100 26100
2000-2B 4025 6007 8150 1525 2241 2296 2038 4125 200 x 4 350 x 2 100 x 2 50 x 2 50 x 2 10200 26200
2500-2B 4230 6780 8560 2239 2270 2682 2140 4330 200 x 4 400 x 2 100 x 2 50 x 2 50 x 2 14550 32400
3000-2B 4230 7380 8560 2440 2470 2982 2140 4330 200 x 4 400 x 2 100 x 2 50 x 2 50 x 2 17100 42000
* Note: 1.) For Internal Piping Detail, Please Contact Truwater's Engineer. 2.) Balancing Pipe Connection Is Available Upon Request.
3.) External Piping to Open End. Internal Piping & Water Outlet to JIS10K FF Flange. 4.) Overflow, Drain, Make Up Auto & Manual to BSP Male Thread. 6
5.) Power source other than the above, please contact Truwater’s Engineer.
TX-C Series Quick Selection Table
The diagrams below show the common combinations of various cold water, hot water, wet bulb temperature.
However, if there is a difference in temperature combination, please contact the company for a selection
of the cooling tower by our computer software.

In 95 98.6 95 97 98 98.6 97 100 98.6 100 100


Deg F Out 85.1 89.6 86 87 88 89.6 87 90 89.6 90 90
WB 80.6 80.6 81 81 82 81.5 82 82 82.4 83 84

In 35 37 35 36.1 36.7 37 36.1 37.8 37 37.8 37.8


Deg C Out 29.5 32 30 30.6 31.1 32 30.6 32.2 32 32.2 32.2
WB 27 27 27.2 27.2 27.8 27.5 27.8 27.8 28 28.3 28.3

Model Motor
TX-C HRT kW m3/hr

500 500 15.0 215 390 263 280 263 364 258 342 340 319 296

525 525 18.5 234 409 272 288 276 385 261 362 360 336 309

550 550 22.0 252 429 284 308 289 403 278 378 377 352 324

600 600 18.5 270 468 308 335 316 440 300 412 411 383 352

625 625 22.0 285 487 319 347 329 458 312 429 427 398 365

650 650 30.0 299 507 330 358 342 475 320 445 442 412 376

700 700 30.0 323 546 363 395 372 512 355 484 480 450 414

750 750 37.0 337 585 390 424 390 550 382 518 516 483 445

800 800 37.0 360 624 414 450 420 586 406 552 550 514 472

850 850 45.0 372 663 448 485 447 625 438 590 586 550 508

900 900 30.0 394 702 467 506 472 661 456 622 618 578 532

950 950 37.0 416 741 494 536 499 698 482 656 654 610 562

1000 1000 45.0 438 780 527 557 526 728 516 684 680 638 592

1250 1250 45.0 548 975 659 696 658 910 645 855 850 798 740

1500 1500 55.0 674 1170 780 848 780 1100 764 1036 1032 966 890

1600 1600 37.0 x 2 719 1248 828 900 840 1172 812 1104 1100 1028 944

1700 1700 45.0 x 2 745 1326 896 970 894 1250 876 1180 1172 1100 1016

1800 1800 30.0 x 2 787 1404 934 1012 944 1322 912 1244 1236 1156 1064

1900 1900 37.0 x 2 832 1482 988 1072 998 1396 964 1312 1308 1220 1124

2000 2000 45.0 x 2 876 1560 1054 1114 1052 1456 1032 1368 1360 1276 1184

2500 2500 45.0 x 2 1095 1950 1318 1393 1315 1820 1290 1710 1700 1595 1480

3000 3000 55.0 X 2 1348 2340 1560 1696 1560 2200 1528 2072 2064 1932 1780

7
SOUND LEVEL CHART (FROM 500~3000 TON)
The measuring point at 45 degrees is diagonally above the top edge of the fan stack, opposite of motor driver side. If
fan diameter is less than 1.5m, the measuring distance should be limited to 1.5m standard.

MEASURING DIRECTION (W) MEASURING DIRECTION (L)


(OPPOSITE OF
MOTOR-DRIVEN SIDE)

SOUND LEVEL dB(A) - SINGLE CELL (500~1000 TON) SOUND LEVEL dB(A) - 2 CELLS (1000~2000 TON)
Louver Panel Fan Louver Panel Fan
2m 10m 2m 10m 45 deg 2m 10m 2m 10m 45 deg
500-1B 75.0 62.0 70.0 57.0 73.5 1000-2B 78.0 65.0 71.0 58.0 76.5
525-1B 77.0 64.0 71.0 58.0 75.0 1050-2B 80.0 67.0 71.0 58.0 78.0
550-1B 78.0 65.0 72.0 59.0 76.0 1100-2B 81.0 68.0 72.0 59.0 79.0
600-1B 77.0 64.0 71.0 58.0 75.0 1200-2B 80.0 67.0 72.0 59.0 78.0
625-1B 79.0 66.0 72.0 59.0 77.0 1250-2B 82.0 69.0 73.0 60.0 80.0
650-1B 81.0 68.0 73.0 60.0 79.0 1300-2B 83.0 70.0 74.0 61.0 82.0
700-1B 81.0 68.0 73.0 60.0 79.0 1400-2B 83.0 70.0 73.0 60.0 82.0
750-1B 82.0 69.0 74.0 61.0 80.0 1500-2B 84.5 71.5 74.0 61.0 83.0
800-1B 82.0 69.0 74.0 61.0 80.0 1600-2B 84.5 71.5 74.0 61.0 83.0
850-1B 84.0 71.0 77.0 64.0 82.0 1700-2B 85.5 72.5 78.0 65.0 85.0
900-1B 81.0 68.0 73.0 60.0 79.0 1800-2B 83.0 70.0 73.0 60.0 82.0
950-1B 82.0 69.0 74.0 61.0 80.0 1900-2B 84.5 71.5 74.0 61.0 83.0
1000-1B 84.0 71.0 78.0 65.0 82.0 2000-2B 85.5 72.5 79.0 66.0 85.0
1250-1B 84.0 71.0 78.0 65.0 82.0 2500-2B 85.5 72.5 79.0 66.0 85.0
1500-1B 85.0 72.0 80.0 67.0 84.0 3000-2B 87.0 74.0 81.0 68.0 86.0

8
RECOMMENDED UNIT LAYOUT
It is advisable to select and design the best layout or location to avoid air recirculation. Recirculation occurs when some of
the hot moist discharge air leaving the cooling tower flows back into the fresh air inlet. The following guidelines will provide
the best location or layout which will minimize recirculation, maximize fresh air flow and allow adequate maintenance acces-
sibility.

A. SINGLE UNIT INSTALLATIONS


The best place for TX-C Series Cooling Tower is in an open space. However, when this is not possible, correct layout
guidelines must be followed to provide satisfactory installation.

Ensure that the top of the cooling tower is higher than any adjacent walls, buildings or other structures.
Figure 1(a) and 1(b) are examples of incorrect installation. These conditions can be corrected by elevating the unit on
structural steel/concrete plinths so that the top is higher that the wall as shown in Figure 1(c).

INCORRECT : Wind effect with top of unit lower than top of wall CORRECT : Installation elevated so that top of unit is
higher than top of wall
WIND DISCHARGE AIR
DISCHARGE AIR DISCHARGE AIR DIRECTION
WIND
DIRECTION

When a cooling tower is located near a wall, consider-


ation must be given to the clearance distance between
the air inlets of the tower and the wall structure(s). See
Figure 2, Recommended Dimensions D1 and D2.

The minimum dimensions, D1 and D2, as shown in Table


1 must be maintained to ensure that the unit is provided FIGURE 2 :
adequate air flow. In some installation, consideration Installation next
must also be given to access to the unit for mainte- to a wall.
nance. Room must be provided for piping, removals of
access panels, etc.

Sometimes other pieces of equipment such as pumps,


filters, piping etc are placed in front of the air inlets.
These obstructions should not be located any closer
than the minimum dimensions in Table 1.

TABLE 1 TABLE 2
Tower Model Minimum Dimension (mm) Tower Model End Wall Minimum Dimension, mm
TXC Length, L mm D3 (End-to-End)
TXC D1 (At Louver Side) D2 (At Panel Side)
All models All sizes 1000
Tower Model Louver Width, Minimum Dimension, mm
500-1B ~ 550-1B 2000 1000 TXC W mm D4 (Side-by-Side)

1000-2B ~ 1100-2B Below 6000 3500

600-1B ~ 850-1B 3000 1000


1200-2B ~ 1700-2B Below 8000 4500

1800-2B ~ 3000-2B Below 10000 5000


900-1B ~ 1500-1B 4000 1000

The minimum dimensions are as listed in Table 2

9
B. MULTIPLE UNIT INSTALLATIONS
When more than one cooling tower is installed at the same
location, recirculation becomes a bigger problem. TABLE 3
Tower Model End Wall Minimum Dimension, mm
With the installations of two cooling towers, they should be TXC Length, L mm D5 (End Wall Panel Side)
placed end to end with the narrows ends adjacent as All models All sizes 1000
shown in Figure 3. Another method is to locate the units Tower Model Louver Width, Minimum Dimension, mm
side-by-side with the longer sides parallel to each other as TXC W mm D6 (Louver Side to Solid wall)
shown in Figure 4. In either configuration, the distance
between the units must provide adequate airflow as well 1000-2B ~ 1100-2B Below 6000 3500
as room for piping to the unit and access for maintenance.
1200-2B ~ 1700-2B Below 8000 4500

1800-2B ~ 3000-2B Below 10000 5000

Louvered Wall Enclosures


TX-C Series Cooling Tower can also be installed in enclo-
FIGURE 3: MULTIPLE UNITS PLACED END TO END sures with louvered or slotted walls and an open top (Figure
6) with this type of enclosure, the air flow patterns will be a
mixture of the open type and well installation. The inlet air
will be drawn from the top as well as through the louvers or
slots

When considering a multiple-cell unit located in a louvered


wall enclosures, the D7 and D8 dimensions, found in Table
4, must be used as absolute minimums.

FIGURE 6 : LOUVERED WALL ENCLOSURE


FIGURE 4: MULTIPLE UNITS PLACED SIDE-BY-SIDE

LOUVER WALL
SPECIAL ENCLOSURE INSTALLATION
1) Solid Wall Enclosures or Wells
Figure 5 shown a cooling tower is installed in a well. When
considering a multiple-cell unit located in a well, the D5
and D6 dimensions, found in Table 3, must be used as
absolute minimums.

Tower Model End Wall Minimum Dimension, mm


TXC Length, L mm D7 (End Wall Panel Side)
FIGURE 5 WELL INSTALLATION All models All sizes 1000
Tower Model Louver Width, Minimum Dimension, mm
The unit should be oriented so that the air flow uniformly to TXC W mm D8 (Louver Side to Louvered wall)
the air inlets on all louver sides of the unit. The air discharge All models All sizes 2500
of the unit must be level with or higher than surrounding
walls.

10
TX-C SERIES CROSSFLOW COOLING TOWER SPECIFICATION
1.0 GENERAL with integral louver and drift eliminator that
are conducive to cooling water and UV
The cooling tower shall be induced-draft
protected. Fills shall be suspended from
vertical discharge type, crossflow,
structural tubing supported from the upper
rectangular, film filled, FRP Cooling Tower. It
tower structure, and shall be elevated at
shall be designed with high efficiency drift
least 50mm above the floor of the cold
eliminators to meet current environmental
water basin to facilitate cleaning.
standards and guidelines for microbial
6.2 Drift eliminators shall be efficient
control.
enough to effectively limit drift loss to
0.005% of the designed flow rate.
2.0 CAPACITY
Cooling Tower shall be capable of 7.0 HOT WATER DISTRIBUTION
providing the thermal performance Inlet Louver
scheduled.
SYSTEM
An open basin above the fill bank shall
receive hot water piped to each cell of
3.0 PERFORMANCE WARRANTY the tower. Water shall enter the basin
The cooling tower manufacturer shall through a removable splash box.
guarantee that the tower supplied will Removable and replaceable
meet the specified performance polypropylene nozzles installed in the floor
conditions when the tower is installed of the basin shall provide full coverage of
according to plans. the fill by gravity flow.

4.0 CONSTRUCTION 8.0 COLD WATER BASIN


The cooling tower main frame structure The cold water basin shall be of FRP and
shall be hot dip galvanized steel (HDG). supported on HDG steel framework. The
Belt & Pulley Drive System
The casing shall be made of fiberglass basin shall be designed with sufficient
reinforced polyester (FRP). water capacity to avoid air entrainment in
the outlet during operating conditions. The
5.0 MECHANICAL EQUIPMENT basin shall be equipped with suction
5.1 Fan(s) shall be propeller-type, strainer, make-up ball valve, overflow and
incorporating heavy-duty blades of drain. For multiple tower arrangement,
aluminum alloy. Blades shall be individually equalizing pipes between basins shall be
adjustable. provided to maintain the same level of
5.2 The V-belts shall be of rubber with water in each basin.
fabric impregnated able to withstand the
adverse ambient conditions of 50°C and 9.0 ACCESS AND SAFETY
100% R.H. The pulleys shall be cast iron with Ladder shall be provided for inspection &
the grooves of standard dimensions. The Gear Reducer Drive System maintenance purposes. HDG steel fan
entire V-belt & pulley set must be fully guard shall be provided over each fan
enclosed in a FRP molded case to protect cylinder.
the v-belts from in contact with the humid
discharge air.
5.3 Motor(s) shall be TEFC, weatherproof
sq. caged induction type suitable for 3ph
/50Hz/415V power supply and with 1450
rpm. Motor shall be installed outside the
discharge air stream.

6.0 INFILL
6.1 Fill shall be high efficiency hanging
film-type, rigid, corrugated PVC sheets Maintenance Platform
TCT/2007/010

Truwater Cooling Towers Sdn Bhd (188113-A)


Executive Suite 702, Block B, Kelana Business Centre, No. 97, Jalan SS7/2, Kelana Jaya, 47301 Petaling Jaya, Selangor, Malaysia.
Tel. : +603 7880 8800 Fax : +603 7804 5519
E-mail : Tw.Cooling@truwater.com.my Website : www.truwater.com.my